Purpose
To provide a reliable efficient &
flexible interconnection between
the WAPDA & the station's main
Generator to feed the power to
WAPDA & station auxiliary power
system.
System Equipments
M M
System
D9Q1
B D8Q1
B
BUS 1
D10Q11
M D9Q11 M D8Q11 M M M
D7Q11 D6Q11
D10Q1
B
BUS 2 M
Generator GSU
D7Q1
B
G UAT
SUT
Excitation
BCA16
B BBA22
B
BBA12
B
Protection Philosophy
Relay Back-Up
Breaker Back-Up
Generator Protection
Purpose
The purpose of the system is to
provides 11Kv,3Ph,50Hz power
for unit auxiliary
equipment as well as common
start-up and emergency
shutdown operations
System Equipments
UAT
BCA16
Main Generator BBA22 BBA12
11Kv Unit Switchgear-A 11Kv Unit Switchgear-B
500KVA- 500KVA-
11Kv/6.6Kv 11Kv/6.6Kv
ATS-Secondary
ATS-Bypass
Diesel
ATS-Primary
Generator
Emergency
Services Bus
M M
11Kv Unit Switchgear-C 11Kv Unit Switchgear-D
M M
Motor Type Motor Type
M M
Motor Type Motor Type
Water Treatment MCC-A Cooling Tower MCC-A Cooling Tower MCC-B Water Treatment MCC-B
11Kv Switchgear Protections
Purpose
The DC power system supplies
a reliable source of DC
electrical power to those plant
loads required to function on
loss of AC power
Plant DC System
DC power system consists of two 220v
plant battery banks
Each bank consists of 110 battery cells
Each cell rated at 2.25v per cell
Each battery bank has a total rating of
3400 amp hours
Plant DC system is ungrounded
Fully equalize charge voltage is 256.3v
Float voltages maximum 238.7 volts
Plant DC System Cont.
Bypass Secondary
Emergency
ATS
CTTS-A CTTS-B
1200 A 600 A
Purpose
The UPS system provides a reliable,
regulated, filtered & uninterrupted
110V, 50Hz, single phase AC electrical
power to essential plant auxiliary &
low voltage load & control system. In
addition, it provides for a safe unit
shutdown in the event of a unit power
system blackout.
UPS System
General System Descriptions
UPS system is a 75KVA single phase
system
220v DC normal input,220v, 50Hz
bypass input & 110v, 50Hz output
UPS system consists of two full function
UPS (Primary & secondary)
A bypass regulating transformer is
provided as an alternate power source
Cascade operation mode
Individual UPS operation mode
DC Input 230v
UPS SYSTEM
Inverter
Circuit Breaker
Fuse Fuse
Diode AC
Output
110v
Static switch
50Hz
Primary UPS 75KVA
B2
B1
B3
DC Input 230v
Static switch
Standby UPS
B2
AC Input 220v 50Hz
B1
B3
Regulator
UPS System Cont,
Operation , Controls & Alarms
Alternate source synchronizes with the
Secondary inverter
Secondary inverter synchronizes with
the primary inverter
Two static switches one in primary UPS
& one in secondary UPS
Static switch will automatically transfer
the load to alternate source in a fraction
of a cycle should the inverter voltage
drop below a preset level
DC filter charge switch
UPS System Cont,
Operation , Controls & Alarms
Synch Monitor
DC Fail Alarm
On Alternate
Alternate Source Fail Alarm
Synch Disconnect Alarm
Over Temp Alarm
Output Under Freq/Over Freq
Maintenance Bypass Switch
UPS System Cont,
UPS System Cont,