You are on page 1of 6

ENERGO ENG

PROJECT-

CONVERSION OF I-BED

CLIENT-

RASHTRIYA ISPAT NIGAM LIMITED

DOC.NO.:

EEPL/PRJ-111/EE/H-003

DOC. Name:

POWER CABLE SCHEDULE

S.No

Rev

Cable Tag

From

To

Type

Location

Qty

Unit
Rating Voltage
distanc
(kW)
(V)
es (m)

MCC-PC-000

LC-8 MCC

415V MCC

A2XFY

OM-16

100

460

415

MCC-PC-001

415V MCC

Belt Conveyor CO-33S

AYFY

JT O-21

207

45

415

MCC-PC-003

415V MCC

PJB1 for Belt Conveyor CO33M

AYFY

New JSP-1

235

160

415

MCC-PC-004

PJB1,Belt Conveyor CO-33M

Belt Conveyor CO-33M

FLE X IBLE
COPPER

New JSP-1

10

160

415

MCC-PC-006

415V MCC

Flap Gate FG-1

AYWY

New JSP-1

235

4.35

415

MCC-PC-007

415V MCC

LCP FOR DE

AYFY

Conveyor SP-1

270

57

415

MCC-PC-008

415V MCC

Elect. Hoist EH-1

AYFY

New JSP-1

235

5.1

415

MCC-PC-009

415V MCC

Belt Conveyor SP-1

AYFY

New JSP-2

304

55

415

MCC-PC-011

415V MCC

Flap Gate FG-2

AYFY

New JSP-2

304

4.35

415

10

MCC-PC-012

415V MCC

Elect. Hoist EH-2

AYFY

New JSP-2

304

3.4

415

11

MCC-PC-013

415V MCC

Belt Conveyor SP-2

AYFY

JT O-13

340

37

415

12

MCC-PC-015

415V MCC

MLDB

AYFY

OM-16

30

42.5

415

13

MCC-PC-016

415V MCC

Elect. Hoist EH-3

AYFY

JT 0-13

340

4.1

415

ENERGO ENGINEERING PROJECTS LTD.

Efficien
cy

Running

cosR

sinR

Starting

cosS

sinS

Full load
current

Current
at
starting

DF

Resistan Reactan
Derated ce of
ce of %Voltage dop
current Cable/k Cable/k
at Runing
m
m

%Voltage
drop at
Starting

%VDR=(1.732
(PVC
(PVC *Ir*L*(RcosR
Idr= Ir/d Insulatio Insulati
+X
n)
on)
sinR)*100)/
(V*1000*N)

%VDR=(1.73
2*Is*L*(Rcos
S+ X
sinS)*100)/
(V*1000*N)

Ir=A*1000/
(1.732*P*V*
E)

7.2*Ir

Ir

Is

Idr

Size of the
cable (mm)

No of
run

0.85

0.53

0.00

0.00

752.91

752.91

0.68

1107.22

0.12

0.09

2.31

0.00

3.5C X 300

0.92

0.73

0.68

0.30

0.95

80.06

576.42

0.68

117.73

0.30

0.09

1.93

8.60

3C X 120

0.95

0.88

0.47

0.30

0.95

275.66

1984.79

0.68

405.39

0.12

0.09

1.98

11.46

3C X 300

0.95

0.88

0.47497

0.3

0.95

275.6649

0.246

0.04

0.10

1C X 95

0.85

0.70

0.71

0.30

0.95

8.38

60.31

0.68

12.32

2.29

0.10

1.37

4.61

3C X 16

0.92

0.84

0.54

0.00

0.00

101.41

730.14

0.68

149.13

0.15

0.09

1.98

0.00

3.5C X 240

0.85

0.70

0.71

0.30

0.95

9.82

7.89

0.68

14.44

1.44

0.10

1.04

0.41

3.5C X 25

0.94

0.85

0.53

0.30

0.95

95.77

689.53

0.68

140.84

0.12

0.09

1.79

10.30

3C X 300

0.85

0.70

0.71

0.30

0.95

8.38

60.31

0.68

12.32

1.44

0.10

1.14

4.01

3C X 25

275.66489727 1984.787

0.85

0.70

0.71

0.30

0.95

6.55

7.89

0.68

9.63

1.44

0.10

0.89

0.53

3.5C X 25

0.92

0.77

0.64

0.30

0.95

65.83

473.95

0.68

96.80

0.20

0.09

1.96

9.59

3C X 185

0.92

0.78

0.63

0.00

0.00

75.61

76.50

0.68

111.19

1.44

0.10

0.56

0.00

3.5C X 25

0.85

0.70

0.71

0.30

0.95

7.89

7.89

0.68

11.61

1.44

0.10

1.21

0.59

3.5C X 25

REV.2
SHEET 2 OF 2

Max .
current
rating of
Single
run of
Cable (A)

Net Max.
rating of
Appro X
Current
Dia of Remark
for total
Cable
runs of
cable

(N *
Imax.)

Imax.
461.00

922.00

59.30

180.00

180.00

39.40

315.00

630.00

58.40

200

1200.00

18.5

51.00

51.00

20.20

280.00

280.00

58.90

70.00

70.00

25.40

315.00

315.00

58.40

70.00

70.00

22.90

70.00

70.00

25.40

240.00

240.00

47.90

70.00

140.00

25.40

70.00

70.00

25.40