230KV TRANSMISSION
LINE BY OTHERS
230KV
SUBSTATION
230KV
SUBSTATION
STATION
CLASS
SURGE
ARRESTORS
1 -EE - MT - M1
58/77.14/86.4MVA
230KV-13.8KV
9%Z 55/65
OA/FA
1 -EE - BD - M1
3750A, 15KV
NON-SEGREGATED
BUS DUCT W.P.
2 -EE - MT - M1
58/77.14/86.4MVA
230KV-13.8KV
9%Z 55/65
OA/FA
1 -EE - BD -G2
3750A, 15KV
NON-SEGREGATED
BUS DUCT
2 -EE - BD -G2
3750A, 15KV
NON-SEGREGATED
BUS DUCT
TRANSFER
CONNECTION
( DURING TA)
G - 101
66MW
G - 101
66MW
1 -EE - SG -3
480V SWITCHGEAR
1 -EE - TX -1A
5000/5600/7000KVA
13.8KV-4.16KV
OA/F.A., 55/65
55% Z
2 -EE - SG -3
480V SWITCHGEAR
220
kVA
48OV
RENTED
DIESEL
GENERATOR
1 -EE - BD -A1
1200A, 5KV, 3
NON-SEGREGATED
BUS DUCT W.P.
TO
TO
1-EE-MCC-A 1-EE-MCC-B
TO
1-EE-MCC-C
TO
TO
2-EE-MCC-A 2-EE-MCC-B
SPARE
1-EE-SG-2 5KV SWITCHGEAR
SPARE
TO
2-EE-MCC-C
2 -EE - TX -1A
5000/5600/7000KVA
13.8KV-4.16KV
OA/F.A., 55/65
55% Z
1 -EE - BD -A1
1200A, 5KV, 3
NON-SEGREGATED
BUS DUCT W.P.
1 -EE - MCC - A
UNIT NO. 1
4160V
CUT-OUT FUSE
480V
750 kVA TX
4160V
2 -EE - MCC - A
UNIT NO. 2
STATION
CLASS
SURGE
ARRESTORS
2 -EE - BD - M1
3750A, 15KV
NON-SEGREGATED
BUS DUCT W.P.