Professional Documents
Culture Documents
) Fans Selection
With the calculated flow rate, it is possible to do a fan selection for the main unit and the rest of the air
handler to every zone. From previous section it is noted that around 15,000 cubic feet per minute is
required to be distributed to all zones inside the building. In order to compensate the flow rate required,
a suitable fan has to be selected. 3 major parameters that are used in fan selection is the size of the fan,
type of the fan and the efficiency of the fan.
Considering the three constraint mentioned from previous sections, the team did an online research to
find a suitable fans for the application. The first attempt was to select a single fan that operates under
the calculated air flow rate of 15,000 cubic feet per minute. Table 1 below shows the specification of the
largest forward curved blade fan available from Twin City corporation [ CITATION Twi12 \l 1033 ]. From
table 1, it is found that a fan of 36.5 inches in diameter is required for the application. This diameter is
within the size constraint but it is located on the edge of the range. Therefore smaller fans will be
preferable for such conditions. A low efficiency of 53% also indicates that this fan is undersized and will
be unstable during its operation.
Table 1 Specification of a single fan for main handler unit from Twin City Corporation
Fan Selection TOTAL SYSTEM
Total Flow rate in the Zone (cfm) 15472
Outlet Velocity (fpm) 2000
Total pressure (in-wg) 0.75
Total Static Pressure (in-wg) 0.5
Type of Fan FCV 365
Diameter Size (in) 36.5
rpm 249
Shaft Power (hp) 3.5
Static Power (hp) 1.2
Total Power (hp) 1.8
Total Fan Efficiency (%) 53
Static Fan Efficiency (%) 35
Total Power Main Fans (hp) 7.3
A parallel option is then used to obtain a more desirable result. With the parallel arrangement, the
supply air flow rate is reduced from 15,000 cubic feet per minute to 7,500 cubic feet per minute which
then allow us to select smaller and more efficient fans. Table 2 below depicts the specification for two
parallel fans inside the main unit. Specification for all the fans used in other sub air handler units can be
found in Appendix B.
Table 2 Specification two parallel fans arrangement for main handler unit from Twin City Corporation
From Table 2 above, it can be seen that the efficiency is increased to 63% and is within the acceptable
theoretical range of a forward curved blade fan. The diameter of the fan is also reduced to less than the
attic height constraint of 3 feet. Another notable finding is the parallel arrangement requires less
operating power compare to a single fan unit. A combined power 7.3 horsepower is needed for a single
large fan while only 5.6 horsepower is needed for two smaller fans in parallel. This will provide a good
improvement in terms of power consumption and energy savings.
9.) Appendix B
Fan Selection Fan Zone 1-2-3
Total Flow rate in the Zone (cfm) 4464
Outlet Velocity (fpm) 1294
Total pressure (in-wg) 0.60
Total Static Pressure (in-wg) 0.5
Type of Fan FCV 245
Diameter Size (in) 24.5
rpm 320
Shaft Power (hp) 0.7
Static Power (hp) 0.4
Total Power (hp) 0.42
Total Fan Efficiency (%) 62
Static Fan Efficiency (%) 51
Total Power Main Fans (hp) 0.4