1 11 KV STEP UP TRANSFORMER
0.265kv/11 KV STEP UP TRANSFORMER , CLASS
PX FOR DIFFERENTIAL RELAYING , CLASS 5P20
FOR OTHER RELAYING , CLASS 1.0 & ISF < FOR
METERING
0.33KV/11 KV STEP UP TRANSFORMER
2 11/66 KV TRANSFORMER 1 NOS. 11 MVA STEP UP TRANSFORMER 2 NOS. 8 MVA STEP UP TRANSFORMER
3 11 KV CIRCUIT BREAKER - VCB
SHORT CIRCUIT WITHSTAND CAPACITY-20 KA
RMS
VCB RATING IN AMP
630 A VCB , SHORT CIRCUIT WITHSTAND CAPACITY-18
KA FOR 1 SEC
4 66 KV CIRCUIT BREAKER - SF6 CIRCUIT BREAKER CAPACITY 31.5 KA FOR 3 SEC SF6 RATING
630 A SF6 , SHORT CIRCUIT WITHSTAND CAPACITY-
26.3 KA FOR 1 SEC
5 66 KV POTENTIAL TRANSFORMER
RATING - (66kV/sqrt3) / (110V/sqrt3) /
(110V/sqrt3) / (110V/sqrt3), CLASS OF
ACCURACY - 0.5/3P/3P BURDEN - 100 VA
RATING - (66kV/3) / (110V/sqrt3) / (110V/sqrt3) /
(110V/sqrt3), CLASS OF ACCURACY - CORE-1 (CL:3P,15
VA) , CORE-2(CL:3P,15VA),CORE-3(CL:0.2,15VA)
6 66 KV LIGHTNING ARRESTOR
RATING-60 KV , NOMINAL DISCHARGE CURRENT-
10 KA
RATING-60 KV , NOMINAL DISCHARGE CURRENT- 40
KA
7 AUXILLARY STATION TRANSFORMER
FROM WHERE WE ARE GETTING
AUXILLARY TRANSFORMER SUPPLY
OTHER THEN DG SET SUPPLY.