HW-DC-373-4044-512
BHEL Doc. No. 4044-0512
Rev 01, Dtd.08/03/2012
TECHNICAL DATA SHEET
Customer : The West Bengal Power Development Corporation Limited
Project : SAGARDIGHI THERMAL POWER EXTENSION PROJECT
PHASE-II, UNITS – 3 & 4[2 X 500 MW SUB-CRITICAL ]
MVA 588
2.02.00 Maximum continuous rating (M.C.R.) MW 500
MVA 588
2.03.00 Rated power factor --- 0.85 (lagging)
2.04.00 Rated terminal voltage KV 21.0
2.05.00 Rated stator current Amps. 16166
2.06.00 I. Phase Nos. 3
II. Phase Connection Double Star
III. Direction of Rotation when viewed Anticlockwise
from Turbine end
IV. Negative Sequence Current 8%
Capability
2.07.00 Rated frequency Hz. 50
2.08.00 Excitation at rated output and power
factor
a) Voltage Volts 340
b) Current Amps 4040
2.09.00 a) Short circuit ratio at (S.C.R) rated -- Not less than 0.48
6* 20.03.2012
output S.M.
b) Permissible (+
_) Tolerance in S.C.R. % + 30%, -0%
3.000.0 Performance *
3.01.00 Efficiency at
3.01.01 100% load % 98.65
3.01.02 75% load % 98.64
3.01.03 50% load % 98.43
3.01.04 25% load % 97.47
3.02.00 Regulation at rated output, speed and
voltage.
3.02.01 0.85 power factor lag % 33.8
3.02.02 Unity power factor % 26.0
3.02.03 0.85 power factor lead % 18.0
3.03.00 At generator rated output, rated speed
& power factor, the permissible
variation in
3.03.01 Terminal voltage % +5%
3.03.02 Frequency % - 5 % to + 3 %
3.03.03 Absolute sum of combined voltage and % 5%
frequency variation
3.04.00 Voltage rise during sudden rejection of
full load at rated power factor
a) With A.V.R % 15%
b) Without A.V.R % 33.8 %
3.05.00 Generator reactive capability
3.05.01 Maximum inductive loading (zero lag) MVAR 432
3.05.02 Maximum capacitive loading (zero lead) MVAR 250
3.05.03 Capacitive loading at rated load and MVAR 160
voltage, (Rated Power Factor)
3.06.00 Permissible unbalanced loading subject
to current not being exceeded the rated
current in any phase
3.06.01 Maximum continuous negative sequence % 8
current-I2
3.06.02 Maximum value of I22t for transient operation --- 10
under system fault (I2 in P.U. and t
in secs.)
3.07.00 Generator asynchronous operation
3.07.01 Permissible load % f.l Refer Curve No.
TG:THDF:500:28
3.07.02 Duration Min. Refer Curve No.
TG:THDF:500:28
3.08.00 Short circuit withstand
3.08.01 3-phase terminal fault
i) Current KA 24.6 (Steady state value)
ii) Duration Secs 3
3.08.02 Stator ground fault (For Core)
i) Current (Steady State) Amps 15
ii) Duration Secs 1
3.09.00 Overload performance
3.09.01 Stator current % f. l. 150
3.09.02 Time Secs 30
3.10.00 Generator pull out power at rated voltage MW 782
3.11.00 Maximum continuous generator capability MVA 392
under one H2 cooler out of operation
3.12.00 Generator Capability on variation of coolant Refer curve No.
pressure TG:THDF115/59-085
3.13.00 Minimum H2 gas pressure and Bar, MW 2.5 Bar(g), 470 MW
corresponding MW
4.00.00 Temperatures
4.01.00 Ambient temperature
4.01.01 Cooling water at inlet to heat exchanger Deg.C 39
4.01.02 Ambient air Deg.C NA
4.02.00 Coolant temperatures
4.02.01 Cooled H2 gas Deg.C 45
4.02.02 Hot H2 gas Deg.C 75 (Max.)
4.02.03 Stator Water Inlet Deg.C 50
4.02.04 Stator Water Outlet Deg.C 90
4.03.00 Guaranteed Temp. rise over specified
ambient
4.03.01 Stator winding Deg.C As per IEC
4.03.02 Stator core
i) In contact with insulated winding Deg.C As per IEC
ii) Not in contact with insulated winding Deg.C As per IEC
4.03.03 Rotor winding Deg.C As per IEC
4.03.04 Collector rings, if any Deg.C NA
5.00.00 Miscellaneous Parameters
Prepared By Asha Gupta
Approved By S D Nagar
Customer’s Doc. No. HW-DC-373-4044-512
BHEL Doc. No. 4044-0512
Rev 01, Dtd.08/03/2012
TECHNICAL DATA SHEET
Customer : The West Bengal Power Development Corporation Limited
Project : SAGARDIGHI THERMAL POWER EXTENSION PROJECT
PHASE-II, UNITS – 3 & 4[2 X 500 MW SUB-CRITICAL ]
curves
17.07.00 Open and short circuit characteristics --- TG-THDF-500-072
17.08.00 Heat load curves for hydrogen and seal oil TG:THDF:500:45
18.00.00 Drawings
18.01.00 Turbine and Generator General Refer Drawing No.
arrangement drawing enclosed with full 01390001399
dimensions, also showing
18.01.01 Condensor, CW inlet and outlet Refer Drawing No.
01390001399
18.01.02 Generator Rotor Withdrawl Space Refer Drawing No.
I. Straight 01390001399
II. Skewed
18.01.03 Generator Terminal Boxes Refer Drawing No.
I. Phase 01390001399
II. Neutral
19.00.00 Additional Data
19.01.00 Furnish Details of Generator Protection Refer Enclosed Write-up No.
4033 0010
19.02.01 Is it necessary to provide any surge --- Recommended
capacitor ?
19.02.02 If so, state the reasons and requirement To protect the transformer
--- against over-voltages when
the generator is isolated from
the transformer
19.03.00 Furnish the description of standard practice Data shall be furnished
in coordinating connection of isolated phase separately by Bus-Duct
bus duct to generator main leads. supplier.
19.04.00 Furnish detailed literature for the excitation Shall be furnished separately
system alongwith AVR by EDN, BHEL, Bangalore.
20.00.00 All shop tests to be carried out as -- Yes, As per QP
specified
40
14
30
13
PERMISSIBLE SHORT TIME
OPERATION (IN MINUTES) WITH
20
RATED MVA AT RATED PF WITH 12
10 % VOLTAGE DEVIATION
10
11
10
7
VOLTAGE DEVIATION (%)
2
1 MIN 2 5 10
1
0
-12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5
-1
90 95 99 100%
-5
t
<1)0.1 -
~
:I:
0
-
0
<..!)w
z'<r
0-3
z~
-u
3-3
«
c::u
"
,- 0
()::
~
LL
~
.g"""'0.O9
~ u
z
«
I-
(.f)
(.f)
w
Ct:
0.08
..
0-07
"
0-06
0
0 20 40 60 80 100 120 C
TEMPERATURE I
TGE-500-0082
OVERLOAD CAPABILITY
2.4
2.2
1. ARMATURE WINDING SHORT TIME THERMAL
1 REQUIREMENTS (STATOR CURRENT VS TIME)
1.8
1.6
2
FIELD
1.4
1.2
1
1 10 100 1000
TIME IN SEC
T-~
t-J
t~
at-
~
,..
" . a>
" '
I.f) Q)
:J
a
:J
~
Z t0o-
I a
u
I.D ;:
~,.
; !."
I .
~
, .
,,;-c- ,. ~.
-' '\. ~
,,"
~ \
.,
,
"
,. .
~
"\ N
a
9 0..1 2 t':' a
.-0.. a
.
."
..
TG~ THDF: 5QOj28
UNLOADING SCHEDULE
(GENERATOR TYPE : THDF 115/59)
(588 MVA, 500 MW, 21 KV, 50 HZ, 0.85 P.F.)
1.2
0.8
1.0 P.U. = 500 MW
LOAD (P.U.)
0.6
0.4
0.2
0
40 42 44 46 48 50 52 54
COLD GAS TEMPERATURE (DEG C)