SENTRON
Answers for infrastructure.
Siemens AG 2011
Siemens AG 2011
Introduction
3WL air circuit breakers
6
12
19
24
34
36
49
51
52
53
53
57
58
Siemens AG 2011
All dimensions in mm.
Siemens 2012
Siemens AG 2011
Overview
Size I
Size III
Size II
Sizes
I, II, III
II
3-pole, 4-pole
3-pole, 4-pole
... 690/1000/1150
--
-... 1000
Rated current In
Number of poles
Rated operational
voltage Ue
V AC
V DC
Rated ultimate
short-circuit breaking
capacity at 500 V AC
kA
Endurance
Size I
Size II
Size III
55/66/85
66/80/100
100/150 (3-pole),
130 (4-pole)
30/25/20
(at 300/600/1000 V DC)
10000
15000
Mounting position
30 30
30 30
NSE0_00062a
NSE0_00061a
Degree of protection
With cover
Without cover
(with door sealing frame)
W mm
320/410
460/590
704/914
460/590
Fixed
mounting
H mm
D mm
434
291
434
291
434
291
434
291
Withdrawable
H mm
D mm
465,5
471
465,5
471
465,5
471
465,5
471
ETU25B
ETU27B
ETU45B
ETU76B
Overload protection
Short-time delayed
short-circuit protection
--
Instantaneous
short-circuit protection
--
--
Ground-fault protection
--
--
--
--
--
LCD, 4-line
--
--
--
--
LCD, graphic
--
--
--
--
Communication
--
--
--
--
--
--
--
--
--
--
--
--
--
--
CubicleBUS
--
--
--
Type
Rating Plug
Standard
-- Not available
Optional
1)
Siemens 2012
NSE0_01111a
NSE0_01108a
ETU15B1)
NSE0_01106a
NSE0_01107a
NSS0_00535
IP55
IP41
NSE0_01109a
NSE0_00062a
NSE0_00061a
IP55
IP41
Dimensions 3-/4-pole
30 30
30 30
Siemens AG 2011
Switching capacity
Sizes
II
Type
3WL11
3WL12
III
3WL13
C
H 3-pole
C
C 4-pole
Icu
Ics
Icm
55
55
121
66
66
145
85
85
187
66
66
145
80
80
176
100
100
220
100
100
220
150
150
330
130
130
286
55
55
121
66
66
145
85
85
187
66
66
145
80
80
176
100
100
220
100
100
220
150
150
330
130
130
286
42
42
88
50
50
105
66
66
145
50
50
105
75
75
165
85
85
187
85
85
187
150
150
330
130
130
286
----
----
509)
509)
1059)
----
----
50
50
105
50
50
105
704)
704)
1544)
704)
704)
1544)
55
42
29,5
24
66
50
35
29
75
66
46
37
66
55
39
32
80
66
46
44
100
80
651)/702)
501)/652)
100
100
80
65
100
100
80
65
100
100
80
65
55
42
--
66
50
--
75
66
509)
66
50
--
80
75
--
100
85
504)
100
85
504)
100
100
704)
100
100
704)
Icu
Ics
Icm
Icu
Ics
Icm
Rated operational voltage Ue
up to 1000 V/1150 V AC
kA
kA
kA
Icu
Ics
Icm
kA
kA
kA
kA
kA
kA
kA
Sizes
II
Type
3WL12
DC
DC
Icc
Icc
Icc
Icc
kA
kA
kA
kA
35
30
25
20
kA
kA
kA
kA
-355)/306)/257)/208)
---
Abbreviations
(functions)
= Overload protection
= Short-circuit protection
(short-time delayed)
= Instantaneous
= Short-circuit protection
(instantaneous)
= Neutral Protection
= Ground Fault
Ground-fault protection
DC
1)
6)
At Ue = 300 V DC.
2)
7)
At Ue = 600 V DC.
3)
At a rated voltage of 690 V the Icw value of the circuit breaker cannot be
greater than the Icu or Ics value at 690 V.
8)
At Ue = 1000 V DC.
9)
4)
5)
At Ue = 220 V DC.
Siemens 2012
Siemens AG 2011
Introduction
3WL air circuit breakers:
Superior individual products integrated into uniform power distribution systems - up to and including industry-specific industrial and infrastructure solutions
6
7
8
5
9
1
25
21
10
19
22
11
23
12
24
18
13
14
20
16
15
$
%
&
(
)
*
+
,
.
/
0
1
2
3
Guide frame
Main circuit connection, front, flange, horizontal, vertical
Position signaling switch
Grounding connection, leading
Shutter
COM15 PROFIBUS modules or COM16 MODBUS modules
External CubicleBUS modules
Closing solenoid, auxiliary release
Auxiliary conductor plug-in system
Auxiliary switch block
Door sealing frame
Interlocking set for mechanical ON/OFF
Transparent panel, function insert
EMERGENCY-STOP pushbutton, key operated
Motorized operating mechanism
Siemens 2012
4
5
6
7
8
9
:
;
<
=
NSE0_01887c
17
Siemens AG 2011
18
Ethernet
16
17
PROFIBUS
11
19
13
12
15
14
ab Release 2
CubicleBUS
7
8
NSE0_01105k
9
10
17 PLC, e. g. SIMATIC S7
Features
Coordinated communication concept using the
PROFIBUS DP or MODBUS, ranging from 16 A to 6300 A with
3VL compact circuit breakers and 3WL air circuit breakers
The high level of modularity of circuit breakers and accessories allows easy retrofitting of all communication components
Significant additional benefits for the switchboard due to the
possibility of linking up external input and output modules to
the circuit breaker-internal CubicleBUS of the 3WL air circuit
breaker
Communication:
For air circuit breakers with optional communication function
(ETU45B or ETU76B electronic release)
see Catalog LV 10.1.
For accessories see Catalog LV 10.1.
For more information see also Catalog LV 10.1, chapter "Measuring Devices and energy management" and "Software".
Siemens 2012
Siemens AG 2011
Design
Circuit breaker
rated current n max (A)
Breaking capacity
cu at 500 V AC (kA) or
cc at 300 V DC (kA)
Size III
6300
5000
H
100
4000
C
150 (3p)
130 (4p)
Dimensions
Fixed-mounted,
3- /4-pole
Withdrawable
3- /4-pole
704 / 914
704 / 914
Width
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
460 / 590
460 / 590
Width
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
320 / 410
320 / 410
Width
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
4000
3200
2500
Size II
2000
1600
DC
30
66
80
100
1250
1000
800
2000
1600
Size I
1250
1000
800
55
66
85
630
The dimension for the depth of the circuit breaker is from the circuit breaker rear to the inner surface of the closed switchgear door.
NSE0_00887p
Coordinated dimensions
Versions
Installation types
Operating mechanisms
Ambient temperatures
The 3WL circuit breakers are climate-proof according to
IEC 60068-2-30. They are intended for use in enclosed areas
where no severe operating conditions (e. g. dust, corrosive vapors, damaging gases) are present.
When installed in dusty and damp areas, suitable enclosures
must be provided.
Siemens 2012
Siemens AG 2011
Horizontal
connection
The system contains many blocking devices to protect the circuit breakers and plant against unauthorized switching and to
protect maintenance and operator personnel from danger.
Others can be retrofitted.
N S E 0 _ 0 0 9 7 9 a
N S E 0 _ 0 0 9 6 9 b
N S E 0 _ 0 0 9 6 7 b
N S E 0 _ 0 0 9 6 8 b
Vertical
connection
Horizontal
connection
Vertical
connection
N S E 0 _ 0 0 9 7 3 b
N S E 0 _ 0 0 9 7 2 b
N S E 0 _ 0 0 9 7 1 b
N S E 0 _ 0 0 9 6 7 b
N S E 0 _ 0 0 9 7 0 b
Flange
connection
Connection using
screw connection
system (SIGUT)
(standard)
N S E 0 _ 0 0 9 7 6 b
N S E 0 _ 0 0 9 7 5 b
Siemens 2012
Siemens AG 2011
Standards
The closing solenoid is used to close the circuit breaker electrically by means of a local electrical "ON" command or by a remote unit.
Motorized operating mechanism
Control switch for switching off the motorized operating mechanism (automatic loading).
Operating cycles counter
The motorized operating mechanism can be supplied with a
5-digit operating cycles counter. The display is incremented by
"1" as soon as the storage spring is fully loaded.
Resetting the manual tripped signal
When the circuit breaker has tripped, this is indicated by the protruding red mechanical tripped indicator on the ETU. When the
mechanical tripped indicator is activated, the tripping solenoid
and tripped signal are reset. If this display is to be reset remotely,
the reset button can be equipped with a reset solenoid.
Auxiliary releases
1 shunt release
or 1 undervoltage release
or 2 shunt releases
or 1 shunt release
+ 1 undervoltage release.
When the ETU is activated, reclosing of the circuit breaker is prevented until the release is either electrically or manually reset. If
the "Automatic resetting of reclosing lockout" option is used, the
pre-tensioned circuit breaker is ready to close immediately after
tripping. Resetting the manual tripped indicator is not included
in this option.
One signaling contact is used for each auxiliary release to determine the switch positions of the auxiliary releases.
If the circuit breaker has tripped due to an overload, short-circuit, ground fault or extended protection function, the tripped
signaling switch can indicate this. This signaling switch is available as an option. If the circuit breaker is used for communication, this option is supplied as standard.
Shunt release
When the operational voltage is connected to the shunt release,
the circuit breaker is opened immediately. The shunt release is
available in the versions 5 % OP for over-excitation
and 100 % OP for permanent excitation. This means that it is also
possible to block the circuit breaker against being jogged into
closing.
Siemens 2012
Siemens AG 2011
(2 8 )
(2 )
(2 7 )
(3 )
(2 6 )
(4 )
(2 5 )
(5 )
(1)
Arc chute
(2)
Carrying handle
(3)
Labeling plates
(4)
(5)
(6)
(7)
(8)
(9)
Positioning pictogram
(2 4 )
(6 )
(2 3 )
(7 )
(2 2 )
(2 1 )
(8 )
(2 0 )
(9 )
(1 9 )
(1 0 )
(1 1 )
(1 8 )
(1 7 )
(1 2 )
(1 6 )
(1 3 )
(1 4 )
(1 5 )
N S E 0 _ 0 0 9 6 5 b
Guide frames
(1 )
(2 )
(3 )
(1 8 )
(1)
(2)
Blow-out openings
(3)
(4)
Shutter (option)
(5)
(6)
(7)
Isolating contacts
(8)
Ground terminal 14 mm
(9)
(1 7 )
(4 )
(5 )
(6 )
(1 6 )
(7 )
(1 5 )
(1 4 )
(8 )
(1 3 )
(1 2 )
(9 )
(1 1 )
(1 0 )
N S E 0 _ 0 0 9 6 6 b
Siemens 2012
Siemens AG 2011
Sealing devices
This function prevents closing of the circuit breaker and complies to the specifications for main switches according to
EN 60204 (VDE 0113) - disconnector unit. This lockout only affects this circuit breaker.
Locking mechanisms
Locking device against movement for withdrawable circuit
breakers when the control cabinet door is open
The crank handle is blocked when the control cabinet door is
open and cannot be removed. The withdrawable circuit breaker
cannot be moved. The lock only affects the inserted crank handle.
Interlocking of the control cabinet door
The control cabinet door cannot be opened if
The fixed-mounted circuit breaker is closed (the blocking signal is transmitted via the Bowden wire) or
The withdrawable circuit breaker is in the connected position.
Blocking mechanism using "Mechanical ON" and "OFF" buttons
The "Mechanical ON" and "OFF" buttons are covered with a cap
which only allows actuation with a tool. These covering caps are
part of the interlocking set.
Accessories for guide frames
Shutters
The sealing strips can be manually opened using the strip levers.
The position of the sealing strips can be locked in various positions using padlocks for securing against tampering.
10
Siemens 2012
Siemens AG 2011
Equipment-dependent coding
Withdrawable circuit breakers and guide frames can be retrofitted with an equipment-dependent coding unit.
This allows different designs of circuit breakers and guide
frames to be uniquely assigned. If the circuit breaker and guide
frame have been assigned different codes, the circuit breaker
cannot be inserted.
36 different coding options can be selected.
N S E 0 _ 0 1 0 3 2 a
N S E 0 _ 0 1 0 3 1 a
(1 )
(4 )
(2 )
(5 )
(3 )
(1) Guide frame, interior of l/h side; interior of r/h side similar
(2) Coding pin on racking rail in guide frame
(3) Racking rail
(4) Withdrawable circuit breaker, r/h side; l/h side similar
(5) Coding pin on guide frame
Rated current coding unit between circuit breaker and guide frame
Position indicator
(2 )
CONNECT
Main circuit
Auxiliary circuit
Control cabinet
door
Shutters
Disconnected
Disconnected
Open
Closed
Disconnected
Disconnected
Closed
Closed
Disconnected
Connected
Closed
Closed
Connected
Connected
Closed
Open
(1 )
TEST
(4 )
N S E 0 _ 0 1 0 3 3 a
DISCON
NSE01037
Disconnected position
CONNECT
(3 )
TEST
DISCON
N S E 0 _ 0 1 0 3 4 a
NSE01038
Test position
CONNECT
TEST
DISCON
N S E 0 _ 0 1 0 3 5 a
NSE01039
Connected position
CONNECT
TEST
DISCON
N S E 0
0 1 0 3 6 a
NSE01040
(4) Shutter
Phase barriers
3WL circuit breakers have degree of protection IP20 as standard. However, if the switchgear is to be equipped with a higher
degree of protection, a door sealing frame with IP41 and a cover
with IP55 are available.
Siemens 2012
11
Siemens AG 2011
NSE0_00880b
NSE0_00881b
NSE0_00882b
Function
R
R
s d
s d
t
i
s d
t
g
N S E 0 _ 0 0 9 5 2 b
N S E 0 _ 0 0 9 5 1 b
N S E 0 _ 0 0 9 5 0 c
ETU15B
ETU25B
ETU27B
--
--
--
Ground-fault protection
--
--
--
--
--
--
--
--
--
--
Additional functions
--
--
--
--
--
--
Load monitoring
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
LCD alphanumerical
--
--
--
Graphic LCD
--
--
--
--
--
--
CubicleBUS
--
--
--
--
--
--
--
--
--
--
--
--
Measurement function
Measurement function Plus
Communication
-- Not available
Optional
Detailed information about the functions of the electronic releases is given in the following.
12
Siemens 2012
s d
Siemens AG 2011
ETU76B
Rating Plug
NSE0_00883b
NSE0_00886c
12
IR
IR
tR
tR
Ig
tg
Isd
t sd
Ii
NSE0 00953a
Ig
tg
Isd
t sd
Ii
NSE0 00953a
ETU45B
ETU76B
--
--
--
--
--
--
--
Siemens 2012
13
Siemens AG 2011
Tripped indicator/
Reset button
Communication capability
LCD alphanumeric
with 15
inclination
and rotatable
through 180
Rated current
module/
rating plug
Slide switch
for switchable
overload
characteristic
curve
Ground-fault
protection
module (retrofittable)
This means that it is not only possible to monitor the device remotely, but also to transmit current values from the entire system
and perform switching operations remotely.
I2t and I4t characteristic curve for overload protection
The best protection for the whole switchgear is achieved by setting the tripping characteristic curve to an optimum value. In order to achieve optimal discrimination for upstream fuses or medium voltage protection systems, the inclination of the
characteristic curve can be selected for the overload range.
The overload protection L (long time protection) for the electronic releases ETU45B and ETU76B allows the characteristic
curve to be switched between I2t and I4t.
The I4t characteristic improves discrimination for downstream
circuit breakers and fuses.
Electronic releases ETU
Modularity has also been strictly emphasized during the development of the electronic releases. These are some of the modules which can be easily retrofitted at any time:
Ground-fault protection module
Communication
Measurement function
Display
Rated current module (Rating Plug)
This allows quick adaptation to new local mains specifications.
In addition, innovative functions have been included in the ETUs.
Rated current module/Rating Plug
The rated current module is an exchangeable module which allows the user to reduce the rated device current so as to adapt
it optimally to the plant; e.g.if a new plant section is taken into operation. The rated current module must be selected to fit the
rated current of the plant.
14
Siemens 2012
Selectable parameters
In the case of quick changes of power supply conditions,
e. g. for switchovers from transformer to generator operation or
if a section of the supply is disconnected when the shift
changes, the 3WL circuit breaker allows the relevant protection
parameters to be quickly adapted to the new conditions.
The ETU76B contains two independent tripping characteristic
curves (parameter sets). The switchover is completed within
200 ms and is performed with the help of an external signal.
Siemens AG 2011
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Indicator: overcurrent
release activated
Indicator: fault in
overcurrent release
Sealing ring
NSE0_00954b
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Indicator: overcurrent
release activated
Indicator: overload alarm
ETU25B
Indicator: fault in
overcurrent release
Rating Plug
NSE0_00955b
Query pushbutton
Test pushbutton
Sealing ring
Clear pushbutton
Test socket
Siemens 2012
15
Siemens AG 2011
NSE0_00956c
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Indicator: overcurrent
release activated
ETU27B
Features:
N-conductor protection
on/off
OFF ON
Rating Plug
Indicator: fault in
overcurrent release
Short-circuit protection
fixed setting
Rotary switch for setting
value, earth-fault protection
Sealing ring
OFF
Query pushbutton
Test pushbutton
Clear pushbutton
Test socket
Indicators:
Overcurrent release
activated
Overload alarm
ETU45B
OFF ON
1
1
1
1
1
12
SI
g
Test pushbutton
Query pushbutton
NSE0_00957b
Scroll down
Indicator: fault in
overcurrent release
COMMUNICATION
EXPANDED
Selector for
earth-fault protection
Application:
tg
16
Siemens 2012
Siemens AG 2011
ETU76B
Indicators:
Overcurrent release
activated
Overload alarm
COMMUNICATION
EXPANDED
Graphical display
Indicator: fault in
overcurrent release
Rating Plug
Test pushbutton
Clear pushbutton
Query pushbutton
Test socket
NSE0_00960b
Ground-fault protection
Selector for
ground-fault
detection
I
Rotary switch
for setting
value,
ground-fault
protection
g TRIP
ALARM
A
B
C
D
E
OFF
ALARM t
Indicators:
Ground-fault
alarm
GFM AT 45B
Ground-fault
tripped
(s)
.5
.4
.3
.2
.1
TRIP
.1
.2
.3
.4
.5
NSE0_00962a
Rotary switch
for setting value
ground-fault alarm
I 2t g
Rotary switch
for setting
value, groundfault protection delay
2
t g/I t
When setting the parameters for the electronic release it is possible to choose between "alarm" and "trip" in the event that the
set current value is exceeded. The reason for tripping is indicated by means of an LED when the query button is activated.
The ETU45B and ETU76B electronic release versions can be retrofitted with a ground-fault protection module. This ground fault
protection function is integrated in ETU27B electronic releases.
ALARM
I g=
Fields for
noting setting
values
Ground-fault
alarm
GFM AT 55B-76B
Ground-fault
tripped
ALARM
A
I 2t
TRIP
TRIP
I g=
Indicators:
t g=
NSE0_00964a
ms
Fields for
noting setting
values
Siemens 2012
17
Siemens AG 2011
Setting
The three phase currents and the N conductor current are measured directly.
SENTRON WL
T5
L1
L2
L3
N
PE
NSE 00946
SENTRON WL
L1
L2
L3
N
T6
PE
NSE 00947
SENTRON WL
L1
L2
L3
N
T6
PE
NSE 00948
18
Siemens 2012
This setting can be implemented for the electronic release version ETU76B with Menu/Comm.
Siemens AG 2011
DIGmat S100
The DIGmat S100 tripping unit monitors the image of the primary
current thus supplied and compares it with the tripping characteristic curve set on the device. The parameter settings on the
DIGmat S100 apply also for DC feedbacks.
Reversing duty is possible therefore.
Short-circuit protection:
Setting range Ii = 1.25 IR up to max. 4 In
If the set value is exceeded, tripping occurs in less than
50 ms.
In
IR
tR
Ii
=
=
=
=
Configuration
The bending radii of the Bowden wire must be > 500 mm.
The sum of all bending angles along the Bowden cable must
not exceed 640.
In a vertical arrangement of circuit breakers to be interlocked,
the interlocking mechanisms must be in line.
Circuit breakers to be interlocked must be arranged so that
Bowden cables can be optimally installed in compliance with
the conditions mentioned in the above points.
The installed Bowden cable must be fixed (with cable ties or
the like) before the interlock is adjusted.
Select the width of switchgear cubicle to allow enough freedom of movement for adjusting the interlock!
Openings and cut-outs in system elements must be designed
so that Bowden cables are not changed in direction or obstructed when they are passed through.
S1
S2
S1
S3
S2
NSE01041
NSE01042
S1
S1
NSE01043
S2
S2
S3
S1
S3
S2
S3
NSE01044
NSE01045
Siemens 2012
19
Siemens AG 2011
NSE0_01820b
BDA Plus
ETU
Measurementfunction Plus
BSS
COM15
Zone Selective
Interlocking module
Output device
e.g. notebook
with browser
Ethernet/
Intranet/
Internet
Configuration and
display software
MODBUS Master
PLC or monitoring software
MODBUS
BSS
BDAPlus
NSE0_01894a
ETU
Measurement
function Plus
COM16
Output device
e.g. notebook
with browser
Zone Selective
Interlocking module
Ethernet/
Intranet/
Internet
The requirements for power distribution in terms of communication capability, data transparency, flexibility and integration are
constantly increasing. An integrated and modular communication architecture was designed for the 3WL circuit breaker to ensure that it can satisfy these requirements.
The core component of this architecture is the CubicleBUS,
which links together all of the intelligent components within the
3WL circuit breaker and enables the easy and safe connection
of other additional external components to the circuit breaker.
The CubicleBUS is already incorporated and pre-connected in
all complete circuit breakers with ETU45B and ETU76B releases.
20
Siemens 2012
Siemens AG 2011
Electronic
release version
ETU45B
ETU76B
Measurement
function
Plus
--
--
--
--
--
Required
Function can optionally be taken over by more than one release.
Siemens 2012
21
Siemens AG 2011
BDAPLUS BSS
F01
+"BDAPLUS"Order No.
Order No.
COM15/COM16
F02/F12
Potential applications
Transmission of circuit breaker data to PROFIBUS DP or MODBUS and integration into
higher-level visualization systems are possible
e. g. in PCS7, Power Management Systems, WinCC (including add-ons like the text message radio server)
--
Transmission of circuit breaker data and software (i. e. HTML pages with data) to a local output
device, or remotely through Ethernet/Intranet/Internet (without the possibility of integration into
higher-level visualization systems)
e. g. for monitoring, diagnostics, maintenance and parameterization of individual circuit breakers
--
1)
--
--1)
--1)
Control commands
Switch circuit breakers ON/OFF, switch free user output ON/OFF
Reset tripped signal
Delete event and history memory
Rest min./max. measured values, reset maintenance information
--1)
--1)
History
Read out the event protocol, read out the release protocol
--1)
Information on maintenance
Number of tripping operations - L, S/I and total, contact erosion
Number of switching operations - under load and total, operating hours
--1)
Event signals
Tripped signals with data on tripping currents
Alarmsignals (e. g. overload) with incoming/outgoing information
All named event signals with time stamp
--1)
--1)
2)
2)
2)
2)
Measured values
Phase currents, each with min./max. value
Temperature in the circuit breaker with min./max. value
Temperature in the control cabinet with min./max. value
All named measured values with time stamp
--1)
--1)
--1)
F05
1)
Data only available in conjunction with the COM15 module (BUS connection not required).
2)
22
Siemens 2012
Available
-- Not available
Siemens AG 2011
One module each of this type can be used for holding the six
items of digital information and for automatically switching over
the parameters.
Siemens 2012
23
Siemens AG 2011
Technical specifications
Switching capacity
Sizes
II
Type
3WL11
3WL12
III
3WL13
C
3-pole
C
4-pole
Icu
Ics
Icm
55
55
121
66
66
145
85
85
187
66
66
145
80
80
176
100
100
220
100
100
220
150
150
330
130
130
286
55
55
121
66
66
145
85
85
187
66
66
145
80
80
176
100
100
220
100
100
220
150
150
330
130
130
286
42
42
88
50
50
105
66
66
145
50
50
105
75
75
165
85
85
187
85
85
187
150
150
330
130
130
286
----
----
509)
509)
1059)
----
----
50
50
105
50
50
105
704)
704)
1544)
704)
704)
1544)
55
42
29.5
24
66
50
35
29
75
66
46
37
66
55
39
32
80
66
46
44
100
80
651)/702)
501)/652)
100
100
80
65
100
100
80
65
100
100
80
65
55
42
--
66
50
--
75
66
509)
66
50
--
80
75
--
100
85
504)
100
85
504)
100
100
704)
100
100
704)
Icu
Ics
Icm
Icu
Ics
Icm
Rated operational voltage Ue
up to 1000 V/1150 V AC
kA
kA
kA
Icu
Ics
Icm
kA
kA
kA
kA
kA
kA
kA
Sizes
II
Type
3WL12
DC
DC
Icc
Icc
Icc
Icc
kA
kA
kA
kA
35
30
25
20
kA
kA
kA
kA
-355)/306)/257)/208)
---
Abbreviations
(functions)
= Overload protection
= Short-circuit protection
(short-time delayed)
= Instantaneous
= Short-circuit protection
(instantaneous)
= Neutral Protection
= Ground Fault
Ground-fault protection
DC
1)
6)
At Ue = 300 V DC.
2)
7)
At Ue = 600 V DC.
3)
At a rated voltage of 690 V the Icw value of the circuit breaker cannot be
greater than the Icu or Ics value at 690 V.
8)
At Ue = 1000 V DC.
9)
4)
5)
At Ue = 220 V DC.
24
Siemens 2012
Siemens AG 2011
I
II
... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16
A ... 1000
A ... 1000
V AC ...
690/1000
V AC 1000
1250
1250
...
690/1000
1000
1600
1600
...
690/1000
1000
2000
2000
...
690/1000
1000
800
800
...
690/1000
1000
1000
1000
...
690/1000
1000
1250
1250
...
690/1000
1000
1600
1600
...
690/1000
1000
kV 12
kV 4
kV 2.5
Yes
B
12
4
2.5
Yes
12
4
2.5
Yes
12
4
2.5
Yes
12
4
2.5
Yes
12
4
2.5
Yes
12
4
2.5
Yes
12
4
2.5
Yes
C 25/+70
C 40/+70
25/+70
40/+70
25/+70
40/+70
25/+70
40/+70
25/+70
40/+70
25/+70
40/+70
25/+70
40/+70
25/+70
40/+70
A 1000
A 1000
A 1000
1250
1250
1210
1600
1600
14908)
2000
1930
1780
800
800
800
1000
1000
1000
1250
1250
1250
1600
1600
1600
V 2000
2000
2000
2000
2000
2000
2000
2000
W 100
W 195
105
205
150
350
240
440
40
85
45
95
80
165
85
175
ms 35
ms 38
35
38
35
38
35
38
35
34
35
34
35
34
35
34
ms 80
ms 73
80
73
80
73
80
73
100
73
100
73
100
73
100
73
73
73
73
73
73
73
73
50
1)
1)
1)
1)
50
50
50
10 000
20 000
10 000
--
10 000
20 000
10 000
--
10 000
20 000
10 000
--
10 000
15 000
7500
1000
--
--
--
--
20 000
20 000
20 000
10 000
15 000
7 500
1000
10 000
15 000
7 500
1000
--
50
1)
1)
50
50
73
1)
501)
10 000
15 000
7500
1000
10 000
15 000
7500
1000
10 000
15 000
7500
1000
10 000
15 000
7500
1000
500
500
500
500
15 000
15 000
15 000
15 000
15 000
10 000
15 000
7 500
1000
10 000
15 000
7500
1000
10 000
15 000
7500
1000
10 000
15 000
7500
1000
10 000
15 000
7500
1000
10 000
15 000
7500
1000
--
--
--
500
500
500
500
15 000
15 000
15 000
15 000
15 000
15 000
15 000
15 000
10 000
15 000
7 500
1000
10 000
15 000
7 500
1000
10 000
15 000
7 500
1000
10 000
15 000
7500
1000
10 000
15 000
7500
1000
10 000
15 000
7500
1000
10 000
15 000
7500
1000
10 000
15 000
7500
1000
--
--
--
--
500
500
500
500
10 000
10 000
10 000
10 000
15 000
15 000
15 000
15 000
607)
--80
607)
--80
607)
--80
60
20
-80
607)
20
20
80
607)
20
20
80
607)
20
20
80
607)
20
20
80
5)
6)
7)
8)
9)
The main contacts of size I circuit breakers with switching capacity H can
only be replaced at the factory.
Maintenance means: replace main contact elements and arc chutes (see
Operating Manual).
Use of releases from 20 C
Siemens 2012
25
Siemens AG 2011
3 0
3 0
3 0
and/or
N S E 0 _ 0 0 0 6 1 a
Degree of protection
Main conductor
minimum
cross-sections
Unit(s)
Copper bars,
mm2
bare
Unit(s)
Copper bars,
mm2
painted black
Auxiliary conductors (Cu)
Standard connection = strainMax. number of
relief clamp
auxiliary conductors cross- Without end sleeve
section
With end sleeve according to
(solid/stranded)
DIN 46228 Part 2
With twin end sleeve
Optional connection = tension
spring
Without end sleeve
With end sleeve according to
DIN 46228 Part 2
26
Siemens 2012
kg
kg
kg
kg
kg
kg
h m a x .
= 1 m m
Sizes
Type
Mounting position
N S E 0 _ 0 0 0 6 2 a
N S E 0 _ 0 0 9 2 7 a
IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
1
2
2
3
1
1
2
60 10
40 10
50 10
50 10
50 10
60 10
40 10
1
2
2
3
1
1
2
60 10
40 10
50 10
50 10
50 10
60 10
40 10
2
50 10
2
50 10
2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14)
1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16)
2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
2 0.5 mm2 (AWG 20) ... 2 2.5 mm2 (AWG 14)
2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
1 0.5 mm2 (AWG 20) ... 1 2.5 mm2 (AWG 14)
43
43
43
43
56
45
45
45
45
60
25
25
25
25
31
50
50
50
50
67
54
54
54
54
72
30
30
30
30
37
56
60
31
67
72
37
56
60
31
67
72
37
56
60
31
67
72
37
Siemens AG 2011
II
Type
III
A 2000
A 2000
2500
2500
3200
3200
4000
4000
4000
4000
5000
5000
6300
6300
V AC ...
690/1000
...
690/1000
...
690/1000
... 690
...
690/1000
...
690/1000
...
690/1000
V AC 1000
1000
1000
1000
1000
1000
1000
kV 12
kV 4
kV 2.5
12
4
2.5
12
4
2.5
12
4
2.5
12
4
2.5
12
4
2.5
12
4
2.5
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Utilization category
Power loss at In
with 3-phase symmetrical load
Fixed-mounted circuit breakers
Withdrawable circuit breakers
C 25/+70
C 40/+70
25/+70
40/+70
25/+70
40/+70
25/+70
40/+70
25/+70
40/+70
25/+70
40/+70
25/+70
40/+70
A 2000
A 2000
A 2000
2500
2500
2280
3200
3020
2870
3950
3810
3600
4000
4000
4000
5000
5000
5000
5920
5810
5500
V 2000
2000
2000
2000
2000
2000
2000
W 180
W 320
270
520
410
710
750
925
520
810
630
1050
900
1600
Switching times
Make-time
Opening time
ms
ms
35
34
35
34
35
34
35
34
35
34
35
34
35
34
ms 100
ms 73
100
73
100
73
100
73
100
73
100
73
100
73
ms
ms
73
50
73
50
73
50
Endurance
Mechanical (without maintenance)
Mechanical (with maintenance)3)
Electrical (without maintenance) up to 690 V
1000 V version, electrical (without maintenance)
1150 V version, electrical7) (without maintenance)
Switching capacity C: Electrical
(without maintenance) up to 690 V
Switching capacity C: Electrical
(without maintenance) up to 1150 V
Electrical (with maintenance)3)
73
501)
73
501)
73
501)
10000
15000
7500
1000
500
--
10000
15000
4000
1000
500
--
10000
15000
2000
1000
500
--
Operating cycles --
--
--
--
15000
15000
1/h 609)
1/h 20
1/h 20
609)
20
20
ms 80
80
Switching frequency8)
690 V version
1000 V version
1150 V version7)
Minimum interval between tripping operation by electronic
release and next making operation of the
circuit breaker (only with automatic
mechanical resetting of the lockout device)
73
501)
5000
10000
2000
1000
500
1000
5000
10000
2000
1000
500
1000
5000
10000
2000
1000
500
1000
500
500
500
15000
10000
10000
10000
609)
20
20
609)
20
20
60
20
20
60
20
20
60
20
20
80
80
80
80
80
5)
6)
2)
7)
3)
8)
9)
4)
Siemens 2012
27
Siemens AG 2011
Type
III
3 0
Mounting position
3 0
3 0
h m a x .
= 1 m m
Sizes
3 0
and/
or
N S E 0 _ 0 0 0 6 1 a
N S E 0 _ 0 0 9 2 7 a
N S E 0 _ 0 0 0 6 2 a
IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Degree of protection
Main conductor
minimum
cross-sections
Copper bars,
bare
Unit(s) 3
mm2 50 10
2
100 10
3
100 10
4
120 10
4x
100 x 10
6x
100 x 10
6x
120 x 10
Copper bars,
painted black
Unit(s) 3
mm2 50 10
2
100 10
3
100 10
4
4
100 101) 100 10
6
100 10
6
120 10
Auxiliary conductors
(Cu)
Max. no. of
auxiliary conductors
cross-section
(solid/stranded)
2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14)
1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16)
2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
Position signaling
switches
Weights 3-pole
kg 56
kg 60
kg 31
59
63
39
64
68
45
85
121
52
82
88
60
82
88
60
90
96
70
kg 67
kg 72
kg 37
71
76
47
77
82
54
103
146
62
99
106
84
99
106
84
108
108
119
4-pole
1)
28
Siemens 2012
Siemens AG 2011
I to III
Type
3WL1
N 230
9
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
50/60 Hz AC
DC
Power consumption
AC/DC
Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic
1 A TDz (slow)/1 A
Manual operating
mechanism
Motor
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
AC/DC
VA/W 135/135
s 10
Closing solenoid
For motor and
closing solenoid
Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/miniature circuit breaker with
C characteristic; Motor and closing solenoid for identical rated control supply voltages
6 A TDz (slow)/2 A
6A
6A
2A
At Us = 24 ... 30 V
At Us = 48 ... 60 V
At Us = 110 ... 125 V DC/
110 ... 127 V AC
At Us = 220 ... 250 V DC/
208 ... 240 V AC
2A
Auxiliary releases
Undervoltage
releases
UVR (F3) and
UVR-td (F4)
Response values
Pick-up
Dropout
At 24 V DC, 30 V DC,
48 V DC, 110 V DC, 220 V DC
Instantaneous
50/60 Hz AC
DC
Delayed
50/60 Hz AC
DC
AC
DC
VA 20/5
W 20/5
ms 200
ms 80
ms 200
s 0.2 ... 3.2
ms 100
1 A TDz (slow)/1 A
Siemens 2012
29
Siemens AG 2011
I to III
Type
3WL1
Auxiliary releases
Shunt release (ST)
(F1, F2)
- Response value
Pick-up
> 0.7 Us
(circuit breaker is tripped)
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
50/60 Hz AC
DC
- Power consumption
AC/DC
VA/W 15/15
AC/DC
ms 80
5 % OP
ms 60
- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational
class)/miniature circuit breaker with C characteristic
1 A TDz (slow)/1 A
- Response value
> 0.7 Us
(circuit breaker is tripped)
Pick-up
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
50/60 Hz AC
DC
- Power consumption
AC/DC
VA/W 15/15
AC/DC
ms 50
ms 25
- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational
class)/miniature circuit breaker with C characteristic
- Rated control supply voltage Us
1 A TDz (slow)/1 A
50/60 Hz AC
DC
V 110; 230
V 110; 220
VA/W 1/1
max. 5 min/min. 5 s
At 24 V DC, 48 V DC
110 V DC
220 V DC
- Power consumption
AC/DC
VA/W 50/50
ms 60
- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic
2 A TDz (slow)/1 A at 24 V DC
and 48 V DC,
1 A TDz (slow)/1 A at 110 V and
208 ... 250 V
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
Rated insulation voltage Ui
V AC/DC 500
V AC/DC 500
kV 4
Alternating current
50/60 Hz
Direct current
Short-circuit protection
30
Siemens 2012
V 24 ... 230
A 10
A 4
V 24
48
A 10
A 8
8
4
380/400
500
10
3
10
2
110
220
3.5
1.2
10 A TDz, 10 A Dz
10 A
1
0.4
Siemens AG 2011
I to III
Type
3WL1
Short-circuit protection
Alternating current
V 250
A
8
Direct current
V 125
A
0.4
250
0.2
2 A Dz (quick)
Tripped signaling switch (S24) and signaling switch for auxiliary releases (S22, S23)
(according to DIN VDE 0630)
Switching capacity
Alternating current
V 250
A
8
Direct current
V 24
A 6
125
0.4
Short-circuit protection
6 A Dz (quick)
250
0.2
Signal:
- Ie/AC-12
V 440
V 250
- Ie/DC-13
24 V 10 A, 110/127 V 10 A,
220/240 V 10 A, 320/440 V 10 A
220/240 V 4 A,
320/440 V 3 A,
24 V 10 A, 48 V 2.5 A,
220/240 V 0.2 A,
24 V 3.0 A, 220/240 V 0.1 A
- A 300 (AC)
120 V 6 A, 240 V 3 A
- R 300 (DC)
- Ie/AC-15
- Ie/DC-12
Short-circuit protection
1 CO
1 CO
1 CO
kV 4
or
V 250
3 CO
2 CO
1 CO
8 A TDz (slow)
8 A TDz (slow)
Siemens 2012
31
Siemens AG 2011
ETU15B
D
ETU25B
D
ETU27B
D&S
-0.5-0.55-0.6-0.65-0.70.75-0.8-0.85-0.9-1
--
-0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1
--
-0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1
--
10 s fixed
--At tsd = 20 ms (M)
---
-1.25-1.5-2-2.5-3-4-6-8-10-12
0-M-100-200-300-400 ms
--
10 s fixed
--At tsd = 20 ms (M)
-1.25-1.5-2-2.5-3-4-6-8-10-12
0-M-100-200-300-400 ms
--
--
-Fixed for Ii 20 In, max. 50 kA
------
--
-Fixed for Ii 20 In, max. 50 kA
Fixed mounted
-
-
N S E 0 _ 0 0 8 8 8 b
Function can be switched on/off
-Setting range Ii = In ...
2-3-4-5-6-7-8
Ground-fault protection
-Tripping and alarm function
-Tripping function can be switched on/off
-Alarm function can be switched on/off
-Detection of the ground-fault current through summa- -tion current formation with internal or external N cong
ductor transformer
Detection of ground-fault current through external
-current transformer
g
Setting range of the operating current Ig for tripping --Setting range of the operating current Ig for alarm
N S E 0 _ 0 0 8 8 9 a
Setting range of the delay time tg
-Switchable ground-fault protection characteristic
-2
curve (I t-dependent function)
Setting range for delay time tg at I2t
-Zone Selective Interlocking ground-fault protect.
-function
Parameter set switchover
Switchable between parameter set A and B
-LCD
Alphanumeric LCD (4-line)
-Graphical LCD (24 V, external power supply required) -Communication
CubicleBUS integrated
-Communication-capable through PROFIBUS DP
-Measurement function
Measurement-function capable with measurement -function Plus
LED display
Electronic release active
Alarm
ETU fault
L-release
-S-release
-I-release
-N-release
-NSE00890
G-release
-G-alarm
-Release through extended protection function
-Communication
-Signals from signaling switches with external CubicleBUS modules (relays)
Overload warning
-Load shedding, load receiving
-Leading signal overload trip 200 ms
-Temperature alarm
-Phase unbalance
-Instantaneous short-circuit release
-Short-time delayed short-circuit release
-Overload trip
-Neutral conductor release
-NSE00891
Ground-fault protection release
-Ground-fault alarm
-Auxiliary relay
-ETU fault
-R
N
S
I
For the setting range of the operating current Ig, see page 33.
32
Siemens 2012
--
--
-----
A-B-C-D-E
-100-200-300-400-500 ms
--
---
---
--
--
---
---
---
---
--
--
------
----
--------------
------------- Available.
-- Not available.
Optional.
Siemens AG 2011
ETU45B
D& S
ETU76B
M/K
-0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1
2-3.5-5.5-8-10-14-17-21-25-30 s
1-2-3-4-5 s
At tsd = 20 ms (M)
0.5 ... 1
1.25-1.5-2-2.5-3-4-6-8-10-12
M-100-200-300-400 ms
Overload protection
Function can be switched on/off
Setting range IR = In ...
current transformer
Setting range of the operating current Ig
A-B-C-D-E
for tripping
Setting range of the operating current Ig for alarm
A-B-C-D-E
Setting range of the delay time tg
100-200-300-400-500 ms
Measurement function
Measurement-function capable with measurement function
Plus
LED display
Electronic release active
Alarm
ETU fault
L-release
S-release
I-release
N-release
G-release
(only with ground-fault protection module)
G-alarm
(only with ground-fault protection module)
Release through extended protection functions
Communication
Temperature alarm
Phase unbalance
Overload trip
ETU fault
100 A
300 A
600 A
900 A
1200 A
400 A
600 A
800 A
1000 A
1200 A
0.4 ... 1
2 ... 30 s
1 ... 5 s
(on/off)
0.2 ... 2
A ... E
A ... E
100 ... 500 ms
Siemens 2012
33
Siemens AG 2011
Characteristic curves2)
1,25 ... 12 x
R min
100
10
sd min
sd max
1,25 ... 12 x
sd max
0 ... 0,4 s
sd min
i > 20 x n
max. 50 kA
0,01
0,1
10
100
/
[s]
1000
10000
Opening Time
100
10000
100
g min
R max
1000
0,1
10
NSE0_01527
[s]
10000
i > 20 x n
max. 50 kA
10
100
/
0,01
1
10
sd min
0,1
0,1
0,1
sd max
0 ... 0,4 s
i max
n
0,01
sd max
n
i min
0,1
10
sd min
10
2 ... 8 x
100
100
g max
1000
NSE0_01523a
1000
R max
NSE0_01519
R max
1000
R min
R min
NSE0_01520
10000
10000
Opening time
Every release type and every setting has its own characteristic
curve. Only a selection is shown in the following. The characteristic curves each show the largest and smallest setting range of
3WL circuit breakers with 1000 A rated current at 500 V rated
voltage with various releases. In order to obtain a complete tripping characteristic, the relevant parts of the characteristics have
to be combined. The characteristic curves show the behavior of
the release when it is activated by a current that is already flowing before the tripping operation. If the overcurrent tripping occurs immediately after switch on and the release is therefore not
yet enabled, the opening time is extended, depending on the
level of the overcurrent by up to 15 ms. In order to determine the
break-times of the circuit breakers, approximately 15 ms must
be added to the opening times shown for the arcing time.
Refer to the following legend for tolerances.
The characteristic curves shown apply to ambient temperatures
at the circuit breaker between -5 and +55 C. The release can
be operated at ambient temperatures of -20 to +70C.
An extended tolerance band can apply at these temperatures.
sd
1,25 ... 12 x
100
2
sd =
const
10
g max
2
sd =
g min
const
sd =
const
0,1
0,02 ... 0,4 s
0,01
100
1000
10000
0,01
100000
0,1
34
Siemens 2012
10
100
/
2)
With single-pole loading in the lowest rated current range, the response
times of the short-circuit release can be extended by approx. 10 % and
the tripping times by approx. 15% compared to the characteristic curve.
Siemens AG 2011
NSE0_01525a
10000
Every release type and every setting has its own characteristic
curve. Only a selection is shown in the following. The characteristic curves each show the largest and smallest setting range of
3WL circuit breakers with 1000 A rated current at 500 V rated
voltage with various releases.
1000
100
g
10
= const
1
g
0,1
0,01
100
1000
10000
100000
1000
= const
n
2
= const
1000
NSE0_01526a
10000
Opening time [s]
10000
NSE0_01522a
sd
1,25 x
100
n ... 0,8
cw
10
100
2
R
2 ... 30s for 2
1 ... 5s for 4
10
sd =
0,1
sd =
const
const
0,1 ... 0,4 s
0,02 ... 4 s
1
0,01
0,1
0,1
10
/ n
1
/
cw
0,01
0,1
10
100
/
10000
1000
100
1
i
1,5 x
n ... 0,8
10
0,1
cs
0,01
0,1
10
/ n
1
/
cs
Siemens 2012
35
Siemens AG 2011
Dimensional drawings
Voltage transformer for 3WL air circuit breakers
260
125
1 6
8
8 ,9
N S E 0 _ 0 1 3 7 5
87
2 2
4 0
For mounting on
35 mm standard
mounting rail
1 3 ,1
2 2
8 1
9 6 ,8
R
NSE0_01103b
1 8
5 1
3 6
7 0
8 3
N S E 0 _ 0 1 3 7 6
5 4
1 1 5
1 3 1
6 5 ,5
1 3 ,5
2 7
4 1
5 1
8 8
9 5
1 1 3
1 7 0
9 1
1 3 0
6 8
5 1
2 4
4 4
1 5
9 7
1 6 1
1 0 7
1 2 3
R 1 5
4 5
5 5
8 3
N S E 0 _ 0 1 3 7 7
N S E 0 _ 0 0 6 0 6 b
3 1
3 0
3 0
5 0 ,5
5 1
1 6 0
1 8 4
4 4
1 3 ,5
9 1
1 7 0
1 3 0
6 8
5 1
2 4
N S E 0 _ 0 0 6 0 7 b
2 9 5
1 3 1
3 4 0
9 0
1 1 3
3 1 0
3 0
5 2
2 4 0
3 0
1 3 ,5
1 2 3
3 0 0
1 2 0
5 ,5
4 0
3 )
N S E 0 _ 0 0 6 1 0 c
2 )
5 ,5
Mounting surface
2)
3)
4)
36
Siemens 2012
1 1 ,5
1)
1 8 0
4 0
1 2 0
5 ,5
6 5
1 4 0
1 7 5
3 5 0
1 4 0
R 5
R 5
1 8 5
N S E 0 _ 0 0 6 0 8 b
1 6 0
1 8 4
1 7 0
N S E 0 _ 0 0 1 6 4 c
9 1
1 3 0
6 8
5 1
2 4
4 4
1 )
1 2
2 1
4 )
4 0
Siemens AG 2011
3WL9 111-0AT2.-0AA0
3WL9 111-0AT28-0AA0
70
3WL9 111-0AT33-0AA0
81,9
45,5
38
19
16(B
153
16(B
94
47,5
86
30
Siemens 2012
37
Siemens AG 2011
NSE0_01029c
4 x R5
4 x 5,5
72
340-350
85
70
68
435
72
295-300
Lateral
Rear
(each side)
mm
mm
501)
501)
0
0
0
0
0
0
0
0
02)
02)
0
0
0
0
0
0
0
0
751)
751)
180
501)
501)
100
0
0
0
0
0
0
0
0
02)
02)
0
0
0
0
0
0
0
0
751)
751)
180
501)
501)
100
0
0
0
0
0
0
0
0
02)
02)
0
0
0
0
0
0
0
0
45
200
150
All safety clearances above the circuit breaker refer to the upper
edge of the auxiliary connector - not to the upper edge of the arc
chute! See dimensional drawings on pages 39 to 47, Parts 4)
and 5).
38
Siemens 2012
500
690
1000
150
300
5003)
Lateral
Rear
(each side)
mm
mm
14
14
20
50
1003)
20
125
1403)
504)
2254)
14
14
20
50
1003)
14
14
1403)
150
300
5003)
100
100
14
14
50
100
100
20
140
125
50
100
100
14
30
14
50
225
14
14
20
100
100
20
125
125
20
100
100
14
14
14
50
200
14
14
250
600
430
250
600
350
500
690
148
Circuit breaker
mounting level
17
313
14
14
75
500
430
50
500
350
14
14
1)
2)
40 mm (size II: 70 mm) for plates, which cover the lateral openings in the
guide frame
3)
4)
Siemens AG 2011
4 7
421
N S E 0 _ 0 0 6 1 2 c
275
440,5
55
55
3)
123,5
26
8 2
60 90
90
90
9)
14)
8)
13,5
47
55
40
60,5
55
55
55
80
19) 1) 2)
NSE00616b
421
3)
11)
76
45
NSE0_00614h
80
5,5
6)
150
210
230
40
14
150
275
3)
327,5
461,5
NSE0_00615h
33,5
621
541,5
516
451,5
11)
35
437,5
55
15
10
270
300
390
55
13,5
35
5)
4)
NSE0_00611h
NSE00613b
Standard version
Horizontal connection
7)
82
60 90
90
90
106
127
Vertical connection
90
90
60
55
35
11)
4x M8
4x 9
20
139
320
410
58
3)
NSE0_00618h
110 (150)
127,5
7)
3)
7)
267,5
30
11)
NSE0_00617j
NSE00619
13,5
60
35
90
13,5
7)
113,5
128,5
60
Rated
a
circuit breaker
current
NSE00620
90
90
90
A
3)
60
90
90
Up to 1000
10
10
10
11
451
34
541
15
20
15
461
39
551
90
4-pole version
1)
2)
Arc quenching space 690 V circuit breaker facing grounded or nonconductive surfaces.
3)
4)
5)
6)
7)
8)
9)
11)
Terminal face.
14)
18)
Circuit breaker upper edge, only 690 V (+20 %) and 1000 V circuit
breakers.
19)
Arc quenching space, circuit breaker facing grounded or non-conductive surfaces, only 690 V (+20 %) and 1000 V circuit breakers.
Siemens 2012
39
Siemens AG 2011
5 5
5 5
3 5
1 1 )
2 8 7
3 )
169,5
9 0
1 5
2 6
11
30
55
382,5
367,5
327
19)
62,5
55
80
8)
9)
350
260
55
55
40
7)
NSE0_00625h
NSE0_00624g
9 0
373
13,5
2)
18)
55
9 0
3 5
13
210
300
10)
6 9
123,5
3 7 3
403
465,5
5 5
1 3 ,5
N S E 0 _ 0 0 6 2 3 b
NSE0_00621j
275
468,5
5)
3 5 0
2 6 0
5 5
11)
55
55
220
45
58
88,5
121,5
140,5
169,5
10)
80
40
6)
15
Vertical connection
NSE0_00628h
10)
287
69
NSE0_00630h
10)
90
90
Up to 1000
1250 ... 2000
10
15
10
15
10
15
40
90
90
90
4-pole version
3)
55
287
287
150
165
69
25
3)
15
15
90
90
30
267,5
127,5
NSE00627a
68
350
260
10)
90
NSE0_00629h
60
11)
139
270
320
410
38
13,5
90
350
260
b
11)
13,5
69
NSE0_00626h
493
518,5
34
10)
38
55
27
42
14
40
14
76
3)
275
150
31
55
327,5
620
519
460
12)
Siemens 2012
2)
For guide frame without arc chute cover, arc quenching space 690 V circuit
breaker facing grounded or non-conductive surfaces.
3)
4)
5)
6)
7)
8)
9)
10)
11)
Terminal face.
18)
Circuit breaker upper edge, only 690 V (+20 %)and 1000 V circuit breakers.
19)
Siemens AG 2011
Flange connection
55
NSE0_00631h
14
350
260
55
55
55
282,5
142,5
26
287
59
33
M 12
NSE0_00632h
69
121
59
3)
10)
15
3)
10)
90
90
90
Siemens 2012
41
Siemens AG 2011
4 7
5)
90
90
421
NSE00635c
275
440,5
437,5
90
40
40
N S E 0 _ 0 0 6 3 4 d
4)
NSE0_00633a
35
Standard version
Horizontal connection
123,5
85
26
10
270
440
570
90
2)
130
130
130
90
40
90
12)
4 7
90
90
40
NSE00638c
3)
11)
14
275
3)
421
327,5
461,5
N S E 0 _ 0 0 6 3 7 d
80
14)
621
541,5
516
451,5
13,5
8 2
40
13) 1)
11)
35
3)
80
40
NSE0_00636e
76
150
a
5,5
45
150
210
230
6)
106
127
90 130
130
130
13,5
8 2
30
30
30
90
11)
3)
13,5
NSE0_00639f
128
11)
130
Rated
a
circuit breaker
current
130
130
130
130
2)
Arc quenching space " 690 V" circuit breaker facing grounded or non-conductive
surfaces.
3)
4)
5)
6)
7)
11)
Terminal face.
12)
Circuit breaker upper edge, only 1000 V and 1150 V circuit breaker.
13)
Arc quenching space, 1000 V and 1150 V circuit breaker facing grounded or nonconductive surfaces.
14)
Up to 2000
10
15
10
11
451
34
541
2500
15
15
20
461
39
551
3200
30
30
20
461
39
551
90
4-pole version
42
113,5
128,5
1)
3)
130
35
NSE00640b
NSE00642
90
NSE00641
98
134,5
139
460
590
3)
7)
290
7)
30
90
130
35
130
13,5
Siemens AG 2011
2)
85 Nm
13,5
NSE0_01868a
541,5
516
345,5
79,5
100
30
30
1)
4011)
142
162
10
20
200
130
200
1)
2)
Arc quenching space " 690 V" circuit breaker facing grounded or nonconductive surfaces.
11)
Terminal face.
Siemens 2012
43
Siemens AG 2011
5 3 0
62,5
NSE00644b
9 0
9 0
4 0
4 0
1 3 ,5
6
3 )
1 1 )
10)
2 6
c
169,5
6 9
40
10)
270
350
55
4 5 ,1
1 3 0
5 5
1 3 0
1 3 0
9 0
9 0
3 5
11
123,5
3 7 3
403
275
468,5
465,5
4 0 0
9 0
9 0
2 8 7
5)
3 5
4)
NSE0_00643b
N S E 0 _ 0 0 6 4 5 c
Standard version
Horizontal connection
8)
9)
1 3 ,5
9 0
4 0
4 0
4 0
3 7 3
3 )
1 1 )
1 4
34
518,5
327,5
3)
10)
8 0
6 9
c
169,5
40
31
4 0
14
76
275
150
620
520
460
4 0 0
9 0
8 0
7)
NSE00647b
13)
2)
12)
493
NSE0_00646f
5 3 0
62,5
2 8 7
382,5
367,5
327
N S E 0 _ 0 0 6 4 8 c
480
27
42
45
58
88,5
121,5
140,5
220
5 5 4 5
1 3 0
1 3 0
1 3 0
6)
4-pole version
30
38
30
13,5
2)
For guide frame 690 V, without arc chute cover, arc quenching space facing
grounded or non-conductive surfaces.
3)
4)
5)
11)
NSE00649a
6)
139
270
460
590
7)
8)
9)
10)
138
95
11)
12)
13)
530
400
90
90
90
NSE0_00652b
90
69
287
3)
10)
55 45
130
130
10)
130
Up to 2000
10
15
10
2500
15
15
20
3200/4000
30
30
20
44
Siemens 2012
Siemens AG 2011
30
30
NSE00650a
11)
38
4 0 0
b
N S E 0 _ 0 0 6 5 1 a
2 8 7
6 9
135
100
290
3 )
157
172
5 5 4 5
1 3 0
1 3 0
1 3 0
NSE0_01869
30
109,5
315,5
100
30
4011)
177
197
4,6
10
20
55
45
200
200
130
5 3 0
1 2
9 0
N S E 0 _ 0 0 6 5 4 a
4 0 0
4 0
5 9
2 6
3 3
NSE00653
Flange connection
6 9
1 4 2 ,5
5 9
2 8 2 ,5
2 8 7
3 )
121
4 5
1 3 0
1 3 0
1 3 0
4-pole version
3)
11)
Siemens 2012
45
Siemens AG 2011
47
12
205
NSE00656c
160
160
50
421
3)
130
20
82
11
270
680
890
160
50
11)
26
451
123,5
437,5
275
440,5
13,5
NSE00657c
5)
210
210
35
4)
NSE0_00655a
35
Standard version
Horizontal connection
210
1 3 ,5
4 7
1 6 0
1 6 0
N S E 0 _ 0 0 6 6 0 c
5 4 1
3 )
8 0
76
2 1 0
1 3 0
4 0
2 0
2 1 0
2 1 0
8 2
45
150
210
230
1 1 )
1 4
327,5
461,5
3 4
275
35
1 6 0
5 0 5 0
5,5
150
30
NSE0_00658e
N S E 0 _ 0 0 6 5 9 d
30
621
541,5
516
451,5
3)
1 6 0
5 0 5 0
8 0
4 0
2)
12)
14)
4 2 1
13)
6)
106
127
Vertical connection
160
30
130
107
15
30
210
15
35
210
210
20
10
NSE00663
11)
3)
139
704
248
914
NSE0_00661e
M10
40
13,5
142
162
NSE00662a
3)
40
94,5
120
7)
330,5
11)
13,5
7)
85
210
210
210
NSE00664a
3)
130
210
210
210
130
4-pole version
1)
2)
3)
4)
5)
6)
7)
11)
Terminal face.
12)
Circuit breaker upper edge, only 1000 V circuit breaker and circuit
breaker with switching capacity C.
46
Siemens 2012
13)
Arc quenching space, 1000 V circuit breaker and circuit breaker with
switching capacity C, facing grounded or non-conductive surfaces.
14)
Siemens AG 2011
8 4 0
62,5
5)
6 9
2 1 0
8 5
5 9 0
6 3 0
1 6 0
4 0
1 6 0
5 0
1 6 0
1 6 0
8 0
5 0
3 7 3
1 1 )
1 4
8 0
40
31
27
42
220
45
58
88,5
121,5
140,5
34
20
169,5
2 1 0
8 5
4 0
10)
76
14
2 8 7
493
518,5
30
3)
275
150
NSE00669b
8)
9)
327,5
30
620
520
460
8 4 0
62,5
8 0 0
1 3 ,5
13)
2)
12)
2 1 0
2 1 0
3 5
20
169,5
N S E 0 _ 0 0 6 7 0 c
57
7)
2 8 7
3 7 3
403
1 1 )
5 7
NSE0_00668d
1 6 0
10)
800
382,5
367,5
327
1 6 0
5 0
5 9 0
5 7
2 1 0
6 9
160
1 6 0
5 0
2 6
270
590
10)
11
10)
6 3 0
1 6 0
123,5
465,5
275
468,5
NSE00666b
NSE0_00665b
1 3 ,5
4)
N S E 0 _ 0 0 6 6 7 c
Standard version
Horizontal connection up to 5000 A
3 5
2 1 0
8 0 0
6)
38
2 0
1 0
N S E 0 _ 0 0 6 7 3 b
260
217
13,5
2 8 7
24
177
197
6 9
NSE00671a
914
6 3 0
7 0 4
330,5
94,5
124,5
11)
139
270
704
8 4 0
NSE00672a
38
11)
13,5
30
30
30
30
5 7
a
b
5 9 0
2 1 0
8 0 0
9 1 4
4-pole version
840
630
160
160
160
69
287
NSE0_00674a
160
57 85
210
210
210
40
40
5
210
210
245
A
4000
5000
6300
2)
For guide frame 690 V, without arc chute cover, arc quenching space facing
grounded or non-conductive surfaces.
3)
4)
5)
6)
7)
8)
9)
10)
11)
Terminal face.
12)
Guide frame upper edge only 1000 V and 150/130 kA guide frame.
13)
Arc quenching space, 1000 V circuit breaker and circuit breaker with switching
capacity C, facing grounded or non-conductive surfaces.
Siemens 2012
47
Siemens AG 2011
1 6 0
1 6 0
5 7 8 5
121
5 9
5
6 9
2 8 2 ,5
1 4 2 ,5
2 6
2 8 7
5 9
M
3 3
1 2
1 6 0
N S E 0 _ 0 0 6 7 6 a
NSE00675
8 4 0
6 3 0
7 0 4
1 6 0
3 0
2 1 0
2 1 0
5 9 0
2 1 0
8 0 0
9 1 4
48
Siemens 2012
Siemens AG 2011
Circuit diagrams
Terminal assignment diagram
Internal wiring
optional
Accessories
(Auxiliary switch S1, S2 = Standard)
Terminals
External wiring
L+
L
13
G transformer S2
12
G transformer S1
11
N sensor S2
10
N sensor S1
L3
L2
0 V DC
24 V DC
BUS +
BUS
7
6
5
4
3
S23
Signaling contact at the 2nd auxiliary release
Open
+ OUT
F1, 2
1 2 3 4 5 6 7 8 9
/COM16
(Option F02/F12)
L+
Internal
External
10
Y1
11
"Spring charged" signal S21
Close
+
12
Termination resistor,
if not external CB-module!
Free
+
13
L1
24 V DC input
DPWrite Free
Enable
14
IN
14
14
L+
13
12
S1 "NO"
11
10
S1 "NC"
Closing solenoid
L+
6
5
S2 "NO"
3
2
S2 "NC"
14
13
12
11
EMERGENCY STOP
or short terminals
L+
c
L
10
S3 "NO" or S7 "NO"
9
8
S3 "NC" or S7 "NO"
7
6
S4 "NO" or S8 "NO"
5
4
Charging motor
opt. motor main switch S12
NSE0_00605p
S4 "NC" or S8 "NO"
(sw)
(br)
3
2
1
L+
L
Siemens 2012
49
Siemens AG 2011
release
contact
signaling switch (optionC22), with LSING release, with "UVR" undervoltage release (F3), with "ST" shunt release (F1), with tripped
signaling switch (option K07), with auxiliary switch 4 NO + 4 NC.
L1
(L+)
OFF
version
electr.
ON
-X5.6
-X5.4
-X5.10
-X5.8
-X6.4
-X6.2
-X6.12
-X6.10
ETU
-S10
-A1
1
3
-X6.6
-X7.12
-X7.14
-X5.12
-X6.14
-X6.7
-X7.9
-X5.2
ON
S
I
N N
G
-S11
-F3
-T2
-A1
-S1/-S2
-S3/-S4
-S7 (optional)
F1
-S8 (optional)
F2
F3
M1
Q1
S1 & S2
S3 & S4
1
F5
Y1
A1
T1
T2
T3
T4
NSE0_01559c
50
Siemens 2012
-X5.5
-X5.3
-X5.9
-X5.7
ETU release
1st auxiliary switch block (2 NO + 2 NC)
2nd auxiliary switch block (2 NO + 2 NC)
2nd auxiliary switch block, S7 (2 NO) can be used
if there is no S3 - S3 and S7 have
the same terminal assignment/mounting space
2nd auxiliary switch block, S8 (2 NO) can be used
if there is no S4 - S4 and S8 have
the same terminal assignment/mounting space
3WL1. ..-.....-...2
3WL1. ..-.....-...4
3WL1. ..-.....-...7
3WL1. ..-.....-...8
F4
S24
-X6.3
-X6.1
Function diagram of
3WL circuit breaker
S20
-X6.9
2
4
-X8.9
N
(L-)
-X8.10
-X6.5
-X7.13
-X5.11
-X6.13
-X6.8
NSE0_01558b
-T3
-F1
-X6.11
-S12
U<
-Y1
-X5.1
N
(L-)
-S4
-S3
-T1
mech.
OFF
-S2
-S1
-Q1
QS
mech.
ON
-S24
-F5
-S20
L
S
I
N N
G
-S10
-S11
-S12
(2 NO + 2 NC) S1+S2
(4 NO + 4 NC) S1+S2+S3+S4
(6 NO+ 2 NC) S1+S2+S7+S8
(5 NO + 3 NC) S1+S2+S3+S8
-S20
-S24
Electrical ON button
Internal motor shutdown switch (if spring is tensioned)
Motor shutdown switch
(no automatic tensioning of spring)
Ready-to-close signaling switch
Tripped signaling switch
-F1
-F3
-F5
-M
-P
-QS
-Q1
-T1/-T2/-T3
-X5/-X6/-X7/-X8
-Y1
-R
-X8.9/-X8.10
Siemens AG 2011
SENTRON 3WL
3
4
5
6
5
6
1
2
3
4
ZSI module
SENTRON 3WL
3
4
5
6
ZSI
module
SENTRON 3WL
3
4
5
6
ZSI
module
ZSI
module
SENTRON 3WL
3
4
5
6
ZSI
module
ZSI
module
SENTRON 3WL
3
4
5
6
SENTRON 3WL
3
4
5
6
ZSI
module
ZSI
module
SENTRON 3WL
3
4
5
6
NSE0_01898
SENTRON 3WL
SENTRON 3WL
3
4
5
6
Circuit diagram for a Zone Selective Interlocking functionality with multiple infeed and several outgoing units with 3WL circuit breakers
NSE0_01897
ZSI
module
SENTRON 3VL
ZSI module
SENTRON 3WL
3
4
5
6
ZSI
module
5
6
1
2
3
4
ZSI
module
SENTRON 3WL
3
4
5
6
NSE0_01899
SENTRON 3WL
SENTRON 3WL
3
4
5
6
ZSI
module
ZSI
module
SENTRON 3WL
3
4
5
6
More information
Up-to-date information on the Internet at:
www.siemens.com/sentron
Siemens 2012
51
Siemens AG 2011
Technical specifications
Sizes
II
Type
3WL12 10
Rated current In at 40 C
Main conductors
A ... 1000
3WL12 20
3WL12 40
2000
4000
V DC ... 600/1000
... 600/1000
... 600/1000
V DC 1000
1000
1000
kV 12
kV 4
kV 2,5
12
4
2,5
12
4
2,5
Yes
Yes
25/+70
40/+70
25/+70
40/+70
2000
2000
2000
1950
4000
3640
3500
3250
770
1640
Yes
C 25/+70
C 40/+70
Permissible load
at rear horizontal main circuit
connections
(Cu painted black)
up to 40 C
up to 55 C
up to 60 C
up to 70 C
A
A
A
A
1000
1000
1000
1000
W 280
Switching times
Make-time
Opening time
ms
ms
35
34
35
34
35
34
ms 100
ms 73
100
73
100
73
ms
73
73
Operating cycles
Operating cycles
Operating cycles
Operating cycles
Operating cycles
Switching frequency
600 V version
1000 V version
73
10000
15000
6000
1000
15000
1/h 60
1/h 20
Mounting position
10000
15000
6000
1000
15000
10000
15000
4000
1000
15000
60
20
60
20
3 0
3 0
3 0
h m a x .
= 1 m m
Endurance3)
Mechanical (without maintenance)
Mechanical (with maintenance)2)
Electrical (without maintenance)
1000 V version
Electrical (with maintenance)2)
3 0
and/
or
N S E 0 _ 0 0 9 2 7 a
N S E 0 _ 0 0 0 6 2 a
N S E 0 _ 0 0 0 6 1 a
Degree of protection
Weights
1)
3-pole
kg 56
kg 60
kg 31
56
60
31
64
68
45
4-pole
kg 67
kg 72
kg 37
67
72
37
77
82
54
2)
3)
Sizes
II
Type
3WL12
DC
Icc
Icc
Icc
Icc
kA
kA
kA
kA
35
30
25
20
kA
kA
kA
kA
-351)/302)/253)/204)
---
At Ue = 220 V DC.
At Ue = 300 V DC.
52
Siemens 2012
3)
At Ue = 600 V DC.
4)
At Ue = 1000 V DC.
Siemens AG 2011
Characteristic curves
R=
1000
= 0.4
R=
= 1.0
R=
100
MIN
1.25
I=
0,1
I=
0,01
0,1
10 s [B]
2 s [A]
10
1
R
n
1.5
MAX
4 n
I=
NSE0_01578
[s]
10000
10
n
Dimensional drawings
DIGmat S100
257
250
DIG S100
3,5
R1
AUTO
MAN
PEAK
DIAG
MAIN
MENUE
271
DIGmat S100
NSE0_01575
R2
122
115
ON
NSE0_01576
136
AUTO
Siemens 2012
53
Siemens AG 2011
90
90
40
40
421
NSE00635c
275
440,5
437,5
90
4 7
5)
N S E 0 _ 0 0 6 3 4 d
4)
NSE0_00633a
35
Standard version
Horizontal connection
123,5
10
26
85
570
40
2)
12)
15)
14)
130
90
40
90
13,5
90
40
90
3)
11)
14
275
3)
40
76
NSE0_02003
80
5,5
150
a
130
NSE00638c
327,5
461,5
602
541,5
516
451,5
447
130
80
4 7
1)
N S E 0 _ 0 0 6 3 7 d
16) 17)
90
8 2
421
270
440
11)
35
3)
45
150
210
230
106
127
6)
90 130
130
130
13,5
8 2
30
30
30
90
11)
3)
13,5
NSE0_00639f
128
11)
1)
3)
3)
4)
5)
6)
7)
11)
12)
130
14)
130
15)
16)
17)
Rated
a
circuit breaker
current
A
Up to 2000
10
15
10
11
451
34
541
4000
30
30
20
461
39
551
54
Siemens 2012
113,5
128,5
90
130
130
130
4-pole version
2)
130
35
NSE00640b
NSE00642
90
NSE00641
98
134,5
139
460
590
3)
7)
290
7)
30
90
130
35
130
13,5
Vertical connection
130
Siemens AG 2011
5 3 0
62,5
NSE00644b
9 0
9 0
4 0
4 0
1 3 ,5
403
275
468,5
3 )
1 1 )
6 9
10)
270
350
55
4 5 ,1
1 3 0
5 5
1 3 0
1 3 0
9 0
9 0
3 5
10)
c
169,5
11
40
2 6
123,5
3 7 3
465,5
4 0 0
9 0
9 0
2 8 7
5)
3 5
4)
NSE0_00643b
N S E 0 _ 0 0 6 4 5 c
Standard version
Horizontal connection
8)
9)
493
7)
1 3 ,5
4 0
3 )
3 7 3
1 4
3)
1 1 )
34
327,5
518,5
9 0
8 0
27
42
76
10)
45
58
88,5
121,5
140,5
220
6 9
8 0
4 0
c
169,5
14
40
31
275
150
4 0 0
9 0
4 0
4 0
NSE00647b
16) 17)
2)
15)
12)
NSE0_02084
651
520
496
460
5 3 0
62,5
2 8 7
382,5
367,5
327
N S E 0 _ 0 0 6 4 8 c
480
5 5 4 5
1 3 0
1 3 0
1 3 0
6)
4-pole version
2)
30
30
For guide frame 690 V, without arc chute cover, arc quenching space facing
grounded or non-conductive surfaces.
3)
38
13,5
4)
11)
NSE00649a
6)
139
270
460
590
138
95
8)
9)
10)
11)
Terminal face.
12)
15)
16)
17)
Arc quenching space, 1000 V circuit breaker (with high arc chute) facing grounded or
non-conductive surfaces.
530
400
90
90
90
NSE0_00652b
90
69
287
3)
7)
10)
55 45
130
130
10)
130
Up to 2000
10
10
10
4000
30
30
20
Siemens 2012
55
Siemens AG 2011
NSE00650a
30
30
11)
38
N S E 0 _ 0 0 6 5 1 a
2 8 7
6 9
135
100
290
3 )
157
172
5 5 4 5
1 3 0
1 3 0
1 3 0
NSE00653
Flange connection
5 3 0
1 2
9 0
N S E 0 _ 0 0 6 5 4 a
4 0 0
4 0
5 9
2 6
3 3
6 9
1 4 2 ,5
5 9
2 8 2 ,5
2 8 7
3 )
121
4 5
1 3 0
1 3 0
1 3 0
4-pole version
3)
11)
56
Siemens 2012
Siemens AG 2011
Circuit diagrams
L1
AC230
N
PE
DC24
AC230
X1.2 X1.1
X5.2 X5.1
DIGmat S100
Auxiliary power
Emergency STOP
+
X4.i1+
DC24
X4.i1-
X2.1 +
Digital input
X4.i2+
Shunt
(60mV)
X2.3 -
X4.i2Automatic RESET
Digital output
X4.01 X4.01 X4.02 X4.02 X4.03 X4.03 X4.04 X4.04
+
-K1
Automatic / Reset
NSE0_01577a
Excitation / Alarm
12
11
12
-K2
11
14
14
-Q01
-X6.14 -X5.12
SENTRON
3WL
-F1
-F3
-X6.13 -X5.11
-Q01 2
Circuit diagram of the DIGmat S100 and the 3WL non-automatic air circuit
breaker
Application examples
Rated operational
voltage
Required,
series-connected
breaks at
rated voltage
Up to 300 V + 10 %
1-pole,
2 parallel conducting
paths,
only with groundedneutral system
2-pole
1-pole,
3 parallel conducting paths,
only with grounded-neutral
system
2-pole
2 parallel conducting
paths
2-pole,
only with groundedneutral system
1-pole,
2 parallel conducting paths,
only with grounded-neutral
system
2-pole
1-pole,
only with groundedneutral system
2-pole,
only with grounded-neutral
system
1-pole,
only with groundedneutral system
Over 300 V + 10 %
Up to 600 V + 10 %
Over 600 V + 10 %
Up to 1000 V + 10 %
(version for 1000 V
required, order with "-Z"
and order code A05)
The connection to the circuit breakers is not dependent on direction and polarity; the circuit diagrams can be adapted accordingly.
Grounded-neutral system
Load
Siemens 2012
57
Siemens AG 2011
More information
Up-to-date information on the Internet at:
www.siemens.com/sentron