CALCUALTION OF AIR VENTILATION FOR GENERATOR ROOM

I. VENTILATION FOR GENERATOR – 2000KVA


1. Air inlet

Generator performance technical features follow below table.


STAND - BY
ITEM UNIT POWER PRIME POWER
60Hz 50Hz 60Hz 50Hz
Engine Speed rpm 1800 1500 1800 1500
Bore mm 170
(in.) (6.69)
Stroke mm 180
(in.) (7.09)
Displacement liter 65.37
(in.3) (3989)
Brake Horse power with Fan HP 2822 2540 2540 2258
(kW) (2105) (1895) (1895) (1684)
Brake Mean Effective Pressure kgf/cm2 21.9 23.6 19.7 21.0
with Fan (psi) (311) (336) (280) (299)
Mean Piston Speed m/s 10.8 9.0 10.8 9.0
(ft/min) (2126) (1772) (2126) (1772)
Maximum Regenerative Power HP 258 188 258 188
Absorption Capacity without Fan (kW) (192) (140) (192) (140)
Intake Air flow m3/min 182 159 164 141
(CFM) (6426) (5614) (5791) (4979)
Exhaust Gas Flow m3/min 482 420 434 374
(CFM) (17019) (14830) (15325) (13206)
Coolant Flow liter/min 1850 1300 1850 1300
(U.S. GPM) (489) (343) (489) (343)
Cooling Air Flow m3/min 2500 2500 2500 2500
(CFM) (88275) (88275) (88275) (88275)
Fan Loss Horse Power HP 59 59 59 59
(kW) (44) (44) (44) (44)
Radiated Heat to Ambient cal/hr 137302 119695 123581 106406
(BTU/min) (9081) (7916) (8173) (7038)
Heat Rejection to Coolant cal/hr 594974 518678 535518 461093
(BTU/min) (39351) (34305) (35418) (30496)
Heat Rejection to Air to Air Cooler cal/hr 549206 478780 494325 425624
(BTU/min) (36324) (31666) (32694) (28150)
Heat Rejection to Exhaust cal/hr 1485112 1243437 1336706 1105386
(BTU/min) (98223) (82239) (88408) (73109)
Noise Level (1 m height & distance) dB(A) 113 111 110 109
(excludes, lntake,Exhaust & Fan)
a. Incoming data:
- Cooling air flow of generator = 2500 m3/minute
- Intake air flow = 159 m3/ minute
b. Calculation:
- Total air inlet = cooling air flow + intake air flow
Where:
+ Qv1 = total air inlet
+ Qq1 = cooling air flow
+ Qđ1 = intake air flow
 Qv1 = Qq1 + Qdd1 = 2500 + 159 = 2659 m3/ minute = 44.3m3/ second

- Cross section area of air inlet: Sv = Qv/V.h


Where:
+ Sv: air inlet cross section area
+ v: velocity of air inlet (v ≤6m/s)
+ h: free are factor (h = 0.5)
 Sv = 44.3/(6x0.5) = 14.7 m2
Air inlet cross section area = 14.7 m2
2. Air outlet
- Dimension of radiator: Skn = W x H
 Skn = 2200mm x 2200mm = 4.84m2
- Cross section of air outlet louver needed for ventilation Sr =Skn/h
Where:
+ Sr = air outlet cross section area
+ Skn = cross section area of radiator
+ h: free area factor of air outlet baffler (h = 0.5)
 Sr = 4.84/0.5 = 9.68m2
Air inlet cross section area = 9.68m2
II. VENTILATION FOR GENERATOR – 1600KVA

1. Air inlet
a. Incoming data:
- Cooling air flow of generator = 1950 m3/minute
- Intake air flow = 128 m3/ minute
b. Calculation:
- Total air inlet = cooling air flow + intake air flow
Where:
+ Qv1 = total air inlet
+ Qq1 = cooling air flow
+ Qđ1 = intake air flow
 Qv1 = Qq1 + Qdd1 = 1950 + 128 = 2078 m3/ minute = 34.6m3/ second
- Cross section area of air inlet: Sv = Qv/V.h
Where:
+ Sv: air inlet cross section area
+ v: velocity of air inlet (v ≤6m/s)
+ h: free are factor (h = 0.5)
 Sv = 34.6/(6x0.5) = 11.5m2
Air inlet cross section area = 11.5 m2
2. Air outlet
- Dimension of radiator: Skn = W x H
 Skn = 2100mm x 2100mm = 4.41m2
- Cross section of air outlet louver needed for ventilation Sr =Skn/h
Where:
+ Sr = air outlet cross section area
+ Skn = cross section area of radiator
+ h: free area factor of air outlet baffler (h = 0.5)
 Sr = 4.41/0.5 = 8.82m2
Air inlet cross section area = 8.82m2
III. VENTILATION FOR GENERATOR – 800KVA

1. Air inlet
a. Incoming data:
- Cooling air flow of generator = 726 m3/minute
- Intake air flow = 67 m3/ minute
b. Calculation:
- Total air inlet = cooling air flow + intake air flow
Where:
+ Qv1 = total air inlet
+ Qq1 = cooling air flow
+ Qđ1 = intake air flow
 Qv1 = Qq1 + Qdd1 = 726 + 67 = 793 m3/ minute = 13.2 m3/ second
- Cross section area of air inlet: Sv = Qv/V.h
Where:
+ Sv: air inlet cross section area
+ v: velocity of air inlet (v ≤6m/s)
+ h: free are factor (h = 0.5)
 Sv = 13.2/(6x0.5) = 4.4m2
Air inlet cross section area = 4.4 m2
2. Air outlet
- Dimension of radiator: Skn = W x H
 Skn = 1600mm x 1600mm = 2.56m2
- Cross section of air outlet louver needed for ventilation Sr =Skn/h
Where:
+ Sr = air outlet cross section area
+ Skn = cross section area of radiator
+ h: free area factor of air outlet baffler (h = 0.5)
 Sr = 2.56/0.5 = 5.12m2
Air inlet cross section area = 5.12m2