You are on page 1of 92

Belimo Aircontrols, Inc.

(USA)

Basic Hydronic Training

BELIMO Aircontrols

Basic Hydronic Training 1

System Components

BELIMO Aircontrols

Basic Hydronic Training 2

Components in a Hydronic System

6 7
2

3
4

BELIMO Aircontrols

Load

Source

1.
2.
3.
4.
5.
6.
7.

Pump
Load
Control Valve
Balancing Valve
Source
Air Removal System
Expansion Unit

Basic Hydronic Training 3

Source Carrier Load


Water, Air, Refrigerant, Electricity

Heating
Cooling

BELIMO Aircontrols

Source

Load

Heating Load
Cooling Load

Basic Hydronic Training 4

Hydronic Systems
Heating

Cooling
43F

57F

BELIMO Aircontrols

55F

250F

185F

240F
Heating Coil

Cooling Coil

Chiller

45F

Boiler

40F

245F

190F

Basic Hydronic Training 5

Load

Source

Load

Source

Water Systems

Expansion
Chamber
Closed System
BELIMO Aircontrols

Open System
Basic Hydronic Training 6

Closed Water Systems


Low Temperature Water (LTW)
- Max. 160PSI and max. 250F
Medium Temperature Water (MTW)
-Max. 160PSI / 250F to 350F
High Temperature Water (HTW)
-Max. 300 PSI and max. 350F
Chilled Water Systems (CWS)
- Max. 120 PSI / 40F to 55F (44F or 45F)

BELIMO Aircontrols

Basic Hydronic Training 7

Piping Circuits

Two Pipe System


Three Pipe System
Four Pipe System
Direct and Reverse Return Systems
Primary-Secondary System

BELIMO Aircontrols

Basic Hydronic Training 8

Two Pipe System

Main Supply Chilled Water or Heat Water


Supply one pipe, Return one pipe
Cooling or heating at source
Loads must all require cooling or heating
coincidentally

BELIMO Aircontrols

Basic Hydronic Training 9

BELIMO Aircontrols

Load

Load

Load

Chiller

Boiler

Two Pipe System

Basic Hydronic Training 10

Two Pipe System

BELIMO Aircontrols

Basic Hydronic Training 11

BELIMO Aircontrols

Load

Load

Load

Chiller

Boiler

Three Pipe System

Basic Hydronic Training 12

Three Pipe System

BELIMO Aircontrols

Basic Hydronic Training 13

Three-Pipe System

BELIMO Aircontrols

Basic Hydronic Training 14

Four Pipe System

BELIMO Aircontrols

Basic Hydronic Training 15

Four Pipe System with One Coil

BELIMO Aircontrols

Basic Hydronic Training 16

Four Pipe System with H&C Coil

BELIMO Aircontrols

Basic Hydronic Training 17

Cost for Four Pipe System


High first cost due to the second water system and the
need for either two coils or more costly control valves
at each terminal unit.
High operating cost due to the two pumps operating,
but do provide good flexibility in meeting varying loads.

BELIMO Aircontrols

Basic Hydronic Training 18

Advantages of Four Pipe Systems


All year availability of heating and cooling with individual
zone temperature control

Chilled and hot water are typically only simultaneously


supplied during the Spring and Fall seasons
Elimination of zoning cost and complexity
Simpler changeover decisions
The lowest and quietest fan speed is adequate most of
the time.

BELIMO Aircontrols

Basic Hydronic Training 19

Piping - Direct Return Piping


Coil #4
0 - 100 gpm

Coil #3
0 - 100 gpm

Coil #2
0 - 100 gpm

Coil #1
0 - 100 gpm

Source

BELIMO Aircontrols

Basic Hydronic Training 20

Piping - Reverse Return Piping


Coil #4
0 - 100 gpm

Coil #3
0 - 100 gpm

Coil #2
0 - 100 gpm

Coil #1
0 - 100 gpm

Source

BELIMO Aircontrols

Basic Hydronic Training 21

BELIMO Aircontrols

Load

Load

Load

Source

Source

Source

Primary Secondary System

Basic Hydronic Training 22

Pipe Design

BELIMO Aircontrols

Basic Hydronic Training 23

Bernoullis Law
pstat

pdyn

const.

The Bernoullis law is stating the principle of


energy conservation. The sum of the two energies
represented by static pressure and dynamic
pressure is constant between two points in the
pipe, assuming no energy exchange with the
exterior or transformation of energy into heat by
friction between these two points.
BELIMO Aircontrols

Basic Hydronic Training 24

Bernoullis Law

pdyn1

pdyn2
ptotal1

pstatic1

BELIMO Aircontrols

ptotal2

pstatic2

Basic Hydronic Training 25

Z1

V12
2g

P1

Z2

V22
2g

P2

hL

V2 P2

hL

V1 P1

Z2
1

Z1
BELIMO Aircontrols

Basic Hydronic Training 26

Pipe Sizing and Pressure Drop Equations


h

L
f
D

V2
2g

Darcy-Weisbach Equation

h pressure drop, in ft
f friction factor, dimensionl ess (from Moody )
L Length of pipe, ft
D Internal Diameter of pipe, in
V Fluid average velocity, ft/sec
g gravitatio nal constan, 32.2 ft/sec 2
BELIMO Aircontrols

Basic Hydronic Training 27

Sizing a Piping System Pipe Friction Loss


Suggested head loss in range from 1 to 4ft per 100ft
- 1997 ASHRAE Handbook-Fundamentals
Max. 4 ft/sec velocity in pipe 2
Suggested 4 ft/sec velocity in pipes larger than 2

BELIMO Aircontrols

Basic Hydronic Training 28

Simplified Method
D

S Q 0 .4

D = Pipe Diameter
Q = Flow Rate, GPM
S = Pipe Sizing Constant
- S= 0.44, assuming 4 ft head drop/100ft
- S = 0.5 assuming 2 ft head drop/ 100ft

BELIMO Aircontrols

Basic Hydronic Training 29

Examples
Load: 100GPM
D = SQ0.4 = 0.44 x 1000.4 = 2.78 3

Load: 200GPM
D = SQ0.4 = 0.44 x 2000.4 = 3.66 4
Load: 300GPM
D = SQ0.4 = 0.44 x 3000.4 = 4.31 4
Load: 400GPM
D = SQ0.4 = 0.44 x 4000.4 = 4.83 5
BELIMO Aircontrols

Basic Hydronic Training 30

Head Loss Calculation


Pipes (Friction Loss for Water in Commercial Steel Pipe
(Schedule 40)
Strainers, Fitting, Elbows, Reduction, etc
Valves, Balancing Valves (Valve - Manufacturer)

Head loss Load (Coil, etc.)


Head loss Source (Chiller, etc.)

=Total Head Loss


BELIMO Aircontrols

Basic Hydronic Training 31

Head Loss in Pipes


Head Loss

Pipes (Friction Loss for Water in


Commercial Steel Pipe (Schedule 40)

Flow Rate

100GPM

2.5ft

BELIMO Aircontrols

hspec =ft/100ft pipe


Total h=L x hspec /100

Basic Hydronic Training 32

Fittings
h

V2
k
2g

h = head loss in feet of water


k = resistance coefficient for valve or fitting
V2/2g = velocity head, ft based on flow gpm in connect pipe (example Figure
2 15 for 2 in)
V = fluid velocity, ft/sec
g = 32.2 ft/sec2, gravitational constant

BELIMO Aircontrols

Basic Hydronic Training 33

BELIMO Aircontrols

Basic Hydronic Training 34

GPM

GPM
BELIMO Aircontrols

Coil

Total Pipe length = 300 ft


BTU/HR = 500,000 BTU/HR
T = 10F
GPM = ?

Chiller

Which pump do we choose?

BTUH
T 500

BTUH
T 500

500000
100GPM
10x500
Basic Hydronic Training 35

What is the pipe size?


Required Flow: 100GPM
Pipe Diameter: ?
D

S Q 0 .4

D = SQ0.4 = 0.44 x 1000.4 = 2.78 3

D = Pipe Diameter
Q = Flow Rate, GPM
S = Pipe Sizing Constant
S= 0.44, assuming 4 ft head loss/100ft
S = 0.5 assuming 2 ft head loss/ 100ft
BELIMO Aircontrols

Basic Hydronic Training 36

Head loss elbows?

V2
k
2g

42
0.8
2 32.2

Coil

Chiller

Pipe: 3, Steel Pipe, screwed


Head loss of total elbows?

0.2 ft

4 Elbow 0.8ft
BELIMO Aircontrols

Basic Hydronic Training 37

Head loss pipe?

Coil

Pipes (Friction Loss for Water in


Commercial Steel Pipe (Schedule 40)
Figure 2-14 Friction Loss - Water

Chiller

Pipe: 3, Steel Pipe, screwed


Total Pipe length = 300 ft

2.5 ft/100ft

h = 300 x 2.5 /100 = 7.5ft


BELIMO Aircontrols

Basic Hydronic Training 38

Coil

1 Chiller 9 ft (4PSI, Info Manuf.)


1 Cooling Coil 9 ft (4PSI, Info Manuf.)
1 Control Valve 9 ft (4PSI)
1 Balance Valve 3 ft (1PSI)
4 Elbows each 0.2 ft 0.8 ft
1 Pipe System 7.5 ft

Chiller

Total head loss?

Total Head Loss of 38.3ft at 100GPM

BELIMO Aircontrols

Basic Hydronic Training 39

System Curve
80

Head (ft)

60

System Point at
design load

40

20

10

Head Loss of 38.3 at 100GPM


0

20

40

60

80

100

120

140

160

180

200

Flow GPM
BELIMO Aircontrols

Basic Hydronic Training 40

Pumps in HVAC

BELIMO Aircontrols

Basic Hydronic Training 41

Pumps in HVAC
Pumps

Dynamic

Centrifugal

Volute Type

Single Suction

BELIMO Aircontrols

Special Effect

Displacement

Reciprocating

Rotary Pumps

Axial Flow Type

Double Suction

Basic Hydronic Training 42

Outlet Flow

Impeller

Inlet
Flow

BELIMO Aircontrols

Blade

Basic Hydronic Training 43

Pump Curve

Pump Characteristic

Coil

Chiller

Pump
Head

Operating Point
System
Head
V

100%

BELIMO Aircontrols

Volume

Basic Hydronic Training 44

Pump Curve (Steep)

Pump Characteristic

Coil

Chiller

Operating Point

100%

BELIMO Aircontrols

Volume

Basic Hydronic Training 45

Pump Curve (Flat)

Coil

Chiller

Pump Characteristic

Operating Point

25%
V

100%

Volume

BELIMO Aircontrols

Basic Hydronic Training 46

Operating Point
Pump Head
Capacity Curve

Coil

Chiller

Operating Point
Load 100% Flow

100%

System Head
Curve

BELIMO Aircontrols

Basic Hydronic Training 47

System Curves for a Pump Type


80

Head (ft)

60

40

7.0

70%65% 60% 55%

6.5
6.0

20

5.5
5.0

10

20

40

60

80

100

120

Flow GPM
BELIMO Aircontrols

140

160

180

200

Motor Horsepower
Basic Hydronic Training 48

Minimum Flow of Pump


Depends on pump construction and energy generated
by pump
Not enough flow could result in overheating and
cavitation
Some low power pumps can operate at zero flow
Installation of bypass circuit

BELIMO Aircontrols

Basic Hydronic Training 49

Valves in HVAC

BELIMO Aircontrols

Basic Hydronic Training 50

What Control Characteristic is Preferred?


100
90

Heat Output

Heat Output (%)

80
70
60
50
40
30
20
10

10

20

30

40

50

60

70

80

90

100

Control Signal (%)

BELIMO Aircontrols

Basic Hydronic Training 51

What are the Coil Characteristics?


100
90

Characteristic of
a coil
Heat Output (%)

Heat Output

80
70
60
50
40
30
20
10

10

20

30

40

50

60

70

80

90

100

Valve Opening (%)

BELIMO Aircontrols

Basic Hydronic Training 52

What are the Valve Characteristics?


100

Heat Output

Flow, Heat Output (%)

Characteristic of
a Coil

90
80
70
60
50

Characteristic of
Control Valve

40
30
20
10

10

20

30

40

50

60

70

80

90

100

Signal (%)

BELIMO Aircontrols

Basic Hydronic Training 53

Valve Characteristics
Modified Equal Percentage
100

Lift

Theoretical
Flow

Corrected
Flow

100

100

100

90

80

80

80

64

64

70

51

51

60

41

41

50

33

33

40

26

26

30

21

19.5

20

17

13

10

13.4

6.5

10.7

90

Flow (%)

80
70
60
50
40
30

Equal %

20

10.7

Linear Curve

10

10

20

30

40

50

60

70

80

90

100

Valve Opening (Signal) (%)


BELIMO Aircontrols

Basic Hydronic Training 54

Valve Authority

BELIMO Aircontrols

Basic Hydronic Training 55

Authority of Control Valves


with Variable Flow Through the Coil
Authority of two way control valves
Authority of three way control valves

BELIMO Aircontrols

Basic Hydronic Training 56

3-way Control Valve


4

12

20 psi
Const

A
BELIMO Aircontrols

pv100

4
8

pv100
pFlowVariable

pv100
pv 0

0.5
Basic Hydronic Training 57

3-way Control Valve


4

12

20 psi
Const

A
BELIMO Aircontrols

pv100

4
8

pv100
pFlowVariable

pv100
pv 0

0.5
Basic Hydronic Training 58

3-way Control Valve


45

41

1214

50%
01
20 psi
Const

BELIMO Aircontrols

Basic Hydronic Training 59

Valve Authority - Flow 100%

P Valve

P Terminal

Coil

P Terminal =const
BELIMO Aircontrols

Basic Hydronic Training 60

Valve Authority - Flow 50%

P Valve

P Terminal

Coil

P Terminal =const
BELIMO Aircontrols

Basic Hydronic Training 61

Valve Authority - Flow 0%

P Valve

P Terminal

Coil

P Terminal =const
BELIMO Aircontrols

Basic Hydronic Training 62

2-way Control Valve


4

12

20 psi
VFD

A
BELIMO Aircontrols

pv100

4
20

pv100
pFlowVariable

pv100
pv 0

0.2
Basic Hydronic Training 63

2-way Control Valve


41

416 123

50%

20 psi
VFD

BELIMO Aircontrols

Basic Hydronic Training 64

Valve Authority - Flow 100%

BELIMO Aircontrols

P Valve

P Terminal

Coil

Basic Hydronic Training 65

Valve Authority - Flow 50%

BELIMO Aircontrols

P Valve

P Terminal

Coil

Basic Hydronic Training 66

Valve Authority - Flow 0%

P Valve

P Terminal

Coil

P Terminal =const
BELIMO Aircontrols

Basic Hydronic Training 67

Sizing Rules

Authority = 0.4 to 0.5


Min. pvalve = 0.25 p pumphead

BELIMO Aircontrols

Basic Hydronic Training 68

Authority Distortion of Linear Flow


Characteristics
100
90

Flow (%)

80

0.1

70

0.2
0.4

60
0.6
0.8

50

1
40
30
20
10

10

20

30

40

50

60

70

80

90

100

Valve Opening (%)


BELIMO Aircontrols

Basic Hydronic Training 69

Authority Distortion of Equal Percentage


Flow Characteristics
100
90
80

Flow (%)

70
60

0.1

50

0.2

40

0.4
0.6

30

0.8
1

20
10

10

20

30

40

50

60

70

80

90

100

Valve Opening (%)


BELIMO Aircontrols

Basic Hydronic Training 70

Counter-Flow

Cross-Flow

Parallel-Flow

Counter-flow, cross-flow or parallel-flow heat exchangers are used


depending on the application. They have different efficiencies.

BELIMO Aircontrols

Basic Hydronic Training 71

Constant or Variable Flow


e.g. air

Regardless of valve position, the


full water flow is always circulating
through the heat exchanger
=> Temperature control

Depending of valve position,


0..100% of the water flow
circulates through the heat
exchanger

=> Flow control

BELIMO Aircontrols

Basic Hydronic Training 72

Constant or Variable Flow


Prevention of
freezing

yes
no

Large outside flow?

no

no

yes

Are different temperature


levels in coil acceptable?

no
Temperature control
constant Flow
Variable temperature
BELIMO Aircontrols

yes

Dehumidification

yes

yes

Flow Control
Constant Temperature
Variable Flow
Basic Hydronic Training 73

Diverting Circuit with Mixing Valve


pFV

Coil
var

var
var

pV100
100%

BELIMO Aircontrols

100%

Basic Hydronic Training 74

Diverting Circuit with Diverting Valve


pFV

Coil
var

var
var

pV100
100%

BELIMO Aircontrols

100%

Basic Hydronic Training 75

Throttling Circuit
pFV

Coil
var

var

pV100

BELIMO Aircontrols

Basic Hydronic Training 76

Mixing Circuit with Mixing Valve


Coil
100%

100%
var

p v100

var

BELIMO Aircontrols

var

Basic Hydronic Training 77

Heat Exchanger Characteristics


100
0.05

90

0.15

Energy (%)

80

0.25
0.4
0.6
0.8
1

70
60

1.5
2

50

40
30
20
10

10

20

30

40

50

60

70

80

90

Application

a-Value

Pre Heating
Coil
Heating Coil

0.25 to 0.4

Cooling Coil

0.25 to 0.5

Radiators

0.5 to 0.65

Converters

0.5 3.0

0.15 to 0.4

100

Flow (%)

BELIMO Aircontrols

Basic Hydronic Training 78

Heat Exchanger Characteristics


100
90

Variable Flow

Energy (%)

80
70

Constant Flow

60
50
40
30
20
10

10

20

30

40

50

60

70

80

90

100

Flow (%)
BELIMO Aircontrols

Basic Hydronic Training 79

Heat Exchanger Characteristics


100
90

T = 10F

Energy (%)

80
70

T = 30F

60
50
40
30
20
10

10

20

30

40

50

60

70

80

90

100

Flow (%)
BELIMO Aircontrols

Basic Hydronic Training 80

Heat Exchanger Characteristics


100
90

Heating Coil

Energy (%)

80
70

Cooling Coil

60
50
40
30
20
10

10

20

30

40

50

60

70

80

90

100

Flow (%)
BELIMO Aircontrols

Basic Hydronic Training 81

Influencing Factors
Valve with
Hydraulics

Base Valve
Characteristic

BELIMO Aircontrols

Hydraulic
System

Heat
Exchanger

System Valve
Coil
Characteristic Characteristic

Resulting
Characteristic

Basic Hydronic Training 82

Conventional Sizing Methods

BELIMO Aircontrols

Basic Hydronic Training 83

Application
Pressure Differential Sensor

Coil #4
0 - 100 gpm

10 psi
p=2 psi

p=12 psi

p=22 psi

20 psi
p =4 psi

p=4 psi
Coil #2
0 - 100 gpm

30 psi

p =4 psi

p=4 psi
Coil #3
0 - 100 gpm

20 psi

10 psi

30 psi
p=4 psi

p=4 psi

40 psi

Coil #1
0 - 100 gpm

40 psi
p=32 psi

p=4 psi

p=4 psi

Chiller
VFD-Pump
BELIMO Aircontrols

Basic Hydronic Training 84

Application
Authority

Pressure Differential Sensor

Coil #4
0 - 100 gpm
p=2 psi

p=12 psi

p=22 psi

p =4 psi

p=4 psi
Coil #2
0 - 100 gpm

30 psi

p =4 psi

p=4 psi
Coil #3
0 - 100 gpm

20 psi

A=4/10=0.4

p=4 psi

p=4 psi

Flow/Heat output %

10 psi

A=4/20=0.2

A=4/30=0.14

Coil #1
0 - 100 gpm

40 psi
p=32 psi

p=4 psi

Chiller

A=4/40=0.1

p=4 psi

Signal

VFD-Pump
BELIMO Aircontrols

Basic Hydronic Training 85

Shift to Variable Supply with VFD-Pumps


and Two-way Valves 4
4
12

20 psi

Const

12

20 psi

VFD
BELIMO Aircontrols

Basic Hydronic Training 86

Authority Method

BELIMO Aircontrols

Basic Hydronic Training 87

Application
Coil #1
0 - 100 gpm

10 psi
p=2 psi

p=4 psi
Coil #2
0 - 100 gpm

20 psi

p=6 psi

p=11 psi

p =10psi

A=0.5

A=0.5

p=4 psi
Coil #3
0 - 100 gpm

30 psi

p =4 psi

Flow/Heatoutput

Pressure Differential Sensor

p=15 psi

A=0.5

p=20 psi

A=0.5

p=4 psi
Coil #4
0 - 100 gpm

40 psi
p=16 psi

p=4 psi

Chiller

Signal

VFD-Pump
BELIMO Aircontrols

Basic Hydronic Training 88

Current Concepts for Valve Sizing


Exact
calculation
f( p and V)

Rule:
pvalve = pCoil

Rule:
pvalve= 3 5 psi
BELIMO Aircontrols

Correct sized components


Generally less expensive components, like valves
Complex procedures for all involved
More detailed information is required
Consideration of diversity factors
No feedback of sized devices from suppliers

Very simple rule


Used by all involved in the project
Good base for price comparison
Oversized valves overpriced valves
Bad authority
Hunting
Instable control loops
Basic Hydronic Training 89

Additional Valve Sizing Considerations


Two-way valves:
For the close-off pressure the pump
head needs to be considered.
Three-way valves:
Pressure difference valve

For the selection of the valve bodies it is


necessary to consider elevation of
system, pump pressure and fill pressure
BELIMO Aircontrols

Basic Hydronic Training 90

Reference Literature
Total Hydronic Balancing
Robert Petitjean, Tour & Andersson Hydronic AB
HVAC Pump Handbook
James B. Rishel, McGraw-Hill
ASHRAE Handbooks
HVAC Equations, Data, and Rules of Thumb
Bell, McGraw-Hill

BELIMO Aircontrols

Basic Hydronic Training 92

Thank You

BELIMO Aircontrols

Basic Hydronic Training 93