Overview

The following tables list the recommended and maximum


possible cable connections at the line and motor ends for a
single circuit connection (versions A and C) and a parallel circuit
(version A).
The recommended cross-sections are based on the specified
fuses. They are applicable for 3-wire cables manufactured out of
copper with PVC insulation, routed horizontally in air and a
permissible wire temperature of 70 C (e.g. Protodur NYY or
NYCWY) for an ambient temperature of 40 C and individual
routing.
When the conditions differ from those specified above (cable
routing, cable grouping, ambient temperature), the appropriate
correction factors according to IEC 60364-5-52 must be taken
into account.
The SINAMICS Low Voltage Engineering Manual contains additional
information and is available as a PDF file on the CD-ROM
included with Catalog D 11.
Single circuit
Type
rating
Converter Line connection Motor connection Cabinet grounding
SINAMICS G150
Version A
Recommended
crosssection
1)

Maximum
conductor
crosssection
M12
fixing
screw
Recommended
crosssection
1)

Maximum
conductor
crosssection
M12
fixing
screw
M12
fixing
screw
Comment
IEC IEC (Number of
holes)
IEC IEC (Number of
holes)
(Number of
holes)
kW mm2 mm2 mm2 mm2
380 ... 480 V 3 AC
110 6SL3710-1GE32-1AA3 2 x 70 4 x 240 (2) 2 x 50 2 x 150 (2) (2)
132 6SL3710-1GE32-6AA3 2 x 95 4 x 240 (2) 2 x 70 2 x 150 (2) (2)
160 6SL3710-1GE33-1AA3 2 x 120 4 x 240 (2) 2 x 95 2 x 150 (2) (2)
200 6SL3710-1GE33-8AA3 2 x 120 4 x 240 (2) 2 x 95 2 x 150 (2) (2)
250 6SL3710-1GE35-0AA3 2 x 185 4 x 240 (2) 2 x 150 2 x 240 (2) (2)
315 6SL3710-1GE36-1AA3 2 x 240 4 x 240 (2) 2 x 185 4 x 240 (2) (2)
400 6SL3710-1GE37-5AA3 3 x 185 4 x 240 (2) 2 x 240 4 x 240 (2) (10) Cu busbar
450 6SL3710-1GE38-4AA3 4 x 150 8 x 240 (4) 3 x 185 4 x 240 (2) (16) Cu busbar
560 6SL3710-1GE41-0AA3 4 x 185 8 x 240 (4) 4 x 185 6 x 240 (3) (18) Cu busbar
500 ... 600 V 3 AC
110 6SL3710-1GF31-8AA3 120 4 x 240 (2) 95 2 x 150 (2) (2)
132 6SL3710-1GF32-2AA3 2 x 70 4 x 240 (2) 120 2 x 150 (2) (2)
160 6SL3710-1GF32-6AA3 2 x 95 4 x 240 (2) 2 x 70 2 x 185 (2) (2)
200 6SL3710-1GF33-3AA3 2 x 120 4 x 240 (2) 2 x 95 2 x 240 (2) (2)
250 6SL3710-1GF34-1AA3 2 x 185 4 x 240 (2) 2 x 120 4 x 240 (2) (2)
315 6SL3710-1GF34-7AA3 2 x 185 4 x 240 (2) 2 x 150 4 x 240 (2) (2)
400 6SL3710-1GF35-8AA3 2 x 240 4 x 240 (2) 2 x 185 4 x 240 (2) (2)

500 6SL3710-1GF37-4AA3 3 x 185 8 x 240 (4) 2 x 240 6 x 240 (3) (18) Cu busbar
560 6SL3710-1GF38-1AA3 4 x 150 8 x 240 (4) 3 x 185 6 x 240 (3) (18) Cu busbar
660 ... 690 V 3 AC
75 6SL3710-1GH28-5AA3 50 4 x 240 (2) 35 2 x 70 (2) (2)
90 6SL3710-1GH31-0AA3 50 4 x 240 (2) 50 2 x 150 (2) (2)
110 6SL3710-1GH31-2AA3 70 4 x 240 (2) 70 2 x 150 (2) (2)
132 6SL3710-1GH31-5AA3 95 4 x 240 (2) 70 2 x 150 (2) (2)
160 6SL3710-1GH31-8AA3 120 4 x 240 (2) 95 2 x 150 (2) (2)
200 6SL3710-1GH32-2AA3 2 x 70 4 x 240 (2) 120 2 x 150 (2) (2)
250 6SL3710-1GH32-6AA3 2 x 95 4 x 240 (2) 2 x 70 2 x 185 (2) (2)
315 6SL3710-1GH33-3AA3 2 x 120 4 x 240 (2) 2 x 95 2 x 240 (2) (2)
400 6SL3710-1GH34-1AA3 2 x 185 4 x 240 (2) 2 x 120 4 x 240 (2) (2)
450 6SL3710-1GH34-7AA3 2 x 185 4 x 240 (2) 2 x 150 4 x 240 (2) (2)
560 6SL3710-1GH35-8AA3 2 x 240 4 x 240 (2) 2 x 185 4 x 240 (2) (2)
710 6SL3710-1GH37-4AA3 3 x 185 8 x 240 (4) 3 x 150 6 x 240 (3) (18) Cu busbar
800 6SL3710-1GH38-1AA3 4 x 150 8 x 240 (4) 3 x 185 6 x 240 (3) (18) Cu busbar
The recommendations for the North American market in AWG or MCM
must be