230KV TRANSMISSION

LINE BY OTHERS

230KV TRANSMISSION
LINE BY OTHERS

230KV
SUBSTATION

230KV
SUBSTATION

STATION
CLASS
SURGE
ARRESTORS

1 -EE - MT - M1
58/77.14/86.4MVA
230KV-13.8KV
9%Z 55/65
OA/FA
1 -EE - BD - M1
3750A, 15KV
NON-SEGREGATED
BUS DUCT W.P.

2 -EE - SG1 15KV SWITCHGEAR

1 -EE - SG1 15KV SWITCHGEAR

2 -EE - MT - M1
58/77.14/86.4MVA
230KV-13.8KV
9%Z 55/65
OA/FA

1 -EE - BD -G2
3750A, 15KV
NON-SEGREGATED
BUS DUCT

2 -EE - BD -G2
3750A, 15KV
NON-SEGREGATED
BUS DUCT
TRANSFER
CONNECTION
( DURING TA)

G - 101
66MW

G - 101
66MW

1 -EE - SG -3
480V SWITCHGEAR

1 -EE - TX -1A
5000/5600/7000KVA
13.8KV-4.16KV
OA/F.A., 55/65
55% Z

2 -EE - SG -3
480V SWITCHGEAR

220
kVA

48OV
RENTED
DIESEL
GENERATOR
1 -EE - BD -A1
1200A, 5KV, 3
NON-SEGREGATED
BUS DUCT W.P.

TO
TO
1-EE-MCC-A 1-EE-MCC-B

TO
1-EE-MCC-C

TO
TO
2-EE-MCC-A 2-EE-MCC-B

SPARE
1-EE-SG-2 5KV SWITCHGEAR

SPARE

TO
2-EE-MCC-C

2 -EE - TX -1A
5000/5600/7000KVA
13.8KV-4.16KV
OA/F.A., 55/65
55% Z

1 -EE - BD -A1
1200A, 5KV, 3
NON-SEGREGATED
BUS DUCT W.P.

2-EE-SG-2 5KV SWITCHGEAR

1000 A CKT. BKR


PLANT A
UNITS NO. 1 AND NO. 2
TIE CIRCUIT BREAKER

1 -EE - MCC - A

UNIT NO. 1

4160V
CUT-OUT FUSE

480V
750 kVA TX
4160V
2 -EE - MCC - A

UNIT NO. 2

STATION
CLASS
SURGE
ARRESTORS

2 -EE - BD - M1
3750A, 15KV
NON-SEGREGATED
BUS DUCT W.P.