Data Aire

Mini Ceiling Systems


1, 1.5, 2, and 2.5 ton capacities

ISO 9001 Certified

Data Aire
the pioneer and builder of the
most complete line of
precision cooling equipment
Data Aires first precision cooling system was developed by data processing engineers who sought optimum
environmental conditions for early computers. It was clear that people comfort air conditioning system were
unable to meet the environmental requirements of computers and data processing equipment. Precision
environmental control equipment with high sensible cooling ratios was a necessity. Problems with paper sticking ,
head crash, and static electricity were eliminated. Humidity fluctuation were controlled saving possible electrical and
mechanical failures and more importantly Downtime. Data Aires innovative response to the challenge of
eliminating problems within the computer room environment was the start of wide use precision cooling.
As in the past, Data Aire is meeting todays challenge of not only the computer room but also the ever expanding
telecommunications industry where precision cooling is vital to our everyday communications. Telecommunication
equipment requires a controlled environment with clean and properly distributed air. As in the computer room, the
environment must be precisely controlled 24 hour a day, 365 days a year.
Data Aire produces solutions. We have offered environmental control solutions to meet specific needs in the smallest
of places and in areas of thousands of square feet. We are prepared to assist you, your in-house engineering
department, consulting engineer, or construction department in defining the proper solutions and bringing them to a
predefined outcome.
Data Aire is committed to being the supplier of choice for environmental process cooling with flexibility, reliability,
and expertise required to meet our customers needs. To be successful, it is essential to be creative and use our
resources to their fullest capabilities. The Data Aire goal is to benefit the employees, partners, and most of all our
customers with honesty and integrity.
Data Aire Delivers!

Mini Ceiling System


1, 1.5, 2, and 2.5 ton
Air and Water Cooled and Chilled Water

TABLE OF CONTENTS

Design Features ................................................................................................. 6


Options ............................................................................................................. 8
Configuration Drawings
Package Systems ............................................................................ 10
Split Systems .................................................................................. 12
Performance Data Air and Water Cooled ......................................................... 14
Electrical Data
Air Cooled ..................................................................................... 17
Water Cooled ................................................................................. 19
Performance Data Chilled Water ...................................................................... 20
Electrical Data Chilled Water ............................................................................ 21
Dimensional and Component Drawings ............................................................. 22
Guide Specifications ......................................................................................... 38
Weights ........................................................................................................... 42

DATA AIRE, FOR ALL THE RIGHT REASONS!


PRECISION COOLING

PERFORMANCE, LOW COST

Computers, batteries, electronic and telephone equipment have special comfort requirements. These spaces
require air which is clean with precisely controlled
temperature and humidity. Data Aire Mini Ceiling
SystemsTM are designed with this in mind. Building or
"people comfort" systems simply are not designed to
meet demands.

Engineered and built by the people who introduced computer room air conditioning, the Mini Ceiling unit offers
quality at a competitive price. Every Mini Ceiling System
comes with Data Aire's commitment to excellence which
began with our first air conditioner and has been tested and
proven for more than forty years.

PEOPLE COMFORT

Units shown with optional side drain connections.

Although "thru-the-wall" systems may help cool your


staff, they still fall short where precision cooling is
needed. Data Aire's Mini Ceiling Systems are the
practical answer. It will keep your equipment on-line
and will add to your personnel's comfort as well.

DATA AIRE DELIVERS


Data Aire's reputation for speedy delivery applies with special emphasis to the Mini Ceiling System. Units
are shipped within a few days from receipt of order. Call your nearest Data Aire representative for details.

MINI CEILING SYSTEMSTM


1, 1.5, 2, and 2.5 ton capacities
Air Cooled
Water Cooled
Chilled Water

ata Aire's Mini Ceiling Series is the perfect environmental control system for small computer centers,
electronic, telephone, and battery rooms, or wherever spot cooling may be necessary and space is a
problem. While vertical supply/return air units are designed to fit in a 2 ft x 4 ft standard T-bar ceiling grid
space, horizontal units hang in the ceiling space with duct work connected to supply and return connections. The
system offers an unsurpassed combination of features and options along with a high standard of performance. Mini
Ceiling Systems are available as air cooled, water cooled, or chilled water systems with a variety of return and supply
air arrangements. Air cooled can be specified as packaged indoor units or split systems with either remote outdoor
condensers or condensing units.

CONTROLS

EVAPORATOR SECTION

Precise temperature regulation is provided by a built-in


control system. All electrical components, including
capacitors, contactors, relays, and control transformers
are pre-wired and contained in an electrical box that is
hinged and swings out for easy access and servicing. A
factory installed microswitch will disable the unit prior to
condensate pan overflow should the drain line become
plugged with debris. Each unit is shipped with a
thermostat and subbase as standard. A red indicator
light is unit mounted to indicate a condensate problem.
Units with the optional Mini Data Alarm ProcessorIITM have a high condensate water level alarm standard.

The evaporator coil contained in each unit is constructed


with copper tubes and aluminum fins mounted in a
stainless steel drain pan. The drain pan is made with a
bottom drain connection and installed in a manner that
provides a positive drain to prevent standing water in the
condensate pan. The refrigeration circuit includes a
scroll compressor with internal overload protection and
crankcase heater. The circuit includes an expansion
valve with an external equalizer, filter drier, sight-glass,
and high and low pressure safety switches. The high and
low pressure safety switches are connected to the
refrigerant system with a Schrader fitting that allows
replacement without affecting the refrigerant charge,
making recovery unnecessary.

CABINET

The blower assembly is a draw-through type with a


centrifugal, forward curved, double width, double inlet
blower configuration engineered for quiet, reliable operation. The belt driven variable pitch drive provides
adjustable air flow capability to match the requirements
of the controlled space. The draw-through design
insures even distribution across the coil, low internal
cabinet losses, and static sealing of the filter section.
The motor has internal overload protection and is
mounted on an adjustable slide base.

Units are designed with a supply and return air plenum


that fits in a 2 ft x 4 ft opening of a standard dropped
ceiling grid. The field installed supply and return air
plenum is constructed of aluminum and finished with offwhite textured paint. Both the supply and return air
grilles are hinged for easy access when replacing filters.
A 2 inch, 60% efficient filter (based on ASHRAE Std.
52.1-1992) is provided behind the return air grille. Mini
Ceiling Systems are constructed with tubular steel
frames for strength and service access. Removable
panels of galvanized steel are lined with 1/2 inch thick,
closed cell insulation for quiet and efficient operation.
6

SELF-CONTAINED UNITS

SPLIT SYSTEMS

Air Cooled - The cabinet houses the evaporator


section, evaporator blower assembly, filter section
(located in air distribution plenum), and the condenser
coil. The condenser coil is constructed of copper tubes
and aluminum fins. The condenser blower section is
field installed. The condenser fan is double inlet, double
width, with direct drive type two-speed motor that is
controlled with a temperature operated switch. The
condenser blower motor electrical connection is through
a factory wired plug.

Air cooled systems are available with an outdoor


condensing unit or remote air cooled condenser.

Water Cooled - The cabinet houses the evaporator


section, evaporator blower assembly, and filter section
(located in air distribution plenum). In addition, a high
efficiency coaxial condenser with head pressure activated 2-way water regulating valve is built into the
refrigeration system and is contained in the evaporator
section. The capillary tube connection from the water
regulating valve to the refrigerant system is connected
with a Schrader fitting that allows replacement without
affecting the refrigerant charge, making recovery unnecessary.
Chilled Water - All components are housed within the
cabinet. Chilled water units utilize an existing chilled
water loop. Chilled water flow is controlled by a 2-way
valve for accurate and economical temperature control
and dehumidification. The maximum operating water
pressure is 150 psi.

Remote Outdoor Condensing Unit - The outdoor


condensing unit contains the scroll compressor, sightglass, filter drier, high and low pressure safety switches,
and condenser coil. The high and low pressure safety
switches are connected to the refrigerant system with a
Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary.
The condenser coil is constructed with copper tubes
and aluminum fins. Air discharge is vertical. The
condenser fan is variable speed for head pressure
control down to -20 F. The capillary tube connection
from the fan speed control to the refrigerant system is
connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making
recovery unnecessary. Field piping and wiring is
required from the condensing unit to the indoor evaporator section.
Remote Outdoor Air Cooled Condenser - Condensers are industrial duty design with galvanized corrosion resistant housing, aluminum finned/copper tube
coils, coated fan guard, energy efficient, thermally
protected motor, and variable fan speed control with an
integral factory wired and tested control panel. The
capillary tube connection from the fan speed control to
the refrigerant system is connected with a Schrader
fitting that allows replacement without affecting the
refrigerant charge, making recovery unnecessary. Air
discharge is vertical. Field piping and wiring is required
from the condenser to the indoor compressor/evaporator section.

Unit Shown with Optional


Side Drain Connections

Mini Ceiling Systems - OPTIONS


Mini Data Alarm Processor-II - The microprocessor
based Mini Data Alarm Processor-II is wall mounted
and has a single row, 16 character liquid crystal display
(LCD) in clear vernacular format. The Mini Data
Alarm Processor-II not only controls and monitors
your room's temperature, humidity, air flow, and cleanliness, but also provides alarm history and an automatic
self-test of the microprocessor system start-up. Multiple messages will be displayed by automatically scrolling from each message to the next. Multiple alarms will
be displayed sequentially in order of occurrence.

Normal functions are monitored and displayed


on the LCD and include, in addition to the
above set points, the following:

Operation - Unit on/off operation is controlled by a


slide switch and push button control switches which
allow menu selection for programming, operational
information, diagnostics, and historical data. A password feature prevents unauthorized access. Menu
programmed information for basic system operation and
alarm parameters is nonvolatile.

Alarms - Alarm conditions are monitored on the


LCD and are enunciated by an audible alarm. The
alarm silence button will quiet the audible alarm but
the display will continue to indicate the alarm condition until the problem is corrected.

Programmable Functions/Monitoring - The user


friendly switch permits step-by-step programming and
display of the following functions:
Temperature setpoint
(60-80 F, 15.6-26.7 C)
Temperature sensitivity
(+1 to + 5 F or .5 to 2.7 C,
in 0.1 increments)
Humidity setpoint
(30-70% RH)
Humidity sensitivity
(+1 to +15% RH in 0.1% increments)
Temperature alarm points
(50-90 F, 10-32.2 C)
Humidity alarm points
(10-90% RH)
Unit start time delay
Interstage time delay
Password 1st level
Password 2nd level
Audio alarm level
Restart mode
Firestat trip temperature
Local alarm function

Current temperature (F or C)
Current humidity (% RH)
Cooling
Reheat
Humidification
Dehumidification
Date and time

The following alarms are standard:

High temperature
Low temperature
High humidity
Low humidity
Compressor high pressure
Compressor short cycle
High condensate water
Firestat tripped
No air flow alarm
Temperature sensor failure
Humidity sensor failure

Historical Data - The current temperature and


humidity, with minimum and maximum readings for
the last 24 hours of operation can be recalled and
displayed. Alarm history of the last five alarms is
maintained in sequential order.
Diagnostics - Automatic and manual diagnostics
sequences simplify troubleshooting.
Each Mini Data Alarm Processor-II is shipped with
25 feet of cable for field connection, (additional cable
is available). Contact factory for cable lengths in
excess of 75 feet.
For full details on the Mini Data Alarm ProcessorII, see product brochure.

Site Monitoring
DARA-4 (Data Aire Relay Autochangeover)
Controls up to four Mini Ceiling units using a dry set of
relay contracts. The DARA-4 provides unit rotation,
backup capacity and the ability to interface with most
BMS systems.

Unit Options

damper kit is field installed and consists of a 14" x 14"


damper section and head pressure operator. The low
ambient control damper allows unit to operate down to
-30 F (-34.4 C). The capillary tube connection from the
head pressure control to the refrigerant system is connected
with a Schrader fitting that allows replacement without
affecting the refrigerant charge, making recovery unnecessary.

Remote Mounted Temperature and


Humidity Sensors
Condensate Pumps
Temperature and humidity sensors are provided in a
wall mounted plastic case for remote sensing of temperature and humidity. Standard unit sensors are
removed. Requires field wiring of (field provided)
shielded cable. Remote temperature and humidity
sensors option only available when used with the Mini
Data Alarm Processor-II.

Condensate pumps can be provided for field mounting


or factory installed and wired. The pump body can be
placed within the unit coil pan. Pump capacity is 60
GPH at 8 feet of head. Field installed condensate
pumps require either separate 110 or 230 volt power
source.

Steam Generator Humidifier

Horizontal, Front, or Side Supply Air

The steam generator humidifier eliminates air contamination caused by mineral deposits. The totally selfcontained system includes a quick change, disposable
cartridge, and automatic flush cycle. When steam
generator humidifier option is selected, a Mini Data
Alarm Processor-II is required.

Units may be ordered with optional horizontal supply air


configurations of front or either side. Optional supply air
converts unit for ducted supply air connection.

Electric Reheat
Low-watt density finned tubular sheathed coils are
constructed of stainless steel and provide ample capacity to maintain room dry bulb conditions on a call for
dehumidification. Low-watt density coils eliminate
ionization associated with open wire electrical resistance
heating. Electric reheat is available in 2, 4, or 5 kW
capacities, shipped factory installed with high limit
cutout.

Side Return Air


Units may be ordered with optional side return consisting of a factory modified flanged for ducting return air.
Optional side return air converts unit for ducted return
air connection. An additional option provides ceiling
mounted return air filter grille, ceiling mounted return air
filter box with hinged grille, and filter for duct connection. Filter included with this option is a 20" x 20" x 4"
deep, 60% efficient (based on ASHRAE Std. 52.11992) pleated filter.

Extended Compressor Warranty


Low Ambient Control Damper
A low ambient control damper is available for use with
ducted outside condenser air. The low ambient control

Extended compressor warranties are available from


Data Aire. Contact your local representative for one
that best suites your needs.

CONFIGURATION VERSATILITY
Data Aire Mini Ceiling Systems allow for a wide variety of supply and return options capable of satisfying the most
demanding installation requirements.

PACKAGED SYSTEMS
Standard Configuration - is provided with one ducted attachment, the condenser air out from the end of the unit with
flange. Condenser air intake is supplied from the side and top. Evaporator return air is supplied from below and the
evaporator supply air is returned to the space below.

Mini Ceiling Systems with non-ducted condenser supply air


Ducted alternate end supply air

Shown with option 260

Ducted alternate front air supply

Shown with option 261

10

Ducted alternate rear air supply

Shown with option 262

Ducted alternate return air and


alternate end supply air

Shown with options 260 and 263

PACKAGED SYSTEMS
Mini Ceiling Systems with non-ducted condenser supply air
Ducted alternate return air and
alternate rear supply air

Ducted alternate return air and


alternate front supply air

Shown with options 262 and 263

Shown with options 261 and

PACKAGED SYSTEMS
Mini Ceiling Systems with flange for condenser supply air
Standard Configuration - has flange for condenser air intake and condenser discharge air. Evaporator return and
supply air are from the space below.
Ducted condenser air intake

Ducted alternate end supply air

Shown with option 260

Ducted alternate return air and alternate


front supply air

Shown with options 261 and 263

11

CONFIGURATION VERSATILITY

continued

PACKAGED SYSTEMS -

continued

Ducted alternate return air and


alternate rear supply air

Ducted alternate return air and


alternate end supply air

Shown with options 262 and 263

Shown with options 260 and 263

SPLIT SYSTEMS
Configuration of a split system is the same as the package system, except that you dont have to take into consideration the condenser supply and return air. Typical configuration is with the evaporator supply and return air
from the space below, however all the following options are available to meet your requirements.
Standard configuration with
standard supply air and
standard return air

Ducted alternate end supply air

Ducted alternate front


supply air

Shown with option 260

Shown with option 261

12

SPLIT SYSTEMS
Ducted alternate rear supply air and alternate
return air

Ducted alternate end supply air and alternate


return air

Shown with option 260 and 263

Shown with option 262 and 263

Ducted alternate front supply air and alternate


return air

Shown with options 261 and 263

- continued

Ducted alternate end supply air and


special return air

Shown with options 260 and special

Ducted alternate front supply air and alternate


return air

Shown with options 262 and special

13

AIR, WATER or GLYCOL COOLED: Performance data


MODEL NUMBER

DAM*-01

DAM*-1.5

DAM*-02

DAM*-2.5

CAPACITY in Btu/hr - Gross


80 DB/67 WB
50% RH

Total
Sensible

16,300
12,400

20,400
16,000

25,800
21,300

32,200
26,000

75 DB/62.5 WB
50% RH

Total
Sensible

14,900
12,100

18,800
15,800

23,700
20,900

29,300
25,300

75 DB/61 WB
45% RH

Total
Sensible

14,500
12,900

18,300
17,900

24,200
22,800

28,800
27,200

72 DB/60 WB
50% RH

Total
Sensible

14,100
11,800

17,900
15,400

22,700
20,500

28,100
24,800

72 DB/58.6 WB
45% RH

Total
Sensible

13,800
12,600

17,400
16,400

22,000
21,800

27,500
26,500

550
3/4
0.5

775
3/4
0.5

1000
3/4
0.5

1225
3/4
0.5

2.4
208
3

2.4
328
3

2.4
424
4

2.4
519
4

2.4
500
4

2.4
500
6

2.4
500
6

1,200
1/2
0.5

1,200
1/2
0.5

1,200
1/2
0.5

Coaxial
2-way
3/8
150

Coaxial
2-way
3/4
150

Coaxial
2-way
3/4
150

* Insert: A - Air cooled W - Water cooled

EVAPORATOR BLOWER
Airflow - CFM
Standard motor - horsepower
External Static Pressure (E.S.P.) - inches of W.G.

EVAPORATOR COIL
Face area - sq ft
Face velocity - fpm
Rows of coil

CONDENSER COIL
Face area - sq ft
Face velocity - fpm
Rows of coil

CONDENSER BLOWER
Standard airflow - CFM
Standard motor - horsepower
External Static Pressure (E.S.P.) - inches of W.G.

CONDENSER DATA
Type
Water regulating valve
Size - inches
Maximum working pressure - PSI
14

Air cooled indoor packaged units


2.4
500
4

Air cooled indoor packaged units


1,200
1/2
0.5

Water cooled units


Coaxial
2-way
3/8
150

AIR, WATER or GLYCOL COOLED: Performance data


MODEL NUMBER

DAM*-01

ENTERING WATER
Using 65 F EWT
Using 75 F EWT
Using 85 F EWT
With Fluid Cooler

GPM
PD in PSI
GPM
PD in PSI
GPM
PD in PSI
GPM
PD in PSI

DAM*-1.5

DAM*-02

DAM*-2.5

1.2
1.3
2.0
2.0
2.8
3.0
3.5
5.8

1.9
2.9
3.0
4.3
4.2
6.7
5.3
12.4

2.5
2.1
3.9
3.1
5.6
4.8
7.0
9.2

3.1
3.0
4.9
4.5
7.0
6.9
8.8
13.3

Scroll
1
1
R-22
Standard

Scroll
1
1
R-22
Standard

Scroll
1
1
R-22
Standard

Scroll
1
1
R-22
Standard

2
6,830
4
13,660
N/A

2
6,830
4
13,660
5
17,075

2
6,830
4
13,660
5
17,075

5
1.7

5
1.7

5
1.7

5
1.7

Pleated
1
20x20x2
60

Pleated
1
20x20x2
60

Pleated
1
20x20x2
60

Pleated
1
20x20x2
60

3/4
3/4
1/4

3/4
3/4
1/4

3/4
3/4
1/4

3/4
3/4
1/4

Water cooled units

COMPRESSOR DATA
Type
Quantity
Cooling stages
Refrigerant type
Crankcase heater
REHEAT SECTION
Type - Electric
Capacity- kW
Btu/hr
Capacity - kW
Btu/hr
Capacity- kW
Btu/hr
HUMIDIFIER SECTION
Type - Steam Generator
Capacity - lb/hr
kW

Optional
2
6,830
4
13,660
N/A

Optional

FILTER SECTION
Type
Quantity
Size - inches
Efficiency - percentage
CONNECTION SIZES
Condenser water - In/Out
Condensate drain - fpt
Humidifier
CONNECTION SIZES

Air Cooled Split Systems

With condensing unit:


Liquid line - O.D. Copper
Suction line - O.D. Copper

1/2
3/4

1/2
3/4

1/2
3/4

1/2
3/4

With condenser:
Liquid line - O.D. Copper
Hot gas line - O.D. Copper

1/2
1/2

1/2
1/2

1/2
1/2

1/2
1/2
15

AIR COOLED: Electrical data


ELECTRICAL SECTION
AIR COOLED (Packaged Systems)
MODEL NUMBER

DAMA-01-P

DAMA-1.5-P

DAMA-02-P

DAMA-2.5-P

16/18/25
16/18/25

18/21/30
17/19/25

21/25/35
19/22/30

Electrical data based on: electric reheat - NO, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
24/28/30
24/28/30
277 V
FLA/MCA/MFS
22/25/30
22/25/30

26/31/35
23/26/30

30/35/45
26/30/35

Electrical data based on: 2 kW electric reheat -YES, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
26/30/35
26/30/35
277 V
FLA/MCA/MFS
23/27/30
23/27/30

28/33/40
24/28/30

31/37/45
27/31/40

Electrical data based on: 4 kW electric reheat -YES, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
35/42/45
35/42/45
277 V
FLA/MCA/MFS
30/36/40
30/36/40

37/45/50
31/37/40

41/49/50
34/40/45

Electrical data based on: 5 kW electric reheat -YES, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
N/A
N/A
277 V
FLA/MCA/MFS
N/A
N/A

42/51/60
35/41/45

45/55/60
37/45/45

Electrical data based on: 2 kW electric reheat -YES, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
26/30/35
26/30/35
277 V
FLA/MCA/MFS
23/27/30
23/27/30

28/33/40
24/28/30

31/37/45
27/31/40

Electrical data based on: 4 kW electric reheat -YES, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
35/42/45
35/42/45
277 V
FLA/MCA/MFS
30/36/40
30/36/40

37/45/50
31/37/40

41/49/50
34/40/45

Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
N/A
N/A
277 V
FLA/MCA/MFS
N/A
N/A

42/51/60
35/41/45

45/55/60
37/45/50

DAMA-1.5-AO

DAMA-02-AO

DAMA-2.5-AO

Electrical data based on: electric reheat - NO, steam generator humidifier - NO.
208-230 V
Indoor FLA/MCA/MFS
5.3/6.6/15
5.3/6.6/15
Outdoor FLA/MCA/MFS
13/15/20
13/15/20
277 V
Indoor FLA/MCA/MFS
4.3/5.4/15
4.3/5.4/15

5.3/6.6/15
15/17/25

5.3/6.6/15
18/21/30

4.3/5.4/15

4.3/5.4/15

Electrical data based on: electric reheat - NO, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
16/18/25
277 V
FLA/MCA/MFS
16/18/25

AIR COOLED (Split Systems with Outdoor Condensing Unit)


MODEL NUMBER

DAMA-01-AO

** Continued **

Note: Transformers are required to step from 277 volt to 208-230 volt on outdoor condensing units. 277 volt condensing units are not available.

FLA - Full load amps MCA - Minimum circuit amps wire sizing ampsMFS - Maximum overcurrent protection device amp
16

AIR COOLED: Electrical data


AIR COOLED (Split Systems with Outdoor Condensing Unit)
MODEL NUMBER

** Continued **

DAMA-01-AO

DAMA-1.5-AO

DAMA-02-AO

DAMA-2.5-AO

Electrical data based on: electric reheat - NO, steam generator humidifier - YES.
208-230 V
Indoor FLA/MCA/MFS
13/17/20
13/17/20
Outdoor FLA/MCA/MFS
13/15/20
13/15/20
277 V
Indoor FLA/MCA/MFS
10/13/15
10/13/15

13/17/20
15/17/25

13/17/20
18/21/30

10/13/15

10/13/15

Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
Indoor FLA/MCA/MFS
15/19/20
15/19/20
Outdoor FLA/MCA/MFS
13/15/20
13/15/20
277 V
Indoor FLA/MCA/MFS
12/14/15
12/14/15

15/19/20
15/17/25

15/19/20
18/21/30

12/14/15

12/14/15

Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
Indoor FLA/MCA/MFS
25/31/35
25/31/35
Outdoor FLA/MCA/MFS
13/15/20
13/15/20
277 V
Indoor FLA/MCA/MFS
19/23/25
19/23/25

25/31/35
15/17/25

25/31/35
18/21/30

19/23/25

19/23/25

Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
Indoor FLA/MCA/MFS
N/A
N/A
Outdoor FLA/MCA/MFS
N/A
N/A
277 V
Indoor FLA/MCA/MFS
N/A
N/A

29/37/40
15/17/25

29/37/40
18/21/30

22/28/30

22/28/30

Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
Indoor FLA/MCA/MFS
15/19/20
15/19/20
Outdoor FLA/MCA/MFS
13/15/20
13/15/20
277 V
Indoor FLA/MCA/MFS
12/14/15
12/14/15

15/19/20
15/17/25

15/19/20
18/21/30

12/14/15

12/14/15

Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
Indoor FLA/MCA/MFS
25/31/35
25/31/35
Outdoor FLA/MCA/MFS
13/15/20
13/15/20
277 V
Indoor FLA/MCA/MFS
19/23/25
19/23/25

25/31/35
15/17/25

25/31/35
18/21/30

19/23/25

19/23/25

Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
Indoor FLA/MCA/MFS
N/A
N/A
Outdoor FLA/MCA/MFS
N/A
N/A
277 V
Indoor FLA/MCA/MFS
N/A
N/A

29/37/40
15/17/25

29/37/40
18/21/30

22/28/30

2/28/30

Note: Transformers are required to step from 277 volt to 208-230 volt on outdoor condensing units. 277 volt condensing units are not available.

FLA - Full load amps

MCA - Minimum circuit amps wire sizing amps

MFS - Maximum overcurrent protection device amps


17

AIR COOLED: Electrical data


AIR COOLED (Split Systems with Remote Air Cooled Condenser)
MODEL NUMBER

DAMA-01-CO

DAMA-1.5-CO

DAMA-02-CO

DAMA-2.5-CO

Electrical data based on: electric reheat - NO, steam generator humidifier - NO.
208-230 V
Indoor FLA/MCA/MFS
14/16/20
14/16/20
Outdoor FLA/MCA/MFS
4.2/5.3/15
4.2/5.3/15
277 V
Indoor FLA/MCA/MFS
12/14/20
12/14/20

16/18/25
4.2/5.3/15

19/22/35
4.2/5.3/15

13/15/20

16/19/30

Electrical data based on: electric reheat - NO, steam generator humidifier - YES.
208-230 V
Indoor FLA/MCA/MFS
22/26/30
22/26/30
Outdoor FLA/MCA/MFS
4.2/5.3/15
4.2/5.3/15
277 V
Indoor FLA/MCA/MFS
18/22/25
18/22/25

24/28/35
4.2/5.3/15

27/32/40
4.2/5.3/15

19/23/30

22/26/35

Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
Indoor FLA/MCA/MFS
23/28/30
23/28/30
Outdoor FLA/MCA/MFS
4.2/5.3/15
4.2/5.3/15
277 V
Indoor FLA/MCA/MFS
19/23/25
19/23/25

25/30/35
4.2/5.3/15

28/34/45
4.2/5.3/15

20/24/30

23/28/35

Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
Indoor FLA/MCA/MFS
33/40/45
33/40/45
Outdoor FLA/MCA/MFS
4.2/5.3/15
4.2/5.3/15
277V
Indoor FLA/MCA/MFS
26/32/35
26/32/35

35/42/45
4.3/5.3/15

38/46/50
4.2/5.3/15

27/33/35

30/37/40

Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
Indoor FLA/MCA/MFS
N/A
N/A
Outdoor FLA/MCA/MFS
N/A
N/A
277 V
Indoor FLA/MCA/MFS
N/A
N/A

40/48/50
4.2/5.3/15

43/52/60
4.2/5.3/15

31/38/40

34/41/45

Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
Indoor FLA/MCA/MFS
23/28/30
23/28/30
Outdoor FLA/MCA/MFS
4.2/5.3/15
4.2/5.3/15
277 V
Indoor FLA/MCA/MFS
19/23/25
19/23/25

25/30/35
4.2/5.3/15

28/34/45
422/5.3/15

20/24/30

23/28/35

Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
33/40/45
33/40/45
Indoor FLA/MCA/MFS
Outdoor FLA/MCA/MFS
4.2/5.3/15
4.2/5.3/15
277 V
Indoor FLA/MCA/MFS
26/32/35
26/32/35

35/42/45
4.2/5.3/15

38/46/50
4.2/5.3/15

27/33/35

30/37/40

40/48/50
4.2/5.3/15

43/52/60
4.2/5.3/15

Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
Indoor FLA/MCA/MFS
N/A
N/A
Outdoor FLA/MCA/MFS
N/A
N/A
277 V
18

WATER or GLYCOL COOLED: Electrical data


WATER COOLED (Packaged Systems)
MODEL NUMBER

DAMW-01

DAMW-1.5

DAMW-02

DAMW-2.5

14/16/20
12/14/20

16/18/25
13/15/20

19/22/35
16/19/30

Electrical data based on: electric reheat - NO, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
22/26/30
22/26/30
277 V
FLA/MCA/MFS
18/22/25
18/22/25

24/28/35
19/23/30

27/32/40
22/26/35

Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
23/28/30
23/28/30
277 V
FLA/MCA/MFS
19/23/25
19/23/25

25/30/35
20/24/30

28/34/45
23/28/35

Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
33/40/45
33/40/45
277 V
FLA/MCA/MFS
26/32/35
26/32/35

35/42/45
27/33/35

38/46/50
30/37/40

Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
N/A
N/A
277 V
FLA/MCA/MFS
N/A
N/A

40/48/50
31/38/40

43/52/60
34/41/45

Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
23/28/30
23/28/30
277 V
FLA/MCA/MFS
19/23/25
19/23/25

25/30/35
20/24/30

28/34/40
23/28/35

Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
33/40/45
33/40/45
277 V
FLA/MCA/MFS
26/32/35
26/32/35

35/42/45
27/33/35

38/46/50
30/37/40

Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
N/A
N/A
277 V
FLA/MCA/MFS
N/A
N/A

40/48/50
31/38/40

43/52/60
34/41/45

Electrical data based on: electric reheat - NO, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
14/16/20
277 V
FLA/MCA/MFS
12/14/20

COMPRESSORS and MOTORS (DX Units, Air Cooled, and Water Cooled)
MODEL NUMBER

DAM*-01

DAM*-1.5

DAM*-02

DAM*-2.5

3/4
5.3
4.3

3/4
5.3
4.3

3/4
5.3
4.3

3/4
5.3
4.3

CONDENSER FAN MOTOR


Standard motor - horsepower
FLA at 208-230 V
FLA at 277 V

(Air Cooled Indoor Packaged Units)


1/2
1/2
2.6
2.6
3.6
3.6

1/2
2.6
3.6

1/2
2.6
3.6

CONDENSER FAN MOTOR


Standard motor - horsepower
Motor FLA at 208-230 V

(Air Cooled Split Systems - Condensing Units or Air Cooled Condensers)


3/4
3/4
3/4
4.2
4.2
4.2

EVAPORATOR FAN MOTOR


Standard motor - horsepower
FLA at 208-230 V
FLA at 277 V

COMPRESSOR
Standard motor - horsepower
FLA at 208-230 V
FLA at 277 V
FLA - Full load amps

1.5
8.3
7.7

1.5
8.3
7.7

2.0
10.3
8.7

3/4
4.2
2.5
13.5
11.5

MCA - Minimum circuit amps wire sizing amps MFS - Maximum overcurrent protection device amp
19

CHILLED WATER: Performance data


MODEL NUMBER

DAMC-01

DAMC-1.5

DAMC-02

DAMC-2.5

15,800
12,200
12,500
11,000
11,900
11,400
10,800
10,200
10,500
10,400

21,300
16,500
16,800
14,900
16,000
15,400
14,600
13,700
14,100
14,000

28,700
22,400
22,800
20,200
21,700
21,000
19,800
18,700
19,200
19,200

33,900
26,600
26,900
24,000
25,600
24,900
23,300
22,200
22,700
22,700

2.4
3
208

2.4
3
328

2.4
4
424

2.4
4
519

550
3/4
0.5
1

775
3/4
0.5
1

1000
3/4
0.5
1

1225
3/4
0.5
1

3.0
2.4

4.5
5.3

6.0
7.7

7.5
10.5

2-WAY
3/4

2-WAY
3/4

2-WAY
3/4

2-WAY
3/4

2
6,825
4
13,650
N/A
N/A

2
6,825
4
13,650
5
17,075

2
6,825
4
13,650
5
17,075

5
1.7

5
1.7

5
1.7

CAPACITY in Btu/hr - Gross


80 DB/67 WB
50% RH
75 DB/62.5 WB
50% RH
75 DB/61 WB
45% RH
72 DB/60 WB
50% RH
72 DB/58.6 WB
45% RH

Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible

Note: Chilled Water capacity based on 45 F entering chilled water temperature.


CHILLED WATER COIL
Face are - sq ft
Rows of coil
Face velocity - fpm
BLOWER SECTION
Airflow - cfm
Standard fan motor - hp
External Static Pressure (E.S.P.) - inches of W.G.
Number of fans
CHILLED WATER REQUIRED
Using 45 F EWT
GPM
PSI

(Maximum 150 PSI)

CHILLED WATER VALVE


Valve body
Valve size - inches
REHEAT SECTION
Electric
kW
Btu/hr
kW
Btu/hr
kW
Btu/hr
HUMIDIFIER SECTION
Steam generator
Capacity - lbs/hr
kW

20

(Optional)
2
6,825
4
13,650
N/A
N/A
(Optional)
5
1.7

CHILLED WATER: Performance data


MODEL NUMBER

DAMC-01

DAMC-1.5

DAMC-02

DAMC-2.5

Pleated
1
20x20x2
60

Pleated
1
20x20x2
60

Pleated
1
20x20x2
60

Pleated
1
20x20x2
60

3/4
3/4
1/4

3/4
3/4
1/4

3/4
3/4
1/4

3/4
3/4
1/4

Electrical data based on: electric reheat - NO, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
5.3/6.6/15
5.3/6.6/15
277 V
FLA/MCA/MFS
4.3/5.4/15
4.3/5.4/15

5.3/6.6/15
4.3/5.4/15

5.3/6.6/15
4.3/5.4/15

Electrical data based on: electric reheat - NO, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
13/17/20
13/17/20
277 V
FLA/MCA/MFS
10/13/15
10/13/15

13/17/20
10/13/15

13/17/20
10/13/15

Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
15/19/20
15/19/20
277 V
FLA/MCA/MFS
12/14/15
12/14/15

15/19/20
12/14/15

15/19/ 20
12/14/15

Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
25/31/35
25/31/35
277 V
FLA/MCA/MFS
19/23/25
19/23/25

25/31/35
19/23/25

25/31/35
19/23/25

Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - YES.
208-230 V
FLA/MCA/MFS
N/A
N/A
277 V
FLA/MCA/MFS
N/A
N/A

29/37/40
22/28/30

29/37/40
22/28/30

Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
15/19/20
15/19/20
277V
FLA/MCA/MFS
12/14/15
12/14/15

15/19/20
12/14/15

15/19/20
12/14/15

Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
25/31/35
25/31/35
277 V
FLA/MCA/MFS
19/23/25
19/23/25

25/31/35
19/23/25

25/31/35
19/23/25

Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - NO.
208-230 V
FLA/MCA/MFS
N/A
N/A
277 V
FLA/MCA/MFS
N/A
N/A

29/37/40
22/28/30

29/37/40
22/28/30

3/4
5.3
4.3

3/4
5.3
4.3

FILTER SECTION
Type
Quantity
Size - inches
Efficiency - percentage
CONNECTION SIZES
Chilled water in/out
O.D. copper
Condensate drain - FPT
Humidifier
ELECTRICAL SECTION

BLOWER SECTION
Standard motor - hp
FLA at 208-230 V
FLA at 277 V

FLA - Full load amps

3/4
5.3
4.3

MCA - Minimum circuit amps wire sizing amps

3/4
5.3
4.3

MFS - Maximum overcurrent protection device amp


21

Air Cooled Split with DARC Outdoor Condenser

22

DAMA-XXXX-CO

Air Cooled Split with DARC Outdoor Condenser

DAMA-XXXX-CO

23

Air Cooled Split with DRCU Outdoor Condensing Unit

24

DAMA-XXXX-AO

Air Cooled Split with DRCU Outdoor Condensing Unit

DAMA-XXXX-AO

25

Air Cooled Packaged

26

DAMA-XXXX-P

Air Cooled Packaged

DAMA-XXXX-P

27

Air Cooled Split with Indoor Condenser DAMA-XXXX-CI

28

Air Cooled Split with Indoor Condenser DAMA-XXXX-CI

29

Air Cooled Split with Indoor Condensing Unit DAMA-XXXX-AI

230 W. BlueRidge Ave.


Orange, CA 92865

30

Air Cooled Split with Indoor Condensing Unit DAMA-XXXX-AI

31

Water/Glycol Cooled DAMW-XXXX

32

Water/Glycol Cooled DAMW-XXXX

33

Chilled Water DAMC-XXXX

34

Chilled Water DAMC-XXXX

35

Condenser and Condensing Unit Dimensional Drawings

Condenser Unit

Condensing Unit

36

Return Air Filter Box

Typical Hanging Installation Detail


MINI CEILING SYSTEM
TYPICAL
HANGING INSTALLATION

5/8" Threaded Rod


(4) Required

See
Mounting
Detail

5/8" Flat Washer

5/8" Nut

5/8" Jam Nut

MINI CEILING SYSTEM


LOW AMBIENT DAMPER
CONTROL PACKAGE
(Optional)

All Mounting Hardware


Field Provided
Connect to
Schrader Valve Fitting
on Discharge Line

5 1/2"
16" x 16" Ambient Controlled
Damper Supplied by
Data Aire
(Shipped Loose)

See
Damper
Detail
Duct Work Supplied
and Installed by Others

37

Mini Ceiling Systems


Guide Specifications
General
Provide and install an air conditioning system designed
specifically for use in small computer/data processing
areas, or controlled office environments, and shall be
capable of cooling, humidifying, dehumidifying, and
filtering air.
Units shall be ETL or UL listed.
The frame shall be constructed of 14 gauge welded
tubular steel and be coated with a heavy corrosion
inhibiting finish for long life. The side panels shall be of
galvanized steel. The cabinet shall be insulated with
one-half inch (1/2") thick, closed cell insulation. The
plenum shall be of cold rolled steel and painted in a
cloud white finish. The plenum (vertical unit only) shall
be field mounted. The unit shall be serviceable through
the removable side panels.
The vertical air flow unit is to be ceiling mounted and
sized to fit a standard 2 ft x 4 ft T-bar ceiling grid
opening. The horizontal supply/return air unit is to be
ceiling hung with duct work attached to supply and
return openings. The total cooling capacity shall be
______ Btu/hr at ____ degree F DB and ____ degree
F WB entering air temperature. The voltage shall be
___, 1 ph, 60 hz.
Electrical - All electrical components including
contactors, relays, control transformers, and capacitors
shall be pre-wired. The control circuit voltage shall be
24 volts. A micro-switch shall disable the unit operation
prior to condensate pan overflow should the drain line
become plugged with debris.
Filter - Provide a two (2") inch, 60% efficient (based
on ASHRAE Std. 52.1-1992) disposable filter of
twenty inches square (20" x 20"). The filter shall be
located behind and accessible through the hinged return
air grille.
Air Cooled Self-Contained - The refrigeration system
shall be self-contained, factory assembled, charged, and
tested. No refrigerant piping shall be required. The unit
shall contain an evaporator and condenser section.
The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The
single refrigeration circuit shall include the expansion
valve with external equalizer, filter drier, high and low
pressure safety switches. The scroll type compressor
shall have internal overload protection. Units with
38

capillary tube metering devices shall not be acceptable.


The evaporator blower assembly shall be draw-through
configuration consisting of a double inlet, double width,
direct drive centrifugal fan with belt drive and variable
pitch sheave, and self-aligning ball bearings rated for an
average life of 100,000 hours. The fan motor shall be
____ horsepower. Air delivery shall be a minimum of
____ cfm. The condensate drain pan shall be constructed of stainless steel and provide a positive drain to
prevent standing water in the condensate pan.
The field attached condenser section shall have a
condenser coil constructed with copper tubes and
aluminum fins and built into the refrigeration system. The
condenser fan shall be double inlet, double width, direct
drive type. The condenser blower motor electrical
connection shall be through a factory wired plug.
Air Cooled Split System (with outdoor condensing unit) - The refrigeration system shall be split
consisting of an evaporator section and remote outdoor
condensing unit. The evaporator and condensing unit
shall be factory assembled and tested.
The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The
single refrigeration circuit shall include the expansion
valve with external equalizer, filter drier, and high and
low pressure safety switches. The high and low
pressure safety switches are connected to the refrigerant
system with a Schrader fitting that allows replacement
without affecting the refrigerant charge, making recovery unnecessary. The scroll type compressor shall have
internal overload protection. Units with capillary tube
metering devices shall not be acceptable. The evaporator blower assembly shall be draw-through type consisting of a double inlet, double width, centrifugal fan
with belt drive and variable pitch sheave, and selfaligning ball bearings rated for an average life of
100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm.
The condensate drain pan shall be constructed of
stainless steel.
The condensing unit shall be constructed of heavy duty
gauge corrosion resistant steel with a powder coated
finish and contain a scroll type compressor with crankcase heater, filter drier, sightglass, and condenser coil.
The coil shall be constructed with copper tubes and
aluminum fins. The condenser fan motor shall be
variable speed for head pressure control down to -20

GUIDE SPECIFICATIONS continued

degrees F. The capillary tube connection from the fan


speed control to the refrigerant system shall be connected with a Schrader fitting that allows replacement
without affecting the refrigerant charge, making recovery unnecessary. The condenser motor shall be direct
drive with a propeller type fan.
Air Cooled Split System (with outdoor condenser) The refrigeration system shall be split consisting of an
evaporator section and remote outdoor condenser. The
evaporator and condenser shall be factory assembled
and tested.
The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The
single refrigeration circuit shall include the expansion
valve with external equalizer, filter drier, and high and
low pressure safety switches. The scroll type compressor shall have internal overload protection. Units with
capillary tube metering devices shall not be acceptable.
The evaporator blower assembly shall be draw-through
configuration consisting of a double inlet, double width,
centrifugal fan with belt drive, variable pitch sheave, and
self-aligning ball bearings rated for an average life of
100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm.
The condensate drain pan shall be constructed of
stainless steel.
The condenser section shall be a low profile, slow
speed, direct drive propeller fan type. The condenser
shall be constructed of heavy duty gauge corrosion
resistant steel with a powder coated finish and contain a
copper tube aluminum fin coil with vertical air discharge.
The condenser shall have fan speed control with
transducers to modulate the speed of the condenser fan
and provide positive start-up and operation at ambient
temperatures to -20 F. All controls including the fan
speed control, shall be factory mounted in the air cooled
condenser.
Water Cooled Self-Contained - The refrigeration
system shall be self-contained, factory assembled,
charged and tested. No refrigerant piping connections
shall be required. The unit shall contain an evaporator
and condenser section.
The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The
single refrigeration circuit shall include the expansion
valve with external equalizer, filter drier, and high and

low pressure safety switches. The scroll type compressor shall have internal overload protection. Units with
capillary tube metering devices shall not be acceptable.
The evaporator blower assembly shall be draw-through
configuration consisting of a double inlet, double width,
centrifugal fan with belt drive, variable pitch sheave, and
self-aligning ball bearings rated for an average life of
100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm.
The condensate drain pan shall be constructed of
stainless steel and provide a positive drain to prevent
standing water in the condensate pan.
A high efficiency coaxial water cooled condenser with
head pressure activated water regulating valve built into
the refrigeration system shall be provided. The capillary
tube connection from the water regulating valve to the
refrigerant system shall be connected with a Schrader
fitting that allows replacement without affecting the
refrigerant charge, making recovery unnecessary.
Maximum operating water pressure shall be 150 psi.
Chilled Water - Provide a packaged system designed
to utilize an existing chilled water loop. The unit shall be
factory assembled, piped, wired, and tested. A chilled
water coil consisting of copper tubes and aluminum fins
shall be provided. The chilled water flow shall be
controlled by a two-way valve for accurate and economical temperature control and dehumidification. The
blower assembly shall be drawn through a configuration
consisting of a double inlet, double width, direct drive
centrifugal fan with belt drive, variable pitch sheave, and
self-aligning ball bearings rated for an average life of
100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm.
The condensate drain pan shall be constructed of
stainless steel and provide a positive drain to prevent
standing water in the condensate pan. All components
shall be housed within the same cabinet.
Controls -The control system shall be electromechanical type, utilizing a 24 volt thermostat. A sub-base shall
be provided for remote wall mounting of thermostat.
The controls shall be accessible through the side panel
of the unit and contained in a hinged electrical box that
shall swing out for easy access and servicing.
Removal of the unit from the ceiling space shall
not be required for access.

39

OPTIONS

Unit Control
Mini Data Alarm Processor-II - The control system
shall be furnished with the microprocessor based Mini
Data Alarm Processor-II. The panel shall include unit
switching functions and display normal functions, malfunctions, and service diagnostics on a one row, 16
character liquid crystal display (LCD) in clear vernacular format. The panel shall automatically display temperature and humidity along with all operational and
alarm messages. The panel shall recall and display the
high and low temperature and the high and low humidity
for the last 24 hours, date and time, reheat, humidification, dehumidification, and chilled water operation (as
applicable).
Programming shall have a two level password security
to prevent unauthorized access. Programming shall be
accomplished entirely from the microprocessor. Programmable functions shall be entered on nonvolatile
EEPROM to insure program retention should power
fail. Multiple messages shall be displayed by automatically scrolling from each message to the next. Alarm
conditions, in addition to being displayed, shall enunciate an audible alarm with variable output. Additional
test or service terminals shall not be required for any
functions.
An alarm condition shall continue to be displayed until
the malfunction is corrected. Multiple alarms shall be
displayed sequentially in order of occurrence and only
those alarms which have not been acknowledged shall
continue to sound an audible alarm. The Mini Data
Alarm Processor-II shall perform an automatic self-test
on system start-up. A user accessible diagnostic
program shall aid in system component trouble shooting
by displaying on the unit LCD screen output relay
number, terminal plug and pin number for each controlled item.
The following functions shall be programmable:
Temperature setpoint
(60-80 F, 15.6-26.7 C),
Temperature sensitivity
(1-5 F, .5-2.7 C in 0.1 increments),
Humidity setpoint
(30-70% RH),
Humidity sensitivity
(1-15% RH in 0.1% increments),
Temperature alarm points,
Humidity alarm points,
Unit start time delay,
40

Interstage time relay,


Password 1st level,
Password 2nd level,
Audio alarm level,
Restart mode,
Firestat trip temperature,
Local alarm function
The following normal functions shall be monitored and
displayed:
Current temperature (F or C),
Current humidity (% RH),
Cooling,
Reheat,
Humidification,
Dehumidification,
Date and time
The following alarm functions shall be monitored and
displayed when they occur, in addition to enunciating an
audible alarm:
High temperature,
Low temperature,
High humidity,
Low humidity,
Compressor high pressure,
High condensate water,
Firestat tripped,
No air flow,
Compressor short cycle,
Temperature sensor error,
Humidity Sensor error
The following switching and control functions
shall be included:
System On/Off switch,
Menu selection button for:
Programming operational information,
Diagnostics,
Historical data, and
Alarm silence/program set button

Site Monitoring
DARA-4 (Data Aire Relay Autochangeover)
Controls up to four Mini Ceiling units using a dry set of
relay contracts. The DARA-4 provides unit rotation,
backup capacity and the ability to interface with most
BMS systems.

Unit Options
HUMIDIFIER
Provide a steam generator type humidifier. The steam
humidifier shall be of the self-contained cylinder type
with electronic controls. The humidifier shall discharge
pure steam with no material dust carry-over, and shall
have self-regulating flush cycle. Cylinders shall be
disposable not requiring cleaning or maintenance. Humidifier rate shall automatically adapt, both in frequency
and duration, to variations in the incoming water. The
humidifier capacity shall be 5 pounds per hour with
power consumption of 1.7 kW.
(Note: When specifying the steam generator type
humidifier, a Mini Data Alarm Processor-II is required.)

HORIZONTAL SUPPLY AND RETURN AIR


Supply and return air shall be horizontal for ducted
connection. Refer to the project drawings.
FRONT SUPPLY AIR
Supply air shall be through the front of the unit for
ducted connection. The unit shall be provided with a
flange connection. Refer to the project drawings.
SIDE SUPPLY AIR
Supply air shall be through the side of the unit for ducted
connection. The unit shall be provided with a flange
connection. Refer to the project drawings.
SIDE RETURN AIR

REHEAT
Provide electric reheat. The electrical heating element
shall be of the finned tube resistant type and constructed
of stainless steel with high limit cutout. The capacity shall
be ____ kW, _____ Btu/hr.

Return air shall be through the side of the unit for ducted
connection. The return air shall be through a factory
provided ceiling mounted return air grille. The ceiling
mounted return air grille shall be hinged for easy access
and shall contain a 60% efficient (based on ASHRAE
Std. 52.1-1992) 20" x 20" x 4" pleated filter. Refer to
the project drawings.

CONDENSATE PUMP
A condensate pump shall be provided with the unit and
shall have a capacity of 60 GPH at 8 feet of head. The
pump shall be shipped loose for field mounting and
installation. It is also available installed and wired from
the factory. The pump voltage shall be ___.

EXTENDED COMPRESSOR WARRANTY


Extended compressor warranties are available from
Data Aire. Contact your local representative for one
that best suites your needs.

LOW AMBIENT CONTROL DAMPER


Provide a low ambient control damper for ducting of
outside condenser air. The low ambient control damper
shall consist of a 14" x 14" damper section with
headpressure operator. The control shall enable the unit
to operate down to -30 F ambient. The capillary tube
connection from the head pressure control to the
refrigerant system shall be connected with a Schrader
fitting that allows replacement without affecting the
refrigerant charge, making recovery unnecessary.

41

Weights - lbs
Packaged Systems
Air Cooled
Water Cooled
Chilled Water
Split Systems*
Air Cooled - AO
Air Cooled - CO

1.0

Operational
1.5
2.0

2.5

425
350
300

425
350
300

425
350
300

425
350
300

280/300 280/300
325/260 325/260

280/300
325/260

280/300
325/260

1.0

Shipping
1.5
2.0

2.5

450
375
325

450
375
325

450
375
325

305/340 305/340
350/300 350/300

450
375
325

305/340 305/340
350/300 350/300

* Weights provided are for the evaporator section (inside-first number) and condensing or condenser section (outside-second
number). Each section shipped separately. Weights shown are for standard units.

42

43

230 W. BlueRidge Avenue


Orange CA 92865
800-347-2473
www.dataaire.com e-mail: sales@dataaire.com
A Member of the CS Group of Companies
2003 Data Aire Inc.
Data Aire, Inc. reserves the right to make design changes for the purposes of
product improvement, or to withdraw any design without notice.

DAMCS-0605