Passive Components for RS-485 Networks

Figure 4-13

Fitting the LAN Cables in the FastConnect Bus Connector


6ES7972-0B.50-0XA0

Figure 4-14

Fitting the LAN Cables in the FastConnect Bus Connector 6G1500-0FC00

PROFIBUS Networks SIMATIC NET


6GK1970-5CA20-0AA1 Release 2 05/2000

4-29

Passive Components for RS-485 Networks

4.2.3

Using the FastConnect Stripping Tool for Preparing FC Cables


The steps required to strip a cable are illustrated using the using the FastConnect
bus connector with a 90 cable outlet 6ES7972-0BB50-0XA0.
They apply analogously to the FastConnect bus connector with a 180 cable outlet
6GK1500-0FC00.

4-30

1. How to hold the stripping


tool in the right hand

2. Measure the length to be


stripped by holding the cable
against the template. Mark
the position using the index
finger of your left hand.

3. Insert the measured end of


the cable into the tool as far
as allowed by the index finger
of the left hand.

4. Clamp the end of the cable


in the stripping tool.

5. Turn the tool four times in


the direction of the arrow for
PVC insulation (eight times
for PUR or PE insulation).

6. Keeping the tool closed,


remove it from the end of the
cable. If the cut is poor,
change the blade cassette.

7. Remnants remain in the


tool. After opening the tool,
the remnants of the cable can
be removed.

8. Remove the protective


layer from the cores.

9. Fit the FastConnect cable


into the connector.

PROFIBUS Networks SIMATIC NET


6GK1970-5CA20-0AA1 Release 2 05/2000

Passive Components for RS-485 Networks

A1, B1

Switch

Switch

ON

OFF

A2, B2

Incoming cable A1, B1


Outgoing cable A2, B2
Terminating resistor with
disconnect function

When you use the connector


at the end of a segment, set
the switch to ON
(disconnect function)

When you use the connector


within a segment, set the
switch to OFF.

2
1. Undo the screw of the
strain relief.

2. Turn back the strain relief


clamp.

3. Lift the contact cover.

4. Fit the incoming cable into


the contact cover labeled A1,
B1 (remember to keep the
color coding consistent).

5. Press down the contact


cover firmly.

6. If you use the connector


within a segment, fit the
outgoing cable into the
contact cover labeled A2, B2.

1
7. Press down the contact
cover firmly.

PROFIBUS Networks SIMATIC NET


6GK1970-5CA20-0AA1 Release 2 05/2000

8. Turn back the strain relief


clamp.

9. Tighten the screw of the


strain relief clamp.

4-31