Professional Documents
Culture Documents
The equal-friction method assumes that there is a consistent pressure loss per foot of duct length for
the entire system. To estimate the pressure loss, the longest run or longest distance from the plenum to
diffuser needed to be considered for the calculation. Next equivalent lengths for the fittings along the
selected longest run were determined and summed with the longest run length to get a total duct
length. The total available pressure for the ducting was then divided by the calculated total length which
resulted in a pressure loss per unit length. Next the friction loss and supply flow rate were used to look
up duct diameters from Figure 12-21 in the HVAC analysis and design text book (McQuiston, 420). At a
standard duct size the actual pressure drop per 100ft section was obtained from the chart as well. With
the actual pressure drop and equivalent length a pressure drop could be calculated for each section of
ducting. The pressure drop for each run in the zone was then calculated. This process was repeated for
every zone in the building to determine fan sizing.
A sample zone 1, 2 and 3 is taken for pressure loss and equal friction analysis while those from other
zones can be found in Appendix G. Figure 6 below shows the ducting design for zone 1, 2, and 3 starting
from the plenum located near the simulation room.
In Figure 6, the plenum is shown by the blue box and the longest run runs from section 1 to section 6. It
is seen that the ducting system is designed utilizing as less tee junction four way intersection as possible
to minimize pressure loss. By using the equal friction method, the duct size for every section in the zone
can be calculated and is shown in Table 6 below.
Table 6 Flow rate and Duct Diameter for each section in zone 1, 2 and 3
From table 6, ducts diameter is consistent where the main ducts such as section 1 and 2 has a larger
diameter compare to the branch ducts connected to diffusers such as section 19. The largest diameter
for ducts coming out directly from plenum is 24 inch. By using the diameter and the air flow rate, the
pressure loss through every run can also be calculated. Figure 7 below illustrates the pressure loss for
the longest run in the zone (run 6).
0.5
0.4
Pressure in wg
0.3
Total Pressure
Static Pressure
0.2
0.1
0
0 1 2 3 4 5 6 7
-0.1
Run
4
It is seen that pressure is decreasing steadily as air going further to the diffuser number 6. It is seen from
the figure that both static pressure and total pressure losses does not exceed the supply pressure in the
plenum. An ending static pressure of approximately 0 inch of water column also further indicates that
the room is in an atmospheric pressure. The pressure drop diagram for other zones can be found in
Appendix G on the end of the report.
Appendix G
Zone 11
5
0.5
0.4
Pressure (in-wg)
Total Pressure
0.3
Static Pressure
0.2
0.1
0
Plenum 1 2 3 5 18 16 6 12
Section