You are on page 1of 13

OptiX 2500+(Metro3000)

Hardware Description Manual

Contents

Contents
3 Power Box ....................................................................................................................................3-1
3.1 Functions.......................................................................................................................................................3-2
3.2 Panel Description ..........................................................................................................................................3-3
3.3 DIP Switches .................................................................................................................................................3-5
3.4 Interface ........................................................................................................................................................3-6
3.4.1 SERIAL Interface ................................................................................................................................3-6
3.4.2 ALARM Interface ................................................................................................................................3-6
3.5 Parameters .....................................................................................................................................................3-9

Issue 01 (2007-11-05)

Huawei Technologies Proprietary

OptiX Metro XXX Terminal STM-1


Hardware Description Manual

Figures

Figures
Figure 3-1 Functional block diagram of the power box .....................................................................................3-2
Figure 3-2 Front view of the power box.............................................................................................................3-3
Figure 3-3 DIP switches of the PMU .................................................................................................................3-5
Figure 3-4 Cable between the SERIAL interface and the subracks....................................................................3-6
Figure 3-5 Pins of the ALARM interface ...........................................................................................................3-7
Figure 3-6 Alarm cable.......................................................................................................................................3-9

ii

Huawei Technologies Proprietary

T2-042503-20060620-C-1.80

OptiX 2500+(Metro3000)
Hardware Description Manual

Tables

Tables
Table 3-1 Functions of the units in the power box..............................................................................................3-2
Table 3-2 Description of the power box panel....................................................................................................3-4
Table 3-3 DIP switches setting and the corresponding meanings .......................................................................3-5
Table 3-4 Pin assignment of the ALARM interface............................................................................................3-8
Table 3-5 Usage of the pins of the ALARM interface ........................................................................................3-8

Issue 01 (2007-11-05)

Huawei Technologies Proprietary

iii

OptiX 2500+(Metro3000)
Hardware Description Manual

3 Power Box

Power Box

About This Chapter


The power box for the OptiX 2500+(Metro3000) is mounted at the top of the cabinet. It provides
the standard 48 V DC or 60 V DC for the entire cabinet.
All external interfaces are located on the front panel of the power box.
The following table lists the contents of this chapter.
Section

Description

3.1 Functions

This section describes the functions of the power box of the


OptiX 2500+(Metro3000) system.

3.2 Panel Description

This section describes the front panel of the power box of the
OptiX 2500+(Metro3000) system.

3.3 DIP Switches

This section describes the setting of the DIP switches of the


Power box of the OptiX 2500+(Metro3000) system.

3.4 Interface

This section describes the interfaces on the power box of the


OptiX 2500+(Metro3000) system.

3.5 Parameters

This section describes the related parameters of the power box


of the OptiX 2500+(Metro3000) system.

Issue 01 (2007-11-05)

Huawei Technologies Proprietary

3-1

OptiX 2500+(Metro3000)
Hardware Description Manual

3 Power Box

3.1 Functions
The power box provides reliable power supply for the cabinet.
Figure 3-1 shows the functional block diagram of the power box.
Table 3-1 lists the functions of each unit in the power box.
Figure 3-1 Functional block diagram of the power box
PDU
ORing Diode

Fuse
48V1

Lightning
Protection
Unit

EMI filter

ORing Diode

Power Output Switch

EMI filter

ORing Diode

Power Output Switch

EMI filter

ORing Diode

20A

ORing Diode

2A

20A
20A

PMC

Fuse
Lightning
Protection
Unit

Output
Cable
Terminal

Power Output Switch

PMU

48V2

2A

Power Output Switch

EMI filter

ORing Diode

Power Output Switch

EMI filter

ORing Diode

Power Output Switch

EMI filter

ORing Diode

PDU

Output
Cable
Terminal

20A
20A
20A

Alarm Monitor Signal

Table 3-1 Functions of the units in the power box


Unit

Acronym

Function

Power distribution
unit

PDU

Provides power distribution and protects the system


from lightning.

Power monitoring
unit

PMU

Generates the ringing current;


Monitors the ringing current, the 48 V/60 V DC
voltage and temperature in the power box.
Accesses 16 external alarms and outputs 4 alarms.
Provides low-voltage protection.
Controls cabinet indicators and SCC
communication.

3-2

Power monitoring
connection board

PMC

Power output switch

Supplies working voltage to the PMU.


Provides two lines of testing voltages.
Is a magnetic circuit breaker used to control the
corresponding power outputs.

Huawei Technologies Proprietary

Issue 01 (2007-11-05)

OptiX 2500+(Metro3000)
Hardware Description Manual

3 Power Box

The PMU board is the main part of the power box. It has the following functions:
z

Generating ringing current:

The PMU board provides ringing current for the orderwire.


z

Monitoring ringing current:

The PMU board tests whether the ringing current for the orderwire is normal, and reports the
alarms such as "invalid ringing current".
z

Monitoring the voltage.

The PMU can monitor the input voltage of the two 48 V and the 60 V power and report the
voltage value and voltage alarms. The voltage alarms include the over-voltage alarm and
under-voltage alarm.
The alarming threshold may be the default value in the system, or may be set by the user
according to the requirement. In different applications, the thresholds can be set as follows:
Over-voltage threshold: 60 V1 V for the nominal 48 V DC, or 71 V1 V for the nominal
60 V DC.
Under-voltage threshold: 41 V1 V for the nominal 48 V DC, or 51 V1 V for the
nominal 60 V DC.
z

Monitoring the temperature

The temperature sensor in the power box monitors the temperature. Note that the sensor
measures the ambient temperature inside the power box, not that in the subracks or boards.
z

Monitoring alarms

The PMU can monitor 16 external alarm inputs and 4 equipment alarms. It outputs the alarms
that occur and supervises the external environment.

3.2 Panel Description


Figure 3-2 shows the front view of the power box.
Figure 3-2 Front view of the power box
3

RTN(+)

20A
-

20A
+

20A
+
-

2A

RTN(+)

OUT1

OUT2

OUT3

ON

ON

OFF

OFF

OFF

SW 1

SW 2

SW 3

RUN

20A

OUT1

OUT2

OUT3

2A

ALM

AUX

ON

ON

ON

OFF

OFF

OFF

SW 1

SW 2

SW 3

ALARM

PDU

Huawei Technologies Proprietary

RUN

MUTE

ALM

PMU

PDU

SERIAL

TEST
POW ER IN

ALM

11

RUN
POW ER IN

Issue 01 (2007-11-05)

20A
+
-

10

NEG(-)

AUX

ON

20A
-

NEG(-)

12

3-3

OptiX 2500+(Metro3000)
Hardware Description Manual

3 Power Box

Table 3-2 describes the items shown in Figure 3-2.


Table 3-2 Description of the power box panel
Mark

Functional Unit

Function

PDU

Provides power distribution and protects the system from


lightning.

RUN and ALM indicators on the


PDU

Running and the alarm indicators of the PDU.

Protection grounding screws

Lead in the PGND cable.

Input cable terminals

Lead in the 48 V and the 60 V power cables and BGND cables.

Three power distribution


switches

SW1

Controls power supply of the upper subrack.

SW2

Controls power supply of the middle subrack.

SW3

Controls power supply of the lower subrack.

Output cable terminal

Lead in the power cables connected to the subracks (35 A), HUB
(2 A) and COA (2 A).

TEST switch

Used for the audio/visual alarm test.


Usually the TEST switch is in the lower state. When it is in the
upper state, the green, yellow and red indicators on the cabinet top
flash, and the buzzer reports an alarm.
This shows that the alarm system is in the normal state.

MUTE switch

Used for muting the audio alarm.


When the MUTE switch is off, the audio alarm is shut down
completely.
If there is a critical alarm, no audio alarm is reported.
Normally this switch is required to be set to ON.

ALARM interface

Used for alarm input, alarm output and alarm cascade.

10

SERIAL interface

Used for subrack communication.

11

PMU

Power monitoring unit.

12

RUN and ALM indicators on


PMU

Running and the alarm indicators of the PMU.

The boards of the subrack are fed with power as follows:

3-4

The external 48 V or 60 V DC power is fed into the power box through a power cable.

The 48 V or 60 V DC power is distributed to every subrack and HUB through the


power input switches in the power distribution board.

Each board on the subracks is fed with proper power from the backplane through its own
power connector.

The secondary power module on each board converts the power into the operating
voltage required by each chip on the board at the same time.

Huawei Technologies Proprietary

Issue 01 (2007-11-05)

OptiX 2500+(Metro3000)
Hardware Description Manual

3 Power Box

3.3 DIP Switches


The PMU board of the power box provides four DIP switches, which are used to set the PMU
state.
See Figure 3-3.
Figure 3-3 DIP switches of the PMU
ON

ON

ON

ON

The following describes the function of each DIP switch.


DIP switch 1 and DIP switch 2 are used to set communication with the exact subrack.

Different settings of the two switches enable the PMU to communicate with the right subrack.
The PMU reports the information such as environment variables and voltage to the ASCC of
the subrack. Then, the ASCC reports the information to the T2000 server.
In Table 3-3, different combinations and their corresponding meanings are listed.
Table 3-3 DIP switches setting and the corresponding meanings
DIP Switch 1

DIP Switch 2

PMU Communicates with

ON

ON

Upper subrack.

ON

OFF

Middle subrack.

OFF

ON

Lower subrack.

OFF

OFF

None of the subracks.

ON indicates the DIP switch is in the upper position.


OFF indicates the DIP switch is in the lower position.
z

DIP switch 3 is used to select the subrack for the control of cabinet indicators.

DIP switch 3 is OFF by default. It means the cabinet indicators are controlled by the upper
subrack. In special cases, DIP switch 3 can be set to ON.
z

Issue 01 (2007-11-05)

DIP switch 4 is used to set the accessed power.

When the 48 V power is accessed, the switch should be turned down in normal cases.
When the switch is turned up, common overvoltage alarms can be suppressed (mainly
used in special areas).

When the 60 V power is accessed, the switch should be turned up in normal cases.
When the switch is turned up, common overvoltage alarms can be suppressed.

Huawei Technologies Proprietary

3-5

OptiX 2500+(Metro3000)
Hardware Description Manual

3 Power Box

When the 48 V and 60 V power supplies are accessed at the same time, the 60 V
power reports common overvoltage alarms if the switch is turned down. If the switch
is turned down, the overvoltage alarm cannot be reported when the 48V power is
overvoltaged.

3.4 Interface
The PMU in the power box can access external and internal alarms.
These alarms are accessed by ALARM and SERIAL interfaces of the PMU.

3.4.1 SERIAL Interface


The SERIAL interface is the internal alarm interface and connects with the subrack alarm
interface.
Figure 3-4 shows the cable between the SERIAL interface and subracks.
Cable W1 is connected with the upper subrack, cable W2 is connected with the middle
subrack and cable W3 is connected with the bottom subrack.
Cable W4 is used to transmit the driving signals to the cabinet indicators.
Figure 3-4 Cable between the SERIAL interface and the subracks

There are two types of alarms in the transmission equipment cabinet:


One is the visual alarm such as the red indicator alarm (critical) and the yellow indicator
alarm (major). The other is the audio alarm reported by a buzzer.
The audio alarm is mainly triggered by critical alarms. If the SCC board sends a critical alarm
signal, the red indicator flashes and the buzzer rings.
The alarm MUTE switch at the cabinet top or the ALC switch of the SCC board controls the
buzz sound.

3.4.2 ALARM Interface


The ALARM interface is the external alarm interface.

3-6

Huawei Technologies Proprietary

Issue 01 (2007-11-05)

OptiX 2500+(Metro3000)
Hardware Description Manual

3 Power Box

This interface collects data from external alarm devices and outputs alarm value to centralized
alarm system.
The power box provides four alarm outputs, one for the major alarm, one for the critical alarm,
and the other two for the auxiliary On/Off value. If the centralized alarm system is in the
mode of audio alarm, the alarm mute function is required. The alarm signal is led out from the
ALARM interface of the PMU.
Figure 3-5 shows the pins of the ALARM interface (DB50).
Table 3-4 shows the pin assignment of the DB50 connector and Table 3-5 shows the usage of
the pins of the ALARM interface.
Figure 3-5 Pins of the ALARM interface

26

27

28

29

30

31

32

33

34

10

35

11

36

12

37

13

38

14

39

15

40

16

41

17

42

18

43

19

44

20

45

21

46

22

47

23

48

24

49

25

50

Issue 01 (2007-11-05)

Huawei Technologies Proprietary

3-7

OptiX 2500+(Metro3000)
Hardware Description Manual

3 Power Box

Table 3-4 Pin assignment of the ALARM interface


PIN No.

Definition

PIN No.

Definition

RELAY1

34

ALMOUT1

RELAY2

35

ALMOUT1

RELAY3

36

ALMOUT2

RELAY4

37

ALMOUT2

RELAY5

38

ALMOUT3

11

RELAY6

39

ALMOUT3

13

RELAY7

40

ALMOUT4

15

RELAY8

41

ALMOUT4

17

RELAY9

42

ALMOUT5

19

RELAY10

43

ALMOUT5

21

RELAY11

44

ALMOUT6

23

RELAY12

45

ALMOUT6

26

RELAY13

46

ALMOUT7

28

RELAY14

47

ALMOUT7

30

RELAY15

48

ALMOUT8

32

RELAY16

49

ALMOUT8

2, 4, 6, 8, 10, 12, 14, 16, 18, 20,


22, 24, 27, 29, 31, 33

GND

25, 50

Undefined

Table 3-5 Usage of the pins of the ALARM interface


Pin Name

Usage

ALMOUT1 and ALMOUT2

Major alarm output

ALMOUT3 and ALMOUT4

Critical alarm output

ALMOUT5 and ALMOUT6

1st auxiliary alarm output

ALMOUT7 and ALMOUT8

2nd auxiliary alarm output

RELAY1-16

16 external alarm input

If several cabinets are installed side by side, the alarms of these cabinets can be cascaded.

3-8

Huawei Technologies Proprietary

Issue 01 (2007-11-05)

OptiX 2500+(Metro3000)
Hardware Description Manual

3 Power Box

One end of external alarm cable contains the DB50 connector, while the other end is divided
into branches, contains two separate alarm output/alarm cascade connectors (DB9) and one
external alarm input connector (DB37).
See Figure 3-6.
Figure 3-6 Alarm cable

In Figure 3-6, W2 and W3 are alarm output/cascade cables. The alarm signals are cascaded
between cabinets through W2 and W3, and the last cabinet transmits the signals to the
centralized alarm system.
As the alarm output interface and the alarm cascade interface uses DB9 male connectors, a
3-m cable with DB9 female connectors on both ends is required to cascade the alarm signals
of two cabinets.
The power box provides 16 external alarm input interfaces. The alarm input function is
designed for remote monitoring of the external system (for example, environment monitoring
system) alarms. The user may configure the names of the 16 input alarms accordingly, and
thus achieve remote monitoring of external alarms together with the external system.
The external alarms include those caused by access control, smoke, and other environmental
factors. In other words, it accesses the environmental alarms in the equipment room for
centralized monitoring. The external alarms are accessed by the user, and processed with
software program to determine whether it is valid before being displayed on the T2000 server.
W1 is the external alarm input connector, DB37 female connector. A 10-meter alarm input
cable (DB37 connector on one end and the other end reserved) is connected to the W1 cable
to realize external alarm input.
The transmission system cannot monitor external alarms by itself. The monitoring needs the cooperation
of the external environment monitoring system of the customer.

3.5 Parameters
Dimensions: 400 mm (W) x 258 mm (D) x 100 mm (H)
Rating current: 65 A

Issue 01 (2007-11-05)

Huawei Technologies Proprietary

3-9

You might also like