Section VI Employers Requirements 2-1-10

Electrical Design Data




Item


Description

Unit
Voltage
Level
33 11 0.4
1. Nominal system voltage phase to phase kV 33 11 0.4
2. Highest system voltage
phase phase

kV

36

12

0.44
3. System Frequency Hz 50 50 50
4. Method of System Earthing
(on 11 kV level E/C limited to 500 A)
Resist. Resist. Solid
5. Rated Voltage according to IEC of
Required Equipment
kV 40.5 15
6. Impulse withstand voltage (1.2/50 sec
wave)
Internal insulation
External insulation, sea level

kV peak
kV peak

170
200

75
95

-
7. Power frequency withstand voltage 1
minute
Internal insulation
External insulation, sea level

kV peak
kV peak

70
90

28
36

-
2.5
8. Short Circuit Rating kA/3s 20 20 -
9. Substation clearances for equipment not
subject to impulse tests
Phase - earth
Phase - phase
Terminals across isolating
distance


mm
mm
mm


320
320
380


250
270
270


100
100
150
10. Cable box clearances for fully insulation
shrouded terminals

Phase earth mm 100 32 20
Phase phase mm 125 45 20
Phase - earth over cable surface mm 250 125 25
11. Transformers
Winding insulation Full Full
Max flux density at any ratio or
tap position
T 1.8 1.8 -
Acceptable noise levels dB 60 55
12. Creepage Distance for Porcelain/Silicon
Bushings and Insulators
kV/mm 31/25 31/25

General Electric Requirements

Health, Safety and Environmental Considerations
The most important factors in the design and installation of the electrical power system
shall be the health and safety of personnel and preservation of property. It shall be the
responsibility of the contractor to ensure compliance with all health, safety and