This document provides electrical design data for a power system including:
1. Nominal system voltages from 33kV to 0.4kV, highest voltages from 36kV to 0.44kV, and a frequency of 50Hz.
2. The method of earthing is resistive for the 33kV and 11kV levels and solid for the 0.4kV level.
3. Impulse withstand voltages range from 170kV to 75kV and power frequency withstand voltages range from 70kV to 28kV.
This document provides electrical design data for a power system including:
1. Nominal system voltages from 33kV to 0.4kV, highest voltages from 36kV to 0.44kV, and a frequency of 50Hz.
2. The method of earthing is resistive for the 33kV and 11kV levels and solid for the 0.4kV level.
3. Impulse withstand voltages range from 170kV to 75kV and power frequency withstand voltages range from 70kV to 28kV.
This document provides electrical design data for a power system including:
1. Nominal system voltages from 33kV to 0.4kV, highest voltages from 36kV to 0.44kV, and a frequency of 50Hz.
2. The method of earthing is resistive for the 33kV and 11kV levels and solid for the 0.4kV level.
3. Impulse withstand voltages range from 170kV to 75kV and power frequency withstand voltages range from 70kV to 28kV.
Unit Voltage Level 33 11 0.4 1. Nominal system voltage phase to phase kV 33 11 0.4 2. Highest system voltage phase phase
kV
36
12
0.44 3. System Frequency Hz 50 50 50 4. Method of System Earthing (on 11 kV level E/C limited to 500 A) Resist. Resist. Solid 5. Rated Voltage according to IEC of Required Equipment kV 40.5 15 6. Impulse withstand voltage (1.2/50 sec wave) Internal insulation External insulation, sea level
kV peak kV peak
170 200
75 95
- 7. Power frequency withstand voltage 1 minute Internal insulation External insulation, sea level
kV peak kV peak
70 90
28 36
- 2.5 8. Short Circuit Rating kA/3s 20 20 - 9. Substation clearances for equipment not subject to impulse tests Phase - earth Phase - phase Terminals across isolating distance
Phase earth mm 100 32 20 Phase phase mm 125 45 20 Phase - earth over cable surface mm 250 125 25 11. Transformers Winding insulation Full Full Max flux density at any ratio or tap position T 1.8 1.8 - Acceptable noise levels dB 60 55 12. Creepage Distance for Porcelain/Silicon Bushings and Insulators kV/mm 31/25 31/25
General Electric Requirements
Health, Safety and Environmental Considerations The most important factors in the design and installation of the electrical power system shall be the health and safety of personnel and preservation of property. It shall be the responsibility of the contractor to ensure compliance with all health, safety and