TECHNICAL DIARY
210MW
NTPC
NATIONAL THERMAL POWER STATION
INDEX
Sr. No.
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12
1.13
1.14
1.15
2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.4
3.5
4.0
4.1
4.2
4.3
4.4
5.0
5.1
Contents
BOLIER & AUXLIARIES
Specifications
Performance data
F.S.S.S
Fans (ID, FD, PA,Ignitor & Scanner)
Air Heater
Soot blower
Electrostatic Precipitator
Coal burners & oil guns
Coal mill
Raw coal feeder
Fuel oil transfer pump
Dosing system
Ash handling system
D.M. Make up system
Coal Mill Reject System
TURBINE & AUXILIARIES
Specifications
Governing system
Turbine lubrication system
Condensate system
L.P.Heaters & air ejection system
Feed water sytem
H.P. Heaters
C.W. pump & C.W. booster pump
HP & LP Bypass system
GENERATOR & AUXILIARIES
Generator Specification
Specification Of Static Excitation System Unit
IV & V
Generator Seal Oil System
Stator Water Cooling System
Generator & UAT Transformers
PROTECTION & INTERLOCK
Unit protections
Partial load conditions
Protection & interlock of unit auxiliaries
Electrical protection for unit auxiliaries
PROTECTION RELAYS SETTINGS
Recommended Settings of Generator, GT &
Page No.
4-29
30-46
47-57
58-72
73-86
5.2
5.3
6.0
7.0
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8
7.9
7.10
UATs
Recommended Settings Of 6.6 KV Sections
Recommended Setting Of MCB Relays
NEW C&I SYSTEM COMMISSIONED
OFF-SITE AUXILIARIES
Switchyard
Air compressors
Control structure pump house
Ash Handling Plant
Cooling Tower
Diesel generator
Water Treatment Plant
Old Coal Handling Plant
New Coal Handling Plant
Fuel Oil System
87-89
90-132
SECTION-I
BOILER
AND
AUXILIARY
1.1 SPECIFICATIONS
1.1.1 TYPE Natural circulation , Dry Bottom , Tangentially fired , Balanced Draft ,
Radiant Reheat type with direct fired pulverised coal system.
1.1.2 DESIGNED FUEL
Fixed
Carbon
38 %
Volatile
Matter
26 %
1.1.3 FURNACE
Moistur
e
8%
Ash
Grindibility (HGI )
28 %
55
High Heating
Value
4860 Kcal / Kg
Width
13.86 m
1.1.4
Depth
10.59 m
Height
42.79 m
Volume
5210 cu. m.
Description
Heating
Surface
( sq. m )
No. of
Coils / Tube
Size (mm)
Material
1.
Low Temp.
S/H
8209.5
Upper Bank
67
44.5 x 5
44.5 x 4.5
44.5 x 4.5
44.5 x 4.5
1 Cr , Mo
( SA 213
T11 )
SA210CrAl
SA209T1
SA213T11
2.
Platen S/H
944.5
Lower Bank
67
Terminal
Tubes 67 x 6 =
402
29
3.
Final S/H
1036
119
4.
Ceiling &
Enclosures
540
Roof Panels
120
Front Wall
a) 51 x
4.5/5.6/
7.1/8.8
a) 47.6 x
7.1
b) 47.6 x
6.6
c) 47.6 x
8.6
54 x 4.5
51x 4.5
1 Cr , Mo
( SA
213T11 ) &
SA213T22
2 Cr , 1
Mo
( SA
213T22 )
Carbon Mo
(SA209T1)
Carbon
181
Rear Wall
136
Side Wall 66
x2
1.1.5
51 x 4.5
5.
Reheater
2650
Front assembly
59
Rear assembly
- 89
54 x 3.6
47.6 x 3.4
6.
Economiser
5440
67
44.5 x 4.5
Steel
(SA210GrA
1)
Carbon
Steel
(SA210GrA
1
Carbon Mo
(SA209T)
2 Cr , 1
Mo
( SA
213T22 )
1 Cr , Mo
( SA
213T11 )
SA213T22
SA213Tp34
7A
Carbon
Steel
(SA210A)
ATTEMPERATOR
Type
Spray
No. of Stages
One
1.1.6
FUEL SPECIFICATIONS
A)
COAL
i.
ii.
iii.
iv.
v.
vi.
vii.
Fixed Carbon
Volatile Matter
Moisture
Ash
Grindability
High Heat
Coal size to Mill
Location
Medium of Spray
Between Horizontal Feed Water
& Platen S/H
38.%
26%
8.0%
28%
55HGI
4860 Kcal/Kg
20 mm
B)
OIL
i.
ii.
iii.
iv.
v.
vi.
1.1.7
SAFETY VALVES
No.
per
boiler
1
Size
Set pressure
(kg/cm2)
158.2
Relieving
capacity
(t/hr.)
190.04
161
162.41
144
162.08
195.08
86.73
142
88.06
a)dresser
1775wa
b)dresser
1785
33.4
94.7
dresser
1705 rwd
33.75
34
34.45
30.58
136.01
137.38
138.76
114.93
Location
Make &
type
Drum
a)dresser
1749wa
b)dresser
1749wa
dresser
1739wd
dresser
1538-vx
Super
Heater
SH-electro
magnetic
Relief valve
Reheater
inlet
Reheater
outlet
10000 kcal/kg
4.5% w/w
1% w/w
660 C.
1500 redwood at 37.80 C .
0.98 at 380 C.
1.2
PERFORMANCE DATA
Description
Steam
Steam at
final SH
Outlet
Steam at
Temperature ( C0.)
Flow (t/hr) Load
MCR NCR 60%MCR MCR NCR 60%MCR
210mw
210mw
700
662
420
540
540
540
137
136
13.2
580
575
375
540
540
540
24.5
24.7
14.9
Reheater
Outlet
Steam at
Reheater
Steam
from Drum
Steam
leaving
Horizontal
SH
Steam
leaving
Platen SH
Water
Feed water
entering
economiser
Feed water
leaving
Economiser
Flue gas
Flue gas
leaving
Furnace
Flue gas
entering
Reheater
Flue gas
entering
Horizontal
SH
Flue gas
entering
Eco.
Flue gas
entering
APH
Flue gas
leaving
APH
Air
PA flow at
APH Outlet
SA flow at
APH Outlet
Tempering
- -
332
331
293
26.4
26.5
16.0
- -
342
340
334
150.7
148
137.4
- -
430
433
452
146
144
135.5
- -
514
514
512
- -
247
246
220
153
150
139.2
- -
278
277
262
- -
- -
1125
1135
1118
- -
- -
1020
1017
981
- -
- -
697
690
670
463
459
433
364
366
336
146
143
129
700
643
371
96.7
77.8
70.3
338
336
316
678.3
624.5
481.5
330
329
311
120.8
85.5
92.9
38
38
38
air
919.3
Total
combustion
air
110.1
Fuel
Coal(HHV
=5000Kcal/
Kg.)
1.2.2
869.3
668.2
105.1
71.5
PRIMARY AIR
Description
Units
MCR
NCR
mmwc
mmwc
mmwc
mmwc
mmwc
740
727
672
634
228
734
723
672
634
228
Control load
60% MCR
700
691
661
634
228
SECONDARY AIR
Description
Units
MCR
NCR
F.D.FanOutlet
SCAH Inlet
SCAH Outlet
AH Inlet
AH Outlet
Aerofoil Inlet
Windbox Pr.
Windbox to
Furnace Diff.
mmwc
mmwc
mmwc
mmwc
mmwc
mmwc
mmwc
mmwc
317
312
287
282
193
180
140
140
291
286
265
261
185
174
140
140
Description
Units
MCR
NCR
SH Platen Inlet
RH Inlet
Finish SH Inlet
mmwc
mmwc
mmwc
-5
-6
-14
-5
-6
-13
Control load
60% MCR
213
211
201
198
162
157
140
140
FLUE GAS
Control load
60% MCR
-5
-6
-9
LTSH Inlet
Economiser
Inlet
A.H. Inlet
E.P. Inlet
I.D. Fan Inlet(
Including Static
Head)
1.2.3
mmwc
mmwc
-20
-37
-19
-35
-12
-20
mmwc
mmwc
mmwc
-54
-184
-242
-49
-165
-222
-31
-84
-128
Description
Units
MCR
NCR
No. of Burner
in operation
Burner Tilt
No. of mills in
operation
Mill Loading
Air flow per
Mill
Air Temp. at
Mill Inlet
Mill Outlet
Temp.
Fineness
16
16
Control load
60% MCR
12
Degree
-
0
4
+10
4
+30
3
%
T/hr
80
52.3
79
52.3
70
52.3
172
171
160
77
77
77
70
70
70
1.2.4
% Thru 200
Mesh
Description
Units
MCR
NCR
O2 in Gas at
Economiser
Outlet
CO2 in Gas at
Economiser
Outlet
Excess air in
Gas at
Economiser
Outlet
4.3
4.3
Control load
60% MCR
5.5
14.9
14.8
13.7
25
25
36
1.2.5
Description
Units
MCR
NCR
SH System
RH System
Economiser
System
Kg/cm2
Kg/cm2
Kg/cm2
13.7
1.9
2.1
12.0
1.8
2.0
A.
Air
Wind-box
APH
Air-duct
Aero-foil
mmwc
115
94
63
25
Across Pulv.
Fuel Piping
305
308
C.
Flue Gas
Furnace
S/H & R/H
Eco
Flue gas Duct & Dampers
Regenerative APH
Static Head
Velocity Head & Exit Loss
ESPS
Total Loss
mmwc
4
48
19
52
110
20
20
22
295
Control load
60% MCR
5.4
1.1
1.8
4.63%
2%
0.26%
1.5%
4.9%
13.3%
86.7%
61-100
Nil
8.8-9.2
9.0-9.4
0.007
0.01
0.02
0.5
8.8-9.2
9.0-9.4
0.007
0.01
0.02
0.3
0.02-0.04
Nil
Not allowed
Not allowed
0.005
0.02 - 0.04
Nil
Not allowed
Not allowed
0.005
61-100
100
200
<20
9.0-10.0
2.0
<4000
Nil
Note: # If the Boiler water pH is not maintained in the prescribed limit, residual
Phosphate may be increased but upto 10 ppm only.
Silica value in Boiler water should commensurate with the drum pressure.
1.3 FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FSSS facilitates remote manual/automatic control of fuel firing equipment through
mechanized system and suitable interlocks/logics. The system provides protection against
malfunctions of fuel firing equipment and associated air systems.
1.3.1 FSSS INTERLOCKS AND PROTECTION
1.
i) 220vDC and 110vAC supply to FSSS panel estd.(crl 53 and tdr 10 are both on)
ii) Boiler Drum level normal(CR 169 is off)
iii) At least one ID and one FD fan running(CR 151 is off)
iv) Ignitor trip v/v proven closed(CR 263 is on)
v) Warm-up trip v/v proven closed(CR 279 is on)
vi) All Ignitors oil/air v/vs proven closed(CR12 is on)
vii) All WO and HO nozzle hydromotor v/vs proven closed(CR16 is on)
SR.
NO.
1.
DESCRI
PTION
Ignitor
trip v/v
PERMISSIVE
INTERLOCK
PROTECTION
1. Ignitor Oil
Supply Pr. Is
Adequate (>13kg
/Sq.Cm)
a. ignitor oil
header pr. Falls
below 9kg for >
2sec. And
ignitor V/v not
closed.
b. Boiler trip
command
present(icrl 61
off)
c. When ignitor
trip v/v is closed
v/v closed green
signal comes on
(cr63 on)
1. HO header
pressure is low for
more than 2 secs
(TDR 281 is ON)
2. Steam and
heavy oil
differential pressure
is low (less than 0.3
Kg/Sq.Cm) for
more than 2 secs
and provided no
guns are being
started or stopped
(TDR 287 is ON)
3. Boiler trip
occurs (2 CRL 61 is
OFF)
2. All Ignitor
V/Vs are
closed(cr12 on)
2.
Heavy Oil
Trip
Valve
1. Boiler trip
circuit (MFR)
is reset. (2
CRL 61 is
ON)
2. All HO nozzle
valves of AB,
CD & EF oil
guns are
proven fully
closed. (1
CRL 107 AB,
CD, EF are
ON)
3. HO supply
pressure is
adequate
(more than 7
Kg/Sq.Cm)
4. HO pressure
3.
Heavy Oil
Elevation
start
1.
2.
3.
4.
5.
6.
Heavy Oil
corner
start
1.
2.
3.
4.
are proven ON (1
CR131 AB is ON)
2
25 secs later a
start command is sent
to corner 3 (when pair
1&3 are started) or 4
(when 2&4 is started)
3
When the gun is
fully advanced the
atimising
steam
nozzle valve opens.
4 When the atomising
steam valve is proven
fully open the heavy
oil nozzle valve opens
placing HO gun in
service. (Total time
taken for proving the
pair of guns is 90
secs)
Depressing the associated
elevation pair button will
initiate a 375 secs stop
time trial to shut down
the scavenge the
associated pair of LO
guns as follows.
HO
elevation
shut down
1.4 FANS
1.4.1
SPECIFICATIONS
RPM
1300
Motor
Voltage
KV/V
6.6
50
800
6.6
490
50
1250
6.6
1485
11
415v
1460
Press. Temp
mmwc 0C
KW
Capaci
ty
m3/sec
230.9
387
150
103.8
520.5
65.3
1345.5
400
Sefm
4WG -
Sr.
No.
Descri
ption
Type
No Of
Boiler
ID Fan
FD Fan
PA Fan
Ignitor
Air Fan
Axial
Impulse
Type
Axial
Reaction
Type
Radial
Backward
Curved
Centrifu
Gal
990
1.4.2
A:
2
2
1100
M3
11000
M3
160
50
1.1
415v
3000
150
50
10
440V
2850
S.N.
PUMP
MOTOR
TYPE-Gear type
Power-0.5HP
II
Capacity-5LPM
Voltage-415v
Frequency-50C/S,3
Ph.
Speed-1380 RPM
III
Operating Press-2Kg/cm2
IV
B:
FAN
Fan control
Pump
Type-Gear type
II
Capacity-79.2 LPM
III
Voltage-415V,
Frequency-50c/s,3Ph
Speed-1400 rpm
Rated Current-11
Amp
C:
Sr.N
PUMP
MOTOR
TYPE-Gear type
Power-0.5HP
II
Capacity-5LPM
Voltage-415v
Frequency-50C/S,3
Ph.
Speed-1425 RPM
III
Operating Press-2Kg/cm2
IV
Rated current
1.2 Amps
1.5
1.5.1
AIR HEATER
H.S. IN M2
HEATING ELEMENT
i) Hot layer-864 mm
Open hearth steel
ii) Intermediate
Layer-864mm
Open hearth steel
iii) Cold layer-305mm
corten A steel
SUPPORTING BEARING
i) Type- Spherical Thurst
Bearing
ii) Lubrication-Oil
bath type
iii) 18 Gallons
iv) Motor rating-3/4 HP
ROTOR DRIVE
i)
Motor-GE 15 HP
ii)
Voltage-415v
CLEANING
DEVICE
i) Motor-0.25 HP
ii) Speed reducer
4800:1
GUIDE BEARING
Double roller
bearing
Oil Bath
Oil capacity-4
Gallons
1 to 0.5 HP
AUX.AIR MOTOR
Motor-4 BHP
Air Pr.-5.6 Kg/cm2
Speed-255 rpm
1.5.3
FLOW t/hr
500 PA
NORMAL
ROTATION
mmWC
PRI
SEC
GAS
180
681
999
500 PA
720 PA REVERSE
REVERSE
ROTATION
ROTATION
mmWC
NORMA 20%
L
MORE
165
163
182
697
699
837
999
999
1199
PRI
Air Out
SEC
Air Out
GAS
Gas Out
TEMPERATURE
PRI
Air In
SEC
Air In
GAS
Gas In
97
680
1084
0
C
38
41
369
97
680
1085
0
C
38
41
369
97
680
1085
0
C
38
41
369
116
816
1286
0
C
38
41
369
78
544
884
0
C
38
41
369
PRI
Air Out
SEC
Air Out
GAS
Gas Out
PRESSUR DROP
PRI
Air
SEC
Air
GAS
337
329
146
mmWC C
44
90
112
325
333
146
mmWC
44
90
112
326
334
146
mmWC
22
124
112
321
332
149
mmWC
29
159
146
331
338
142
mmWC
14
107
75
Air In
Air In
Gas In
1.6
Location
i)
ii)
ii)
Furnace
Platen,Convention
Super heater &
Re-heater
Air Heater
20%
LESS
144
561
799
SOOT BLOWER
Header Pr
(Kg/cm2)
30
30
30
Type
Qty./Boiler
Wall
blowers
RWSE
Long
retractable
56
Swiveling
20
Medium
Super
heated
steam
Super
heated
Super
heated
steam
1.7.2
1333709 m3/hr.
1500 C
31.8 gm/m3
2000mmwc
2 FAAX .5x36-9590-2
2
5
133380 m3/hr
1460 C
28.3 gm/Nm3
2000mmwc
2FAA. 5x32-11190-2
2
5
99%
99%
15MMWC
15MMWC
1.08 m/sec.
0.93 m/sec
16.62 sec.
17.243 sec
COLLECTING PLATES
38
1.7.3
UNIT # 5
EMITTING ELECTRODES
No of electrodes in each rows
32
23680
6829M
2.5 mm
Plate/wire spacing
150mm
Type
Spiral with hooks
Spiral hooks
approx one
dropHammer/
Two rows
4.9 kg.
iii) Frequency
iv) Drive
1.7.4
Rapper wt.
1.7.5
ELECTRICAL SYSTEM
RECTIFIER
i) Rating
ii)Number
iii) Type
iv) Location
B)
UNIT # 4
UNIT # 5
Thyristor/microprocessor based)
on controller(PRECICON
20
In the control room at ground level
ii)Number
iii) Location
C)
Geared elec
tric motor
with synch
ronous programmer
Pyramidal
40 (2 per field)
8 hrs. storage
Electrical heating at hopper bottom
A)
10 raps/hr
HOPPERS
i) Type & quality
ii) No. of hoppers
iii) Capacity
iv) Heating
1.7.6
3 kg.
AUX.CONTROL PANEL
i)Number
ii)Equipment controlled
iii) Location
4
Geared motors for rapping mechanism, heating
elements om hoppers & shaft insulators.
In the control room at ground level
D)
MOTORS
For both emitting electrodes
i) Quantity
20 Nos.
ii) Rating
0.5 HP,1.1 rpm at 3 ph,50 c/s , 415v
iii) Location
on the casing side panel
E)
HEATING ELEMENTS
i) HOPPERS
For forty hoppers at the rate of 6 kw /hopper = 240 kw
ii) SHAFT INSULATORS
i)
ii)
COAL BURNERS
i) Type
ii) No. of boiler
iii) Titling limit
B)
IGNITORS
i) Type
ii) NO. off
iii) Location
iv) Capacity
v) Turn down ratio
vi) Oil pr. At control cabinet
vii) Oil firing rate
viii) Atomising air quality
ix) Atomising air pr.
x) Atomising air consumptio
xi) Combustion air quality
xii) Combustion air pr. At wind box
iv) Capacity
v)Turn down ratio
vi) Oil firing rate
vii) Atomising air quality
viii) Atomising air consumption
ix) Atomising air pr.
x)Differencial pr. Between oil & air
C)
i) Type
Tilting,tangential steam atomised internal mix
ii) No. off
12 (4 per elevation)
iii) Location
Elevation AB,CD,EF corners
iv) Capacity
20% of boiler MCR in total
v)Turn down ratio
4:1
vi) Oil firing rate
1320 kg / hr / gun
vii) Oil pr. At gun
8.5 kg / cm2
viii) Atomising steam quality Super heated by 10-15 deg.cent.
ix) Steam consumption
150 kg / hr / gun
x) Steam pressure at gun
9.5 kg / cm2
xi)Differential pressure
1 kg / cm2
between oil & steam
1.9 COAL MILL
i) Type
ii) No. of boiler
iii) System
iv) Capacity
v) Coal grindibility
vi) Max. moisture content
vii)Finness through 200 mesh
MOTORS
i) Rating
ii) Voltage
iii) Frequency
iv) RPM
v) Rated current
vi) No load current
340 kw
6.6 kv 3 phase
50 c/s
990
41.7 Amps
15-16 Amps
chain type
600 mm
iii) Length
iv) Speed variation
v) Depth of coal bed
vi) Capacity max.
12400 mm
1:6
120-200 mm
45 mt / hr.
MOTORS
i) Rating
ii) Voltage
iii) Current
iv) Speed
7.5 kw
415v
15.5 Amps
975 rpm
Capacity
Discharge
Suction
Max. temp. of oil handle
By the pump
TRANSFERPUMP
DRAIN PUMPS
120 m3 /hr
80 MMWC
5 MMWC
600 C
5 m3 / hr
40 MMWC
5 MMWC
600 C
DESCRIPTION
PHOSPHATE
HYDRAZINE
A)
PUMP
I)
ii)
iii)
No. of boiler
Capacity
Type
2
0-100 ltr./hr.
Horizontal
reciprocating
2
0-30 ltr./hr
Horizontal
reciprocating
iv)
Head
195 kg / cm2
110 MMWC
MOTOR
i) Rating
ii) Voltage
iii) Speed
iv) Current rating
2.2 kw
415 v,50 c/s
1430 rpm
4.8 amps.
12 ton/hr.
2.08 ton/hr.
1.74ton/hr
52.36 ton hr/
0.79 ton/hr
12 ton/hr.
56.97 ton/hr.
66.97 ton / hr.
33 M3
9.5 kg/cm2
5.5 kg/cm2
ASH PUMP:
15 m3/hr.
8 kg/cm2
1000 m3 / hr
23-33 MMWC
800 rpm
C)
ASH ANALYSIS
i) Silica
ii) Alumina
iii) Iron oxide
iv) Titanium oxide
v) Lime
vi) Magnesia
vii) Sulfuric acid hydrous
viii) Phosphoric Anhydride
ix) Alkalis
55.09-68.8 %
19.8-29.8 %
3.05-18.3 %
10.0-2.05 %
1.1-2.1 %
0.26-1.2 %
0.4-1.8 %
0.19-0.28 %
0.16-3.04 %
MAKE UP PUMP
5
MOTORS
i) No. 2
ii) Make: Mather & platt
iii) Type: 4/5,two stage MEDI
iv) Discharge-100 m3/hr.
v) Head-50 MMc
vi) Speed-1480 rpm
Make-Crompton greaves
Type-Induction motor
Voltage-415v,3 phase
Current-49 amps
Speed-1475 rpm
MOTORS
i) No.-2
nos
ii) Make : IIIplurovane,5 CHR
iii) Discharge-200 m3/hr.
iv) Head 200 mwc
v) Speed 1480 rpm
Connected to-boiler drum & deaerator.
Make-Crompton greaves
Type-AC induction motor
KW/HP- 187/250,voltage-6000v
21 amps.
Speed 1483 rpm
UNIT ENTIRELY
FILLED (M3)
37.20
126.3
97.18
48.10
25.17
12.05
------------345.00
-------------
UNIT FILLED TO
OPERATING LEVEL (M3)
11.53
126.30
------25.17
---------------163.00
-------------
DESIGN DATA:
Maximum Quantity of rejects per mill
3 TPH
Normal Quantity of reject per mill
1.7 TPH
Average Mean Reject rate per unit of 210 M
9.8 TPH
Average quantity of rejects per day for
470 Tones
2 x 210 MW units
Density of mill rejects is taken as 1.6 T/m3 for volumetric computations
and 2.2 T/ m3 for load/strength computations.
1.15.3 DESIGN CAPACITY PROVIDED IN THE SYSTEM:
Removal capacity at each mill
3 TPH
Removal from storage bunker to tube mill of 100 MW unit 5 TPH
Storage bunker capacity
80 m3
2
5 m3
SECONDARY SYSTEM:
From storage bins to stage-I mills 2C & 3C
Air receiver capacity for secondary system: 10 m3
1.15.6 DENSEVEYOR
Model
System : batch conveying
Vessel capacity:
Pipe size
Design Code
Safe working pressure
Hydraulic test pressure
12/8
12 Ft3
150 mm
BS5500 Class III
110 lb/in2 (7 kg/cm2)
150 lb/in2 (10 kg/cm2 )
Screw
SES-520 single stage
520 cfm +/- 5%
Khosla Indair
7 kg/cm2
4500 RPM
FAD 520 +/- 5% cfm
91%
105.0 HP
130.0 HP
Cylindrical roller and 4 point
Bearings
Oil flooded (forced feed)
EN-8
EN-41B
Mfd.Std.
(coupling) forged steel,
rubber flexible
EN-8
Base plate
Type and size of suction and
discharge valve
Details of special features
Total cooling water quantity
required at 360C
Cooling water out let temp.
MS
Butterfly suction valves MS (CI body) DK-100 (4")
After cooler and oil coolers
150 LPM
100 C above inlet temp. Oil
cooler and after cooler.
Air Pressure drop through the after cooler/oil cooler 2-3 psi
Cooling water inlet/outlet size
1" & 3/4" BSP
Cooling water quantity required at 360 C
150 LPM
Air outlet temp.
100 C above cooling water
temp.
1.15.9
VIBRATORY FEEDER
Approx. weight
940 lb
Type of control panel
Thyristor controller
Type of protection of control Conforming to IP - 54.
panel
SECTION - II
TURBINE
AND
AUXILIARIES
2.1 SPECIFICATION
2.1.1 TURBINE MAIN DATA
Rated Power
210MW
Rated Speed
3000 rpm
Rated Steam(Pressure) before ESV
130 Kg/cm2 abs
Rated Steam Temp. before ESV
5350 C
Rated Steam pressure Before IV
27 Kg/cm2 abs
Rated Steam temp. Before IV
5350 C
Rated Steam Flow
670 T/Hr
HPT Exhaust Pressure
27 Kg/cm2
HPT Exhaust Temperature
3270 C
Rated circulating water quantity
27000 M3
through condenser
Condenser back pressure
0.09 Kg/cm2
Critical Speed
1585,1881,2017&2489
Rated condenser cooling water inlet
240 C to 330 C
temperature
Rated condenser cooling water
1.0 to 1 Kg/cm2
pressure
Type of governing
Hydro mechanical
Nozzle type governing
Type of turbine
condensing, Tandom compound
Three cylinder, Horizontal
Nos. of bearing
5 Nos.( for turbine side only &
HPC front bearing
is combined thrust & journal bearing
Barring gear
3.4rpm, ac motor of 30kw, 730rpm, 50c/s,
415v, 220:1 Ratio
Location of anchor point of
At the middle foundation frame of front
the turbine
exhaust part of the L.P. Cylinder
2.1.2
CONSTRUCTIONAL DETAILS
i) H.P. CYLINDER
BODY
STUDS & NUTS
NOZZLE & STEAM
CHEST
ii) I .P. CYLINDER
BODY
BODY
iv) H.P.ROTOR
v) I.P.ROTOR
2.1.3
STEAM EXTRACTIONS
No of
extractions
Ist (HPT)
Iind (CRH
IIIrd (IPT
IV (IPT)
V (IPT)
VI (IPT)
VII (LPT)
Steam
extraction
stages
9th
12th
15th
18th
21st
23rd
25th
Connected
to
HPH-7
HPH-6/D/A
HPH-5/D/A
LPH4
LPH3
LPH2
LPH1
Ext, steam
press in Kg/
cm2
39.06
26.2
11.96
6.47
2.78
1.28
0.28
Ext.steam
temp.in 0C
in
337
314
433
3680C
252
172
-
Steam flow
T/hr.
400
77
16.2
26
23
28
12.6
2.2
GOVERNING SYSTEM
TYPE: Hydro mechanical automatic governing.
i)
SPEED GOVERNOR:
Directly coupled to turbine rotor through coupling & hydraulically coupled to
speed governor pilot block located front pedestal.
PUPPOSE: Sensing of any speed due to difference between power generated
by turbine & load on it. For this governor sleeve moves proportional to speed
change. ( Range is 4+1% speed change.)
ii)
iii)
iv)
v)
vi)
vii)
LOAD LIMITER:
PURPOSE: To limit the load raising beyond set point by limiting the
opening the control valve by speed governor.( its continuos operation is not
recommended.)
viii)
DIFFERENTIATOR:
PURPOSE: It prevents undue speed rise in case of more than 50% load
through off which causes anticipatory closure of control valve of HPT and
IPT.
ix)
x)
xi)
EMERGENCY GOVERNOR:
PURPOSR: It consists of two centrifugal strikers which operates and trip the
turbine in case 11 to 12% of over speed by closing ESV, IV , HPT and IPT
control valve.
xii)
xiii)
xiv)
EVENT
IV begins to open
ESV begins to open
IV fully open
ESV fully open
IPT & HPT control
valve begin to open
12.8 mm
2.3
28000 Lts
4000 Lts
6000 Lts/Hr
6000 Lts/Hr
6000 Lts/Hr
40 m3 each
45 m3 /Hr, 18 MWC
20 Atg
16 Atg
1Atg
250 Kw
Flexible gear type
2 Nos.
1 Kg/cm2
3 Kg/cm2
3000 rpm
200 Kw
1000 rpm
6.6 KV,3 Ph, 50 C/s
Horizontal
PUMP
Type
150COAV ,BHEL
(multistage, centrifugal oil
Pump, driven by motor)
150 m3 /Hr,(2500 L/Min)
30 MWC
2
Capacity
Head
No. of stages
C/S
Arrangement
Vertical
Impeller material Bronze
Min. oil pressure 0.6 Kg/cm2 For auto starting
MOTOR
Type 22F Q UE/O
Power 25 Kw
Speed 960 rpm
Current 52 amps
Voltage 415 volts,3 Ph, 50
BEARING
Type
Number
Lubricant
2.3.6
PUMP
Type
MOTOR
Power 13 Kw
Voltage 220 volts D.C.
Current 67.6 amps
Speed
1500 rpm
Type
D-62
Capacity
Head
108 m3 /Hr
(1800 L/min)
22 MWC
BEARING
1. 1 no double row self aligning ball bearing for free end.
2. 1 no. double row self aligning spherical roller bearing.
2.3.7
PUMP
MOTOR
MAB-206-S-20
6000 Lts/hr
6000 Lts/ hr
2.35 Kg/cm2
1500 rpm (max)
KW(HP)
7.5(10)
Frequency 50 Hz
Voltage
440 Volt
Current
13.6 amps
Speed
1440 rpm
LUBRICANTS
Lubrication points: (1) Worm gear housing (2) bowl
(2) Bowl spindle(4) bearing of coupling
(3) Gears of lifting devices (60 motor
HEATER
Type
KW
Voltage
2.3.8
WH
120
440 volts
No. of coolers
Cooling surface area of oil coolers
Quantity of oil cooled
Water consumption
No. of water paths
Designed oil pressure
Designed water pressure
Working pressure of oil
Working pressure of water
Inlet oil temperature
Outlet oil temperature
Inlet water temperature
Outlet water temperature
Rated oil velocity
1.25 M/sec
1.6 MWC
19/17 mm
400 Kcal/m2 Hr 0C
1.48 Kg/cm2
22
21
8 Kg/cm2
CONDENSER
0.1 Kg/cm2
2*13500 m3/hr
2*7810=15620
10 mts
30/28 mm
305 tonnes
190/10
70/30
Rolled steel plates
5 Kg/cm2 Gauge
MOTOR
75 0C
75 0C
40 microns
180 0C
L.P.HEATERS
LPH Type
No.
1
Inside upper
part of each
condenser( in
two halves)
2
Mezzine floor
Location
Tube
material
Horizontal
U. shape
surface type brass
16*10
Vertical
--DO-surface type
--DO---DO---DO---DO--
3
4
--DO---DO--
2.5.2
Shell
Tube plate No. of relief
Material
material
valve
Fabricated Mild Steel 2 Nos.(1 for
steam side&
from MS
1 for cond.
plates
side
--DO---DO---DO---DO---DO--
--DO---DO--
--DO---DO--
FUNCTION
a. Eject steam and air mixture from turbine seals
b. Eject spindle leak off from ESV, IV & control valves
Gland sealing steam pressure
1.03 to 1.05 Kg/cm2
Source of gland sealing steam
16 ATA header or D/A
Temperature of sealing steam
1300C to 1500C
Type of seals
Labyrinth glands of radial clearance type
2.5.3
DRIP PUMP
PUMP
Nos. 2(100% capacity)
Type 100 CJH, multistage centrifugal
Horizontal pump
No. of stages
9
MOTOR
Output
Voltage
90 KW
415 V
Current
148 amp
Delivery quantity
Manometric head
Speed
Temp. of liquid
2.5.5
1416 L/min
195 MWC
1475 rpm
1000C max
Speed
Frequency
1475 rpm
50C/S
DEAERATOR
Deaerator pressure
7 Kg/cm2
Deaerator temp.
1700C
Quantity of limiting
0.005 cc/Lit
gases (mainly O2) in feed water
Steam source
Aux source( In starting)/2nd or 3rd Extraction of turbine
Design
Direct contact type heater in two parts
(a) Deaerating Coulmn: Horizontal spray cum tray type fabricated from boiler quality
steel plates, meant for deaeration of gases(O2) from water
(b) Feed storage tank : Horizontal, fabricated from boiler quality steel plates. Means for
water storage and heating
Source tank capacity
87.5 m3
Deaerating capacity
759.110 kg/hr
Test
200 Psig. (14 kg/cm2)
2.5.6
Steam
consumption
in kg/hr
D/A or 16
ATA
header
--Do--
Steam
pressure
in
kg/cm2
4.5
250
1100 kg/hr
4.5
250
750 each
--Do--
4.5
250
1100
--Do--
4.5
250
Type of
ejector
Nos.
Range
Aux.
source of
steam
A)
Starting
ejector
B) Main
ejector
C)
Priming
ejector
D) Gland
steam
cooler
No.1
Up to 450 mm
Hg column in
condenser
Up to 760 mm
Hg column in
condenser
Up to 200 mm
Hg column in
condenser
Eject steam
and air mixture
from end gland
seals of main
turbine
A) PUMP
No. of pumps
Type
Nos. of stages
Max. rated suction pressure
Discharge capacity
Head
Feed water temp.
Speed
Lubrication
Stuffing box
Quantity of water for
minimum take off
Min. suction pressure of BFP
Quantity of water for
Heating take off
Cooling water consumption
Net weight of pump
Drive
B)
MOTOR
Manufacturers
Type
Output
Rated Voltage
Current
Speed
Frequency/ power factor
2.6.2
OPERATING DETAILS
BOOSTER PUMP
No. of pump
Use
H.P.HEATER No.5
166.76
H.P.HEATER No6
184.92
H.P.HEATER No7
220.90
170.70
189.51
227.48
184.92
220.90
242.78
189.51
229.48
251.41
643165
11.96
643165
26.20
643165
39.06
433
314
377
Enthalpy of Ext.
steam in Kcal/kg
Steam flow (kg/hr)
No. of coils
796
727
754
16271
292
44777
288
29880
288
No. of pumps
Make
Number of stage
Capacity of pump
Total dynamic head
Efficiency
Speed
B.H.P.
Motor
Type of pump lubrication
Direction of rotation
Coupling of motor & pump
CW water is used in
2.8.2
60 to 70 Mw
89 kg/cm2
102 kg/cm2
2 Nos.(100% capacity)
FLOWMORE
One
15000 m3 /hr
11.5 MWC
86%
420 rpm
740 HP
BHEL, 950HP,6.6 KV splash proof type
Self water lubricated
Anti clock wise (from top)
Rigid type
Condenser, Main oil coolers& H2 gas
coolers
PUMP
No. of pump
Lubrication in board &
Outboard bearing
Speed
Make
Discharge pressure
Normal bearing temperature
Normal pump vibration
2 Nos.(100% capacity)
Mobilux grease No.2
1487 rpm
Mather Greaves Pvt. Ltd.
2.5 kg/cm2
600C
40 microns
MOTOR
Output
Speed
Amps
55 KW
1487 rpm
96
Voltage
Make
415 V
NGEF
(ii)
2.9.1
Provided to increase the rate of steam temperature rise and warm up the
HRH,CRH, IPT & transfer pipe lines ( at 60% MCR full pressure & temp. can
be obtained i.e. 60% capacity)
All the HP & LP BYPASS valves are hydraulically operated for which oilat
about 50 kg/cm2 is supplied by a separate oil supply unit.
DESIGN CAPACITY OF H.P. BYPASS STATION
Injector water
Nos. of H.P. Bypass valve
Total capacity
Capacity of each bypass valve
Max. MS temp.
Max MS pressure
Down stream temp
2.9.2
Injector water
Nos. of LP Bypass valve
Capacity of each LP bypass valve
Total capacity
Design temp.
Down stream temp
Steam pressure at upstream side
2.10
Condensate water
1 for each HRH line
112T/hr steam flow
224T/hr steam flow
5400C
2000C (max)
6 kg/cm2
4
5
7
8
5 Mw to 30 Mw @ 3 Mw/10 mts
in 70 mts.
Steam pr before ESV =65 Kg/cm2
Steam Temp =4300C
Steam temp before IV =4200C
Soaking time = 20 mts
( All the drain valves in extraction
lines of LP heaters to be closed.)
Raise from 30 Mw to 70 Mw @ 1
Mw/ min in 50 mts.
Steam pr before ESV =105
Kg/cm2
Steam temp before ESV=4900C
Steam temp before IV=4800C
Soaking time= 30 mts
Raise from 70 Mw to 210 Mw in
From 30 Mw to 65
Mw in 35 mts.
Soaking time =35
mts.
Steam
pr
=90
2
Kg/cm
Steam temp =4500C
From 60 Mw to 210
Mw = 45 mts
Depending
upon
other conditions
SECTION-III
GENERATOR
AND
AUXLIARIES
247000 KVA
210000 KW
15750 V
9050 A
0.85 lag
2600 A
310 V
3000 rpm
50 Hz
0.49
98.49%
122t nots
Anticlockwise
Double star
9(6neutral & 3 phase)
THW-210-2
3.1.2
A.
3. 5 Kg/cm2
+/- 0.2 Kg/cm2 (G)
440C
97%
60%
1.2%
370C
150C
350 m3/Hr
4 Kg/cm2 (G)
95 m3/Hr
110 m3/Hr
130 m3/Hr
ELECTRICAL DATA
10 Pu
3.3 Pu
1.4 Pu
REACTANCES
2.0
1.6
10 Secs
100 milisecs
0.214 Pu
0.305 Pu
2.22 Pu
0.26 Pu
0.105
1050 C
1050 C
1150 C
710 C
750 C
850 C
750 C
TIME CONSTANTS
7 secs
0.96 secs
1.5 secs
1.73secs
0.29 secs
0.24 secs
0.25 secs
0.121 secs
56 M3
120 M3
168 M3
300 M3
340 M3
15 M3
(max)
76.32 Tons
8
21.1 T.M2
1370 rpm
3400 rpm
300lit/min
0.3to 0.5
Kg/cm2
160 lit/min
3960 mm
6580 mm
9770 mm
1075 mm
175,000 Kg
1415 Kg
42,000 Kg
49,500 Kg
85 Kg
2000 Kg
239,000 Kg
p.u.
p.u.
0.234
0.266
c)
i)
ii)
p.u.
p.u.
0.179
0.214
8.
i)
sec.
ii)
iii)
iv)
sec.
sec
sec.
0.84
0.03
0.29
9.
Rf 20 ohm
0.0878
10
i)
ii)
iii)
iv)
v)
vi)
vii)
viii)
ix)
VDC
ADC
VDC
ADC
VDC
ADC
VDC
ADC
Sec.
102
917
310
2600
338
2830
620
4500
10
11.
12.
13.
14.
15.
16.
B)
1.
2.
3.
4.
15
5.
6.
7.
8.
9
%
+ 0.5
% 90 Ugn -110 Ugn
% 70 Ufo-110 Ifn
%
upto +
Hz
No
No
IP
47.5-52
4*
1*
31
VDC
ADC
338 *
2830 *
10
11
-MAX. LEAD-O-MAX-LAG
VDC
220
Kvrms
%
AAC/AAC
VAC/VAC
oC
meters
15750/110
50
1000
3.3
3.3.1 SPECIFICATION
i) Type of shaft seals
ii) Hydrogen pressure
iii) seal oil pressure
iv) Inlet seal oil temperature
v) Quantity of seal oil/seal
vi) Thrust oil pressure
vii) Oil required to fill the system
20 Kg/cm2
1 to 1.5 Kg/cm2
8 mm
10 Kg/cm2
MOTOR
i) Type: Compound wound self excited type
ii) Rating: 26 KW
iii) Voltage: 220VDC+10% & -20%
iv) Speed: 1800 or 2900 rpm
v) Rated current: 139 Amp.
vi) Operation Speed: 70-80% of rated speed
2 Nos.
500C
400C
160 lit/min
10 Kg/cm2
420
15*1 mm, copper
5 mwc
330C
37.500C
5 Kg/cm2 (Max)
95 m3/Hr
Clarified water
PRESSURE REGULATOR
MOTOR
i)
ii)
iii)
iv)
v)
vi)
650C
400C
330C
36.50C
95m3/Hr
5 Kg/cm2(max)
15*1mm
1720mm
420
Copper
C. EXPANSION TANK
i) Material:
ii) Tank volume
iii) Volume inside the tank
iv) Water level under normal operating
conditions( from the bottom of the tank)
v) High water level which gives signal
( from the bottom of the tank)
vi) Low/ emergency water level requiring tripping of TG
( from the bottom of the tank)
Stainless Steel
2.1 m3
250 to 300 mmof Hg
850 mm
1200mm
500mm
Clarified
7 to 10m3/Hr
2 Kg/cm2
330C
TRANSFORMER RATING
Make
Type of cooling
MVA
Voltage (HV)
Voltage (LV)
Current (HV)
Current (LV)
Phase HV/LV
Impedance
Frequency
Vector Group
Connection HV/LV
Max temp rise in oil
Temp rise in winding
Weight of core and winding
Weight of oil
Total weight
Quantity of oil
Tap
587/411/293 A
8798/6158/4399 A
3/3
15.55 %
50 Hz
Yd1
Star / Delta
45 Deg C
55 / 60 Deg C
133000 Kg
43100 Kg
238900 Kg
42500 liter
Off load
BUSHING CT
Ratio
Continuous current
Accuracy class
Minimum knee point voltage
Max exciting current at knee point voltage
Max secondary wdg. Resistance at 75 Deg C
3.5.2
600 / 1 Amp
800 Amp
P.S.
1000 Volt
0.14 Amp.
3 Ohm
TRANSFORMER RATING
Make
Type of cooling
MVA
Voltage (HV)
Voltage (LV)
Current (HV)
Current (LV)
Phase HV/LV
Impedance
Frequency
Vector Group
Connection HV/LV
Max temp rise in oil
Temp rise in winding
Weight of core and winding
Weight of oil
Total weight
Quantity of oil
Tap
Off load
BUSHING CT
Ratio
Continuous current
Accuracy class
Minimum knee point voltage
Max exciting current at knee point voltage
Max secondary wdg. Resistance at 75 Deg C
600 / 1 Amp
800 Amp
P.S.
1000 Volt
0.14 Amp.
3 Ohm
2 / Unit
EMCO, Mumbai
12500 KVA
15.75 / 6,9 KV
458.2 / 1045.8 Amp
3/3
ON
Dd0
7.877/7.57 (UAT4A/4B)
7.762/7.725 (UAT 5A/5B)
50 Hz.
On Load
45 Deg C
12000 Kg
6430 Kg
27100 Kg
SECTION IV
PROTECTION
AND
INTERLOCK
4.1
Sl.No.
DESCRIPTION
1
2
3
4
5
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
UNIT PROTECTIONS
ANNUNCIAT
ION
-100 mm
+100 mm
+25 mmwcl
-25 mmwcl
TRIPPING
VALUE
-175 mm
+175 mm
+175 mmwcl
-175 mmwcl
650 mm Hg
750 mm
540 mm Hg
4250 mm
750C
800C
15 secs
+1.2 mm
-1.7 mm
50% of rated
value
11% and 12%
overspeed
14% overspeed
0.3 kg/cm2
TIME DELAY
More than 2
secs
5 to 10 secs
23
24
25
4.2
5200C
-
4500C
-
4.3
Descripti
on
ID Fans
Permissives
Ineterlocks
Protections
a. Bearing temperature
a. Opening of
a. Regulating
too high
outlet damper
vane FG-10 in
b. Motor bearing
FG-12 after a
minimum
temperature too high
time delay of 60
position
c. Lub. Oil pressure for
secs.
b. Outlet damper
motor bearing low
FG-12 closed b. Connecting the
with T.D. of 0-3 mts.
regulating vane
c. Fan/fan motor
d. Both A.H. A&B off (
(FG-10) to
bearing
Provided deregulator
temperature is
interlocking in inter
not very high c. Opening the
locked position)
interconnecting
damper FG-5&
FG-18
d. Closing the
inlet damper
FG-17& outlet
e.
f.
FD fans
Air
Heater
damper FG-13
of other fan
Bringing the
other fan inlet
vane to
minimum
position
Permiisive to
start selected
FD fan
Opening the
outlet damper
BA-3 with T.D.
of 60 secs.
Connecting the
impellar blade
(BA-1) control
drive to
regulator.
Opening the
inter connecting
damper BA-2.
Closing the
outlet damper
of other fan.
Bringing the
impeller blades
of other fan to
min. position.
a. ID fan is
started
b. Control oil
pressure is
adequate(8
kg/cm2)
c. Fan impellar
blades are in
min.
position.(BA1)
d. Outlet damper
(BA-3) is in
closed
position.
e. FD fan
bearing temp.
is not high.
f. FD fan motor
bearing temp.
is not high.
a.
Establish electric
supply to A.H.
motor.
Take out the push
button of the
motor.
Wherever A.H.
trips impulse is
given for starting
air motor provided
guide/supportbearing temp. is
less than 700C.
When A.H. trips
impulse is given for
closing the flue gas
inlet and outlet
dampers FG-1 &
FG-3 and air inlet
& outlet dampers
b.
c.
d.
e.
Ignitor
fan
At least one ID
and one FD fan
must be in
service.
When start push
button is pressed.
Scanner
fan
Primary
air fan
a. The scanner
duct to
furnace
differential
pressure is
less than 115
mmwcl.
b. When start
push button is
pressed.
a. Purge
complete &
NO boiler trip
condition is
present.
b. Regulating
vanes BA-17
in min.
position.
c. Outlet damper
BA-19 in
closed
position.
d. Lub oil
pressure is
adequate
around 2
kg/cm2
e. PA fan
bearing temp
not very high.
BA-12, 14,22&24.
Tripping of
corresponding ID
fans.
Discharge damper
will open & damper
of standby fan
closes.
The fan will start
automatically when
any ignitor or oil
elevation is
initiated.
Discharge damper
will open & damper
of standby fan
closes with T.D. of
5 secs.
a. Fan discharge
damper BA-19
opens with T.D.
of 60 secs.
b. Fan inlet
regulating inlet
vane BA-17 is
connected to
regulator.
c. Inter connecting
damper BA-21
opens.
d. Regulating vane
of other PA fan
closes to min.
position(BA18)
e. Outlet damper
of other PA fan
closes.(BA-20)
f. Load is reduced
by tripping
bottom mills
Seal air
fan
One PA fan is
running
Pulverise
r
a. Discharge
valve are
open.
b. Seal air valve
is open.
c. Cold air shut
off gate is
open.
d. Feeder inlet
gates are
open(Check
only)
e. Tram iron
hopper valve
is open
f. Primary air
pressure is
aduquate.
g. D.C.power to
FSSS is
available.
h. Pulveriser
outlet temp. is
less than
940C.
leaving top
three mills in
service when
one PA fan is
running.
g. When both PA
fan trips all
running mills
will trip.
h. When one PA
fan is running
partial load
relay is
energised.
Manually fan can
be tripped only if
all the mills are
stopped.
Only one seal air
fan can be started at
time.
a. Permissive to
open the hot air
gate.
b. Permissive to
start R.C.feeder.
c. Permissive for
regulators
impulse to act
on hot air
dampers.
Pulverise
r A*
Raw coal
feeder
i. Burner tilt is
horizontal and
air flow is less
than 40%.(
This is
applicable
only to the
first mill to be
started.)
j. Pulveriser
ignition
energy is
available.
a) A min of 3
out of 4
elevation AB
light oil(or
heavy oil)
noozle valve
proven open.
b) Boiler loading
is greater than
30% and
pulveriser B is
in service at
greater than
50% loading.
1) No boiler trip 1) To release
speed control to
condition
auto after 50
persists
secs.
2) Elevation
2) To modulate
D.C. is
fuel air dampers
available
according to
3) Elevation
feeder speed
A.C. is
after 50 secs.
available
4) Ignition
energy is
available.
5) Pulverisor is
on
6) Hot air gate is
open
7) No stop signal
8) Fuel damper
closed
3)
FD fan
lub oil
system
4)
pressure below a
set value and
pump B is
working provided
A/M switch is in
auto position.
Pump B will start
automatically
after 1 secs if
pump A trips
provided A/M
switch is in auto
position.
11
PA fan
Pump A will start
automatically if
pump B trips
provided A/M
switch is in auto
position .
Pump B will start
on auto with time
a delay of 1 secs
if pump A trips
provided A/M
switch is in auto
position.
Furnace temp
If furnace temp
12
Furnace
probe shall be
probe is inside the
temp
prohibited from
furnace and temp.
probe
being advanced
exceeds 5400C it
further into the
will be retracted
furnace if furnace back automatically
temp sensed by it
is more than
5400C
*For pulveriser B to F all conditions regarding their permissive to start, interlock and
protection will be similar as for pulveriser A., except the adjacent elevation nozzle valves
proven open or adjacent pulveriser should have loading more than 50%.
4.3.2 TURBINE AUXLIARIES
Sl.
No.
1
Description
Permissive
Interlock
Protections
Boiler feed
pump
1. Lubricating
oil pressure at
bearing
Circulating
water pump
CW
boosr\ter
pump(Gas
cooler
booster
should be 1
kg/cm2
2. Suction
pressure at
suction of
booster pump
should be
more than 3
kg/cm2 in hot
start up.
3. If suction
pressure at
suction at
booster pump
is less than 3
kg/cm2 for
more than 20
secs. Pump
will trip.
4. Suction
valve
(BF1/2/3) is
fully open.
5.
Recirculation
valve (BF22/23/24) is
fully closed.
1.
Correspondin
g condenser
outlet valve
(CW1&2) is
fully open.
1. At least one
CW pump
should be
inservice.
1. On closing of
discharge valve
CW-1&2 pump
will trip.
2. CW pump will
trip if its motor
bearing
temperature is
more than 800C
3. When both CW
pumps trip CW
booster pump
trips.
1. CW booster pump
will trip if both CW
pump trip.
2. Pump will trip if
motor current goes
pump)
Condensate
pump
A.C. Lube
oil pump
Drip pump
Heater 6
10
HP Heater 5
Pump will
start only if
HD-3(
discharge
valve) is
closed &
opening of
regulating
valve HD-3 is
more than a
preset value.
1.HPH will be
bypassed through
group bypass
protection valve at 750
mm drip level.
2.Turbine will trip at
HPH level 4250 mm.
11
Deaerator
12
H.P.& L.P.
Bypass
system
13
Extraction
Auxiliary
steam to
D/A through
ES-7,ES6&As-57
14
Chamber
heating
valve As43& 44
verses
spindle leak
off valve
I.S.P.U.G.(I
nitial steam
pressure
unloading
gear)
Extraction
NRV on
extraction
lines
Load limiter
15
16
17
manual.
6.When HP bypass valve is
less than 2% open a tight
closure signal is given to
valve 03.01 when it is not
in operation so that spray
water temp valve02.01 is
not subjected to high water
pressure.
1. When extraction steam
pressure build up to the
preset value (9 kg/cm2) for
3rd extraction (Es-7) will
open & Es-6 & AS-57 will
close.
2.When set value of
extraction pressure is more
than 3rd extraction set value
but less than 2nd extraction
then ES-6 will open & ES7 & AS-57 will close.
3. When extraction
pressure of 3rd & 2nd
extraction is less than the
set value ES-6 & ES-7 will
close & AS-57 will open.
4. On turbine tripEs-6 &
ES-7 will close &AS-57
will open.
1. If As-43 is open then
As-47 will close.
2. If As-44 is open then
As-48 will close.
18
A.C. Seal
oil pump
19
D.C. Seal
oil pump
SECTION V
PROTECTION
RELAYS
SETTINGS
5.1
Sr.
Relay
No.
1. Generator Differential
(87 G)
2. Generator Inter Turn
Fault (87 TG)
3. Over All Differential
(87 GT).
4. GT Back up Earth
fault (51 NT)
5. GT Restricted E/F
(87 NT)
6. Gen Over Voltage
(59 G)
Relay
Type
CAG 34
CTR /
PTR
10000/5 Amp
CAG 14
DTH32
Range
Setting
0.25 - 1 A
0.25 Amp
3000 / 5 Amp
1- 4A
4.0 Amp
15% of 5 A
CDG 11
GEN &UAT10000/5
Bushing &
Switchyard 600/1
ICT 1.0 /
2.6 A
600/1
CAG 14
600/1
0.2-0.4 A
PS-0.2 A,
TMS-0.4
0.2 Amp.
VAGM
22
VTT 11
15750/110 V
110 140 %
121 Volt
1.0 to 10 sec
2.0 Sec.
CTU 12
10000/5 A
YCG 15
VTT11
VTT11
CAG 19
VTT 11
CTN 31
10000/5 A,
15750/110 V
VTT 11
CAG 37
VAT 11
VTT 11
DTH31
600/5A
10000/5A
600/5 A
HV=600/5 A
LV=1250/5A
Bias 15,30
& 45 %
High set
1000 %
Fixed
0.1-0.4 A
50 200 %
05 5 Sec
15 % of 5
Amp.
30 %
1000 %
Fixed
102 %
2.5 Sec
K1=6 K2 = 1
0.5 5 Sec St-I 2.5 Sec
St-II- 3Sec
1 10 Sec
2.5-5 A
4.375 A
1 10 Sec
4.0 Sec
A - 70%
T 15%
60 Sec
6 60 Sec
12 A
10-40A
0.5 Sec
0.5 3 Sec
0.5 Sec
0.5 3 Sec
Current Current -15%
15%
of 5A
Bias=30%
Bias
High Set =
15,30,45%
1000 %
High Set =
Fixed
1000 %
Sr.
Relay
No.
13. Stator Earth Fault
(64G)
14. 1ST Rotor E/F (64F1)
15. 2ND Rotor E/F (64 F2)
16. Generator
Transformer Over
Fluxing (99)
17. Low Forward Power
( 37)
18. Reverse Power
( 32)
2/ 32 A
2/32 B
19. Anti Motoring
Protection
(2/32 YA & 2/32YT)
20. Generator Loss of
Field (40)
Relay
Type
VDG14
CTR /
PTR
15750/110 V
VME
VTT 11
CAEM
GTT21
15750/110 V
WCD 11 15750/110 V
10000/5A
VTT 11
15750/110 V
WCD 11 10000/5A
VTT 11
VTT 11
VAT11
VTT 11
YCGF
11
VTT 11
VTT 11
VAGM
22
ZTO 11
SKE 11
Range
Setting
V=5.4-20 V
PS=12.5V
TMS=0.3
4 mA
2.0 Sec
1.1 mA
K=1.125
4 mA
0.5 5 Sec
1.1 mA
K=1-1.25
T=12-120
Sec
0.5 %
1 - 10 Sec
2 Sec
0.5 %
1 10 Sec
12 - 120 Sec
0.5 5 Sec
6 60 Sec
0.5%
2 Sec
120 Sec
5 Sec
10 Sec
1-10 Sec
5-25 Sec
44 88 Volt
K1=0.845,
K2=3.5,
K3=0.5,
K4=3,
K5=18.6
2Sec
10Sec
PS-80.5 V
15750/110 V
10000/5A
15750/110 V
15750/110 V
10000/5A
T=15 Sec
0.5%
5.2 Amp
75 Deg elect
Offset=
3.156 Ohm,
T=52.5mSec
Phase
Angle=10%,
Voltge=6%,
F=0.11%
Sr.
Relay
No.
1. Generator Differential
(87 G)
2. Generator Inter Turn
Fault (87 TG)
3. Over All Differential
(87 GT).
Relay
Type
CAG 34
CTR /
PTR
10000/5 Amp
CAG 14
DTH32
Range
0.25 - 1 A
0.25 Amp
3000 / 5 Amp
1- 4A
4.0 Amp
15% of 5 A
4. GT Back up Earth
fault (51 NT)
5. GT Restricted E/F
(87 NT)
6. Gen Over Voltage
(59 G)
CDG 11
GEN &UAT10000/5
Bushing &
Switchyard 600/1
ICT 1.0 /
2.6 A
600/1
CAG 14
600/1
0.2-0.4 A
VTU 21
15750/110 V
105 110 %
0.5-5 Sec
CTU 12
10000/5 A
50 200 %
05 5 Sec
YCG 15
VTT11
VTT11
CTU12
10000/5 A,
15750/110 V
CTN 31
10000/5A
VTT 11
CAG 37
VAT 11
VTT 11
DTH31
Setting
600/5A
600/5 A
HV=600/5 A
LV=1250/5A
Bias 15,30
& 45 %
High set
1000 %
Fixed
0.1-0.4 A
15 % of 5
Amp.
30 %
1000 %
Fixed
PS-0.2 A,
TMS-0.4
0.2 Amp.
V=110 %
2 Sec
4.75 A
5 Sec
K1=6 K2 = 1
0.5 5 Sec St-I 2.5 Sec
St-II- 3Sec
1 10 Sec
2.5-10 A
4A
1 10 Sec
5 Sec
A - 70%
T 15%
60 Sec
6 60 Sec
12 A
10-40A
0.3 Sec
0.5 3 Sec
0.3 Sec
0.5 3 Sec
Current Current -15%
15%
of 5A
Bias=30%
Bias
High Set =
15,30,45%
1000 %
High Set =
Fixed
1000 %
Sr.
Relay
No.
13. Stator Earth Fault
(64G 1)
14. 100 % Stator E/F
(64 G2)
15. 1ST Rotor E/F (64F1)
16. 2ND Rotor E/F (64 F2)
17. Generator
Transformer Over
Fluxing (99)
18. Low Forward Power
( 37)
19. Reverse Power
( 32)
2/ 32
20. Anti Motoring
Protection
(2/32 YA & 2/32YT)
21. Generator Loss of
Field (40)
Relay
Type
VDG14
CTR /
PTR
15750/110 V
Range
Setting
V=5.4-20 V
PS=5.4V
TMS=0.3
T(119)-1
Sec, T(149)5 Sec
1.1 mA
2.0 Sec
1.1 mA
K=1.1
RAGEA
VAEM
VTT 11
CAEM
GTT21
15750/110 V
WCD 11 15750/110 V
10000/5A
VTT 11
15750/110 V
WCD 11 10000/5A
VTT 11
VAT11
VTT 11
YCGF
11
VTT 11
VTT 11
VAGM
22
ZTO 11
SKE 11
1.1 mA
0.5 5 Sec
1.1 mA
K=1-1.25
T=12-120
Sec
0.5 %
1 - 10 Sec
2 Sec
0.5 %
1 10 Sec
0.5%
2 Sec
1-10 Sec
12-120 Sec
5 Sec
60 Sec
1-10 Sec
5-25 Sec
44 88 Volt
K1=0.845,
K2=3.5,
K3=0.5,
K4=3,
K5=18.6
2Sec
10Sec
PS-80.5 V
15750/110 V
10000/5A
15750/110 V
15750/110 V
10000/5A
T=12 Sec
0.5%
5.2 Amp
75 Deg elect
Offset=
3.156 Ohm,
T=52.5mSec
Phase
Angle=10%,
Voltge=6%,
F=0.11%
5.2
Setting
CAG 37
VTT 11
U/V
400/5 A
10 40 A
0.5 5 sec
CAG 37
VTT 11
U/V
400/5 A
10 40 A
0.5 5 sec
CAG 37
VTT 11
U/V
400/5 A
10 40 A
0.5 5 sec
CAG 37
VTT 11
U/V
400/5 A
10 40 A
0.5 5 sec
CAG 37
VTT 11
1250/5 A
10 40 A
0.5 5 sec
13.7 A
1.1 Sec
20%,1.5
Sec
10 Amp
0.8 Sec
No Trip
10 Amp
0.8 Sec
No Trip
10.8 A
0.8 Sec
No Trip
10.8 A
0.5 Sec
20%,1.5
Sec
12 A
0.5 Sec
20%,1.5
Sec
12 A
0.5 Sec
20%,1.5
Sec
10 A
0.5 Sec
20%,1.5
Sec
10 A
0.5 Sec
20%,1.5
Sec
22 A
0.8 Sec
CAG 37
VTT 11
1250/5 A
10 40 A
0.5 5 sec
10 A
0.8 Sec
CAG 37
VTT 11
U/V
CAG 37
VTT 11
U/V
CAG 37
VTT 11
U/V
CAG 37
VTT 11
U/V
800/5 A
10 40 A
0.5 5 sec
800/5 A
10 40 A
0.5 5 sec
800/5 A
10 40 A
0.5 5 sec
800/5 A
10 40 A
0.5 5 sec
Sr.
Name of Feeder
No.
12. Station Auxiliary T/R 1 &2
(TS3 & TS4 / 1600 KVA)
13. Stand By T/R 1 &2 (TR3 &
TR4 / 1600 KVA)
14. Stand By T/R
(TR5 / 1000 KVA)
15. Control Structure Transformer
(1000 KVA)
16. Lighting Transformer
(TL3 / 1000 KVA)
17. Cooling Tower Transformer
(1600 KVA)
18. Coal Handling Transformer
(TC3 / 1000 KVA)
19. Water Treatment Plant T/R
(1000 KVA)
20. Clarifier Water Transformer
(630 KVA)
21. CT Pumps (930 KW)
Full load current = 111 A
Starting current = 577.2 A
Starting time = 1.67/4.76 Sec
Relay Type
CTR
Range
Setting
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CDGM 62
200 / 5 A
10 40 Amp
0.5 5 Sec
25 100 A
10 40 Amp
0.5 5 Sec
25 100 A
10 40 Amp
0.5 5 Sec
25 100 A
10 40 Amp
0.5 5 Sec
25 100 A
10 40 Amp
0.5 5 Sec
25 100 A
10 40 Amp
0.5 5 Sec
25 100 A
10 40 Amp
0.5 5 Sec
25 100 A
10 40 Amp
0.5 5 Sec
25 100 A
10 40 Amp
0.5 5 Sec
25 100 A
3.6 6.2 A
18.7 A
0.5 Sec
75 A
18.7 A
0.5 Sec
75.7 A
15.5 A
0.5 Sec
66.7 A
15.5 A
0.5 Sec
67.4 A
15.5 A
0.5 Sec
68 A
18.7 A
0.5 Sec
77 A
15.5 A
0.5 Sec
66.7 A
15.5 A
0.5 Sec
66.7 A
14.7 A
0.5 Sec
65 A
PS = 3.95
TMS=0.2
30 A
70%, 0.5
Sec
PS = 3.95
TMS =
0.25
30 A
70%, 0.5
Sec
PS = 4.35
TMS=0.5
30 A
70%, 0.5
Sec
200 / 5 A
150 / 5 A
150 / 5 A
150 / 5 A
200 / 5 A
150 / 5 A
150 / 5 A
100 / 5 A
150/5 A
25 100 A
U/V
CDGM 62
CDGM 62
30/5 A
3.6 6.2 A
25 100 A
U/V
40/5 A
3.6 6.2 A
25 100 A
U/V
Sr.
Name of Feeder
No.
24. Clarified Raw Water Pumps
(280 KW)
Full load current = 31.5 A
Starting current = 173.5 A
Starting time = 2.0 Sec
25. Boiler Fill Pumps (250 HP)
Full load current = 20.4 A
Starting current = 133 A
Starting time = 2.2 Sec
5.2.2
Relay Type
CTR
CDGM 62
40/5 A
Range
3.6 6.2 A
25 100 A
U/V
CDGM 62
30/5 A
3.6 6.2 A
25 100 A
U/V
Setting
PS =3.95
TMS=0.2
37.5 A
70%, 0.5
Sec
PS =4.35
TMS=0.2
42.5 A
70%, 0.5
Sec
Sr.
Name of Feeder
No.
1. Unit Auxiliary T/R
(T4C & T4D / 1000 KVA)
2. EP Transformer
(1600 KVA)
3. Reserve Incomer from
( For Bus 4A & 4B)
4. ID FAN A & B (1300 KW)
Full Load Current = 138 A
Starting Current = 717.6 A
Starting Time = 7/10 Sec
5. Bowl Mills A,B,C,D,E & F
(335 KW)
Full Load Current = 41.7 A
Starting Current =270 A
Starting Time = 4.76 Sec
6. PA Fans A & B (1250 KW)
Full Load Current = 132.5 A
Starting Current =795 A
Starting Time = 24.5/33 Sec
7. SOP (200 KW)
Full Load Current = 21.8 A
Starting Current = 128.4 A
Starting Time = 3/5 Sec
Relay
Type
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CDGM
62
CTR
Range
150 / 5 A
10 40 A
0.5 5 sec
25 100 A
200 / 5 A
10 40 A
0.5 5 sec
25 100 A
1250 / 5 A 10 40 Amp
0.5 5 Sec
200 / 5 A
3.6 to 6.2 A
25 100 A
U/V
CDGM
62
50 / 5 A
3.6 6.2
25 100 A
U/V
CDGM
62
150 / 5 A
a. 6.2
25 100 A
CTU 12
U/V
CDGM
62
30 / 5 A
3.6 6.2
25 100 A
U/V
Setting
18.7 A
0.5 Sec
68 Amp
18.7 A
0.5 Sec
75.7 A
22 Amp
05 Sec
PS = 3.6
TMS=0.35
30 Amp
No Trip
PS = 3.95
TMS=0.2
40 Amp
70%,0.5
Sec
PS = 4.35
TMS=1.0
40 A
9A,15 Sec
50%,9 Sec
PS = 4.35
TMS=0.25
34 A
70%,0.5
Sec
Sr.
Name of Feeder
No.
8. FD Fans A & B (800 KW)
Full Load Current = 84.9 A
Starting Current = 509.4 A
Starting Time = 5.5/8 Sec
9. C W Pumps A & B (950 HP)
Full Load Current = 82.8 A
Starting Current = 422 A
Starting Time = 1.45/2.1 Sec
10. CEP Pumps A,B,C (220 KW)
Full Load Current = 25 A
Starting Current = 135 A
Starting Time = 2.5 Sec
11. BFP A,B & C (4000 KW)
Full Load Current = 421 A
Starting Current = 2020 A
Starting Time = 5/9 Sec
5.2.3
Relay
Type
CDGM
62
CTR
100 / 5 A
Range
3.6 6.2
25 100 A
U/V
CDGM
62
100 / 5 A
3.6 6.2
25 100 A
U/V
CDGM
62
30 / 5 A
3.6 6.2
25 100 A
U/V
CDGM
62
500 / 5 A
3.6 6.2
25 100 A
0.1 1 A
CAG 34
U/V
Setting
PS = 4.35
TMS=0.35
40 A
50%,9 Sec
PS = 3.95
TMS=0.2
33 A
No Trip
PS = 4.35
TMS=0.2
42.5 A
50%,9Sec
PS = 3.95
TMS=0.2
33 A
0.1 A
50%,9 Sec
Sr.
Name of Feeder
No.
1. Main Incomer to CT4
(Cooling Tower) from 3SB at
3SB
2. Main Incomer for CT4 at CT4
Bus
Relay Type
CTR
Range
Setting
CAG 37
VTT 11
U/V
CAG 37
VTT 11
U/V
800/5 A
10 40 A
0.5 5 sec
800/5 A
10 40 A
0.5 5 sec
CAG 37
VTT 11
800/5 A
10 40 A
0.5 5 sec
10 A
0.8 Sec
No Trip
10 A
0.5 Sec
20%,1.5
Sec
10 A
0.5 Sec
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
200 / 5 A
10 40 Amp
0.5 5 Sec
25 100 A
10 40 Amp
0.5 5 Sec
25 100 A
10 40 Amp
0.5 5 Sec
25 100 A
10 A
0.5 Sec
66 A
10 A
0.5 Sec
66 A
10 A
0.5 Sec
65 A
5. Stand By T/R
(TR6 / 1600 KVA)
6. Lighting Transformer
(TL4 / 1000 KVA)
200 / 5 A
150 / 5 A
Sr.
Name of Feeder
No.
7. Cooling Tower Transformer
(1600 KVA)
8. CT Pumps (960 KW)
Full load current = 115 A
Starting current = 632.5 A
Starting time = .5 Sec
Relay Type
CTR
Range
Setting
CAG 37
VTT 11
CAG 37
CDGM 32
200 / 5 A
10 40 Amp
0.5 5 Sec
25 100 A
3.6 6.2 A
10 A
0.5 Sec
66 A
PS = 3.6
TMS=0.2
34 A
70%, 0.5
Sec
150/5 A
25 100 A
CAG 37
U/V
5.2.4
Sr.
Name of Feeder
No.
1. Unit Auxiliary T/R
(T5C & T5D / 1000 KVA)
2. EP Transformer
(1600 KVA)
3. Reserve Incomer from
( For Bus 5A & 5B)
4. ID FAN A & B (1100 KW)
Full Load Current = 116.5 A
Starting Current = 855 A
Starting Time = 7/10 Sec
5. Bowl Mills A,B,C,D,E & F
(340 KW)
Full Load Current = 41.7 A
Starting Current =250.2 A
Starting Time = 2.9/6.1 Sec
6. PA Fans A & B (1250 KW)
Full Load Current = 135.3.A
Starting Current =811.8 A
Starting Time = 19/28 Sec
7. SOP (200 KW)
Full Load Current = 22 A
Starting Current = 132 A
Starting Time = 3.5/5 Sec
Relay
Type
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CAG 37
CAG 37
VTT 11
CDGM
32
CAG 37
U/V
CDGM
32
CAG 37
CTU 12
U/V
CDGM
32
CAG 37
CTU 12
U/V
CDGM
32
CAG 37
U/V
CTR
Range
150 / 5 A
10 40 A
0.5 5 sec
25 100 A
200 / 5 A
10 40 A
0.5 5 sec
25 100 A
1250 / 5 A 10 40 Amp
0.5 5 Sec
150 / 5 A
3.6 to 6.2 A
25 100 A
50 / 5 A
3.6 6.2
25 100 A
150 / 5 A
b. 6.2
25 100 A
30 / 5 A
3.6 6.2
25 100 A
Setting
10 A
0.5 Sec
65 Amp
10 A
0.5 Sec
66 A
22 Amp
0.3 Sec
PS = 4.35
TMS=0.4
43 Amp
No Trip
PS = 3.95
TMS=0.2
40 Amp
8.1A,3 Sec
70%,0.5 S
PS = 4.35
TMS=0.8
40 A
9A,10 Sec
50%,9 Sec
PS = 3.6
TMS=0.2
34 A
70%,0.5
Sec
Sr.
Name of Feeder
No.
8. FD Fans A & B (750 KW)
Full Load Current = 79.5 A
Starting Current = 477 A
Starting Time = 6.5/10 Sec
Relay
Type
CDGM
32
CAG 37
U/V
CDGM
32
CAG 37
U/V
CDGM
32
CAG 37
CAG 34
U/V
CTR
100 / 5 A
Range
3.6 6.2
25 100 A
30 / 5 A
3.6 6.2
25 100 A
500 / 5 A
3.6 6.2
25 100 A
0.1 1 A
Setting
PS = 3.6
TMS=0.5
38 A
50%,9 Sec
PS = 3.95
TMS=0.3
36 A
50%,9Sec
PS = 3.95
TMS=0.3
32 A
0.1 A
50%,9 Sec
Name of Feeder
IP1&IP2
Mehrauli 1&2
Type of
Protection
Distance
Protection
Relay Type
CTR/PTR
Range
Setting
Quadro mho
600/1 A
220KV/110V
Z1=1.792 Ohm
Z2=2.24 Ohm
(t2=350 ms)
Z3=2.56Ohm
(t3=1.05ms)
Z3=0.4 Ohm
E/F Comp.=130%
(R-Ph)O/C=150%
(B-Ph)O/C=150%
E/F
=20%
TMS=0.3 sec
Backup
Protection
CDD21
(Directional)
Distance
Protection
RR3V
Scheme
O/C
50-200%
E/F
20-80%
600/1 A
220KV/110V
Backup
Protection
IDMT
(Directional)
O/C
50-200%
E/F
20-80%
Z1=1.68 Ohm
Z2=3.15 Ohm
(t2=350 ms)
Z3=5.76Ohm
(t3=1.0 sec)
(R-Ph)O/C=150%
(B-Ph)O/C=150%
E/F
=20%
TMS=0.2 sec
Sr.
No.
3
Name of Feeder
Ballbhagarh 1&2
Relay
Type
Distance
Protection
CTR
Range
MM3V
Scheme
600/1 A
Setting
-
Z1=2.396 Ohm
Z2=3.355 Ohm
(t2=350 ms)
Z3=9.1Ohm
(t3=1.0 sec)
220KV/110V
Okhala 1
Okhala 2
NOIDA
Backup
Protection
IDMT
(Directional)
Distance
Protection
RR3V
Backup
Protection
IDMT
(Directional)
Distance
Protection
RR3V
Backup
Protection
IDMT
(Directional)
Distance
Protection
Backup
Protection
IDMT
(Directional)
600/1 A
220KV/110V
600/1 A
220KV/110V
600/1 A
220KV/110V
Sr. No.
O/C
50-200%
E/F
20-80%
-
(R-Ph)O/C=125%
(B-Ph)O/C=125%
E/F
=20%
TMS=0.3 sec
Z1=1.63 Ohm
Z2=2.44 Ohm
(t2=350 ms)
Z3=4.89Ohm
(t3=1.0 sec)
O/C
50-200%
E/F
20-80%
-
(R-Ph)O/C=125%
(B-Ph)O/C=125%
E/F
=20%
TMS=0.3 sec
Z1=0.834 Ohm
Z2=1.44 Ohm
(t2=200 ms)
Z3=2.952Ohm
(t3=1.0 sec)
(R-Ph)O/C=125%
(B-Ph)O/C=125%
E/F
=20%
TMS=0.3 sec
Z1=2.65 Ohm
Z2=4.51 Ohm
(t2=220 ms)
Z3=8.29Ohm
(t3=1.0 sec)
E/F
=20%
TMS=0.3 sec
O/C
50-200%
E/F
20-80%
-
20-80%
Sr.
No.
7
Name of Feeder
Alwar
Bypass
Bus Coupler
Relay
Type
Distance
Protection
CTR
Range
Setting
Sr. No.
MM3V
Scheme
600/1 A
220KV/110V
Backup
Protection
IDMT
(Directional)
Distance
Protection
Backup
Protection
Quadro mho
Z1=13.44 Ohm
Z2=20.16 Ohm
(t2=450 ms)
Z3=26.88Ohm
(t3=1.0 sec)
(R-Ph)O/C=125%
(Y-Ph)O/C=125%
(B-Ph)O/C=125%
E/F
=20%
TMS=0.3 sec
Reqired setting
can be set
Reqired setting
can be set
Instantant
O/C
O/C
50-200%
E/F
20-80%
600/1 A
220KV/110V
IDMT
(Directional)
CAG33
1200/2 A
220KV/110V
10
11
12
Station Tr. 3
Bus Bar
Differential
O/C
50-200%
E/F
20-80%
4 16
Amp.
2 8 Amp
E/F
Instantant
Dead time
O/C
E/F
CAG39
Backup
Protection
IDMT
Biased
Diff.
Protection
Backup
Protection
Differential
Protection
Rest. E/F
Bus Bar
Differential
DMH
IDMT
600/1 A
220KV/110V
600/1 A
220KV/110V
4A
50A(R-Ph)
50C(B-Ph)
2A
50N
0.5-2Amp
1.8 A
(51A,51C)
0.5-2Amp
0.5 A
(64)
(R-Ph)O/C=50%
(B-Ph)O/C=50%
E/F
=20%
O/C
50-200%
E/F
20-80%
15-50%
30%
DTH-31
E/F
10-40%
-
(R,Y,B-Ph) O/C
20%
15%
CAG-14
CAG-34
5-20%
50-200%
10%
125%
600/1 A
NOTE: All feeders, Station transformers, Bus coupler, Bypass breaker and units are
having LBB protection- tripping defective breaker bus after 200 ms.
SECTION VI
6.1
:Levelstart
: 14
: 0-500 mmWCI
:200 kg/cm2
: 4000 C
: Dual for odd & even set of
electrodes
: L&T
: 7.5 KW,415V 3Ph
:6 nos.
: Remote speed indication & facility
for auto control
: Masibus
: Inductive proximity switches
: Digital speed indication in UCB for
each feeder
: An immediate alarm is given in
case of stoppage of the feeder in
UCB
Alarm
: Fuji Tosdic
: 24 V pulsating
1.
a)
b)
c)
d)
2.
: Siemens
: Sieser
: 256
: 1 msec
SECTION VII
OFF-SITE
AUXLIARIES
7.1
7.1.1
SWITCHYARD
TRANSFORMER RATING
Make
MVA
Date Of First Charging
Voltage Ratio HV/LV (kV)
Current HV/LV (Amps.)
Phases
Frequency (Hz)
Vector Group
Type Of Cooling
Tap Changer Type
Impedance %
7.1.2
BHEL
31.5
11-10-1982
220/7
82.67/2598.15
3
50
Yd1
ON
OLTC
13.67
TRANSFORMER RATING
Make
MVA
Date Of First Charging
Voltage Ratio HV/LV (kV)
Current HV/LV (Amps.)
Phases
Frequency (Hz)
Vector Group
Type Of Cooling
Tap Changer Type
Impedance %
7.1.3
BHEL
63/43/20
1973
220/6.9
163.3/1673
3
50
Yd1
OFB
OLTC
16.75
TRANSFORMER RATING
Make
MVA
Date Of First Charging
Voltage Ratio HV/LV (kV)
Current HV/LV (Amps.)
Phases
Frequency (Hz)
BHEL
25
15-06-1977
220/7
65.6/2062
3
50
Vector Group
Type Of Cooling
Tap Changer Type
Impedance %
7.1.4
Yd1
ON/AB
OLTC
12.62
The arrangement in the 220KV switchyard comprises of a 220 KV double bus bar system
with a bus coupler and by pass bus. With this arrangement it is possible to take out any
one breaker on By Pass for maintenance without interruption of supply.
7.1.5
NORMAL OPERATION
The two bus bras (Bus-I and Bus-II) should normally be kept coupled through the bus
coupler. The fixed distribution for bus differential protection should not normally be
disturbed.
7.1.6
For maintenance of a particular bus all feeders connected to the bus requiring
maintenance shall be transferred to the other bus by closing one bus isolator and opening
the other. The bus coupler shall be tripped in the last.
7.1.7
The Air Blast Circuit Breakers (ABCB) are of M/S BHEL and ABB make. The operating
pressures are 26 kg/ cm2and 31 kg/ cm2respectively and their lock-out pressures are 21
kg/ cm2and 27 kg/ cm2.
7.1.8
220 KV, single phase, 4 core current transformers are of M/S ABB and BHEL are in the
switchyard.
1ST Core used for
Differential protection (Station transformer and Generator
Transformer)
Distance Protection (in case of feeders)
2nd Core used for
Back up protection and local breaker back up protection
(LBB)
3rd Core used for
Metering
th
4 Core used for
Bus bar Differential Protection
In case of feeders, distance scheme covers phase to ground, phase to phase protection
with zone indications. In case of failure of main (distance protection), back up IDMT
type of relay trips the line. And if the protection relay comes and breaker fails to operate
due to control circuit or any other problem, LBB protection operates after 200 ms and
makes the 220KV Bus I or II dead (as the case may be). Similarly in case of 220 KV Bus
fault, all feeders of the faulty Bus trip and make the Bus dead through Bus bar
Differential protection.
In the Zone protection: 1st Zone
Instantaneous
2nd Zone
0.35 sec (delay)
rd
3 Zone
1.0 sec (delay)
7.1.9
1
2
3
4
5
6
7.1.10
INTERLOCKS
ABCB can not be closed from remote, if
1
Lockout relay (186) is not resetted
2
Low Air Pressure
3
Control Circuit faulty (DC not available)
Bus and line isolators can not be operated electrically if breaker of that Bay is in
closed position.
2nd Bus isolator of any Bay can only be closed (electrically) when Bus coupler
breaker and its both isolators are in closed position.
By Pass Isolator of any Bay can be operated (electrically) only when By Pass Bay
Breaker is in open position.
Earthling switches have electrical/mechanical interlocks with isolators.
Electrical interlock provided for closing only one by pass isolator at a time.
UNDER FREQUENCY PROTECTION (Islanding)
220KV BUS-I AND II (as the case may be) may become dead if any of the five unit
breakers is under trip position and its Bus and line Isolators are in closed position and the
air pressure drops to 16 kg/ cm2 (approx.)
7.1.11
1
2
3
4
5
6
7
8
There are 20 Bays in 220KV switchyard connected to 220KV Bus-I and Bus-II as per
following description:BUS-I
1
2
3
4
5
6
7
IP-I
Station I, III
Okhla-I
Ballabhgarh-I
Units-I, III, V
Jaipur
Mehrauli-I
BUS-II
1
IP-II
2
Station-II
3
Okhla-II
4
Ballabhgarh-II
5
Units-II, IV
6
Sahbabad
7
Mehrauli-II
By Pass Bay can be connected to either of these buses and bus coupler is used for
coupling both the buses.
7.2
7.2.1
AIR COMPRESSORS
Total Nos.
Jacket water pressure
H.P. Cylinder outlet
Water Temp
7.2.2
3
4.2 kg/cm2 (Max.)
1100 F to 1200 F
Make
Type
Speed
Nos. of Cylinder
Pressure
120 Psig
2
21m3/hr
MOTOR
Motor capacity
Voltage
RPM
Amps
Make
126 KW
415V
1500
221
Siemens
RECEIVER
Capacity
Working pressure
Test pressure
7.2.3
250C.F.
125 Psig
185 Psig
COMPRESSOR NO 3
Make
Working pressure
Max. Unloading Pressure
No.
Consolidated Pneumatic
Tool company(India)Ltd.,
Mumbai.
Slow speed, Two cylinders
Horizontal & double
acting type.
300 RPM
741 CFM at 100Psig
( 20.926M3/min)
100 Psig ( 7 kg/cm2)
100 Psig ( 7 kg/cm2)
One
RECEIVER
Capacity
Design pressure
Test pressure
10 M3.
9.2 kg/cm2
13.8 Kg/cm2
MOTOR
Capacity
Voltage
RPM
Amps
Make
132 KW
415V+ 10%
1500
227
Siemens
Type
Speed
Capacity
7.2.4
No
Capacity
Pressure
Make
2
30 m3/min
70 MWC
Kirlosker Pneumatic
MOTOR
Capacity
Voltage
RPM
Amps
Make
200 KW
6.6 KV
988
23
Kirlosker
7.2.5
Make
Type
Speed
Free air Delivery
Working/cut-off
Pressure
Re-starting Pressure
No. of compressor
Lubrication oil
Pressure
Jacket water pressure
HPC outlet water
Temperature
750 RPM
14.6 m3/min.
8.0 kg/cm2
7 kg/cm2
2
1.5 to 2 kg/cm2
8 kg/cm2
1100 F to 1200 F
MOTOR
Capacity
Voltage
Amps
Make
Speed
100 KW
415 Volts
173/177
Kirlosker Electric
1500 RPM
RECEIVER
Capacity
5 M3
16.19 kg/cm2
10.15 kg/cm2
Purge Reactivation
14.6 kg/cm2
8 kg/cm2
7.6 kg/cm2
440 C
540 C
22 ppm
6 Hrs
2 Hrs
3 Hrs
Continuous
Silica
10 kg/cm2
7.2.6
7.2.7
COMPRESSURE 1&2
Make
Capacity
Pressure
Kirlosker Pneumatic
18 m3./min
(2 Nos)
7 kg/cm2
MOTOR
Capacity
Voltage
RPM
Amps
Make
120 KW
415 V
1000
212
Kirlosker
7.2.8
COMPRESSURE 3
Make
Type
Speed
Free air Delivery
750 RPM
14.6 m3/min.
8.0 kg/cm2
Working/cut-off
Pressure
Re-starting Pressure
Lubrication oil
Pressure
Jacket water pressure
HPC outlet water
Temperature
7 kg/cm2
1.5 to 2 kg/cm2
8 kg/cm2
1100 F to 1200 F
MOTOR
Capacity
Voltage
RPM
Amps
Make
100KW
415 V
1500
173
Kirlosker
7.3
7.3.1
Purge Reactivation
14.6 kg/cm2
8 kg/cm2
7.6 kg/cm2
440 C
540 C
22 ppm
6 Hrs
2 Hrs
3 Hrs
Continuous
Silica
10 kg/cm2
4
Worthigton
Multistage Vertical Turbine Pump
500 m3/Hr
94.5 MWC
1500 RPM
MOTOR
Make
Type
Rating
RPM
Kirloskar
Induction Motor
6.6 KV,187 KW ,22Amp.
1485
7.3.2
No-V, VI
Make
Type
Capacity
Head
2
Kirloskar
Multistage Vertical Turbine Pump
400 m3/Hr
94.5 MWC
MOTOR
Make
Type
Rating
RPM
7.3.3
Kirloskar
Induction Motor (IP23/IC01)
6.6 KV,150 KW
1485
FIRE & SCREEN PUMP
Make
No
Type
Capacity
Head
Worthigton
2
Multistage Vertical Turbine Pump
500 m3/Hr
94.5 MWC
MOTOR
Make
Type
Rating
RPM
Kirloskar
Induction Motor
6.6 KV,185 KW
1485
Kirloskar
DHR-35 Three Stage
500 m3/Hr
10 Kg/cm2
Model NTA-855-F
132 Kw
7.3.5
No
Make
Type
Capacity
Head
Speed
3
Jyoti
B400 D3F 300, Multistage vertical turbine pump
600 m3/Hr
55 MWC
1440 RPM
MOTOR
Make
Type
Rating
RPM
7.3.6
Make
No
Capacity
Head
Kirloskar,(CRW1)/Flowmore(CRW2,3)
3
3500 m3/Hr
20.5 MWC
MOTOR
Make
Type
Rating
RPM
7.3.7
Kirloskar.
Induction Motor
6.6 KV,280 KW
985
TRAVELLING WATER SCREENS
Make
Total no of screens
Capacity
7.3.8
Make
Capacity
Pressure
Motor
7.3.9
No
BSBK
7 nos
20000 cu mt /hr
Type
Capacity
Head
Drive Motor
Vertical
200 m3/Hr
66.75 MWC
55KW/85HP, 415V, 1500RPM, 93Amp
.
7.3.10
Drive Motor
7.3.11
No.
Type
Capacity
Head
Speed
Motor
7.4.1
Make
Model
Capacity
Pressure :
Quantity
Speed
Motor
MOTOR
Capacity
Voltage
RPM
Amps
Make
7.4.2
Make
Model
Capacity:
Pressure
Quantity
194 KW
415 V
1000
331
Siemens
ASH SLURRY PUMPS ( NEW)
Indure
D85D
1300 m3./hr
5.0 kg/cm2
3
MOTOR
Capacity
Voltage
RPM
Amps
Make
7.4.3
322 KW
6.6 KV
991
35
Kirlosker
BOTTOM ASH PUMPS
Quantity
Make
Model
Capacity
Pressure
Motor
2 nos.
Beacon Weir
SDC 200/200
410 m3/hr
8.0 kg/cm2
160KW/1485RPM/220Amp/NGEF
7.5
COOLING TOWER
202 mtrs
MOTOR
Type
Speed
KW
Current
Volts
Make
Induction motor
421 rpm
930
108.5 amps
6600 volts, 3 Ph. 50 C/S
BHEL
Gammon(U4)/ Paharpur(U5)
1 for each unit of 210 MW
16
27000 m3 /hr/Tower
100C
500C
Cooling Range
Max. operating inlet water temp.
7.5.3 COOLING TOWER FANS
Fan Type
No. off fans/Tower
No. off blades/fan
No. off row of fan
Dia.
Reduction gear Ratio
Fan speed
Type
Make
Lub oil
MOTORS
Make
Volts
Current
K.W.
Speed
N.G.E.F.
415V
130 amps
75
1475 rpm
7.6
DIESEL GENERATOR
One Diesel Engine is directly coupled with generator for producing power.
Diesel generator set is capable of supplying power to Barring gear motors of
unit I,II,III,& IV A.C. standby lub. oil pump & Hydrogen seal oil pump of unit
IV.There are 10 numbers of outgoing feeders panels for supplying power of
different motors and emergency lighting Boards when supply to any of feeder
panels fails signal impulse starts the diesel generator set automatically & it
supplies power through solenoid operated air circuit breaker provided in M.C.C.
The control circuit is such that the set can be stopped only manually and also
this can be achieved only when the set is not supplying load to any of the feeder.
A provision is there to start the set manually. However, supplying of load to
the feeders will be automatic through the solenoid operated breakers.
10.6.1 SPECIFICATION
10.6.2 GENERATOR
No
Make
Rated output
2
Jyoti Ltd.
250KVA
0.8/415
50 Hz , 3 ph.
Class B
1500rpm
348 Amps
CR Excitation 85V 50 Amp.
One
200W
230V
RAW WATER
240
64
306
612
304
326
72
214
612
0.1
13.0
3500
72
1300
ANION EXCHANGER
Silica (Reactive) as SiO2
Conductivity at 20 C
Total dissolved solids
7.7.3
PRETREATMENT SECTION
Description
Nos. off
Dimensions
Concentratio
n of solution
High Speed
Mixture
7.7.4
Alum Prep.
Cum storage
tank
2
12300x1200D
Lime
solution tank
1
765Lx380Wx380H
1
765Lx380Wx380H
10%
10%
1
16200
x1480D
10%
2 Nos.
Nil
1 Nos.
Nil
CLARIFLOCULATOR
Nos.
Size
Capacity
7.7.5
One
168000 x 4000D
400 m3/Hr.
Nos.
Make
7.7.6
One set
Hindustan Door Oliver
CHLORINATOR
Nos.
Capacity
Model
Type
Capacity
Operating Pressure/
Unit
Operating water
Qty/Unit
7.7.7
10%
2
0.1 to 5.5 kg/cm2 (Max.)
Banaco Mark II
Press Gaseous Chlorinator
(0.1 5.5 ) kg/Hr
2.0 kg/cm2
3m3/Hr.
TANKS
LOCATION
MODEL
HP/RPM
0.5/1440
MAKE/FRAM
E SIZE
Kirloskar/N80
Alum Prepn.
Cum. Storage
Tank
Lime Soln.Tank
for
PH 5
PM 1
QTY.
3
1.0/1000
Kirloskar/N90L
clarifloculator
Sodium sulphite
Soln. Tank
Alkali dilution
tank
Lime prepn.
Tank for
neutraliasation
PM 5
0.5/1440
Kirloskar/N80
PM 10
1.0/1000
Kirloskar/NPOL
PH 5
0.5/1440
Kirloskar/N80
7.7.8
DESCRIPTION
CLARIFIED WATER
PUMP
2
250M3/hr.
36 MWC
6 DC 124
Best & Crompton
2
60/1440
Kirloskar
2.5 kg/cm2
Nos.
Capacity
Discharge Head
Model No.
Make
Motor
HP/RPM
Make
D.P.
SLUDGE DISPOSAL
PUMP
250M3/hr.
15 MWC
3x2x10 BPO
Best & Crompton
2
5/1440
Kirloskar
PRESSURE
FILTER(DUEL MEDIA)
4
30000 x 1350H
ALKALI CARBON
FILTER
1
8000 x 2300H
Sand+Anthracite
55/28
Active Carbon
-
170
5 mints
4.65
10
5 mints
-
DESCRIPTION
BACKWASH
WATER PUMP
AIR BLOWER
Nos.
Capacity
Discharge Head
Medium
2
170 M3/Hr.
20 MWC
Water
2
4.65 m3/min
0.21 kg/cm2
Air
SODIUM
SULPHATE
DOSING PUMP
2
227 Lit/Hr.
7 kg/cm2
Sodium sulphite
Motors HP/RPM
25/1440
DESCRIPTION
7.5/1440
BACKWASH WATER
PUMP
1
1000Lx6000Wx2580H
-
Nos.
Size
Concentration of Soln.
High speed Mixture
soution
0.5/1440
SODIUM SULPHATE
SOUTION TANKS
2
12200 x 1200D
10 %
2
DESCRIPTION
Nos.
Type
CATION UNIT
4
Strongly Acidic
ANION UNIT
4
Strongly basic
Shell Design
Pressure(kg/cm2)
Max./Min. Treatment
flow (m3/Hr.)
Average Treatment
flow (m3/Hr.)
Capacity between
Regeneration M3
GROSS
Wastw water /
Regeneration M3
Time per
Regeneration
Type of Chemical
100% chemical
Regeneration per
unit(kg)
Type of Resin
Resin qty. M3/unit
4.0
5.3
80/28
70/28
47/28
35
35
35
850
706
700
110
80
25
55 mints.
115 mints.
115 mints.
Hcl
880
NaOH
500
2K 225
12.5
DANIP
6.695
ZK225/DAFFIP
0.77/2.10
FLOW-M3/HR.
55.4
TIME-MIN
5
52.8
20
OPERATION
Back wash (once in a
week)
Acid Injection 5%
w/v
D.A.
M.B.
Down flow
Acid Rinse
Down flow
Final Rinse
Back wash
Alkali Injection
Alkali Transfer
Alkali Rinse
Middle Collector
wash
Back wash
Alkali Injection
Up flow
Alkali Transfer
Up flow
Alkali Rinse
Acid Injection 5%
W/V
Down Flow
Acid Rinse
Drain Down
Air Min.
Final Rinse
79.8
52.8
79.2
35.0
13.6
22.2
22.2
67.0
14.0
20
25
25
5
5
30
5
60
1
14.0
15.3
6.9
14.9
6.9
25.2
7.5
6
30
30
5
5
20
6
3.5
7.4
3.0 M3/Min.
3.5
6
10
5
10
10
7.7.11
DESCRIPTION
DEGASSER TOWER
Nos.
Size
2
2000Lx2000Wx3400H
DESCRIPTION
Nos
Capacity
Discharge Head
Medium
MOTOR HP/RPM
MOTOR-Make
DEGASSER AIRBLOWER
4
75 m3/min.
100MWC
Air
5/1440
Kirloskar
DEGASSED WATERSUMP
2
7500Lx7500Wx2750H
DEGASSED
WATER PUMP
3
120 m3/min.
45 MWC
Acidic water
40/1440
Kirloskar
DESCRIP
TION
ALKALI
PREPAR
ATION
TANK
BULK
ALKALI
STORAG
E TANK
Nos.
Size
Two
12000
x1200D
-
One
16000 x
4500L
-
Solution
Concentrat
ion in
Tank
DESCRIPTIO
N
Nos.
Capacity
Discharge Head
MWC
Media
MOTORHP/RPM
Motor make
DESCRIPTIO
N
Nos
Size mm.
DESCRIPTION
Nos.
Type
Size(mm)
Max.Working
Pr.(kg/cm2)
Min.Treatment
flow(M3/Hr.)
Max. Treatment
flow(M3/Hr.)
ALKALI
DILUTIO
N TANK
FOR
DA/MB
Two
16000
x1500D
20%
ACID
MEASUR
ING
TANK
FOR ZK
Two
18000
x1500D
30%
BULK
ACID
STORAG
E TANK
Five
34000
x6200L
30%
ACID
MEASUR
ING
TRANSF
ER MB
Two
4570
x762D
30%
ACID
TRANSFER
PUMP
1
25
17.5
EFFLUENT
DISCHARGE
PUMP
2
150
18
ALKALI
TRANSFER
PUMP
2
15
20
ALKALI
INJECTION
PUMP
2
5
25
32% Hcl
5/1440
Acid/Alkali
20/1440
20% NaOH
5/1440
Alkali
7.5/1440
Kirloskar
Kirloskar
Kirloskar
Kirloskar
PRIMING
CHAMBER
One
6000 x900D
LIME PREPN.
TANK
One
12000 x1200D
NEUTRALISING PIT
One
10000Lx10000Wx3000H
STRONGLY
ACIDIC CATION
UNIT
Four
Strongly Acidic
2800 x3600H
3.6
STRONGLY
BASIC ANION
UNIT
Four
Strongly Basic
2400 x2600H
4.6
Four
1400 x3000H
4.6
28
28
28
80
70
47
Average Treatment
flow(M3/Hr.)
Capacity between
regeneration(M3)
Period between
regeneration(Hrs.)
Waste Water per
regeneration (M3)
Type per
regeneration(Mints)
35
35
35
850
706
700
20
20
20
110
80
25
55
115
115
RESINTYPE
INDIAN 225
INDIAN NIP
6695
ANION
INDIAN FFIP
2100
CATION
INDIAN 225
770
Resin Quantity
(Lts.)
Regenerant
Chemical
100%
Chemical/Regen
eration(kgs)
12500
Hcl
NaOH
NaOH
Hcl
880
544
Through fan
with 5BA
38.5
Mixed Bed
OPERATION
Middle collector
flushing
Down Flow
Back wash
Acid Injection @ 5%
Down Flow
Acid Rinse
Final Rinse
Back wash
Caustic Injection @
5%
Caustic Transfer
Caustic Rinse
Flushing/ Back wash
Up flow
Caustic Injection 7.2
%
Up flow
FLOW(M3/Hr.)
55.4
TIME(Min.)
1
79.2
55.4
52.8
79.2
52.8
35.0
13.6
20
5
20
25
25
5
5
22.2
30
22.2
67.0
14.0
6.9
15.3
5
60
6
30
30
6.9
20
Caustic Rinse
Up flow
Caustic Transfer
Down flow
Acid Injection @
5%
Drain Down
Air Mix.
Final Rinse
25.2
6.9
6.9
3.5
7.4
20
5
5
10
10
180
35
5
10
10
2
Radial flow clarifloculator
3200 m3/Hr./unit
20 % (Max.)
54300 Dia x4915 Deep.
2(one/unit)
Geo-Miller Private Ltd.
60 Secs.
3.7 mts.
2/unit
Service valve 150 DA.
3/unit
Soln. (10 % strength ) to last for 8 Hrs.
operation while flow of 3200 m3/hr.
Size
2 H.P
1550
1:50
Capacity
Type
1 Ton each
Gear operated travelling trolley are
fitted on monorails.
2/Unit
Semi Circular
3.35(Dia.)x3.600L
12 hrs. to dose 80% pure hydrated lime
slurry Of 10% strength at the rate of 35 ppm
to a normal flow of 3200 m3/hr.
PADDLES
Material
Type
Motor
M.S.
Rotation about horizontal axis
2 H.P., 1500r.p.m., gear ratio 1:
300 m3 /hr
15 M.
23.4
MOTOR
HP
Speed
30
1450 rpm
FEATURES
Quantity (No.)
Type
Normal operating flow
Operating Pressure
Dimensions Dia x HOS
Material of construction
Back wash Time
8.
9.
Four
Vertical down flow.
55.00 m3/Hr
3.5 4.00 (kg/cm2)
2200mm x 2650mm
M.S.
15-20 min. or till the effluent is
clear.
0.8-1.0 kg/cm2
Manual.
7.7.21
SR.
NO.
MATERIAL
1.
Pebble
2x 1
1 x 1
1 x
x
2164.00 x 4 kgs
541.00 x 4 kgs
541.00 x 4 kgs
541.00 x 4 kgs
2.
3.
4.
Quartz cylex
Mixed sand
Activated Carbon
x
-
513 x 4 kgs
93500 x 4 kgs
2508 x 4 kgs
7.8
7.8.1
SIZE
QUANTITY
Moisture
Ash
Volatile Matter
Gross calorific value
Hard grove grindability Index
Bulk density
Size
7.8.2
UNIT
3X100MW
3X100+2X210MW
Coal consumption
Max.daily
Consumption
Average daily
Coal consumption
Annual Coal
Tonnes/Hr
Tonnes
187.5
4500
450
10800
Tonnes
3600
8000
Tonnes
1312500
315,00,00
7.8.3
WAGON TIPPLER
Nos.
Make
Type
Total Time for Tripping
Max.angle of rotation
Total Weight
Capacity
MOTOR
R.P.M.
Amps
H.P.
Voltage
1480
100
75
415V,50c/s, 3 Phase
Induction Motor.
(Power is transmitted through Traction type fluid coupling.)
7.8.4
b) Hoisting Rope
7.8.5
Dia-40mm
Nos. 2
Length 123 ft.(3
Dia 38mm
Nos. 4
Length 24.28 mts
Construction-6X41
CAR PULLER
Rope Size
Braking
Coupling
Speed Reducer
1-3/8 (35mm)
Electro Magnetic
Clutch Type
V-1400 Worm reducer
MOTOR
Capacity
Amps
RPM
30KW/40 HP
52.5
960
7.8.6
COAL CRUSHERS
Make
Type
Coal size input
Coal size output
TRF
Non-reversible ring granulator type
250 mm
20mm
Capacity
Nos.
Working oil temp.
Limit
Rotor Speed
Rotor dia
Rotor length
MOTOR
Voltage
Amps
RPM
Capacity
7.8.7
6.6KV
33.5
1490
300KW
BELT CONVEYERS
Carrying Capacity
Speed
Width
Material
600 Tons/Hr
2.3 mts/sec
1 mt.(For all)
Nylon Fabric with Dead WT.
7.8.8
CONVEYER
NO.
1A & 1B
2A & 2B
3A & 3B
LENGTH & MM
PLY
171548
164345
156371
4
4
4
4
5
6
92087
100262
223778
4
4
4
7
8
9
10A&10B
177000
153832
20900
4
4
4
4
MOTOR SPECIFICATIONS
Speed
Voltage
CONVEYOR NO.
1A & 1B
CAPACITY
150 HP
RAISE OF
INCLINATION
150
140
11698 mm at 150C &
rest is horizontal
130
120
10562 mm at 150C &
rest is horizontal
Horizontal
150
180
Horizontal
1440 rpm
415 V
REDUCTION RATIO
35.5:1
2A & 2B
3A & 3B
4
5
6
7
8
9
10A & 10B
7.8.9
150 HP
100HP
60 HP
75 HP
60 HP
50 HP
100 HP
30 HP
75 HP
35.5:1
20:1
25:1
25:1
20:1
20:1
25:1
20:1
20:1
TRIPPER
Type
Quantity
Belt width
Drum Dia
Speed
MOTOR
Type
Capacity
(Traverse Drive)
Speed
Voltage
Telescopic Chute
drive capacity
2
11700 mm
3500 mm
1980 mm
MOTOR
TRAVERSE MOTOR
PLOUGH MOTOR
Type
Capacity
Speed
Voltage
Speed
Induction Motor
7.5 H.P.
720 rpm
415 V
20 to 30 ft/minute
Induction Motor
40 H.P.
1430 rpm
425V
-
7.8.11
SR. NO.
1.0
2.0
BELT WEIGHER
DESCRIPTION
Location
Quantity
SPECIFICATION
Belt conveyor 2 A,2B
2
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
8.3
9.0
10.0
10.1
11.0
11.1
12.0
13.0
14.0
15.0
15.1
Type
Make
Type of speed sensor
Type of load sensor
No. of load cell per weigher
Capacity
Rated
Maximum(Designed)
Minimum
Accuracy
Calibration
Weight per unit length of chain
Remote Panel
Type of flow indicator
Type of totalising counter
No. of Digits
Whether zero reset button provided
Local
Type of flow indicator
15.2
Mechanical
15.3
Power supply
Mechanical
Gillanders Arbuthnot & Co. Ltd.
Mechanical
Mechanical
600 MTPH
750 MTPH
120 MTPH
10.50%
By test chain
46.85 Kg / m
Moving coil meter
EM counter
6
Yes
NA
Electro ZAVOD
Suspended
2
1500mm x 1350mm x 800 mm
8.5 KW/11.0 KW (Hot/Cold)
220 VDC
METAL DETECTOR
S.NO.
1
2
3
TYPE OF COUPLINGS
STD 08
STD 07
STD 06
]
]
] M/s Fludomate make
STD - -5A
] (Conveyors)
5
6
7
8
FCU 17.75
FCU 16.5
FCU 14.5
FCU 12.75
]
] M/s Pembril Greaves make
] (Conveyors)
]
9
10
HFD 10 B
HFD 14B
11
SCR 41 R
7.8.15
DESC
RIPTIO
N
Belt
PERMISSIVE
Conveyor
i)No Conveyor
belt can be
started before
the belt ahead
of it is kept
running.
ii) No. belt will
run if its
delivery gate is
opened to the
belt not in
service.
Screens
Tripper
Respective
conveyor
INTERLOCK
i)
PROTECTION
i)
ii)
iii)
iv)
Plough
Feeder
Car
Puller &
Beetle
Charger
Wagon
Trippler
should be in
operation.
Respective
conveyor
should be in
service.
Wagon trippler
should not be in
operation.
Car puller or
Beetle charger
should not be in
operation.
Motors
7.9.1
WAGON TIPPLER
SR. NO.
1.0
2.0
3.0
4.0
5.0
6.0
DESCRIPTION
Manufacturer
Type & Model No.
Gross Load Capacity
Minimum nos. of tippling/hr
Maximum angle of rotation
Type of brakes
7.0
8.0
9.0
10.0
11.0
12.0
Control system
7.9.2
SR. NO.
1.0
DESCRIPTION
Type
SPECIFICATION
Elecon Engineering Company Ltd.
Rota side
90T
17
150 Degree
Automatic Electro Hydraulic Thrust
Operated
Beetle Charger
Beetle Charger
Helical Gear Box
Yes
Through 98KW slip ring motor, reduction
gear unit, fluid coupling, flexible brake
coupling, spur and pinion gears
From control desk provided in the wagon
tippler control room.
SPECIFICATION
Ring Type Granulator
2.0
3.0
4.0
Make
Model No.
Quantity
5.0
600 MT/hr
750Mt/hr
R.O.M.Coal
750
50-70
(-) 100 mm
20%
O.B.T./m
100%
(-) 20 mm
16.0
16.1
16.2
16.3
16.4
Capacity- Rated
-Design
Material to be handled
Maximum RPM
Hard Grove Index
Maximum lump size
Maximum moisture content
Bulk density of coal
Guaranteed output of lump
size at specified input size and
moisture
Material of Parts
Material of rotor shaft
Material of upper breaker
plate
Material of breaker plate
Material of suspension bars
Material of side liners
Material of ring hammers
Bearing No.
Method of lubrication of
crusher bearing and life
Specification of motor
Power rating
Speed(RPM)
Duty cycle
Method of mounting
17.0
Granulator weight
7.9.3
VIBRATORY FEEDER
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
13.1
13.2
13.3
13.4
13.5
13.6
14.0
15.0
EN-19
Tiscral
Cast MN steel IS-276, Gr.III
EN-19
Tiscral
IS-276 Grade-III
Torrington 22238
Manual grease lubrication and 40,000
working hours
550 KW
750
Continous, 24 Hours/Day operation
Coupled through fluid coupling with the
crusher
28 T
Sr.No.
1
Description
Location
Specification
Below wagon
tippler hopper
Type
Manufacture
Mechanical turflo
type
Tata Robins Fraser
Ltd.
TE-9
3X8
Specification
Below
reclaim
hopper
Mechanical
turflo type
Tata Robins
Fraser Ltd.
TE-9
4X8
Specification
Above coal
crusher
Mechanical
turflo type
Tata Robins
Fraser Ltd.
TE-11
5X10
5
6
7
8
9
10
Numbers
Guaranteed capacity
Designed capacity
Length of tray
With of tray
Slope of tray
6 Nos.
200 TPH
250 TPH
2438 mm
915 mm
100 down hill
4 Nos.
300TPH
375 TPH
2438 mm
1219 mm
100 down hill
11
12
13
Operating Speed
Feeder stroke
Material of
construction
Tray
Liner
800 rpm
800 rpm
2 Nos.
600 TPH
750 TPH
3038 mm
1524 mm
100 down
hill
800 rpm
M.S. IS-226
10 mm thick tiscral
14
Type of feed
rate controller
By changing the
rpm of feeder
15
HP rating of each
feeder
Approximate weight
Recommended
clearance between
feeder and stationary
chute
10
M.S. IS-226
10 mm thick
tiscral
By changing
the rpm of
feeder
15
M.S. IS-226
10 mm thick
tiscral
By changing
the rpm of
feeder
20
1960 Kg
51 mm
2520 Kg
51 mm
3750 Kg
51 mm
16
17
7.9.4
BELT WEIGHER
SR.
NO.
1.0
2.0
3.0
DESCRIPTION
SPECIFICATION
Location
Quantity
Type
4.0
5.0
6.0
7.0
8.0
8.1
8.2
8.3
9.0
Make
Type of speed sensor
Type of load sensor
No. of load cell per weigher
Capacity
Rated
Maximum(Designed)
Minimum
Accuracy
9.1
9.2
9.3
10.0
10.1
11.0
12.0
13.0
14.0
15.0
15.1
15.2
16.0
17 .0
7.9.5
SR. NO.
1.0
2.0
3.0
4.0
5.0
6.0
6.1
6.2
6.3
6.4
6.5
6.6
6.7
7.9.6
SR. NO.
1.0
2.0
At rated ty(Guaranteed)
At maximum
capacity(Guaranteed)
At minimum pacity(Guaranteed)
Calibration
Weight per unit length of chain
Type of flow indicator
Type of totalising counter
No. of Digits
Whether zero reset button
provided
Remote Panel
Type of flow indicator
Type of totalising counter
Power supply required
Power Demand
+/-0.5% F.S.
+/-0.5% F.S.
+/-0.5% F.S.
By test chain
49.5 Kg / m
Moving coil meter
EM counter
6
Yes
METAL DETECTOR
DESCRIPTION
Type
Make
Model No.
Location
Quantity
Sensitivity at normal working
condition
At maximum capacity with
maximum moisture content
Particular to sensitivity
to other
non ferrous material
Power requirement (Watt)
Power supply required
Enclosure material and
thickness
Degree of protection
Hooter
SPECIFICATION
Electronic
Unique Electromag, Mumbai
Type SCTA
15A, 15B
2 nos in each conveyor
25 mm dia MS/AL sphere
25 mm dia MS/AL sphere
Depends on conductivity properties and
electrical characteristic of materials.
Sensitivity is adjustable.
150 VA
230 V +/- 10% C/S +/- 5%(Combine
+/- 10%)
Search coil 3 mm, Pane 2 mm
IP-54
Provided
MAGNETIC SEPARATOR
DESCRIPTION
Type
Manufacturer
SPECIFICATION
Overband, inline magnetic separator
Electrometike
3.0
4.0
5.0
6.0
6.1
6.2
6.3
6.4
6.5
7.0
8.0
9.0
10.0
11.0
12.0
13.0
13.1
Details of drive
Rating
13.2
Make
14.0
Operating voltage
Of magnet
7.9.7
Sr.No.
1.01
1.02
1.03
1.04
1.04.02
1.04.03
1.04.04
CONVEYER BELT
Description
Designation
Capacity
Rated
Design
Width
Belt position
length C/C (M)
11A/B
12A/B
13A/B
Specification
14A/B 15A/B
16
17A/B
18A/B
600 TPH
750 TPH
1000 mm
A
210.29
B
209.98
23.35
210.3
51.25
21.05
6.0
248.25
170.9
29.8
28.4
Nylon
Troughed
124.45
15.7
A
128.09
B
108.82
14.75
116.7
14.966
troughed
Trughing angle
(Deg)
Belt joints
Cover grade
Belt type/ No.
of plies
Thickness of
covers (M)
Top (mm)
Bottom (mm)
Belt
speed(m/sec)
Allowable
working tension
(KN)
Supplier data of
working tension
(KN/m)
1.04.05
1.04.06
1.05.05
1.06.00
1.09
1.09.01
1.09.02
1.10.00
1.11.00
1.12.00
7.9.8
35
Vulcanised
Fire resistance
800/4
800/4
800/4
800/4
80/4
800/4
800/4
800/4
5
2
2.9
5
2
2.9
5
2
2.5
5
2
2.5
5
2
2.5
5
2
2.5
5
2
2.5
5
2
1.0
48
44.64
24.72
64.8
56.76
40.68
38.04
26.04
50
50
40.1
70
50
50
40
40
Sr. No.
1
2
3
4
Description
Location
Type
Nos.
Manufacturer
5
6
7
8
9
10
11
12
13
Model No.
Rating of motor
Rated KW transmitted
Rated torque transmitting capacity with
torque
Rated input speed
Rated Slip
Temperature at which plug fuses
Weight of the coupling unfilled (Kg)
Type of bearing and life
14
15
MATERIAL OF CONSTRUCTION
a. Impeller
b. Runner
c. Casing
Specification
Ring granulator (Crusher)
Scoop type
2
PEMBRIL FLUIDRIVE LTD,
Auranagabad
41 SWGR 25W Scaled version
550 KW
500 KW
150 to 275% of full load torque
750 rpm
3%
1800 C+/-50 C
1654 Kg
Spherical roller bearing Approx.
Life-3000 working hours
184 Lits of SHELL TELLOS
OIL-29
Aluminum alloy
Aluminum alloy
Aluminum alloy
d. Shaft
e. Flanges for input and output coupling
EN-8
Forged Steel
Sr. No.
1
2
3
Description
Manufacturer
Type
Type of prime mover
4
5
Input rpm
Max. no. of starts per hour
6
7
8
9
10
Direction of rotation
11
Bearing lubrication
12
13
14
Output coupling
Balancing
Material of construction
a. Impellar
b. Runner
c. Casing
d. Shaft
e. Flanges for input and output couplings
Specification
Fluidomat
Traction type
Direct on squirrel cage
induction motor
1470 Approx
2 consecutive starts or 3
starts/hr spaced
No
Yes
3%
Adjustable in the range of
150% to 275 % of full
required torque
Should be capable of
rotation in both direction
Lubrication of bearing
should preferably be done
with the fluid itself
Flexible/Semiflexible
Dynamically balanced
High tensile aluminum
alloy
High tensile aluminum
alloy
High tensile aluminum
alloy
EN-8
Forged steel
7.9.10
Sr.No.
Location Quantity
Motor
Conveyor
rating(KW)
1
2
3
4
5
6
7
8
11A/B
12A/B
13A/B
14A/B
15A/B
16
17A/B
18A/B
7.9.11
Sr.No.
1.0
2.0
2.1
2.2
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
11.1
11.2
11.3
11.3.1
11.4
11.5
12.0
12.1
12.1.1
2
2
2
2
2
1
2
2
125
125
55
150
150
110
110
37
RPM
1470
1470
1470
1470
1470
1470
1470
1470
Coupling
input
rating
(KW)
116.8
109.0
44.0
135.6
119.1
85.1
79.0
22.0
Gear
box
input
rating
(KW)
113.3
105.7
42.7
131.5
115.5
82.9
76.6
21.3
Model No.
STD/E/08
STD/E/08
STD/E/06
STD/E/08
STD/E/08
STD/E/07
STD/E/07
STD/E/05A
BELT FEEDER
Description
Location
Capacity
Rated capacity (TPH)
Designed capacity (TPH)
Quantity & Type
Manufacturer
Feeder Length (M)
Material handled
Bulk density (T/m3)
Design ambient temperature
(0C)
Moisture content of coal (%)
Hours of operation per day
Belt
Belt width
Belt Speed (m/min) approx
Type of fabric
Cover thickness (mm/min)
Top/Bottom
Cover grade
Type of loading & Discharging
Idlers
Carrying idlers
Type
Specification
Crusher house
Breaker house
600
750
750
750
2 (Unidirectional)
2(reveesible)
M/S McNally Bharat engineering Co. Ltd.
6.0
11.0
100 mm crushed coal 20 mm crushed coal
0.8
50
20 (max)
24
1200 mm
24.0
Nylon
9/2
Fire resistant
Through chutes
12.1.2
12.1.3
Configuration
Spacing
12.1.4
Disc material
12.1.5
12.1.6
12.2
12.2.1
12.2.2
12.3
12.4
12.5
12.6
13.0
13.1
13.2
13.3
Return idlers
Type
Spacing
Type of idler seal
Min. tube thickness )mm)
Applicable standard
Shaft material
Pulleys
Pulleys construction
Pulley shaft material
Type of bearing & plummer
block
13.4
13.5
13.6
13.7
Type of lubrication
Quantity & type of pulleys
Pulley dia & width (mm)
Type of lagging on drive
pulley
13.8
Type of lagging on other
pulley
13.9
Height of USOB from
supporting floor
14.0
Skirt Board
14.1
Length
14.2
Material
a. Main plate
b. Liner
c. Cover plate
15.0
Gear Box
15.1
Type
15.2
Type of enclosure
15.3
Type of lubrication
15.4
Additional requirements
Flat
400 mm at loading points & 500 mm at other
portion
Special resilient rubber having greater shock
absorbing capacity
Mounting on slotted pipe sleeves on shaft to
provide friction grip by spring action &
located by collars
Antifriction bearing with labyrinth type seal.
All grease fitting shall be rutton head type
having plastic caps.
152.4 mm dia steel tube flat idler
2000 mm
Double labyrinth seal
4
IS-4776 latest edition
EN-8 or Equivalent
Heavy duty welded steel as per IS-8531
Forged steel to IS-1875 Class-V
Antifriction double row self aligning
spherical roller bearing in split type plummer
block with labyrinth seal. 4000 hours
working life.
Grease
1 no. drive, 1 no. tail pulley per feeder
630 drive & tail pulley per feeder
12 mm thick vulcanized natural rubber
herringbone type lagging
12 mm thick vulcanized plain natural rubber
lagging
1200 mm
Continuous
16 mm thick MS plate
10 mm thick MS scral
4 mm thick MS plate
Worm
Totally enclosed dust proof
Splash
Draining plug & oil level guage
16.0
16.1
16.2
16.3
17.0
18.0
18.1
18.2
18.3
19.0
19.1.0
19.1.1
19.2.0
19.2.1
20.0
20.1.0
20.1.1
20.2.0
20.2.1
Coupling
Type
Location
Coupling guard
Tail pulley guard
Take up unit
Type
Location
Travel
Scrappers
External
Location
Internal
Location
Belt protection Drive
Zero Speed switch
Quantity
Quantity
Belt Sway switch
7.9.12
LOCO WDS-4
No.
Type
Model
Working method
Fuel injection
Weight of engine without water & oil
Maximum length
Maximum Width
Total Height
Number of cylinder
Cylinder bore
Piston stroke
Total swept volume
Swept volume per cylinder
Compression ratio
Nominal output
Rotating speed at nominal load
Idling speed
Torque at nominal load
Mean effective pressure
Sense of rotation viewed at flywheel
Engine cooling
4
6M 282 A(k)
01/21
4 stroke, single acting
Direct injection
7150 Kg
2876 mm
2035 mm
2035 mm with oil sump
1550 mm without oil sump
6
240 mm
280 mm
76 Lit
12.7 Lit
12:2:1
650 HP
1000 rpm
440 rpm
541 Mkg
8.6 Kg/cm2
Anticlockwise
water circulation
ELECTRIACL STARTER
TF-24 V1595 Bosch
24 V
1000 watts
7.9.14
DOZER (D155A-1)
800C
85 to 900
1.8 to 2.1 Kg/cm2
2.4 to 3.0 kg/cm2
0.75 Kg/cm2
1.5 m
Total
Make
6 Nos.
BEMLD155A-1
No.
Model
2
KOMATSU S6D 155-4D
Diesel Engine
2000
320 HP
144 KgM
24 V, 11 KW
5780 Kg
1000 mm
Rated RPM
Rated Horse Power
Maximum torque ( at about 1400 rpm)
Start system- starting motor
Equipment weight
Maximum tilt
7.9.15
CUMMINS DIESEL ENGINE
No.
No. of cylinder
Bore stroke (mm)
Displacement CID/Lit
Maximum HP
Rim
Peak torque (Ft-Lb)
7.10
7.10.1
KT(A)1150
4
6
159 x 159
1150/18.9
525
2100
1550
The fuel oil station in BTPS is located near the coal handling plant. In
conjunction with old receiving header which can unload six nos. oil tankers, another
header of 225M length has been installed in between two rail tracks. From each rail track
25 nos. of oil tankers can be unloaded at a time. For transferring the LDO from the
header to storage tank there are three transfer pumps each of 120m3 /hr. capacity.
7.10.2
STORAGE FACILITIES
Three light oil storage tanks of 2,000 m3 capacity each have been installed at the
back of the fuel oil pump house. Each tank is provided with immersion type steam heater
to keep the oil temp. at around 500 C in case of HFO unloading.
SPECIFICATION OF EQUIPMENT
7.10.3
3
Rotary Gear
L.D.O.
120
5
80
85
45.50%
975 rpm
600 C
9
MOTORS
Type/Make
RPM
Voltage
H.P.
Temp. rise over an ambient temp. of
450 C
TEFC/Crompton
1000
415 V, 3PH, 50 c/s
100
650 C
FILTERS
No. Of coarse filters
Type/Manufacturer
Design Pressure
Maximum pressure drop at 75 %
Cleanliness
7.10.4
3
Duplex/Technique
1 kg/cm2
35 kg/cm2
No. off
Type
Discharge pressure
4
Multi screw positive
displacement
25 kg/cm2
Capacity
250 lit/min.
MOTOR
Manufacturer
Type
Rating
7.10.5
M/s Kirloskar
3ph. Induction motor.
37 KW, 1500 rpm.
LIGHT OIL (HSD) UNLOADING PUMP (STAGE II &III)
No. off
Make
Capacity
1
AROTA
40 m3/hr
MOTOR
Type
Rating
7.10.6
No. off
Model No.
Capacity
Pressure
2
PDE-45-4 GR-22 AU2
250 Lit/min at 2 CST
25 Kg/cm2
MOTOR
Type
Rating
7.10.7
No. off
Type
Make
Model No.
Capacity
Discharge pressure
2
Multi screw positive
displacement , Horizontal
TUSHACO
PDHU-5-4
250 lit/min.
25 kg/cm2
MOTOR
Manufacturer
Type
Rating
M/s Siemens
3ph. Induction motor.
18.5KW, 3000
7.10.8
No. off
Type
Make
Model No.
Capacity
Discharge pressure
2
Multi screw positive
Displacement, Vertical
TUSHACO
PDH-60-SDEF
250 lit/min.
25 kg/cm2
MOTOR
Manufacturer
Type
Rating
7.10.9
M/s Siemens
3ph. Induction motor.
18.5KW, 3000
1. Flash point
2. Pour point maximum
3. Kinematic Viscosity in Cent.
4. Ash content
5. Carbon residue content
6. Sediment content
7. Sulpher content
8. Moisture content
9. Acidity
660 C minimum
120 C for winter
2.5 to 15.7
Stocks at 380 C
0.02 max. by wt.
1.5 by wt.
0.10 by wt.
1.8 by wt.
0.25 maximum by volume
Nil.