220KV LINE-1 PROTECTION

CUSTOMER : POWERGRID 400/220kV DALTONGANJ S/S


PROJECT :POWERGRID DALTONGANJ
P.O. NO.: LOA/5427PK067/ PCP/ 01
DATED: 23.03.12
SALES ORDER NO.: 3269020733
ENGG. REF. NO.: KR87
ENGINEER : MB
LIST OF DOCUMENTS SUBMITTED
S.NO. DESCRIPTION DRAWING NO. ISSUE

1 GA Drawing - Panel Type P2A CPG KR87 P2A (F) Z-29.08.2013


2 GA Drawing - Panel Type P2A CPG KR87 P2A (R) Z-29.08.2013
3 Legend - Panel Type P2A CPG KR87 P2A (L) Z-29.08.2013
4 GA Drawing - Panel Type P2B CPG KR87 P2B (F) Z-29.08.2013
5 GA Drawing - Panel Type P2B CPG KR87 P2B (R) Z-29.08.2013
6 Legend - Panel Type P2B CPG KR87 P2B (L) Z-29.08.2013
7 Schematic Drawing CPD KR87 SC12 Z-29.08.2013
8 Equipment wise schedule ER87 P2A Z-29.08.2013
9 Wire wise schedule WR87 P2A Z-29.08.2013
10 Equipment wise schedule ER87 P2B Z-29.08.2013
11 Wire wise schedule WR87 P2B Z-29.08.2013
DEV REF. MATERIAL NAME MAKE DESCRIPTION

195B MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY - TC-1 B PHASE


1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
195R MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY -TC-1 R PHASE
1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
195Y MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY -TC-1 Y PHASE
1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
21M1 P444316J6M0550K ALSTOM NUMERICAL DIST PROTN RELAY TYPE MICOM P444,110-250V DC/100-240V AC,CT-1&5A;24I/P;46O/P;CHK
SYNC;IEC61850 - MAIN1
80DC1 MVAAM11B1CJ1015A ALSTOM DC SUPPLY SUPERVISION RELAY - DC SOURCE-1 FAIL
4B SR : FLAG-REV : 220-250V DC : 80-120 mS TDDO WD:Z1MVAAM11009SHT1
86A MVAJ205LA1002A ALSTOM HIGH SPEED TRIPPING RELAY - GROUP A
HI/LO BURDEN : FLAG-YES : 220/250V DC : 18M 2B HR WD:01 MVAJ 205 01
86LO MVAJ105JA1002A ALSTOM HIGH SPEED TRIPPING RELAY A/R LOCKOUT RELAY
220-250V DC: ELECTRICAL/HAND RESET: 8M + 2B CONTACT CONFIG: CASE SIZE:2
BCU EC264-G0293 ALSTOM BAY CONTROL UNIT - C264
BLKA MPGTESTBLOCK ALSTOM TEST BLOCK - 21M1
STANDARD TEST BLOCK
BLKB MPGTESTBLOCK ALSTOM TEST BLOCK - 21M1
STANDARD TEST BLOCK
BLKF MPGFQ0001-007 ALSTOM MPG TEST BLOCK WITHOUT TRIP ISOLATION IN WAY-2 - BCU
WD:MPGFQ0001-007
COX1 MVAAM11B1BA2530A ALSTOM AUXILIARY RELAY - CARRIER HEALTHY CH-1
2M 2C FLAG YES 110-125/220-250V DC WD:Z1MVAAM11001
CSS1 S08N90SPPM102 ALSTOM SELECTOR SWITCH - "CARRIER" IN-OUT - CH-1
SELECTOR SWITCH 8 WAY NON-LOCK STAYPUT
RX1 MVAAM11B1BA2530A ALSTOM AUXILIARY RELAY - DIRECT TRIP RECEIVED CH-1
2M 2C FLAG YES 110-125/220-250V DC WD:Z1MVAAM11001
TTX1 GBMVAJM14JB1002A ALSTOM CONTROL RELAY E / R LOW BURDEN - TRIP TRANSFER CONTACT MULTIPLICATION
8 NO, 2NC ER; FOLLOW ON FLAG 220 TO 250 V DC WITHOUT CT SHORT WD:01 MVAJM14 011
TTX2 GBMVAJM14JB1002A ALSTOM CONTROL RELAY E / R LOW BURDEN - TRIP TRANSFER CONTACT MULTIPLICATION
8 NO, 2NC ER; FOLLOW ON FLAG 220 TO 250 V DC WITHOUT CT SHORT WD:01 MVAJM14 011

SCHEME REF: ENGG.REF.NO: KR87 CUSTOMER: POWER GRID CORPORATION OF INDIA LTD. LEGEND TO GA DRAWING PREPARED BY: MB REVISION: Z

NETWORK NO.: . PROJECT: POWERGRID 400/220kV DALTONGANJ S/S PANEL TYPE: P2A FILE: KR87P2A CHECKED BY: JKK DATE: 29.08.2013

FINISHED GOOD: . P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: NIL
Dated 23.03.12
SALES ORDER-ITEM: 3269020733 PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KR87 P2A (L) SHT 1 OF 2
DEV REF. MATERIAL NAME MAKE DESCRIPTION

TTX3 GBMVAJM14JB1002A ALSTOM CONTROL RELAY E / R LOW BURDEN - TRIP TRANSFER CONTACT MULTIPLICATION
8 NO, 2NC ER; FOLLOW ON FLAG 220 TO 250 V DC WITHOUT CT SHORT WD:01 MVAJM14 011
TTX4 GBMVAJM14JB1002A ALSTOM CONTROL RELAY E / R LOW BURDEN - TRIP TRANSFER CONTACT MULTIPLICATION
8 NO, 2NC ER; FOLLOW ON FLAG 220 TO 250 V DC WITHOUT CT SHORT WD:01 MVAJM14 011
52CS S22N120SRL2PM108 ALSTOM SELECTOR SWITCH
CONTROL SWITCH 22 WAY NON-LOCK SPRING RETURN WITH LOST MOTION DEVICE
LIU-14 GBSAS06PRLIUSTC REPUTED LINE INTERFACE UNIT

INTERNALLY MOUNTED EQUIPMENTS

CIL GBCPE0000600 IMTECH CUBICLE ILLUMINATION LAMP


HS GBCPF0500901 SWITRON HEATER SWITCH
HT GBCPA0178101 SOFIA 230V,60 WATTS HEATER
PS GBCPE0000344 ANCHOR 15/5A SOCKET 3 PIN 240V AC
R1 MZB9015006 RESISTOR 3.3K
TH GBCPE0000612 APT THERMOSTAT

SCHEME REF: ENGG.REF.NO: KR87 CUSTOMER: POWER GRID CORPORATION OF INDIA LTD. LEGEND TO GA DRAWING PREPARED BY: MB REVISION: Z

NETWORK NO.: . PROJECT: POWERGRID 400/220kV DALTONGANJ S/S PANEL TYPE: P2A FILE: KR87P2A CHECKED BY: JKK DATE: 29.08.2013

FINISHED GOOD: . P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: NIL
Dated 23.03.12
SALES ORDER-ITEM: 3269020733 PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KR87 P2A (L) SHT 2 OF 2
DEV REF. MATERIAL NAME MAKE DESCRIPTION

21M2 YN1M251400PA ABB REL670 VAR-2 DIST PROTN; VAUX=90-250V DC; TRAFO MODULE TRM 6I+6U 1A,110/220V AC,50/60HZ;16 I/P , 48
O/P;SERIAL COMM;OPTICAL ETHERNET MODULE;IEC61850-8-1;1 CHANNEL;GLASS SLOT X311
295B MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY - TC-2 B PHASE
1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
295R MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY - TC-2 R PHASE
1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
295Y MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY -TC-2 Y PHASE
1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
80CO MVAAM11B1BA2530A ALSTOM AUXILIARY RELAY - BCU DC CHANGEOVER
2M 2C FLAG YES 110-125/220-250V DC WD:Z1MVAAM11001
80DC2 MVAAM11B1CJ1015A ALSTOM DC SUPPLY SUPERVISION RELAY - DC SOURCE-2 FAIL
4B SR : FLAG-REV : 220-250V DC : 80-120 mS TDDO WD:Z1MVAAM11009SHT1
86B MVAJ205LA1002A ALSTOM HIGH SPEED TRIPPING RELAY - GROUP B
HI/LO BURDEN : FLAG-YES : 220/250V DC : 18M 2B HR WD:01 MVAJ 205 01
BLKC MPGTESTBLOCK ALSTOM TEST BLOCK - 21M2
STANDARD TEST BLOCK
BLKD MPGTESTBLOCK ALSTOM TEST BLOCK - 21M2
STANDARD TEST BLOCK
BLKE MPGTESTBLOCK ALSTOM TEST BLOCK - PU
STANDARD TEST BLOCK
COX2 MVAAM11B1BA2530A ALSTOM AUXILIARY RELAY - CARRIER HEALTHY CH-2
2M 2C FLAG YES 110-125/220-250V DC WD:Z1MVAAM11001
CSS2 S08N90SPPM102 ALSTOM SELECTOR SWITCH - "CARRIER" IN-OUT - CH-2
SELECTOR SWITCH 8 WAY NON-LOCK STAYPUT
PU P743316A6M0510K ALSTOM INTEGRATED BUSBAR PROTN-PERIPHERAL UNIT,110-250V DC WITH 1/5A CT INPUT; IEC61850 PROTOCOL ETHERNET
100MPBS
RX2 MVAAM11B1BA2530A ALSTOM AUXILIARY RELAY - DIRECT TRIP RECEIVED CH-2
2M 2C FLAG YES 110-125/220-250V DC WD:Z1MVAAM11001
TTB CTB4000002 DAV DAV MAKE TEST TERMINAL BLOCK 3PH 4 WIRE - EM

SCHEME REF: ENGG.REF.NO: KR87 CUSTOMER: POWER GRID CORPORATION OF INDIA LTD. LEGEND TO GA DRAWING PREPARED BY: MB REVISION: Z

NETWORK NO.: . PROJECT: POWERGRID 400/220kV DALTONGANJ S/S PANEL TYPE: P2B FILE: KR87P2B CHECKED BY: JKK DATE: 29.08.2013

FINISHED GOOD: . P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: NIL
Dated 23.03.12
SALES ORDER-ITEM: 3269020733 PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KR87 P2B (L) SHT 1 OF 2
DEV REF. MATERIAL NAME MAKE DESCRIPTION

INTERNALLY MOUNTED EQUIPMENTS

CIL GBCPE0000600 IMTECH CUBICLE ILLUMINATION LAMP


HS GBCPF0500901 SWITRON HEATER SWITCH
HT GBCPA0178101 SOFIA 230V,60 WATTS HEATER
PS GBCPE0000344 ANCHOR 15/5A SOCKET 3 PIN 240V AC
R2 MZB9015006 RESISTOR 3.3K
TH GBCPE0000612 APT THERMOSTAT

SCHEME REF: ENGG.REF.NO: KR87 CUSTOMER: POWER GRID CORPORATION OF INDIA LTD. LEGEND TO GA DRAWING PREPARED BY: MB REVISION: Z

NETWORK NO.: . PROJECT: POWERGRID 400/220kV DALTONGANJ S/S PANEL TYPE: P2B FILE: KR87P2B CHECKED BY: JKK DATE: 29.08.2013

FINISHED GOOD: . P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: NIL
Dated 23.03.12
SALES ORDER-ITEM: 3269020733 PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KR87 P2B (L) SHT 2 OF 2
SCHEMATIC DRAWING
220KV LINE-1 PROTECTION
PANEL TYPES: P2A P2B

1 LIST OF SYMBOLS 34 BLANK SHEET 67 MAKE SPECIFIC ISOLATOR (202-89B) TERMINALS


2 SINGLE LINE DIAGAM 35 SWITCH CONTACT DISTRIBUTION 68 MAKE SPECIFIC ISOLATOR (202-89B) TERMINALS
3 TRIP LOGIC MATRIX 36 TBC BREAKER (TRIP) CONTACT DISTRIBUTION 69 MAKE SPECIFIC ISOLATOR (202-89C) TERMINALS
4 AUTORECLOSE LOGIC 37 TBC BREAKER (A/R) CONTACT DISTRIBUTION 70 MAKE SPECIFIC ISOLATOR (202-89C) TERMINALS
5 AC DISTRIBUTION 38 TBC BREAKER (LBB) CONTACT DISTRIBUTION 71 MAKE SPECIFIC ISOLATOR (202-89C) TERMINALS
6 DC DISTRIBUTION 39 PROTECTION TRANSFER RELAYS CONTACTS 72 MAKE SPECIFIC ISOLATOR (202-89T) TERMINALS
7 DC SUPERVISION 40 BUS BAR PROTN - AC CKT 73 MAKE SPECIFIC ISOLATOR (202-89T) TERMINALS
8 LINE VT CIRCUIT - 220KV 41 BUS BAR PROTN - OPTO CKT 74 MAKE SPECIFIC ISOLATOR (202-89T) TERMINALS
9 ENERGY METER CIRCUIT 42 BUS BAR PROTN - OUTPUT RELAYS CKT 75 MAKE SPECIFIC EARTH SWITCH(202-89AE) TERMINALS
10 DISTANCE PROTN.(MAIN-1) - AC CIRCUIT 43 BCU INTERLOCK LOGIC CKT 76 MAKE SPECIFIC EARTH SWITCH(202-89AE) TERMINALS
11 DISTANCE PROTN.(MAIN-1) - DC/OPTO I/P CIRCUIT 44 BCU INTERLOCK LOGIC CKT 77 MAKE SPECIFIC EARTH SWITCH(202-89CE1) TERMINALS
12 DISTANCE PROTN.(MAIN-1) - DC/OPTO I/P CIRCUIT 45 BCU INTERLOCK LOGIC CKT 78 MAKE SPECIFIC EARTH SWITCH(202-89CE1) TERMINALS
13 DISTANCE PROTN.(MAIN-1) - OUTPUT RELAY CONTACTS 46 BLANK SHEET 79 MAKE SPECIFIC EARTH SWITCH(202-89CE2) TERMINALS
14 DISTANCE PROTN.(MAIN-1) - OUTPUT RELAY CONTACTS 47 BLANK SHEET 80 MAKE SPECIFIC EARTH SWITCH(202-89CE2) TERMINALS
15 DISTANCE PROTN.(MAIN-1) - I/O & LED CONFIGURATION 48 BCU CARD DETAILS 81 MAKE SPECIFIC PLCC TERMINALS
16 DISTANCE PROTN.(MAIN-1) - CARRIER 49 BCU CT/PT & AUX SUPPLY CKT 82 STANDARD DRAWING REFERENCE
17 DISTANCE PROTN.(MAIN-2) - AC CIRCUIT 50 BCU - DIGITAL INPUT CKT
18 DISTANCE PROTN.(MAIN-2) - DC OPTO I/P CIRCUIT 51 BCU - DIGITAL INPUT CKT
19 DISTANCE PROTN.(MAIN-2) - OUTPUT RELAY CONTACTS 52 BLANK SHEET
20 DISTANCE PROTN.(MAIN-2) - OUTPUT RELAY CONTACTS 53 BLANK SHEET
21 DISTANCE PROTN.(MAIN-2) - I/O & LED CONFIGURATION 54 BLANK SHEET
22 DISTANCE PROTN.MAIN-2 CARRIER AUX. CKT. 55 BCU - DIGITAL OUTPUT CKT
23 AUTORECLOSE LOCKOUT RELAY 56 BCU - DIGITAL OUTPUT CKT
24 BLANK SHEET 57 MAKE SPECIFIC CB (202-52) TERMINALS
25 DIRECT TRIP COMMAND RECEIVE CIRCUIT 58 MAKE SPECIFIC CB (202-52) TERMINALS
26 DIRECT TRIP SEND CIRCUIT (CH-1) 59 MAKE SPECIFIC CB (202-52) TERMINALS
27 DIRECT TRIP SEND CIRCUIT (CH-2) 60 MAKE SPECIFIC CB (202-52) TERMINALS
28 TRIP RELAY CIRCUIT - GROUP-A 61 MAKE SPECIFIC CB (202-52) TERMINALS
29 TRIP RELAY CIRCUIT - GROUP-B 62 MAKE SPECIFIC CB (202-52) TERMINALS
30 CIRCUIT BREAKER CONTROL CKT. (TC-1) 63 MAKE SPECIFIC ISOLATOR (202-89A) TERMINALS
31 CIRCUIT BREAKER CONTROL CKT. (TC-2) 64 MAKE SPECIFIC ISOLATOR (202-89A) TERMINALS
32 ISOLATOR / EARTH SWITCH CKT 65 MAKE SPECIFIC ISOLATOR (202-89A) TERMINALS
33 ISOLATOR / EARTH SWITCH CKT 66 MAKE SPECIFIC ISOLATOR (202-89B) TERMINALS

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871200
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 LIST OF DRAWINGS DRG. NO.: CPD KR87 SC12 SHT 00 OF 82
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION

RELAY COIL - DS
CUB.ILLUMN.LAMP WITH D/S
MAKE CONTACT GENERAL SYMBOL
FERRULE NUMBERING STANDARDS
MAKE CONTACT -
DELAYED PICKUP RELAY COIL - HEATER
FERRULE - "A" : CT CIRCUIT - MAIN PROTECTION
MAKE CONTACT - SLOW RELEASING
DELAYED DROP OFF
FERRULE - "B" : CT CIRCUIT - BUSBAR PROTECTION
MAKE CONTACT WITH RELAY COIL - HEATER SWITCH
BLOWOUT MAGNET
SLOW OPERATING FERRULE - "C" : CT CIRCUIT - BACKUP PROTECTION
MAKE CONTACT - POWER SOCKET
HAND RESET
FERRULE - "D" : CT CIRCUIT - METERING
MAKE CONTACT - THERMOSTAT
THYRISTOR FLASHER RELAY FERRULE - "E" : VT CIRCUIT - PROTECTION/METERING
FUSE
FERRULE - "G" : VT CIRCUIT - SYNCHRONISING
BREAK CONTACT
RELAY COIL - LINK

HAND RESET
FERRULE - "H" : AUXILIARY AC CIRCUIT
TEST BLOCK - MPG
BREAK CONTACT -
RESISTOR FERRULE - "J" : AUXILIARY DC CIRCUIT
DELAYED PICKUP

BREAK CONTACT - FLAG INDICATOR FERRULE - "K" : CONTROL CIRCUITS


STABILISING RESISTOR
DELAYED DROP OFF
FERRULE - "L" : INDICATION & ALARM CIRCUITS
BREAK CONTACT WITH DISCONNECTING METROSIL SURGE DIVERTOR
BLOWOUT MAGNET TB AT C&R PANLES FERRULE - "P" : DC CIRCUIT - BUSBAR PROTECTION CIRCUITS
BREAK CONTACT - TERMINAL BOARD
HAND RESET
CONTROL/SEL SW.-TYPE ODS
AT C&R PANLES
TERMINAL BOARD FERRULE - "S" : EVENT LOGGER/DAS/SCADA CIRCUITS
AT CT/VT KIOSK /PLCC PANEL INDICATING LAMP
FERRULE - "U" : SPARE CONTACTS
TERMINAL BOARD
CHANGE OVER CONTACT SEMAPHORE INDICATOR
AT CIRCUIT BREAKER

CHANGE OVER CONTACT - TERMINAL BOARD ELECTRIC BELL


HAND RESET AT BAY MASHALLING KIOSK

CHANGE OVER CONTACT - TERMINAL BOARD


ELECTRIC HOOTER
DELAYED PICKUP AT ISOLATOR TERMINAL BLOCK NO
TB1
CCC WIRE NO
1
CHANGE OVER CONTACT - WAY NO
DELAYED DROP OFF BUSWIRE PANEL TYPE

NOTE:-
WIRE CROSS REFERENCE STANDARDS
1. SCHEMATIC SYMBOLS GENERALLY COMPLY WITH IEC STANDARDS.
L101 FERRULE NO
2. RELAY CONTACTS SHOWN WITH COIL DE-ENERGISED CONDITION. 20 SHEET NO
3.
SHT NO. REPRESENTATION OF CROSS REFRENCES BETWEEN SHEETS.
FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z
SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871201
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 LIST OF SYMBOLS DRG. NO.: CPD KR87 SC12 SHT 01 OF 82
220KV MAIN BUS-1

BASE FILE:
220KV MAIN BUS-2

FOR ALSTOM REF:


SCHEME TYPE: LINE
202-89A 202-89B

SALES ORDER: 3269020733


202-89AE

ENGG.REF.NO.: KR87
202-52

202-89LE2

Dated 23.03.12
202-89L

P.O.NO.: LOA/5427PK067/ PCP/ 01


202-89LE1

PROJECT: POWERGRID 400/220kV DALTONGANJ S/S


202-89T

220KV TRANSFER BUS

CUSTOMER: POWERGRID CORPORATION OF INDIA LTD


202-CT
P2
CORE-5
RATIO : 1600-800/1A

ALSTOM T&D India


CLASS : PS
Vk=1600-800V MAIN-1 PROTN. CKT. 10
Imag < 50-25mA AT Vk/4
Rct = 8-4 Ohms

CORE-4
RATIO : 1600-800/1A

ABCD
CLASS : PS
MAIN-2 PROTN. CKT. 17

PALLAVARAM CHENNAI 600043


Vk=1600-800V
Imag < 50-25mA AT Vk/4
Rct = 8-4 Ohms

CORE-3

- Limited - AUTOMATION SAS


RATIO : 1600-800/1A
CL:0.2S,IFS<5 METERING CKT 09
BURDEN :20VA

CORE-2
RATIO : 1600-800/1A
CLASS : PS
Vk=1600-800V SPARE
Imag < 50-25mA AT Vk/4
Rct = 8-4 Ohms
PANEL TYPES: P2A, P2B

CORE-1
SCHEMATIC DRAWING

RATIO : 1600-800/1A
SINGLE LINE DIAGAM

CLASS : PS BUSBAR PROTECTION(MAIN)


Vk=1600-800V
Imag < 50-25mA AT Vk/4
TITLE: 220KV LINE-1 PROTECTION

Rct = 8-4 Ohms 40


P1

202-WT
202-CVT
FILE: DR871202

MAIN-1 PROTN. CKT. 10


PREPARED BY:

MAIN-2 PROTN. CKT. 17


MB
CHECKED BY: JKK
APPROVED BY: SSS

METERING CKT. 09

202LA
SCALE:
REVISION:

--
Z

LINE
DATE: 29.08.2013

DRG. NO.: CPD KR87 SC12 SHT 02 OF 82


MAIN BREAKER (NORMAL MODE) TBC BREAKER (TRANSFER MODE)

CARRIER SEND CHANNEL-1

CARRIER SEND CHANNEL-2


3PH MASTER TRIP RELAY
3PH MASTER TRIP RELAY
BLOCK AUTO RECLOSE

BLOCK AUTO RECLOSE

BUSBAR PROTECTION
TO CB TRIP COIL-2

TO CB TRIP COIL-1
TO CB TRIP COIL-1

TO CB TRIP COIL-2

DIRECT TRIP SEND


DIRECT TRIP SEND
CLOSE MAIN CB
AUTO RECLOSE
AUTO RECLOSE

AUTO RECLOSE
LBB INITIATION

LBB INITIATION
AUTO RECLOSE

CLOSE TBC CB
PROTECTION FUNCTION REMARK

CHANNEL-2
CHANNEL-1

DR TRIGGER
ANSI CODE

INITIATION
INITIATION

LOCKOUT

LOCKOUT

GROUP-A

GROUP-B
OUT PUT
3PH AUTO RECLOSE INITIATION
DISTANCE PROTECTION ZONE-1-MAIN1 21 1/3Ph TP TP IP IP TP TP IP IP TP TP IP
ONLY WHEN 3PH A/R IS ENABLED

DIRECTIONAL EARTH FAULT -MAIN 1 67N 3 Ph IP IP TP TP IP BUILT IN MAIN 1 RELAY

DISTANCE PROTECTION Z2,Z3 FAULTS,(SOTF) 3 Ph TP TP IP TP TP IP IP IP IP BUILT IN MAIN 1 RELAY

3PH AUTO RECLOSE INITIATION


DISTANCE PROTECTION TRIP ZONE-1 -MAIN 2 21 1 Ph TP TP IP IP TP TP IP IP TP TP IP ONLY WHEN 3PH A/R IS ENABLED

DIRECTIONAL EARTH FAULT -MAIN 2 67N 3 Ph IP IP TP TP IP BUILT IN MAIN 2 RELAY

DISTANCE PROTECTION Z2,Z3 FAULTS,(SOTF, 50 3 Ph TP TP IP TP TP IP IP IP IP BUILT IN MAIN 2 RELAY


MAIN 2
BREAKER FAIL PROTECTION MAIN TP TP IP BUILT IN MAIN BUS BAR PROTECTION
50BF 3 Ph IP TP TP IP
(NORMAL POSITION)
BREAKER FAIL PROTECTION TBC 3 Ph TP TP TP TP BUILT IN TBC BUS BAR PROTECTION
50BF IP IP IP
(TRANSFER POSITION)

BUSBAR PROTECTION OPERATED MAIN 87 3 Ph TP TP IP IP RS TP TP IP BUILT IN MAIN BUS BAR PROTECTION


* INTERNAL LBB INITIATION

BUSBAR PROTECTION OPERATED TBC 87 3 Ph TP TP IP IP RS TP TP

DIRECT TRIP RECEIVE CHANNEL-1 3 Ph IP IP IP

DIRECT TRIP RECEIVE CHANNEL-2 3 Ph IP IP IP

GROUP-A MASTER TRIP RELAY TP TP IP IP TP TP IP IP RS RS IP


3 Ph

GROUP-B MASTER TRIP RELAY 3 Ph TP TP IP IP TP TP IP IP RS RS IP

AUTO RECLOSE 79 1/3 Ph IP IP BUILT IN BCU

AUTO RECLOSE LOCK OUT (MAIN) 3 Ph TP TP IP RS

MANUAL TRIP MAIN CB IN NORMAL POSITION TP TP

MANUAL TRIP TBC CB IN TRANSFER POSITION TP TP

SINGLE PHASE FAULT AND CARRIER 1&2 FAIL/0UT IP IP

FAULT DURING RECLAIM TIME IP IP

INDICATES RESET STATUS INDICATES TRIP FROM INDICATES INITIATION


RS TP PROTECTION FUNCTION IP FROM PROTECTION FUNCTION
FOR CB CLOSING

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871203
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 TRIP LOGIC MATRIX DRG. NO.: CPD KR87 SC12 SHT 03 OF 82
FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z
SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871204
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 AUTORECLOSE LOGIC DRG. NO.: CPD KR87 SC12 SHT 04 OF 82
P2A P2B

FS TB1
PH H1
41

FS N
TB1
H2
42

1
1

1
FS91

FS92
LK91

LK92
16A

16A
240V AC SUPPLY

2
2

2
H3

H3
CIL

H4

H4
FROM ACDB CIL
DS H4 DS H4
1 2 1 2

HS TH HT HS TH HT
H5 H7 H5 H7
1 2 1 2 1 2 1 2 1 2 1 2
PS PS
SW
H4 SW
H4
1 2 1 2

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871205
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 AC DISTRIBUTION DRG. NO.: CPD KR87 SC12 SHT 05 OF 82
BOARD-1 220V CONTROL P2A
DC SUPPLY-1
+ -

TO DC SUPVN.
FS +VE TB8 LK1A J13
J11
1 2
1
07

FS TB8 J12 LK2A J14


-VE 1 2
2

1
1

1
FS11

FS12

FS15

FS16
FS13

FS14
10A

10A

10A

10A
6A

6A
2

2
2

2
K1

K2

K801

K802
K101

K102
TO CB TC1 & TO MAIN-1 PROTN. 11 TO ISOLATOR &
CLSG CKT 30 EARTH SWITCH
TO GRP-A TRIP 28
32

BOARD-2 220V CONTROL


DC SUPPLY-2
P2B
+ -
FS

TO DC SUPVN.
TB8 LK1B J23
+VE J21
1 2
1
07
FS TB8 LK2B J24
-VE J22
1 2
2

1
FS21

FS22

FS23

FS24
10A

10A

6A

6A
2

2
K51

K52

K201

K202
TO CB TO MAIN-2 PROTN. 18
TC-2 CKT 31
TO GRP-B TRIP 29

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871206
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DC DISTRIBUTION DRG. NO.: CPD KR87 SC12 SHT 06 OF 82
EQPT 80DC1
TYPE MVAAM11
P2A P2B LOC P2A
EQPT 80DC2
+VE J13 TYPE MVAAM11
DC-1 LOC P2B
SUPPLY EQPT 80CO
06
-VE
J14
BCU DC CHANGE TYPE MVAAM11
OVER RELAY LOC P2B
80CO

13 J14
80DC1
14
J14 11
13 14

.
1 3
J13 J17
S101 S107 7 9
51 51 TO BCU
2 4
J14 J18
.
8 10
5 7 J17
5
. J23 .
6 8 3 1
J18
6

1
1

1
J24 .

FS32

FS34
FS31

FS33
4A

6A
4 2

4A

6A
2

2
2

2
S102

K402
S101

K401
+VE J23
DC-2
SUPPLY
J24
-VE
06

TO BCU DC SUPPLY TO BCU DC SUPPLY


49 23
80DC2

J24
13 14

.
1 3

S101 S109
51 2 4 51 TO BCU

.
5 7
.
6 8

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871207
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DC SUPERVISION DRG. NO.: CPD KR87 SC12 SHT 07 OF 82
R Y B

202-CVT

Ua Ua Ua

WDG: 2 WDG: 1
N N N BURDEN: 50VA
WDG: 3 BURDEN: 50VA
BURDEN: 50VA CLASS:3P CLASS:3P
CLASS:0.2

3a 3a 3a 3n 2a1 2a 2a1 2a 2a1 2a 2n 1a1 1a 1a1 1a 1a1 1a 1n


10A
10A

10A

10A

10A

10A

10A

10A

10A

10A

10A

10A

10A

10A

10A
CVTMB

TB3
5,12,19 TB2 5,12,19 TB1 5,12,19
1 8 15 3 1 10 8 17 15 3 1 10 8 17 15

P2B P2A
E371

22
44

21

23

24
46
TB1

TB1
45

47

48
TB1
42

43
41

1
1

1
ETLP2
ETLP3

ETLP1
E331

E351

E371

LINE
E311

E231

E251

E271

E131

E171
E211

E151
E111
37

R Y B N R Y B N A B C N

TO METERING TO MAIN-2 PROTN. TO MAIN-1 PROTN.


09 17 10

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871208
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 LINE VT CIRCUIT - 220KV DRG. NO.: CPD KR87 SC12 SHT 08 OF 82
BUS SIDE
R-PH Y-PH B-PH P2B
202-CT 202-CT MB TTB
P2 1
R TB1
RATIO : 1600-800/1A

3S3-R TB3-4 D11 2 D12


S3 S3 S3
31 3
3S3-Y TB3-11
BURDEN :20VA

D13
CL:0.2S,IFS<5

32
3S3-B TB3-18 4
Y
CORE-3

S2 S2 S2 D31 5 D32
3S2-R TB3-2
33 6
3S2-Y TB3-9 34
D33
S1 S1 S1 TB3-16 7 49
3S2-B B D51 8 D52
3S1-R TB3-1 35
9 TO BCU
3S1-Y TB3-8 36 D53
P1 3S1-B TB3-15 N D71
37
D70
38

6
TBEM
1
LINE SIDE

ETL1
1S 1L 2S 2L 3S 3L
ENERGY METER
(NOT IN ALSTOM SCOPE)
R Y B N

10
7

8
TBEM

9
TTB NOTE: ENERGY METER WIRES
R E311 FS311 E312 A2 A1 E315 TO BE REMOVED FROM TBEM
CORE-3 1 2
2A AND TERIMINATED AT ENERGY METER
LINE VT E331 FS331 E332
Y B2 B1 E335
SUPPLY 1 2
08 B E351 FS351 E352 C2 C1 E355
1 2

N LK371
E371 E372 N2 N1 E375
1 2

49

TO BCU

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871209
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 ENERGY METER CIRCUIT DRG. NO.: CPD KR87 SC12 SHT 09 OF 82
EQPT 21M1
BUS SIDE MiCOMP444
TYPE
R-PH Y-PH B-PH P2A LOC P2A

202-CT 202-CT MB
P2 MiCOM P444
Imag < 50-25mA AT Vk/4

TB5-4 TB1 BLKA


S3 S3 S3 5S3-R A111 A112
C3
21M1 A172
C2
RATIO : 1600-800/1A

TB5-11 1 S3 R3
5S3-Y
Rct = 8-4 Ohms
Vk=1600-800V

5S3-B TB5-18 2 BLKA


A131 A132
S2 S2 S2 C6 C5
CLASS : PS

5S2-R TB5-2 3 S4 R4
CORE-5

5S2-Y TB5-9 4
A151 BLKA
S1 S1 S1 TB5-16 A152
5S2-B
5 S5 R5 C9 C8
5S1-R TB5-1
6 BLKA
5S1-Y TB5-8 A171 A172
P1 5S1-B TB5-15 7 S6 R6

8
PARALLEL LINE PANEL 21M1

A171S
TB1

NOTE:- # TB'S TO BE IDENTIFIED AT SITE


LINE SIDE C11 A179
9

1
A180
TB1 **
C12

ETL2
10

TB1
A177
11
A171
TB1 **
12

FOR MUTUAL
COMPENSATION

FS111 BLKB
21M1
R E111 E112 E113 C19
1 2 S3 R3
2A NOTE:- **SHORTING LINKS TO BE REMOVED ONCE
LINE CVT FS131 BLKB
THE PARALLEL LINE COMPENSATION IS DONE.
Y E131 E132 E133 C20
(CORE-1) S4 R4
1 2A 2
SUPPLY
B E151
FS151 E152 BLKB
08 E153 C21
1 2 S5 R5
2A

N E171 LK171 E172 BLKB E173 C22


1 2 S6 R6

C23

C24

NOTE:- ** SHORTING LINKS WILL BE REMOVED IN FUTURE IF PARALLEL LINE IS RUNNING

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871210
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DISTANCE PROTN.(MAIN-1) - AC CIRCUIT DRG. NO.: CPD KR87 SC12 SHT 10 OF 82
P2A

06 21M1 06

BASE FILE:
+VE -VE
K101
BLKA K105 K105 BLKB
- K106 K102

FOR ALSTOM REF:


+N2 -N1

SCHEME TYPE: LINE


S2 R2 - R2 S2
AUX.VOLTAGE 16 12

SALES ORDER: 3269020733


+N7 -N9
FIELD VOLTAGE

202-52

TTX1 K105A TB2 CB R-PH CB TB2 K111 K106

ENGG.REF.NO.: KR87
D2 D1 MAIN CB R-PH OPEN
1 63 64 2
Y-PH CB L1
39

CB TB2 K113 K106


12 D4 D3 MAIN CB Y-PH OPEN
65 66 3
L2

CB B-PH CB TB2 K115 K106


D6 D5 MAIN CB B-PH OPEN

Dated 23.03.12
67 68 4
L3
FOR MAKE SPECIFIC TERMINAL REF 59
86A

P.O.NO.: LOA/5427PK067/ PCP/ 01


K117 K106
D8 D7 GROUP A TRIP RELAY
28 86A OPTD.
L4

COX1
K119 K106

PROJECT: POWERGRID 400/220kV DALTONGANJ S/S


D10 D9 CARRIER HEALTHY CH-1
16
L5

21M2
K121 K106

CUSTOMER: POWERGRID CORPORATION OF INDIA LTD


D12 D11 MAIN-2 PROTN OPTD
20
L6

PU
K123 K106
D14 D13 BUSBAR OPTD
42

ALSTOM T&D India


L7

K125 K106
16 D16 D15 CARRIER RECEIVED CH-2

ABCD
L8

PALLAVARAM CHENNAI 600043


21M1
21M2
K127 K106
E2 E1 MAIN-2 RELAY HEALTHY
19

- Limited - AUTOMATION SAS


L9

K129
K106
16 E4 E3 CARRIER RECEIVED CH-1
L10
P2B
COX2
K141 K106
22 E6 E5 CARRIER HEALTHY CH-2
PANEL TYPES: P2A, P2B

L11
SCHEMATIC DRAWING

RX1
K106
K143 E7 DIRECT TRIP RECEIVED CH-1
TITLE: 220KV LINE-1 PROTECTION

25 E8
L12

RX2
K145 K106
E10 E9 DIRECT TRIP RECEIVED CH-2
25
L13

K105T 205-52
FILE: DR871211

TTX1 K106
TB5 CB R-PH CB TB5 K147T K147 E12 E11 TBC CB R-PH OPEN
37
63 64 38
L14
PREPARED BY:

CB Y-PH CB TB5 K149 K106


K149T E14 E13 TBC CB Y-PH OPEN
12 39
MB

65
CHECKED BY: JKK

66
APPROVED BY: SSS

L15

CB B-PH CB TB5 K151 K106


12 K151T E16 E15 TBC CB B-PH OPEN
16 67 68 40 39
REF KR87 SC14 SHT-10 L16
REVISION:

SCALE: --
DISTANCE PROTN.(MAIN-1) - DC/OPTO I/P CIRCUIT DRG. NO.: CPD KR87 SC12 SHT 11
Z
DATE: 29.08.2013

OF 82
P2A

GOOSE INPUT SIGNAL TO 21M1 FOR DR

28 TRIP RELAY 86A SUPVN


MAIN/TBC A/R OPTD.
MAIN /TBC LBB OPTD
MAIN CB CLOSE COMMAND(FOR SOTF) FROM MAIN BCU

SOTF INITIATION
MAIN-2 CARRIER RECEIVED FROM 21M2
TBC CB CLOSE COMMAND(FOR SOTF) FROM TBC BCU

SPARE

SPARE

SPARE

SPARE

K103
K106
11

K106
K106

K106

K106
K106
GOOSE OUTPUT SIGNAL TO BCU

F11

F13

F15
F1

F3

F5

F9
F7
MICOMP444

CARRIER CH-1OUT OF SERVICE


21M1

CARRIER CH-2OUT OF SERVICE


L17

L18

L19

L20

L21

L22

L23

L24
86A TRIP RELAY OPTD

F10

F12

F14
F6
F2

F8

F16
F4

GOOSE OUTPUT SIGNAL TO 21M2

K103A
K161
K159
K155

K163
K157

MAIN CB R-PH OPEN

K165
.

TTX1

MAIN CB Y-PH OPEN


TB2

TB2

TB2
K129T

TTX1

39
MAIN CB B-PH OPEN

K145T
K143T
TB5

32

35

28
MAIN-1 CARRIER RECEIVED

TB5
CPD KR87 SC14 SHT-10

TB5

36
35
T N C

52CS

REF KR87 SC14 SHT-08


MAIN-1 PROTECTION OPTD
PU

55
P2A

T N C

52CS DIRECT TRIP RECEIVED CH-1/2


PU

BCU

BCU
42

TBC CB R-PH OPEN


PU(TBC)
TB5 PZ

TB2
5
31

TBC CB Y-PH OPEN


11

K105T

TBC CB B-PH OPEN


34
TB5

BUSBAR PROTN OPTD


11
K105
TTX1

MAIN CB LBB OPTD


39
K105

TBC CB LBB PROTN OPTD


11

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871212
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DISTANCE PROTN.(MAIN-1) - DC/OPTO I/P CIRCUIT DRG. NO.: CPD KR87 SC12 SHT 12 OF 82
P444OP1
21M1

BASE FILE:
. N11 .
N12

FOR ALSTOM REF:


SCHEME TYPE: LINE
K205 N13 K243 RELAY HEALTHY
18 N14 18

SALES ORDER: 3269020733


K3 BLKA K3A
R-PH
K3D M1
30 M2
S1 R1

K3B
Y-PH TO TC-1 - MAIN CB
M3 M4 (ZONE-1,DEF, SOTF,Z2,Z3

ENGG.REF.NO.: KR87
30
K3C B-PH
M5 M6

K53 BLKB K53D M7 K53A R-PH


31 M8
S1 R1

M9 K53B Y-PH TO TC-2 - MAIN CB


M10
(ZONE-1,DEF, SOTF,Z2,Z3

Dated 23.03.12
31

M11 K53C B-PH


M12

P.O.NO.: LOA/5427PK067/ PCP/ 01


M13 .
K104 TO GROUP-A TRIP RELAY
K101 BLKA M15 M14 K103 ( DEF TRIP,SOTF
28 28
S7 R7
MULTI PH./Z2,Z3 FAULTS)
M16 .

PROJECT: POWERGRID 400/220kV DALTONGANJ S/S


BLKB K203 TO GROUP-B TRIP RELAY
K201 K203D M18
M17
29 29 ( DEF TRIP,SOTF
S7 R7
MULTI PH./Z2,Z3 FAULTS)

K405A
R-PH
K403 BLKA

CUSTOMER: POWERGRID CORPORATION OF INDIA LTD


36 L1 L2
S8 R8
TO TC-1 - TIE CB
Y-PH
L3 K405B (ZONE-1,DEF, SOTF,Z2,Z3
L4

36

ALSTOM T&D India


K405C B-PH
L5 L6

TB2 U101 U103 TB2


L7 L8

ABCD
SPARE
46 47

PALLAVARAM CHENNAI 600043


TB2 U105 U107 TB2
L9 L10 GENERAL TRIP
48 49 (FOR RELAY TESTING)

- Limited - AUTOMATION SAS


. L11 .
L12

L13 .
BLKA K131A L15 TO DIRECT TRIP CH-1
26 L14 K133 26
S10 R10 (DEF OPTD)
L16 .
BLKB
TO DIRECT TRIP CH-2
PANEL TYPES: P2A, P2B

K231A L18 L17 K233


27 27
S10 R10 (DEF OPTD)
SCHEMATIC DRAWING

K175 BLKA K175B K1 K106


16 K2 16 TO CARRIER SEND CH-1
S9 R9
TITLE: 220KV LINE-1 PROTECTION

K179 BLKB K179B K3 K106


16 K4 16 TO CARRIER SEND CH-2
S9 R9

K453 BLKB K454 K5 K455A R-PH


36 K6
S8 R8
FILE: DR871213

TO TC-2 - TIE CB
K7 K455B Y-PH (ZONE-1,DEF, SOTF,Z2,Z3
K8
DISTANCE PROTN.(MAIN-1) - OUTPUT RELAY CONTACTS

36
K9 K455C B-PH
PREPARED BY:

K10
MB
CHECKED BY: JKK
APPROVED BY: SSS

P105
LKM1 P111
41 P105B K11 K12 R-PH
1 2

K13 . LBB-1 INITIATION


Y-PH MAIN CB
K15 K14 P113
41
REVISION:

SCALE: --

DRG. NO.: CPD KR87 SC12 SHT 13

K16 .
Z

B-PH
K18 K17 P115
DATE: 29.08.2013

OF 82
P2A

BASE FILE:
FOR ALSTOM REF:
SCHEME TYPE: LINE
TB2 U27 U29 TB2
J1 J2 SPARE
50 51

SALES ORDER: 3269020733


TB2 U31 U33 TB2
J3 J4 SPARE
52 53

P105T
LKM1-A P131T R-PH
P105A J5 J6
38 1 2

ENGG.REF.NO.: KR87
TO LBB INITIATION
J7 P133T Y-PH TBC CB
J8
38

J9 P135T B-PH
J10

S101
LKM1-B S145A R-PH
S101A J11 J12
51

Dated 23.03.12
1 2

J13 .
Y-PH A/R INITIATION

P.O.NO.: LOA/5427PK067/ PCP/ 01


J15 J14 S145B MAIN CB

J16 . 51

J18 J17 S145C


B-PH

PROJECT: POWERGRID 400/220kV DALTONGANJ S/S


K401
LKM1-C K401F K407A TO A/R L/O CKT - MAIN CB
23 H1 H2 23
1 2 SINGLE PHASE FAULT R/Y/B

CLIENT : POWER GRID CORPORATION OF INDIA LTD.


K561

CUSTOMER: POWERGRID CORPORATION OF INDIA LTD


LKM1-D K501A H3 K553 TO A/R L/O CKT - TBC CB
37 1 2 H4 37
SINGLE PHASE FAULT R/Y/B

S103T
LKM1-E S101E S139 R-PH
S101E H5 H6
37 1 2

ALSTOM T&D India


A/R INITIATION
H7 . TBC CB
S101E H9 H8 S141
Y-PH
37

ABCD
H10 .

PALLAVARAM CHENNAI 600043


S101E H12 H11 S143
B-PH

H13 .

- Limited - AUTOMATION SAS


. H15 H14 .

H16 .
. H18 H17 .

. G1 .
G2
PANEL TYPES: P2A, P2B
SCHEMATIC DRAWING

. G3 .
G4
TITLE: 220KV LINE-1 PROTECTION

. G5 .
G6

G7 .
. G9 G8 .
FILE: DR871214

G10 .
. G12 G11 .
DISTANCE PROTN.(MAIN-1) - OUTPUT RELAY CONTACTS

G13 .
.
PREPARED BY:

G15 G14 .
MB
CHECKED BY: JKK
APPROVED BY: SSS

G16 .
. G18 G17 .
REVISION:

SCALE: --

DRG. NO.: CPD KR87 SC12 SHT 14


Z
DATE: 29.08.2013

OF 82
OUTPUT CONTACT ASSIGNMENT INPUT CONFIGURATION
OUTPUT NO. ASSIGNMENT INPUT NO. ASSIGNMENT BUILT IN FUNCTIONS OF P444
RELAY WILL BE SUPPLIED WITH ALL THE FUNCTIONS LISTED BELOW ,CUSTOMER REQ
OUTPUT-RL1 TC-1 R PH TRIP MAIN CB CAN ENABLE ANY FUNCTION BASED ON REQUIREMENT.
OUTPUT-RL2 TC-1 Y PH TRIP MAIN CB INPUT - 1 MAIN CB R-PH OPEN 21 DISTANCE PROTECTION
OUTPUT-RL3 TC-1 B PH TRIP MAIN CB INPUT - 2 MAIN CB Y-PH OPEN 50/51/67 DIRECTIONAL/NON DIRECTIONAL PHASE OVER CURRENT
OUTPUT-RL4 TC-2 R PH TRIP MAIN CB
INPUT - 3 MAIN CB B-PH OPEN 50N/51N/67N DIRECTIONAL/NON DIRECTIONAL E/F
OUTPUT-RL5 TC-2 Y PH TRIP MAIN CB
OUTPUT-RL6 TC-2 B PH TRIP MAIN CB INPUT - 4 GROUP A TRIP RELAY 86A OPT. 67N CHANNEL AIDED DIRECTIONAL E/F
OUTPUT-RL7 SPARE INPUT - 5 CARRIER RECEIVED CH-1 68 POWER SWING BLOCKING/OUT OF STEP TRIPPING
OUTPUT-RL8 SPARE INPUT - 6 MAIN-2 PROTN OPTD 50/27 SWITCH ONTO FAULT(SOTF)
OUTPUT-RL9 TC-1 R PH TRIP TBC CB
INPUT - 7 BUSBAR OPTD. 85 CHANNEL AIDED SCHEMES
OUTPUT-RL10 TC-1 Y PH TRIP TBC CB PERMISSIVE UNDERREACH TRANSFER
OUTPUT-RL11 TC-1 B PH TRIP TBC CB INPUT - 8 CARRIER RECEIVED CH-2
PERMISSIVE OVERREACH TRANSFER
OUTPUT-RL12 TC-2 R PH TRIP TBC CB INPUT - 9 MAIN-2 RELAY HEALTHY
DIRECT TRANSFER TRIP
OUTPUT-RL13 TC-2 Y PH TRIP TBC CB INPUT - 10 CARRIER RECEIVED CH-1
BLOCKING UNDERREACH SCHEME
OUTPUT-RL14 TC-2 B PH TRIP TBC CB
INPUT - 11 CARRIER HEALTHY CH-2 BLOCKING OVERREACH SCHEME
OUTPUT-RL15 MAIN LBB INITIATION R-PH
OUTPUT-RL16 MAIN LBB INITIATION Y-PH INPUT - 12 DIRECT TRIP RECEIVED CH-1 WEAK INFEED ECHO LOGIC
OUTPUT-RL17 MAIN LBB INITIATION B-PH INPUT - 13 DIRECT TRIP RECEIVED CH-2 79 AUTO RECLOSE(1/3PH)
OUTPUT-RL18 TO CARRIER SEND CH-1
INPUT - 14 TBC CB R-PH OPEN 25 CHECK SYNCHRONISING
OUTPUT-RL19 TO GRP-A TRIP RELAY (Z2,Z3 DEF TRIP,SOTF)
INPUT - 15 TBC CB Y-PH OPEN 59 OVER VOLTAGE(2 STAGE)
OUTPUT-RL20 TO GRP-B TRIP RELAY (Z2,Z3 DEF TRIP,SOTF)
OUTPUT-RL21 TO CARRIER SEND CH-2 INPUT - 16 TBC CB B-PH OPEN 46BC OPEN JUMPER
OUTPUT-RL22 TBC LBB INITIATION R-PH INPUT - 17 SPARE 50BF CIRCUIT BREAKER FAILURE
OUTPUT-RL23 TBC LBB INITIATION Y-PH
TBC LBB INITIATION B-PH
INPUT - 18 MAIN /TBC LBB OPTD # NOTE : HOWEVER ALL THE ABOVE FUNCTIONS SHALL BE AVAILABLE
OUTPUT-RL24 -REQ
TBC CB A/R INITIATION R-PH INPUT - 19 SPARE AND USER PROGRAMMABLE AT SITE
OUTPUT-RL25 -NOT REQ
LED CONFIGURATION
OUTPUT-RL26 TBC CB A/R INITIATION Y-PH INPUT - 20 SPARE (USER PROGRAMMABLE LED's)
OUTPUT-RL27 TBC CB A/R INITIATION B-PH
INPUT - 21 SPARE LED REF FUNCTION
OUTPUT-RL28 TO A/R L/O CKT TBC CB SINGLE PH FAULT A/B/C
OUTPUT-RL29 TO A/R L/O CKT MAIN CB SINGLE PH FAULT A/B/C INPUT - 22 SOTF INITIATION 5 ZONE-1 OPTD
OUTPUT-RL30 SPARE
OUTPUT-RL31 SPARE
INPUT - 23 MAIN/TBC A/R OPTD.
INPUT - 24 TRIP RELAY 86A SUPVN 6 ZONE-2 OPTD
OUTPUT-RL32 SPARE
OUTPUT-RL33 SPARE
OUTPUT-RL34 GENERAL TRIP 7 ZONE-3 OPTD
OUTPUT-RL35 MAIN CB A/R INITIATION R-PH MICOMP444
OUTPUT-RL36 LED CONFIGURATION 8 R-PH OPTD
MAIN CB A/R INITIATION Y-PH
(DEDICATED LED's)
OUTPUT-RL37 MAIN CB A/R INITIATION B-PH
OUTPUT-RL38 LED REF FUNCTION Y-PH OPTD
TO DIRECT TRIP CH-1(DEF OPTD) 9
OUTPUT-RL39 TO DIRECT TRIP CH-2(DEF OPTD)
TRIP
1
OUTPUT-RL40 SPARE
10 B-PH OPTD
OUTPUT-RL41 SPARE 2 ALARM
OUTPUT-RL42 SPARE
OUTPUT-RL43 SPARE 3 WARNING 11 PSB OPTD
OUTPUT-RL44 SPARE
OUTPUT-RL45 SPARE 4 HEALTHY 12 SOTF /DEF OPTD
OUTPUT-RL46 SPARE
FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z
SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871215
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DISTANCE PROTN.(MAIN-1) - I/O & LED CONFIGURATION
DRG. NO.: CPD KR87 SC12 SHT 15 OF 82
P2A EQPT COX1
PLCC CHANNEL-1 11 TYPE MVAAM11
OUT IN LOC P2A
TB2 K105
K171 +VE -VE
21 CSS1
35
CARR.RECEIVE
PL-03 PL-04
K129 11 TO MAIN-1 PROTN
(CODE-1) 22

CARR. SEND 21M1


PL-01 PL-02
K175
CS
23
13
(CODE-1)

K105
24
COX1
CARRIER CH-1 HEALTHY
13 K106
PL-05 PL-06
K173 14 CARRIER CH-I HEALTHY
11
25

K407B
23 TO A/R L/O ( MAIN CB )
5
K407A
23
3 1
K557 TO A/R L/O ( TBC CB )
37
6
K553
37
4 2

K105 K119
11 11 TO MAIN-1 PROTN
7 9

.
8 10

PLCC CHANNEL-2
OUT IN
K177
26 CSS2
CARR.RECEIVE 35
PL-09 PL-10
K125 11 TO MAIN-1 PROTN
(CODE-2) 27

CARR. SEND 21M1


PL-07 PL-08
K179
CS
28
13
(CODE-2)

FOR MAKE SPECIFIC TERMINAL REF SHT 81

FOR ALSTOM REF: ENGG.REF.NO.: KR87 CLIENT : POWER GRID CORPORATION OF INDIA LTD. PREPARED BY: MB REVISION: Z
SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871216
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DISTANCE PROTN.(MAIN-1) - CARRIER DRG. NO.: CPD KR87 SC12 SHT 16 OF 82
BUS SIDE EQPT 21M2
TYPE REL670
R-PH Y-PH B-PH
LOC P2B
P2B
202-CT 202-CT MB
P2 REL670
TB1 TXS1
TB4-4 A211 BLKC 21M2 A277A
Imag < 50-25mA AT Vk/4

S3 S3 S3 4S3-R A213 2
1 R3
1
S3
RATIO : 1600-800/1A

4S3-Y TB4-11 1
TB4-18 2 REL670
Rct = 8-4 Ohms

4S3-B
Vk=1600-800V

A231 BLKC A233 A277B


S2 S2 S2
TB4-2 3 4
4S2-R 3 S4 R4
CLASS : PS

2
CORE-4

4S2-Y TB4-9 4
A251 BLKC A277C
S1 S1 S1 TB4-16 A253 5 6
4S2-B
5 S5 R5
TB4-1 3
4S1-R
6 BLKC
4S1-Y TB4-8 A271 A275 A277D
8 7
P1 4S1-B TB4-15 7 S6 R6
4
8 9

A271S
10
LINE SIDE

1
13 15 17 14 16 18 TB1
A279

ETL3
9
A280
TB1 **
10

A277 TB1
11
A271
TB1 **
12

FOR MUTUAL
COMPENSATION
FROM PARALLEL LINE
(IF APPLICABLE)

R E211 FS211 E212 BLKD


E213

E273A
E273B
1 2 S3 R3

E273
2A
WDG-2
Y FS231 BLKD E233
LINE VT E231 E232
R4

5
6
7
SUPPLY 1 2 S4

TXS1
2A
08
B E251
FS251 E252 BLKD
E253
1 2 S5 R5
2A

N E271 LK271 E272 BLKD E273


1 2 S6 R6

NOTE:- ** SHORTING LINKS WILL BE REMOVED IN FUTURE IF PARALLEL LINE IS RUNNING

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871217
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DISTANCE PROTN.(MAIN-2) - AC CIRCUIT DRG. NO.: CPD KR87 SC12 SHT 17 OF 82
P2B

BASE FILE:
06 REL670 06
21M2

FOR ALSTOM REF:


+VE TXS1 -VE

SCHEME TYPE: LINE


BLKC TB9 BLKD
K201 K205 - K204A C1 K204 K202
114 115
S2 R2 8 - P1 R2 S2

22

SALES ORDER: 3269020733


X11 X11

BIX=31

ENGG.REF.NO.: KR87
BI.01
TB2 TB2
K205 K211 312 K204B
311 SPARE
1 2

BI.02
TB2 K213
313 314 K204C SPARE
3
8
BI.03

Dated 23.03.12
TB2
K215 K204D
315 316 SPARE
4

P.O.NO.: LOA/5427PK067/ PCP/ 01


BI.04
K217 318 K204E CARRIER RECEIVED CH-2
22 317
T N C
TTX2 K205A

PROJECT: POWERGRID 400/220kV DALTONGANJ S/S


39 35 BI.05
52CS
K219 3110 K204F SOTF INITIATIO N
P2A PU(TBC) P2A 319
TTX2 TTX4
TB5 T N C TB5 K219T
K205T

CUSTOMER: POWERGRID CORPORATION OF INDIA LTD


42
39 41 52CS 39 BI.06
TB2
REF KR87 SC14 SHT08 K221
3111 3112 K204G SPARE
5

BI.07 9
BCU

ALSTOM T&D India


K223 3114 K204H
3113 BCU HEALTHY
49

C0X2 BI.08
K225 K204I

ABCD
3115 3116 CARRIER HEALTHY CH-2
22

PALLAVARAM CHENNAI 600043


BIX=32
86B BI.09

- Limited - AUTOMATION SAS


K227 K204J
321 322 86B TRIP RELAY OPTD
29

BI.10
TB2
TB2 K251 323 324 K204K
11
9

10
PANEL TYPES: P2A, P2B

PU BI.11
K241
SCHEMATIC DRAWING

325 326 K204L PU HEALTHY


42

BI.12
TITLE: 220KV LINE-1 PROTECTION

21M1 K243
327 328 K204M MAIN-1 RELAY HEALTHY
13

BI.13
K245 329 K204N
22 3210 CARRIER RECEIVED CH-1
FILE: DR871218
IN
OUT

BI.14
TB2 TB2
K205 K247 K204O CARRIER CH-1 OUT OF
3211 3212
35 SERVICE
6 8
CSS1
PREPARED BY:
OUT

IN

BI.15
MB
CHECKED BY: JKK

TB2
APPROVED BY: SSS

K249 11
3213 K204P CARRIER CH-2 OUT OF
35 3214
10 SERVICE
CSS2 BI.16

K203 86B TRIP RELAY


29 3215 3216 29
SUPERVISION
REVISION:

22
SCALE: --
DISTANCE PROTN.(MAIN-2) - DC OPTO I/P CIRCUIT DRG. NO.: CPD KR87 SC12 SHT 18
Z
DATE: 29.08.2013

OF 82
P2B

GOOSE OUTPUT SIGNAL TO BCU

CARRIER CH-1OUT OF SERVICE

TO GROUP-A TRIP RELAY

TO GROUP-B TRIP RELAY


MULTI PH./Z2,Z3 FAULTS)

MULTI PH./Z2,Z3 FAULTS)


(ZONE-1,DEF, SOTF,Z2,Z3 CARRIER CH-2OUT OF SERVICE

(ZONE-1,DEF, SOTF,Z2,Z3

( DEF TRIP,SOTF

( DEF TRIP,SOTF
86B TRIP RELAY OPTD

TO LBB INITIATION
TO TC-2 TRIP
TO TC-1 TRIP
TO TC-1 TRIP

TO TC-2 TRIP
RELAY HEALTHY

MAIN CB.

MAIN CB.

TBC CB.
TBC CB.

MAIN CB
GOOSE INPUT SIGNAL TO MAIN-2
30

36

31

36

28

29
41
MAIN CB R-PH OPEN
11

MAIN CB Y-PH OPEN

MAIN CB B-PH OPEN

MAIN-1 CARRIER RECEIVED

K455C
K455A

K455B
K405C
K405A

K405B

K203
K127

K103
K53C

P115
K53A

K53B

P111

P113
4104 K3C
4101 K3A

4103 K3B

MAIN-1 PROTECTION OPTD

4201

4206
4106

4216

4218
4215
4204
4109

4203

4213
4207

4212
4209

4210
4118
4107

4110
BOX=41

4115

4116
4112

FROM MAIN-1
4113
112

BOX=42
DIRECT TRIP RECEIVED
X11

TBC CB R-PH OPEN


REL670

BO.13

BO.20
BO.19

BO.21
BO.07

BO.08

BO.09

BO.10

BO.11

BO.22

BO.24
BO.04

BO.05

BO.06

BO.16

BO.17

BO.18

BO.23
BO.01

BO.02

BO.03

BO.14

BO.15
21M2

BO.12
WD

TBC CB Y-PH OPEN

BOX=42
TBC CB B-PH OPEN
BOX=41
X11

4208
4114

4217
4205
K53F 4117
4105

K407P 4108

4202
4111

4214
4102

4211
BUS BAR OPTD
111

.
.
.

.
.

.
.

.
.
.

TXS1 K453E
K53E

TXS1 P105C
K407Q

P105D
K453F

K101B

K102B
MAIN-LBB OPTD.
K1D

K1E

34
32
30

33
31
29
26

28
25

27

TXS1
TXS1

TXS1

TXS1
TXS1

TXS1

TXS1

TXS1

TBC LBB OPTD.

MAIN CB A/R OPTD


K453E
K407P

FROM
K53E

MAIN CB CLOSE
K1D

2
LKM2-A
COMMAND(FOR SOTF) MAIN BCU

R10
R1

R1

R7

R8

R9
TBC CB CLOSE FROM

BLKC
BLKD

BLKC

BLKC

BLKC

BLKC
1
COMMAND(FOR SOTF)
P105

TBC BCU

S10
S1

S1

S7

S8

S9
K105

K453

K101
K403

K201
K53
K3
11

30

36

31

36

41

28

29
FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z
SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871219
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DISTANCE PROTN.(MAIN-2) - OUTPUT RELAY CONTACTS
DRG. NO.: CPD KR87 SC12 SHT 19 OF 82
BASE FILE:
FOR ALSTOM REF:
SCHEME TYPE: LINE
P2B

REL670

SALES ORDER: 3269020733


BOX=51 WD BOX=51
TXS1
P105T LKM2-B P105F 5102 P131T
1 2
5101
38 BO.01
35
TO LBB INITIATION
P133T TBC CB
. 5103

ENGG.REF.NO.: KR87
BO.02 38
TXS1
P105G 5104 P135T
5105
36 BO.03

. 5106
BO.04
LKM2-C TXS1 S101B S145A
S101 5107
1 2
5108
51 BO.05
37 TO A/R INITIATION
S145B MAIN CB
. 5109

Dated 23.03.12
BO.06 51
TXS1 S145C
S101C
5111 5110
38

P.O.NO.: LOA/5427PK067/ PCP/ 01


BO.07

. 5112
BO.08

TB9 S101E
S103T LKM2-D S139
1 2 5114 5113
37 BO.09

PROJECT: POWERGRID 400/220kV DALTONGANJ S/S


39 TO A/R INITIATION
S141 TBC CB
. 5115
BO.10 37
TB9 S101F S143
5117 5116

CUSTOMER: POWERGRID CORPORATION OF INDIA LTD


BO.11
40

. 5118
BO.12

ALSTOM T&D India


BOX=52 BOX=52

K204 BLKD K205H K279 TO CARREIR SEND CH-1


22 5202 5201 22 (MAIN-2 PROTN. TRIP)
S7 R7 BO.13

ABCD
K275

PALLAVARAM CHENNAI 600043


. 5203 TO CARREIR SEND CH-2
BO.14 22
(MAIN-2 PROTN. TRIP)
K231 BLKD K231B K233
5205 5204 TO DIRECT TRIP CH-2

- Limited - AUTOMATION SAS


27 S8 R8 BO.15 27
(DEF OPTD)

. 5206
BO.16
K561 LKM2-E K561A K553 TO A/R L/O CKT TBC CB
5208 5207
1 2 BO.17
37 37 SINGLE PHASE FAULT A/B/C
.
. 5209
BO.18
LKM2-F K401D K407A
PANEL TYPES: P2A, P2B

K401 TO A/R L/O CKT MAIN CB


1 2 5211 5210
23 23 SINGLE PHASE FAULT A/B/C
SCHEMATIC DRAWING

BO.19
. 5212
BO.20
TITLE: 220KV LINE-1 PROTECTION

K105 K105 MAIN-2 PROTN OPTD


11 5214 5213 K121 11
BO.21 TO 21M1

. 5215
BO.22

K131 BLKD K131B K133


5217 5216 TO DIRECT TRIP CH-1
26 S10 R10 BO.23 26 (DEF OPTD)
FILE: DR871220

.
. 5218 .
BO.24
DISTANCE PROTN.(MAIN-2) - OUTPUT RELAY CONTACTS
PREPARED BY:
MB
CHECKED BY: JKK
APPROVED BY: SSS
REVISION:

SCALE: --

DRG. NO.: CPD KR87 SC12 SHT 20


Z
DATE: 29.08.2013

OF 82
OUTPUT CONTACT ASSIGNMENT INPUT CONFIGURATION
OUTPUT NO. ASSIGNMENT SLOT- X31,32 ASSIGNMENT BUILT IN FUNCTIONS OF REL670
REQ
SLOT- X41
OUTPUT-BO1 TC-1 R PH TRIP MAIN CB INPUT - BI 1 SPARE 21 DISTANCE PROTECTION

OUTPUT-BO2 TC-1 Y PH TRIP MAIN CB 50/51/67 DIRECTIONAL/NON DIRECTIONAL PHASE OVER CURRENT
INPUT - BI 2 SPARE
OUTPUT-BO3 TC-1 B PH TRIP MAIN CB 50N/51N/67N DIRECTIONAL/NON DIRECTIONAL STAND BY E/F
INPUT - BI 3 SPARE
OUTPUT-BO4 SPARE
INPUT - BI 4 CARRIER RECEIVED CH-2 67N CHANNEL AIDED DIRECTIONAL E/F
OUTPUT-BO5 TC-1 R PH TRIP TBC CB
OUTPUT-BO6 TC-1 Y PH TRIP TBC CB INPUT - BI 5 SOTF INITIATION 68 POWER SWING BLOCKING/OUT OF STEP TRIPPING
OUTPUT-BO7 TC-1 B PH TRIP TBC CB INPUT - BI 6 SPARE 50/27 SWITCH ONTO FAULT(SOTF)
OUTPUT-BO8 SPARE CHANNEL AIDED SCHEMES
INPUT - BI 7 BCU HEALTHY 85
OUTPUT-BO9 TC-2 R PH TRIP MAIN CB PERMISSIVE UNDERREACH TRANSFER
OUTPUT-BO10 TC-2 Y PH TRIP MAIN CB INPUT - BI 8 CARRIER HEALTHY CH-2
PERMISSIVE OVERREACH TRANSFER
OUTPUT-BO11 TC-2 B PH TRIP MAIN CB INPUT - BI 9 86B TRIP RELAY OPTD DIRECT TRANSFER TRIP
OUTPUT-BO12 SPARE
INPUT - BI 10 SPARE BLOCKING UNDERREACH SCHEME
SLOT- X42
OUTPUT-BO13 TC-2 R PH TRIP TBC CB INPUT - BI 11 PU HEALTHY BLOCKING OVERREACH SCHEME
OUTPUT-BO14 TC-2 Y PH TRIP TBC CB INPUT - BI 12 MAIN-1 RELAY HEALTHY WEAK INFEED ECHO LOGIC
OUTPUT-BO15 TC-2 B PH TRIP TBC CB
OUTPUT-BO16 SPARE INPUT - BI 13 CARRIER RECEIVED CH-1 79 AUTO RECLOSE(1/3PH)

OUTPUT-BO17 TO MAIN LBB INITIATION R-PH INPUT - BI 14 CARRIER CH-1 OUT OF SERVICE 25 CHECK SYNCHRONISING
OUTPUT-BO18 TO MAIN LBB INITIATION Y-PH INPUT - BI 15 CARRIER CH-2 OUT OF SERVICE 59 OVER VOLTAGE(2 STAGE)
OUTPUT-BO19 TO MAIN LBB INITIATION B-PH 46BC OPEN JUMPER
INPUT - BI 16 TRIP RELAY 86B SUPVN
OUTPUT-BO20 SPARE
50BF CIRCUIT BREAKER FAILURE
OUTPUT-BO21 TO GR-A TRIP RELAY ( Z2,Z3 DEF, SOTF)
OUTPUT-BO22 SPARE # ALL THE ABOVE FUNCTIONS SHALL BE TAKEN TO BCU IN SOFT -REQ
OUTPUT-BO23 TO GR-B TRIP RELAY ( Z2,Z3 DEF, SOTF)
LED CONFIGURATION REL670
OUTPUT-BO24 SPARE
LED REF FUNCTION LED REF FUNCTION

SLOT- X51 SLOT- X52 1 ZONE-1 OPTD 9 DEF OPTD


OUTPUT-BO13 TO CARREIR SEND CH-1
OUTPUT-BO1 TO TBC LBB INITIATION R-PH SPARE
OUTPUT-BO14 TO CARREIR SEND CH-2
2 ZONE-2 OPTD 10
OUTPUT-BO2 TO TBC LBB INITIATION Y-PH
OUTPUT-BO3 TO TBC LBB INITIATION B-PH OUTPUT-BO15 TO DIRECT TRIP CH-2 (DEF 2) 3 ZONE-3 OPTD 11 SPARE
OUTPUT-BO4 SPARE OUTPUT-BO16 SPARE
OUTPUT-BO5 TO MAIN CB A/R INITIATION R-PH OUTPUT-BO17
4 R-PH OPTD 12 SPARE
TO A/R L/O CKT TBC CB SINGLE PH FAULT A/B/C
OUTPUT-BO6 TO MAIN CB A/R INITIATION Y-PH OUTPUT-BO18 SPARE
OUTPUT-BO7 TO MAIN CB A/R INITIATION B-PH TO A/R L/O CKT MAIN CB SINGLE PH FAULT A/B/C 5 Y-PH OPTD 13 SPARE
OUTPUT-BO19
OUTPUT-BO8 SPARE
OUTPUT-BO20 SPARE B-PH OPTD 14 SPARE
OUTPUT-BO9 TO TBC CB A/R INITIATION R-PH 6
OUTPUT-BO21 MAIN-2 PROTN OPTD
OUTPUT-BO10 TO TBC CB A/R INITIATION Y-PH
OUTPUT-BO22 SPARE 7 PSB DETECTED 15 SPARE
OUTPUT-BO11 TO TBC CB A/R INITIATION B-PH OUTPUT-BO23 TO DIRECT TRIP CH-1 (DEF 2)
OUTPUT-BO12 SPARE OUTPUT-BO24 SPARE 8 SOTF OPERATED

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871221
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DISTANCE PROTN.(MAIN-2) - I/O & LED CONFIGURATION
DRG. NO.: CPD KR87 SC12 SHT 21 OF 82
P2B EQPT COX2
PLCC CHANNEL-2
TYPE MVAAM11
18
LOC P2B
OUT IN +VE -VE
TB2
K271 K205
21 CSS2
CARR.RECEIVE 35
PL-23 PL-24 TB2
K217
18 TO MAIN-2 PROTN
(CODE-1) 22

CARR. SEND 21M2


PL-21 PL-22
K275
CS
23
20
(CODE-1)
K205
24 COX2

CARRIER HEALTHY 13 K204


PL-25 PL-26
K273 14 CARRIER CH-2 HEALTHY
11
25

K407 TO A/R L/O (MAIN BKR)


23
5
K407B
23
3 1
TB2 K409
S101 37 TO A/R L/O (TBC BKR)
6
29 K557
51 37
TO BCU 4 2
SPEECH CHANNEL FAIL
S117 K105 K141
11 11 TO MAIN-1 PROTN
30 7 9

K205 K225
18 18 TO MAIN-2 PROTN
CARR SPEECH CHANNEL 8 10

PLCC CHANNEL-1
OUT IN
K277
26 CSS1
CARR.RECEIVE 35
PL-29 PL-30
K245
18 TO MAIN-2 PROTN
(CODE-2) 27

CARR. SEND 21M2


PL-27 PL-28
K279
CS
28
20
(CODE-2)
FOR MAKE SPECIFIC TERMINAL REF SHT 81

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871222
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DISTANCE PROTN.MAIN-2 CARRIER AUX. CKT. DRG. NO.: CPD KR87 SC12 SHT 22 OF 82
EQPT 86LO
P2A
TYPE MVAJ105
LOC P2A
K401
07
K402
07 K3 K3A
+VE 30 5 7 30
BCU (RESET) 86LO
-VE K3B TO TC-1 OF
K409A K402 9 11
R 30
MAIN CB
25 26
56
K3C
13 15 30

86LO K53 K53A


BCU 31 17 19 31
K407 K402
A/R LOCKOUT 27 K53B TO TC-2 OF
55 OP 28 6 8 31
P2A P2B MAIN CB

21M1
K53C
10 12 31
K407A COX1 K407B COX2

14 S101 S101 S111


16 22 51 14 16 51 AUTO RECLOSE RELAY OPTD
TO BCU
P2B P105 P123
P105
21M2 BCU (A/R OFF) 41 18 20 41 TO MAIN LBB INITIATION

20
55
K10 K10 K19
30 1 3 30 TO CLOSING I/L

.
2 4

AUTO RECLOSE LOCKOUT FROM BCU WILL OPERATE ON THE FOLLOWING CONDITIONS:
1. A/R INITIATION DURING RECLAIM TIME.
2. OUT OF SYNCHRONISM

P2A AUTO RECLOSE BLOCK FROM BCU WILL OPERATE ON THE FOLLOWING CONDITIONS:
86A
S149 1. MAIN-1 / MAIN-2 Z2 & Z3 PROTN. OPTD
28 2. B/B PROTECTION OPTD.
P2B 3. LBB PROTECTION OPTD.
86B
4. SOTF PROTN. OPTD.
29
5. DEF PROTN. OPTD.
P2A
6. POLE DISCREPANCY TRIP
PU
7. DIRECT TRIP RECEIVE FROM THE OPPOSITE END.
42 8. MULTIPHASE FAULTS
9. A/R ON NON-AUTO MODE
TO AUTORECLOSE BLOCK 51

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871223
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 AUTORECLOSE LOCKOUT RELAY DRG. NO.: CPD KR87 SC12 SHT 23 OF 82
BLANK SHEET

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871224
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BLANK SHEET DRG. NO.: CPD KR87 SC12 SHT 24 OF 82
EQPT RX1
P2A TYPE MVAAM11
28 LOC P2A

EQPT RX2
PLCC CHANNEL-1
+VE -VE TYPE MVAAM11
DIRECT TRIP OUT IN
TB2 LOC P2B
K183
19 CSS1
RX1 35
CODE 3 13 K102
K185 14
11
PL-11 PL-12 20
.
5
FOR MAKE SPECIFIC TERMINAL REF SHT 81 K105 K143
11 11 TO 21M1 (D/R)
3 1
.
6
K101 K103
28 28 TO GRP-A TRIP
4 2

TB2 U11 U12 TB2


U12
54 55
SPARE
7 9

K201 K203
29 29 TO GRP-B TRIP
8 10

26

P2B

29
PLCC CHANNEL-2 OUT IN
TB2 +VE -VE
K283
19 CSS2
RX2 35
CODE 3 13 K202
K285 14
11
PL-31 PL-32 20
DIRECT TRIP .
5
K105 K145
11 11 TO 21M1 (D/R)
FOR MAKE SPECIFIC TERMINAL REF SHT 81 3 1
.
6
K201 K203
29 29 TO GRP-B TRIP
4 2

TB4 TB4 27
U13 U14
41 42
SPARE
7 9

K101 K103
28 28 TO GRP-A TRIP
8 10

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871225
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DIRECT TRIP COMMAND RECEIVE CIRCUIT DRG. NO.: CPD KR87 SC12 SHT 25 OF 82
P2A

PLCC CODE-3
DIRECT TRIP CHANNEL-1
OUT IN P2A
LKDT1 TB2 K101 K102 TB2
K131C K101 +VE -VE
2 1 25 25 CS

33
31 32
CSS1 PL13 PL14

TB2
35 BCU
FOR MAKE SPECIFIC TERMINAL REF SHT 81
PU
>BB/LBB TRIP MAIN CB

K133
42

51

>REMOTE TRIP MAIN CB BCU


IN NORMAL MODE
>REMOTE TRIP TBC CB
IN TRANSFER MODE 56

21M1
>MAIN-1 DEF OPTD
13

P2B

21M2
>MAIN-2 DEF OPTD
20
P2A
A/T A/C
T C
TTX4 K135
K131
>MANUAL TRIP MAIN CB
35 52CS
39

P5

A/T A/C
T C

>MANUAL TRIP TBC CB K135T K137T

P2A 52CS P2A

TTX1 TTX2
TB5 PU TB5
>BB/LBB TRIP TBC CB K131 K135T K137T
45 (B/B & LBB TRIP) 46
39 39
REF.DRG.NO. CPD KR87 SC14 SHT-09

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871226
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DIRECT TRIP SEND CIRCUIT (CH-1) DRG. NO.: CPD KR87 SC12 SHT 26 OF 82
P2B

PLCC CODE-3
DIRECT TRIP CHANNEL-2
OUT IN P2B
LKDT2 TB2 K201 K202 TB2
K231C K201 +VE -VE
2 1 25 25
32
CS
31

33
CSS2 35 PL33 PL34

TB2
FOR MAKE SPECIFIC TERMINAL REF SHT 81 P2A
P2A
BCU
PU
>BB/LBB TRIP MAIN CB
42

K233
51
BCU
>REMOTE TRIP MAIN CB
IN NORMAL MODE
>REMOTE TRIP TBC CB 56
IN TRANSFER MODE
21M1
>MAIN-1 DEF OPTD
13

P2B
21M2
>MAIN-2 DEF OPTD
20

P2A A/T A/C


T C
TTX3
K235
K231
>MANUAL TRIP MAIN CB
35 52CS
39

P5

A/T A/C
T C

>MANUAL TRIP TBC CB


52CS
P2A P2A
TTX2 TB5 PU TTX2
>BB/LBB TRIP TBC CB K231 K235T K237T TB5
47 48
39 (B/B & LBB TRIP)
39
REF.DRG.NO. CPD KR87 SC14 SHT-09

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871227
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 DIRECT TRIP SEND CIRCUIT (CH-2) DRG. NO.: CPD KR87 SC12 SHT 27 OF 82
P2A EQPT 86A
TYPE MVAJ205
K101
LOC P2A
06 K3
K103 K102 30 K3A
5 7
+VE 21M1 06 30
MAIN-1 PROTN
K3B
DEF TRIP,SOTF 9 11 TO TC-1 OF
MULTI PH./Z2,Z3 FAULTS K102 -VE
MAIN CB
13
27 86A 28 K3C
13 15

21M2
K403 K405A
MAIN-1 PROTN K103 36 6 8
DEF TRIP,SOTF
MULTI PH./Z2,Z3 FAULTS BCU (RESET) 36
19 K109
K405B
K102 10 12
25 86A 26 TO TC-1 OF
56 TBC CB
K405C
14 16

DIRECT TRIP
K103 K53
COMMAND RECEIVED 31
K53A
33 35
RX1,RX2 25 31
K53B
37 39 TO TC-2 OF
TB2 K101 TB2 K103 MAIN CB
FUTURE TRIP IF ANY K53C
37 38 41 43

K453 K455A
36 34 36
21M1(OPTO)
R86A 36
K101 K103A K455B
1 2 38 40
TO TC-2 OF
(3.3K)
TBC CB
12 K455C
42 44

P105T P137T TO LBB PROTN


38 38
18 20 TBC CB

S101 TO A/R BLOCK


23 S149 23
45 47 MAIN CB

S101T TO A/R BLOCK


37 S147 37 TBC CB
46 48

K9 K10
30
29 31
30 TO CLSG I/L
(MAIN CB)

K443 K449T TO CLSG I/L


36 36
30 32 (TBC CB)

P105 P123 TO LBB PROTN


41 41
2 4 MAIN CB
25 39 39 25
.
1 3

K105 K117 TO MAIN I


11 11
17 19 (86A OPTD)

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871228
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 TRIP RELAY CIRCUIT - GROUP-A DRG. NO.: CPD KR87 SC12 SHT 28 OF 82
EQPT 86B
P2B
TYPE MVAJ205
K201
LOC P2B
06
K3 K3A
K202 30 5 7
+VE 06 30
MAIN-2 PROTN K3B
DEF TRIP, SOTF 9 11 TO TC-1 OF
MULTI PH./Z2,Z3 FAULTS K202 -VE
MAIN CB
19 27 86B 28 K3C
13 15

MAIN-1 PROTN K403 K405A


DEF TRIP, SOTF K203 36 6 8
K201

MULTI PH./Z2,Z3 FAULTS BCU (RESET) 36


13 K405B
K202 10 12
25 86B 26 TO TC-1 OF
56 TBC CB
K405C
14 16
DIRECT TRIP
K203
COMMAND RECEIVED
RX1,RX2 25 K53 K53A
31 33 35
31
TB2
K53B
TB2 K203 37 39 TO TC-2 OF
FUTURE TRIP IF ANY 38 MAIN CB
37
K53C
41 43

21M2(OPTO)
K201
R86B K453
K229 K455A
1 2 36 34 36
(3.3K)
18 36
K455B
38 40
TO TC-2 OF
TBC CB
K455C
42 44

P105T P137T TO LBB PROTN


38 38
18 20 TBC CB

S101 S149 TO A/R BLOCK


23 23
45 47 MAIN CB

S101T S147 TO A/R BLOCK


37 37
46 48 TBC CB

K6 K9 TO CLSG I/L
30 29 31 30
(MAIN CB)

K441 K443 TO CLSG I/L


36 36
30 32 (TBC CB)

25 25 P105 P123 TO LBB PROTN


41 2 4 41
MAIN CB

K205 K205 K227 TO MAIN-2


18 1 3 18
OPTO I/P
. .
17 19

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871229
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 TRIP RELAY CIRCUIT - GROUP-B DRG. NO.: CPD KR87 SC12 SHT 29 OF 82
P2A
06

BASE FILE:
-VE TB3 CB 01
K1 +VE
+VE
1

FOR ALSTOM REF:


SCHEME TYPE: LINE
K2 CB 02
-VE
2
LKT1 TB3
K1A CB 03
2 1
3

SALES ORDER: 3269020733


PROTN TRIP/
21M1 CB 04
K3A POST CLOSE SUPVN
4 CB 05
K3B
13 13 5 CB 06
K3C

ENGG.REF.NO.: KR87
86A 6

28 28
P2B
21M2
195R
TB3
19 19 K31
B
7
86B

Dated 23.03.12
K32
195Y 8 CB 08
29 29
K33

P.O.NO.: LOA/5427PK067/ PCP/ 01


PU B
9

K34
42 42 195B 10 CB 10

PROJECT: POWERGRID 400/220kV DALTONGANJ S/S


86LO K35
B
11
PRECLOSE SUPVN.

23 23 K35A
12 CB 12

CUSTOMER: POWERGRID CORPORATION OF INDIA LTD


TB3 202-89AE
TB3
K3 FUTURE 20
ES1 ES1
TRIP
19 21
22 07 08 CB 13
195R
FOR MAKE SPECIFIC REF

ALSTOM T&D India


K3A 75
A
195Y

K3B 202-89CE1
A
195B
FOR MAKE SPECIFIC TERMINAL REF 57

ES2 ES2
LOCAL CLOSING I/L

ABCD
K3C
A 07 08 CB 14

PALLAVARAM CHENNAI 600043


CIRCUIT BREAKER 202-52 (TC-1)

P2B
FOR MAKE SPECIFIC REF 77

- Limited - AUTOMATION SAS


P2B A/T A/C
T C

35

BCU 52CS TB3


K21 CB 15R
PANEL TYPES: P2A, P2B

REMOTE TRIPPING-1
13
CB 15Y
SCHEMATIC DRAWING

K23
55 14
CB 15B
K25
15
TITLE: 220KV LINE-1 PROTECTION

K6 PU K7
DC +VE
42 16
86A 86LO BCU TB3
86B K9 K19 K27 AUTO RECLOSE
17 CB 16
CIRCUIT BREAKER CONTROL CKT. (TC-1)

55
29 28 23
BCU TB3
K29
REMOTE CLOSE
FILE: DR871230

55 18 CB 18
195R
A A/T A/C
P2B

K2
C T C
S101
B TC-1 FAULTY
195R 51
195Y S113 52CS
C
PREPARED BY:

A K2
C 35
MB
CHECKED BY: JKK
APPROVED BY: SSS

B 195Y S113 195R


C TB2 TB2
U57 U58
195B C
A K2
56 57
C 195B S113
C 195Y TB2
B U60 SPARE
LOC
TYPE

SCALE:

C
EQPT

58
REVISION:

--

195B TB2
Z

195R 195Y 195B U62


. . .
C
P2A

59
DATE: 29.08.2013
195 R,Y,B
MVAXM31

DRG. NO.: CPD KR87 SC12 SHT 30 OF 82


EQPT 295 R,Y,B

CIRCUIT BREAKER 202-52 (TC-2) TYPE MVAXM31


LOC P2B

REMOTE TRIPPING-2
FOR MAKE SPECIFIC TERMINAL REF 57 58

PROTN TRIP/
+VE POST CLOSE SUPVN PRECLOSE SUPVN.

+VE
-VE

CB 32Y

CB 32B
CB 32R
CB 26
CB 19

CB 20

CB 21

CB 28

CB 30
CB 22

CB 23

CB 24
P2B

13

14

15
12
TB3

10

11
1

8
7
4

9
5

TO BCU
K91
K89
K87

SPARE
K53C
K51A

K53A

K85A
K53B
K51

K52

K81

K82

K83

K84

K85

51

TB4

TB4

TB4
44

45

46
295Y

295B
295R

S101

U64

U66

U68
A/C

52CS

S115

S115

S115
A/T
T

35

295B
295Y
295R
295Y

295B
295R

C
C

U63
TB4

43
1
LKT2

BCU
2
K53

55
K53B
19
18
17

P2A

.
TB3

295B
295Y

A
13

28

19

29

42

23

K53C
K53A
21M2

.
FUTUTE
21M1

86LO
86A

86B

295R

295B
USE
PU

K52

K52

K52

295Y
A

295Y

295B
295R

C
C
13

28

19

29

42

23

.
A

A
B

B
P2A

P2A

295R
16
TB3
-VE
06

+VE

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871231
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 CIRCUIT BREAKER CONTROL CKT. (TC-2) DRG. NO.: CPD KR87 SC12 SHT 31 OF 82
P2A P2A
ISOCATOR 202-89L
ISOLATOR 202-89A
32
DC SUPPLY 06
DC SUPPLY
TBOG IS3
TBOG IS1 K801
K801 +VE
25 +VE 27 01
01 +VE -VE DC SUPPLY
+VE -VE DC SUPPLY
TBOG K802
K802 -VE
26
-VE 28 02
02

BCU-DOUG
BCU-DOUF
COMMON
COMMON 03
03

K801

K802
TBOG TBOG
K815 SG1 SG2
TBOF TBOF
K805 SF1 SF2 1 2
56
04 OPEN
1 56 2 OPEN
04
TBOG TBOG
K815 SG3 SG4
TBOF TBOF
K805 SF3 SF4 3 4
56
3 56 4 05 CLOSE
05 CLOSE

TBOG TBOG
K801 SG5 SG6
TBOF TBOF
K801 SF5 SF6 5 6
56 06
5 56 6
06 INTERLOCK
INTERLOCK

07
07
FOR MAKE SPECIFIC TERMINALS REF SHEET: 69
FOR MAKE SPECIFIC TERMINALS REF SHEET: 63
EARTH SWITCH 202-89LE1
ES2
EARTH SWITCH 202-89AE +VE
ES1 01
+VE DC SUPPLY
01 -VE
DC SUPPLY
02
-VE
TBOG TBOG
02 K801 SG7 SG8
7 56 8
K801
TBOF TBOF 03
SF7 SF8 INTERLOCK
7 56 8
03
INTERLOCK
32 04
FOR MAKE SPECIFIC TERMINALS REF SHEET: 77
04
FOR MAKE SPECIFIC TERMINALS REF SHEET: 75 EARTH SWITCH 202-89LE2
ES3
+VE
01
-VE
02
TBOG TBOG
K801 SG9 SG10
9 56 10 INTERLOCK
03

04
33
FOR MAKE SPECIFIC TERMINALS REF SHEET: 79

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871232
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 ISOLATOR / EARTH SWITCH CKT DRG. NO.: CPD KR87 SC12 SHT 32 OF 82
P2A P2A
ISOLATOR 202-89T ISOLATOR 202-89B
DC SUPPLY 32 DC SUPPLY 33

K801
TBOE IS4 K801
TBOE IS2
25 +VE 27 +VE
+VE -VE 01 +VE -VE 01
TBOE DC SUPPLY TBOE DC SUPPLY
K802 K802
26
-VE 28
-VE
02 02

BCU-DOUG BCU-DOUF
COMMON COMMON
03 03
TBOG TBOG TBOF TBOF
K825 SG11 SG12 K835 SF9 SF10
11 56 12 OPEN 9 56 10 OPEN
04 04
TBOG TBOG TBOF TBOF
K825 SG13 SG14 K835 SF11 SF12
13 56 14 11 56 12
05 CLOSE 05 CLOSE

TBOF TBOF
K801 SF13 SF14
13 56 14
06
INTERLOCK

07

FOR MAKE SPECIFIC TERMINALS REF SHEET: 72 FOR MAKE SPECIFIC TERMINALS REF SHEET: 66

33

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871233
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 ISOLATOR / EARTH SWITCH CKT DRG. NO.: CPD KR87 SC12 SHT 33 OF 82
BLANK SHEET

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871234
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BLANK SHEET DRG. NO.: CPD KR87 SC12 SHT 34 OF 82
P2A P2B

ODS/22/N/120/SRL2/PM/108
T A/T A/C C
ODS/08/N/90/SP/PM/102
K19 K29
TO CB CLOSING

OUT
30 30

IN
ODS/08/N/90/SP/PM/102 1P1 1P2
K135 K133
OUT 26 26 D/T CH-1
IN

1P3 1P4 . .
. .
. . 2P2 1P1 1P2
2P1
K235 K233 K205 K271
1P2 27 27 D/T CH-2 22 22
1P1 2P3 2P4
K105 K171 K205A K219 1P3 1P4
16 16 18 18 TO MAIN-2 SOTF . .
3P1 3P2
1P3 1P4 . .
. . 2P1 2P2
3P3 3P4 K201 K283
2P2 K105A K163 25 25
2P1 12 12 TO MAIN-1 SOTF
K101 K183 4P1 4P2 2P3 2P4
25 25 . . K205 K249
2P4 18 18
2P3 4P3 4P4
K205 K247 S101 S103 3P1 3P2
18 18 51 51 TO BCU
5P1 5P2 K231C K231
3P2 27 27
3P1 51
S101 S105
51 TO BCU
K131C K131 3P3 3P4
TB3 5P3 5P4 TB3
26 26 U149 U151 . .
3P3 3P4 SPARE
47 6P2 48
. .
6P1 4P1 4P2
K1A K21
30 30 TO CB TC-1 K105 K177
6P4 16 16
4P1 4P2 6P3
K205 K277 K1A K23 4P3 4P4
22 22 30 30 TO CB TC-1
7P1 7P2
4P3 4P4 K1A K25 CSS2
30 30
7P3 7P4 TO CB TC-1
CSS1 K51A K87
31 31 TO CB TC-2
8P1 8P2
K51A K89
31 31 TO CB TC-2
8P3 8P4
K51A K91
31 31 TO CB TC-2
9P1 9P2
. .

9P3 9P4
. .

10P1 10P2
. .

10P3 10P4
. .

11P1 11P2
. .

11P3 11P4

52CS

NOTE : 52CS SWITCH CB CLOSE WILL BE WITHOUT SYNCHRO CHECK.

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871235
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 SWITCH CONTACT DISTRIBUTION DRG. NO.: CPD KR87 SC12 SHT 35 OF 82
P2A

TO TBC BKR TRIP COIL-2


K403 TB5 K453 TB5

TO TBC BKR TRIP COIL-1


5

REF.DRG.NO.CPD
KR87 SC14 SHT-07
KR87 SC14 SHT-07
TTX2 1 TTX4

REF.DRG.NO.CPD
21M1 21M1
TB5 TB5
K403A K453A
MAIN-1 13 MAIN-1 13
6
2 21M1
21M1
TB5 TB5
K403B K453B
7
3
21M1 21M1
TB5 TB5
K403C K453C
8
4 39
39
86A 86A
GROUP-A 28 GROUP-A 28

P2B

21M2 21M2
MAIN-2
MAIN-2 19 19
21M2 21M2

21M2 21M2

86B 86B
GROUP-B 29 GROUP-B 29

P2B P2A
TTX4 TB5
K441T TO CLSG I/L
39 9
220KV TBC CB
K441 TB5
86B K443 86A K449T REF. DRG. NO.
29 28 10 KR87 SC14 SHT-06

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871236
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 TBC BREAKER (TRIP) CONTACT DISTRIBUTION DRG. NO.: CPD KR87 SC12 SHT 36 OF 82
P2A P2A P2B P2A

TO A/R INITIATION OF TBC BREAKER


TTX4 TB5
S103T S105T COX2
11
21M1 COX1 TB5
K561 K553 K409
21M1 39

TO A/R LOCKOUT TRIP RELAY OF TBC BREAKER


TB5 15
S139 14 16 K409

REF: KR87 SC14 SHT-11


MAIN-1 14
12
22
21M1
TB5
S141
13
21M1 TB5 P2B P2A PU
S143

REF: KR87 SC14 SHT-11


14
21M2 TBC BCU (A/R OFF)
TB5
K553
P2B 16
20
REF.REF: KR87 SC14 SHT-11
21M2
MAIN-2 P2A
20
TTX4 TB5
21M2 K561 K401A
17
39
21M2

P2A
TB5
S101T
P2B 18
P2A
TO BLOCK A/R TBC BREAKER

86B
TTX3
REF: KR87 SC14 SHT-11

GROUP-B TB1
E311 E11

TRANSFERRED VT SUPPLY
REF: KR87 SC14 SHT-09
29
31

LINE CVT SUPPLY


TB1
E331 E31
32
08
P2A TB1
E351 E51
86A TTX2 TB5 33
GROUP-A S145 TB1
19
E371 E71
28 34
39 39

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871237
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 TBC BREAKER (A/R) CONTACT DISTRIBUTION DRG. NO.: CPD KR87 SC12 SHT 37 OF 82
P2A
TB5
P105T
21
21M1 TTX3

TO TBC BKR LBB PROTN


P131T TB5
P111T

REF: KR87 SC14 SHT-07


MAIN-1 14
22
21M1
P133T TB5
P113T
23
21M1 TB5
P135T P115T
24

P137T TB5
P123T
25
39

P2B
21M2
MAIN-2 20
21M2

21M2

86B
GROUP-B
29

P2A
86A
GROUP-A
28

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871238
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 TBC BREAKER (LBB) CONTACT DISTRIBUTION DRG. NO.: CPD KR87 SC12 SHT 38 OF 82
P2A EQPT TTX1/X2/X3/X4
TYPE MVAJM14
28 TTX1 28 LOC P2A
+VE FROM BCU
NOTE K191 K102
-VE

NO CONTACTS - TRANSFER MODE 27 28


55 TTX2
NC CONTACTS - NORMAL MODE
TRANSFER POSITION K102
27 28
TTX3

K191 K102
27 28
TTX4

K102
27 28

FROM BCU
TTX1
K192 K102
25 26 TTX2
55
K102
NORMAL POSITION
TTX3 25 26

K192 K102
25 26 TTX4
K102
25 26

TTX1 K105T TTX2 TTX3 TTX4


K105 K133 K137T E311 E11 K219T K219
12 5 7
12 26 5 7
26 37 5 7
37 18 5 7
18

K129T K155 K231 K235T E331 E31 . .


12 9 11
12 27 9 11
27 37 9 11
37 9 11

K163 K143T S147 S145 E351 E51 K441T K441


12 12 37 13 15
37 37 13 15
37 36 36
13 15 13 15

K233 K237T E371 E71 K453A K455A


K165 K145T 27 17 19
27 37 17 19
37 36 36
17 19
12 17 19
12

K147 K147T K205 K205T P131T P111T K453B K455B


11 11 18 6 8
18 38 6 8
38 36 36
6 8 6 8

K403A K405A P133T P113T K453C K455C


K149 K149T 11 36 36 38 38 36 36
11 10 12
10 12 10 12 10 12

K151T K403B K405B P135T P115T S103T S105T


K151 36 36 38 38 37 37
11 14 16
11 14 16 14 16 14 16

K131 K135T K403C K405C P137T P123T K561 K401A


26 26 36 18 20
36 38 18 20
38 37 18 20
37
18 20

K105 K105A K205 K205A K231 K235 K131 K135


11 11 18 1 3 18 27 1 3
27 26 1 3
26
1 3

S101 S119A S119A S119B S119B S119C S119C S119 51


51 2 4 2 4 2 4 2 4

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871239
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 PROTECTION TRANSFER RELAYS CONTACTS DRG. NO.: CPD KR87 SC12 SHT 39 OF 82
EQPT MICOMP743
TYPE PU
LOC P2B

LINE SIDE
P2B
R-PH Y-PH B-PH

202-CT 202-CT MB
P1 TB1 PU
TB1-1 BLKE B13 B77
S1 S1 S1 1S1-R B11 A3 A2
S3 R3
Imag < 50-25mA AT Vk/4

TB1-8 21
1S1-Y
RATIO : 1600-800/1A

TB1-15 22
1S1-B BLKE B33
Rct = 8-4 Ohms
Vk=1600-800V

S2 S2 S2 B31 A6 A5
1S2-R TB1-2 23 S4 R4
CLASS : PS
CORE-1

1S2-Y TB1-9 24
B51 BLKE B53 A9 A8
S3 S3 S3 1S2-B TB1-16 R5
25 S5
1S3-R TB1-4 26
1S3-Y TB1-11 B71 BLKE B73 A11 A12
S6 R6
P2 1S3-B TB1-18
27

28

B75S
1
ETL4
BUS SIDE

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871240
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BUS BAR PROTN - AC CKT DRG. NO.: CPD KR87 SC12 SHT 40 OF 82
BASE FILE:
FOR ALSTOM REF:
SCHEME TYPE: LINE

SALES ORDER: 3269020733


TB4
P2B

P101
1
P743IP1
DC SUPPLY
BLKE PU
FROM BUSBAR PANEL
S2 R2
AUX.VOLTAGE

ENGG.REF.NO.: KR87
P105 - P104 BLKE TB4
G2 G1 P102
2
202-52 FOR MAKE SPECIFIC TERMINAL REF 58 59 R1 S1
CB CB
-
L1
TB4
39 40 TB4 P107 P104
B2 B1 MAIN CB
3 4
P105 41 42 CLOSED
43 44 L2
CB CBCB CB CB TB4 P109 P104 MAIN CB
B4 B3
5 OPEN
57 58 59 60 61 62

Dated 23.03.12
L3
P104
P111 B6 B5 LBB INITIATION PH-R

P.O.NO.: LOA/5427PK067/ PCP/ 01


SINGLE PHASE LBB INITIATION
L4
CONTACTS MAIN-1 & 2 P113 P104
B8 B7
LBB INITIATION PH-Y

L5

PROJECT: POWERGRID 400/220kV DALTONGANJ S/S


P115 P104
B10 B9 LBB INITIATION PH-B
13 19
L6
86A
P123 P104

CUSTOMER: POWERGRID CORPORATION OF INDIA LTD


B12 B11 LBB INITIATION 3 PHASE
P2B 28
86B L7
P104
29 B14 B13 SPARE
86LO

ALSTOM T&D India


L8
TB4 TB4 P119 P104
B16 B15 SPARE
6 23 7

L9
TB4 P121 P104

ABCD
C2 C1 SPARE
8

PALLAVARAM CHENNAI 600043


L10
TB4 P125 P104
C4 C3 SPARE
9

- Limited - AUTOMATION SAS


202-89A L11
IS1 IS1 TB4 P104
TB4 P127 C6 C5 ISOL CLOSED
11
10
10 11

L12
IS1 IS1 TB4 P129 P104
C8 C7 ISOL OPEN
12
38 39
FOR MAKE SPECIFIC TERMINAL REF 63 64
202-89B L13
PANEL TYPES: P2A, P2B

TB4 IS2 IS2 TB4 P131 P104


SCHEMATIC DRAWING

C10 C9 ISOL CLOSED


14
13
10 11

L14
IS2
TITLE: 220KV LINE-1 PROTECTION

IS2 TB4 P133 P104


BUS BAR PROTN - OPTO CKT

C12 C11 ISOL OPEN


15
38 39
FOR MAKE SPECIFIC TERMINAL REF 66 67
202-89T L15
TB4 IS4 IS4 TB4 P135 P104 ISOL CLOSED
C14 C13
17
16
10 11

L16
IS4 IS4 P104
FILE: DR871241

TB4 P137 ISOL OPEN


C16 C15
18
38 39
FOR MAKE SPECIFIC TERMINAL REF 72 73
PREPARED BY:
MB
CHECKED BY: JKK
APPROVED BY: SSS
SCALE:
REVISION:

--
Z
DATE: 29.08.2013

DRG. NO.: CPD KR87 SC12 SHT 41 OF 82


BASE FILE:
FOR ALSTOM REF:
SCHEME TYPE: LINE
P2B

P743OP1

SALES ORDER: 3269020733


PU
WATCH DOG
. G11
.
G12

WATCH DOG
K205
K205 K241

ENGG.REF.NO.: KR87
18 G13 G14 18 RELAY HEALTHY

(TRIP A)
RL1
K11 F1 K3A
F2

(TRIP B)
RL2
K11 F3 K3B
F4 TO MAIN CB TC-1

(TRIP C)
30

Dated 23.03.12
K3 RL3
BLKE K11 K3C
F5 F6
30 R7
S7

P.O.NO.: LOA/5427PK067/ PCP/ 01


RL4
K61 F7 K53A
F8

RL5
K61 K53B

PROJECT: POWERGRID 400/220kV DALTONGANJ S/S


F9 F10 TO MAIN CB TC-2

RL6 31
K53 BLKE K61 K53C
F11 F12
31 R8
S8

CUSTOMER: POWERGRID CORPORATION OF INDIA LTD


RL7
F13 .
K131 BLKE K131D TO DIRECT TRIP CH-1
26 F15 F14 K133 26
S9 R9 BB/LBB OPTD
RL8
F16 .

ALSTOM T&D India


K231 BLKE K231D
TO DIRECT TRIP CH-2
27 F18 F17 K233 27
S10 R10 P743OP2 BB/LBB OPTD
PU
K105 RL9
K105 E1 K123
11 E2 11 TO DR B/B OPTD

ABCD
PALLAVARAM CHENNAI 600043
K105A RL10
K105A E3 K155
12 E4 12 TO D/R - LBB OPTD

- Limited - AUTOMATION SAS


S101 RL11
LKPU-1 S101D E5 S149 TO A/R BLOCK
23 1 2 E6 23 BB/ LBB OPERATED

RL12
TB4 U21 U22 TB4 GENERAL TRIP
E7 E8
49 50
(FOR RELAY TESTING)

RL13
PANEL TYPES: P2A, P2B

. E9 .
E10
SCHEMATIC DRAWING

RL14
. E11 .
TITLE: 220KV LINE-1 PROTECTION

E12

RL15
E13 K6 30 TO CB CLOSING INTERLOCK
K7 K7
30 E15 E14 .
BUS BAR PROTN - OUTPUT RELAYS CKT

RL16
E16 .
.
E18 E17 .
FILE: DR871242
PREPARED BY:
MB
CHECKED BY: JKK
APPROVED BY: SSS
SCALE:
REVISION:

--
Z
DATE: 29.08.2013

DRG. NO.: CPD KR87 SC12 SHT 42 OF 82


220KV MAIN BUS-1 220KV MAIN BUS-1
220KV MAIN BUS-2 220KV MAIN BUS-2
203-89BE2
203-89AE2

202-89A 203-89A 203-89B 205-89A 205-89B 201-89A 201-89B


202-89B 205-89AE
203-89AE1 203-89BE1
202-89AE
201-89AE
203-52
202-52 205-52 201-52

205-89CE1 201-89CE1
202-89CE1

202-89C 205-89C 201-89C


205-89CE2 201-89CE2
202-89CE2

202-89T 201-89T
220KV TRANSFER BUS

LINE 220KV SIDE OF ICT

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871243
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BLANK SHEET DRG. NO.: CPD KR87 SC12 SHT 43 OF 82
ISOLATOR 202-89A

*
20389AE2 OPEN POSITION

202-52 OPEN POSITION


ISOLATOR 202-89C
202-89AE OPEN POSITION
& 202-52 OPEN POSITION
202-89B OPEN POSITION
202-89A INTERLOCK 202-89AE OPEN POSITION
202-89CE1 OPEN POSITION / & PERMISSIBLE
& 202-89C INTERLOCK
PERMISSIBLE
202-52 CLOSE POSITION 202-89CE1 OPEN POSITION

202-89B CLOSE POSITION 202-89CE2 OPEN POSITION

203-89A CLOSE POSITION & 202-89C CLOSE


& ORDER
203-89B CLOSE POSITION 202-89C CLOSE REQ.
203-52 CLOSE POSITION

& 202-89C OPEN


ORDER
202-89A CLOSE 202-89C OPEN REQ.
& ORDER
202-89A CLOSE REQ.

& 202-89A OPEN


ORDER
202-89A OPEN REQ. ISOLATOR 202-89T

205-89CE2 OPEN POSITION


ISOLATOR 202-89B
*20389BE2 OPEN POSITION 202-89CE2 OPEN POSITION
& 202-89T INTERLOCK
PERMISSIBLE
202-52 OPEN POSITION 205-52 OPEN POSITION
2n-89T OPEN POSITION
202-89AE OPEN POSITION (ALL BAY TRANSFER ISOL)
&
202-89A OPEN POSITION
202-89B INTERLOCK 202-89T CLOSE
202-89CE1 OPEN POSITION / & PERMISSIBLE & ORDER
202-89T CLOSE REQ.
202-52 CLOSE POSITION

202-89A CLOSE POSITION 202-89T OPEN


& ORDER
203-89A CLOSE POSITION & 202-89T OPEN REQ.

203-89B CLOSE POSITION


203-52 CLOSE POSITION

& 202-89B CLOSE


ORDER
202-89B CLOSE REQ.

202-89B OPEN * THIS INTERLOCK SHALL ALSO BE DONE


& ORDER THRU HARDWIRING AT SWITCHYARD.
202-89B OPEN REQ.

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871244
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BCU INTERLOCK LOGIC CKT DRG. NO.: CPD KR87 SC12 SHT 44 OF 82
BUS VOLTAGE SELECTION EARTH SWITCH 202-89AE
202-89A OPEN POSITION
202-89A CLOSE 220kV BUS1 SELECT 202-89AE INTERLOCK
202-89B OPEN POSITION &
PERMISSIVE
202-89C OPEN POSITION
202-89B CLOSE
& 220kV BUS2 SELECT
202-89A OPEN
EARTH SWITCH 202-89CE2

202-89C OPEN POSITION


202-89T OPEN POSITION & 202-89CE2 INTERLOCK
PERMISSIVE
DIRECT TRIP SEND (MANUAL TRIP) UNDER VOLTAGE OPERATED(LINE DEAD)

202-52 OPEN ORDER EARTH SWITCH 202-89CE1


&
NORMAL MODE 202-89C OPEN POSITION
& 202-89CE1 INTERLOCK
202-89A OPEN POSITION PERMISSIVE
OR DIRECT TRIP SEND CH-1
202-89B OPEN POSITION
TRANSFER MODE DIRECT TRIP SEND CH-2
&
205-52 OPEN ORDER

CIRCUIT BREAKER (REMOTE OPERATION)

BUS BAR PROTECTION RELAY OPERATED


PROTECTION GP. A TRIP RELAY OPERATED /

PROTECTION GP. B TRIP RELAY OPERATED

& 202-52 CLOSE ORDER


202-52 REMOTE MODE * CIRCUIT BREAKER (LOCAL OPERATION)
D/L CHARGING MODE
& 202-52 CLOSE REQUEST &
DEAD LINE
OR 202-52 LOCAL MODE
LIVE LINE CHARGING MODE 202-89CE1 CLOSE POSITION & 202-52 OPEN/CLOSE PERMISSIVE
&
CHECK SYNCH. 202-52 OPEN POSITION 202-89AE CLOSE POSITION

202-52 REMOTE MODE 202-52 OPEN ORDER-1 *THIS INTERLOCK SHALL BE DONE THRU HARDWIRING AT SWITCHYARD
&
202-52 OPEN REQUEST 202-52 OPEN ORDER-2

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871245
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BCU INTERLOCK LOGIC CKT DRG. NO.: CPD KR87 SC12 SHT 45 OF 82
BLANK SHEET

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871246
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BLANK SHEET DRG. NO.: CPD KR87 SC12 SHT 46 OF 82
BLANK SHEET

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871247
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BLANK SHEET DRG. NO.: CPD KR87 SC12 SHT 47 OF 82
FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z
SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871248
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BCU CARD DETAILS DRG. NO.: CPD KR87 SC12 SHT 48 OF 82
P2A EQPT BCU
TYPE C264
BCU LOC P2A
C264 TMU 220

BCU
R D13 BLKF D14 15 16 D73 BCU
S7 R7 C264 BIU241
BCU
Y D33 BLKF D34 11 D73
12
S8 R8
CT FROM METG CKT WATCH DOG
A5 .
09
B D53 BLKF
D54 7 8 D73
A4 K223 BCU HEALTHY
S9 R9

A6 K205 18'

N D71 BLKF D72 3 4 D73


S10 R10

RS232 / 12
RS485 RXD/TB

13
GND

14
R E312 BLKF E313 21 RXD/TA
S3 R3

22
RS232 /
RS422
RS485
Y E332 BLKF E333 23 15
S4 R4 GND
LINE VT
16 07
SUPPLY CTS
24 DC SUPPLY
09 17
RXD/TB

18
TXD/TA

B E352 BLKF E353 19


25 RTS/RB
S5 R5
20
RA
N E372 BLKF E373 26 21
DCD
S6 R6
22

TB1 Y TB2
E631A FS631A E632A BLKF E635A 27 V Aux A23 S101
1 2 +ve 39
S1 R1 50
220KV BUS-1 VT 51 A24 S102
(METERING CORE) TB1 N
-ve 40
E671A LK671A 28
REF CPD KR87 SC13 SHT-06 1 2
52
TB1 Y E631B FS631B E632B BLKF E635B 19
1 2 S2 R2
220KV BUS-2 VT 53
(METERING CORE) TB1 N E671B LK671B 20
REF CPD KR87 SC13 SHT-07 1 2
54

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871249
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BCU CT/PT & AUX SUPPLY CKT DRG. NO.: CPD KR87 SC12 SHT 49 OF 82
P2A P2A P2A
S101 S102 S101 S102
49 BCU 49 BCU 49
49 2x-52
DIUP DIUO

202-52 22

TBIP INPUT 1 TBIO INPUT 1 202-52


TBIP CB CB
1 202-52 TBIO CB CB
1 CB TROUBLE
1 5
1 CB R PH OPEN 1 5
1
52 TBIP 117 118 TBIO
51
3
3 3
3
TBIP INPUT 2 21 202-52 TBIO INPUT 2 21 202-52
CB CB 2 2
2 CB R PH CLOSED 2 CB TROUBLE
34 6 6
33

TBIP INPUT 3 202-52 TBIO INPUT 3 202-52

FOR MAKE SPECIFIC TERMINAL REF SHT 58,60,63,64,66,67,72,73,75


CB CB 4 4
4 CB Y PH OPEN 4 CB TROUBLE
54 7 7
53
6
6 6
6
CB TBIP INPUT 4 202-52 TBIO INPUT 4 202-52
CB 5 5
5 CB Y PH CLOSED 5 CB TROUBLE
35 36 8 8

202-89A
CB CB TBIP INPUT 5 202-52 TBIO IS1-36 IS1-37 TBIO INPUT 5 202-89A
7 7
9
7 CB B PH OPEN 2 9
7 ISOLATOR OPEN
55 56
9 9 9 9
TBIP
TBIP 8
INPUT 6 202-52 IS1-08 IS1-09 TBIO 8
INPUT 6 202-89A
CB CB CB B PH CLOSED ISOLATOR CLOSED
2 8 8
38 10 10
37
202-89AE 202-89AE
TBIP INPUT 7 202-52 ES1-17 ES1-18 TBIO INPUT 7
10 CB TROUBLE 10 EARTH SWITCH OPEN
10 10
11 11
12 12 12 12
TBIP INPUT 8 202-52 ES1-05 ES1-06 TBIO INPUT 8 202-89AE
CB CB 11 11
11 CB TROUBLE 11 EARTH SWITCH CLOSED
12 12
93 94
202-52
202-89B
TBIP INPUT 9 TBIO IS2-36 IS2-37 TBIO INPUT 9 202-89B
CB CB
13 13 CB TROUBLE 13 13 ISOLATOR OPEN
13 3 13
95 96 15 15
TBIP 15 15
TBIP INPUT 10 202-52 IS2-08 IS2-09 TBIO INPUT 10 202-89B
3
CB CB 14 CB TROUBLE 14 ISOLATOR CLOSED
14 14
14 14
97 98
202-52 202-89T
TBIP INPUT 11 IS4-36 IS4-37 TBIO INPUT 11 202-89T
16 16 CB TROUBLE 16 16
ISOLATOR OPEN
15 TBIP 15 TBIO
18
18 18
18
TBIP INPUT 12 22 202-52 TBIO INPUT 12 22 202-89T
TBIP 17 IS4-08 IS4-09 17
17 CB TROUBLE 17 ISOLATOR CLOSED
16 16
4

TBIP INPUT 13 202-52 TBIO INPUT 13


CB CB
19 CB TROUBLE 19
17
19
17
19 SPARE
103 104 TBIP TBIO
21
21 21
21
TBIP
INPUT 14 23 202-52 TBIO
INPUT 14 23
20 CB TROUBLE . 20 SPARE
20 20
18 18
AC - KIOSK
TBIP INPUT 15 202-52 TBIO TBIO INPUT 15
22 CB TROUBLE . 22
22 22
19 TBIP 4 19 TBIO
24 24 FIRE DETECTED #
24 202-52 24
TBIP INPUT 16 24 TBIO INPUT 16 24
CB CB 23 23
23 CB TROUBLE .
23
20 20
109 110 AC COMPRESSOR-1 & 2 ON #
PREFAB CABLE PREFAB CABLE
51 51
22 FERRULE IDENTIFICATION FERRULE IDENTIFICATION
# NOTE : APPLICABLE FOR ONE CIRCUIT IN EACH KIOSK
FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z
SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871250
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BCU - DIGITAL INPUT CKT DRG. NO.: CPD KR87 SC12 SHT 50 OF 82
P2A P2A P2A
S101 S102 S101 S102
50 BCU 50 50 BCU 50
DIUN DIUM

TBIM A/T A/C


202-89C 1 T C
TBIN IS3-36 IS3-37 TBIN INPUT 1 TBIM INPUT 1
1 S103 1 EMERGENCY/MANUAL
1 202-89C 1 CB CLOSE
1 5 TBIN 35 5 TBIM
3
3 ISOLATOR OPEN 3
3
TBIN INPUT 2 21 TBIM INPUT 2 21
IS3-08 IS3-09 2 S105 2
2 2 EMERGENCY/MANUAL
6 202-89C 35 6 CB TRIP
ISOLATOR CLOSED TBIM 52CS
202-89CE1 2
TBIN ES2-17 ES2-18 TBIN INPUT 3 80DC1 TBIM INPUT 3

, ,77,79
4 S107 4
4 4 SOURCE-1 FAIL
2 7 202-89CE1 07 7
6 6

FOR MAKE SPECIFIC TERMINAL REF SHT 6970


6 6
ES2-05 ES2-06 INPUT 4
EARTH SWITCH OPEN INPUT 4
TBIN
5 80DC2 S109
TBIM
5 SOURCE-2 FAIL
5 5
8 07 8
202-89CE1
202-89CE2 EARTH SWITCH CLOSED 86LO
ES3-17 ES3-18 TBIN INPUT 5 TBIM INPUT 5
7 S111 7
7 7
9 202-89CE2 23 9 A/R LOCK OUT RELAY OPTD
9 9 EARTH SWITCH OPEN 9 9
INPUT 6 INPUT 6
ES3-05 ES3-06 TBIN 8 195R/Y/B TBIM 8
S113
8 8
10 202-89CE2 30 10 CB TC-1 FAULTY
EARTH SWITCH CLOSED
TBIN 10 INPUT 7 295R/Y/B S115
TBIM 10 INPUT 7
10 10 CB TC-2 FAULTY
11 SPARE 31 11
12 12 12 12
TBIN INPUT 8 TBIM INPUT 8
11 S117 11
11
SPARE 11 SPEECH CH. FAIL
12 22 12

TBIN INPUT 9 TBIM INPUT 9


13 TTX1 TTX2 TTX3 TTX4 S119 13
13 SPARE 13 BAY IN TRANSFER MODE
13 39 13
TBIN 15 TBIM 15
15 15
TBIN INPUT 10 TBIM INPUT 10
3 14 3
S149 14
14 SPARE 14 A/R BLOCK
14 23 14

TBIN INPUT 11 TBIM INPUT 11


S145A 16 16 A/R INITIATION - R PH . 16 16
15 TBIN 15 TBIM
18
18 18
18
INPUT 12 22 INPUT 12 22
TBIN 17 TBIM 17
A/R INITIATION CONTACTS S145B
17 A/R INITIATION - Y PH .
17 SPARE
FROM MAIN-1 & MAIN-2 16 16

TBIN INPUT 13 TBIM INPUT 13


S145C 19 A/R INITIATION - B PH K133 19
19 19
14 20 17 TBIN 26 17 TBIM
21
21 21
21
INPUT 14 23 INPUT 14 23 26
TBIN
20 SPARE .
TBIM
20
20 20 DIRECT TRIP SEND CH-1
18 18

TBIN TBIN INPUT 15 TBIM TBIM INPUT 15


22 SPARE K233 22
22 22
4 19 TBIN 4 27 19 TBIM
24 24 24 24
TBIN INPUT 16 24 TBIM INPUT 16 24 27
23 . 23
20
23 SPARE 20
23
DIRECT TRIP SEND CH-2
PREFAB CABLE PREFAB CABLE
FERRULE IDENTIFICATION FERRULE IDENTIFICATION

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871251
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BCU - DIGITAL INPUT CKT DRG. NO.: CPD KR87 SC12 SHT 51 OF 82
BLANK SHEET

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871252
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BLANK SHEET DRG. NO.: CPD KR87 SC12 SHT 52 OF 82
BLANK SHEET

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871253
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BLANK SHEET DRG. NO.: CPD KR87 SC12 SHT 53 OF 82
BLANK SHEET

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871254
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BLANK SHEET DRG. NO.: CPD KR87 SC12 SHT 54 OF 82
P2A

BCU BCU
DOUD DOUE

TBOD TBOD TBOE TBOE


K407A 1 2 K407 K19 1 2 K29
1 2 A/R OFF/DISABLED 1 2 CB CLOSE
23 1 2 23 30 1 2 30
OP1 TO A/R L/O CKT OP1

TBOD TBOD TBOE TBOE


K105A 3 4 K165 K1A 3 4 K21
3 3 4 4 A/R OPTD TO 21M1 30 3 3 4 4 30 CB TRIP TC-1
12 OP2 12 OP2
FOR DR

TBOD TBOD TBOE TBOE


K401 5 6 K407 5 6 K23
23 5 5 6 6 23 TO A/R L/O TRIP 5 5 6 6 30 CB TRIP TC-1
OP3 OP3

TBOD TBOD TBOE TBOE


K19 7 8 K27 7 8 K25
30 7 7 8 8 30
MAIN CB AUTO RECLOSE 7 7 8 8 30 CB TRIP TC-1
OP4 OP4

TBOD 9 10 TBOD TBOE 9 10 TBOE


K51A K87
9 10 SPARE 9 10 CB TRIP TC-2
9 OP5 10 31 9 OP5 10 31

TBOD 11 12 TBOD TBOE 11 12 TBOE


K89
11
11 12 12
SPARE 11
11 12 12 CB TRIP TC-2
OP6 OP6 31

TBOD 13 14 TBOD TBOE 13 14 TBOE


K91
13
13 14 14
SPARE 13
13 14 14 CB TRIP TC-2
OP7 OP7 31

TBOD 15 16 TBOD TBOE 15 16 TBOE


15
15 16
16
SPARE 15
15 16
16
SPARE
OP8 OP8
TBOD TBOE
20 20 20 20
20 20
TBOD K101 TBOE K191
21 19 21 19
21 19 SPARE 39 21 19 39 TRANSFER MODE
21 19 21 19
OP9 OP9

TBOD TBOE
23 23
23 23
23 23
TBOD K101 TBOE K192
24 22 24 22 NORMAL MODE
24 22 39 24 22 39
24 22 SPARE 24 22
OP10 OP10
PREFAB CABLE PREFAB CABLE
FERRULE IDENTIFICATION FERRULE IDENTIFICATION

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871255
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BCU - DIGITAL OUTPUT CKT DRG. NO.: CPD KR87 SC12 SHT 55 OF 82
P2A

BCU BCU
DOUF DOUG
SF1 SF2 SG1 SG2 ISOLATOR 202-89C OPEN
1 2 ISOLATOR 202-89A OPEN 1 2
32 1 2 32 32 1 2 32
OP1 OP1

SF3 SF4 SG3 SG4


3 4 ISOLATOR 202-89A CLOSE 3 4 ISOLATOR 202-89C CLOSE
32 3 4 32 32 3 4 32
OP2 OP2

SF5 SF6 SG5 SG6


5 6 TO ISOLATOR 202-89A 5 6 TO ISOLATOR 202-89C
32 5 6 32 32 5 6 32
I/L PERMISSIVE I/L PERMISSIVE
OP3 OP3

SF7 SF8 SG7 SG8


7 8 EARTH SWITCH 202-89AE 7 8 EARTH SWITCH 202-89CE1
32 7 8 32 32 7 8 32
OP4 I/L PERMISSIVE OP4 I/L PERMISSIVE

SF9 9 10 SF10 ISOLATOR 202-89B OPEN SG9 9 10 SG10


33 9 10 33 32 9 10 32 EARTH SWITCH 202-89CE2
OP5 OP5 I/L PERMISSIVE

SF11 11 12 SF12 SG11 11 12 SG12


33 11 12 33 ISOLATOR 202-89B CLOSE 33 11 12 33 ISOLATOR 202-89T OPEN
OP6 OP6

SF13 SF14 SG13 SG14


13 14 TO ISOLATOR 202-89B 13 14
33 13 14 33 33 13 14 33 ISOLATOR 202-89T CLOSE
OP7 I/L PERMISSIVE OP7

K101 TBOF K109 TBOG TBOG


15 16 K833T 15 16 K801A
28
15
15 16 16
28 TRIP RELAY GROUP-A RESET
15
15 16 16 ISOLATOR 202-89T
OP8 OP8 I/L PERMISSIVE TO TBC PANEL
TBOF TBOG REF. CPD KR87 SC14 SHT-18
20 20 20 20
20 20
K201 TBOF K207 K131 TBOG K133
21 19 21 19
29 21 19 29 TRIP RELAY GROUP-B RESET 26 21 19 26 DIRECT TRIP CH-1
21 19 21 19
OP9 OP9 MAIN / TBC CB MANUAL TRIP
TBOF TBOG
23 23
23 23
23 23
TBOF K231 TBOG K233
K401 24 22 K409A 24 22
23 24
24 22 22 TO A/R L/O TRIP RELAY RESET
27
24
24 22 22
27 DIRECT TRIP CH-2
23
OP10 OP10 MAIN / TBC CB MANUAL TRIP
PREFAB CABLE PREFAB CABLE
FERRULE IDENTIFICATION FERRULE IDENTIFICATION

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871256
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 BCU - DIGITAL OUTPUT CKT DRG. NO.: CPD KR87 SC12 SHT 56 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR ALSTOM MAKE

DRG.No. E1511000

CB-01 30 P2A DC SUPPLY-1, +VE TB4-05

CB-02 30 P2A DC SUPPLY-1, -VE TB4-06

CB-03 30 P2A

CB-04 30 P2A PROTN TRIP / POST CLOSE SUPVN TC-1 TB1-06

CB-05 30 P2A PROTN TRIP / POST CLOSE SUPVN TC-1 TB2-06

CB-06 30 P2A PROTN TRIP / POST CLOSE SUPVN TC-1 TB3-06

CB-07

CB-08 30 P2A PRE CLOSE SUPVN TB1-08

CB-09

CB-10 30 P2A PRE CLOSE SUPVN TB2-08

CB-11

CB-12 30 P2A PRE CLOSE SUPVN TB3-08

CB-13 30 P2A LOCAL CLOSING I/L TB4-13

CB-14 30 P2A LOCAL CLOSING I/L TB4-12

CB-15 30 P2A REMOTE TRIPPING-1 TB4-14

CB-16 30 P2A SELECTED DC TB4-15

CB-17 AUTO RECLOSE TB4-09

CB-18 30 P2A REMOTE CLOSE TB4-10

CB-19 31 P2B DC SUPPLY-2, +VE TB4-07

CB-20 31 P2B DC SUPPLY-2, -VE TB4-08

CB-21 31 P2B

CB-22 31 P2B PROTN TRIP / POST CLOSE SUPVN TC-2 TB1-21

CB-23 31 P2B PROTN TRIP / POST CLOSE SUPVN TC-2 TB2-21

CB-24 31 P2B PROTN TRIP / POST CLOSE SUPVN TC-2 TB3-21

CB-25

CB-26 31 P2B PRE CLOSE SUPVN TB1-23

CB-27

CB-28 31 P2B PRE CLOSE SUPVN TB2-23

CB-29

CB-30 31 P2B PRE CLOSE SUPVN TB3-23

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871257
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC CB (202-52) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 57 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR ALSTOM MAKE

CB-31 DRG.No. E1511000

CB-32 31 P2B REMOTE TRIPPING-2 TB4-16

CB-33 50 P2A NO CONTACT TB5-01

CB-34 50 P2A NO CONTACT TB5-02

CB-35 50 P2A NO CONTACT TB6-01

CB-36 50 P2A NO CONTACT TB6-02

CB-37 50 P2A NO CONTACT TB7-01

CB-38 50 P2A NO CONTACT TB7-02

CB-39 41 P2A NO CONTACT TB5-03

CB-40 41 P2A NO CONTACT TB5-04

CB-41 41 P2A NO CONTACT TB6-03

CB-42 41 P2A NO CONTACT TB6-04

CB-43 41 P2A NO CONTACT TB7-03

CB-44 41 P2A NO CONTACT TB7-04

CB-45 NO CONTACT TB5-05

CB-46 NO CONTACT TB5-06

CB-47 NO CONTACT TB6-05

CB-48 NO CONTACT TB6-06

CB-49 NO CONTACT TB7-05

CB-50 NO CONTACT TB7-06

CB-51 50 P2A NC CONTACT TB5-09

CB-52 50 P2A NC CONTACT TB5-10

CB-53 50 P2A NC CONTACT TB6-09

CB-54 50 P2A NC CONTACT TB6-10

CB-55 50 P2A NC CONTACT TB7-09

CB-56 50 P2A NC CONTACT TB7-10

CB-57 41 P2A NC CONTACT TB5-11

CB-58 41 P2A NC CONTACT TB5-12

CB-59 41 P2A NC CONTACT TB6-11

CB-60 41 P2A NC CONTACT TB6-12

CB-61 41 P2A NC CONTACT TB7-11

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871258
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC CB (202-52) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 58 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR AREVA MAKE

CB-62 41 P2A NC CONTACT TB7-12

CB-63 11 P2A NC CONTACT TB5-13

CB-64 11 P2A NC CONTACT TB5-14

CB-65 11 P2A NC CONTACT TB6-13

CB-66 11 P2A NC CONTACT TB6-14

CB-67 11 P2A NC CONTACT TB7-13

CB-68 11 P2A NC CONTACT TB7-14

CB-69 NC CONTACT TB5-15

CB-70 NC CONTACT TB5-16

CB-71 NC CONTACT TB6-15

CB-72 NC CONTACT TB6-16

CB-73 NC CONTACT TB7-15

CB-74 NC CONTACT TB7-16

CB-75 NC CONTACT TB5-29

CB-76 NC CONTACT TB5-30

CB-77 NC CONTACT TB6-29

CB-78 NC CONTACT TB6-30

CB-79 NC CONTACT TB7-29

CB-80 NC CONTACT TB7-30

CB-81 NC CONTACT TB5-31

CB-82 NC CONTACT TB5-32

CB-83 NC CONTACT TB6-31

CB-84 NC CONTACT TB6-32

CB-85 NC CONTACT TB7-31

CB-86 NC CONTACT TB7-32

CB-87 NC CONTACT TB5-33

CB-88 NC CONTACT TB5-34

CB-89 NC CONTACT TB6-33

CB-90 NC CONTACT TB6-34

CB-91 NC CONTACT TB7-33

CB-92 NC CONTACT TB7-34

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871259
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC CB (202-52) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 59 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION
TERMINAL FOR ALSTOM MAKE
CB-93 50 P2A (CB TROUBLE) CB DC SUP1
FAIL/DC1 FAIL TB4-28 TB4-29
CB-94 50 P2A

CB-95 50 P2A (CB TROUBLE) CB OPERATION L/O


GRB/( TRIP L/O OIL PRESSURE)/
TB4-24 TB4-25
CB-96 50 P2A CLOSING L/O OIL PRESSURE

CB-97 50 P2A (CB TROUBLE) AC SUPPLY FAIL /


TB4-32 TB4-33
(MOTOR O/L)/MOTOR MCB TRIP/
CB-98 50 P2A AC SUPPLY2 FAIL TB4-34 TB4-35
CB-99 50 P2A
(CB TROUBLE)
50 P2A (SF6 GAS L/O POLEA/ B/C) NA
CB-100

CB-101 50 P2A
(CB TROUBLE) N2 LOCKOUT
NA
CB-102 50 P2A

CB-103 P2A
50 (CB TROUBLE) CB POLE DISC OPTD/
P2A (LOSS OF N2 POLEA/ B/C) TB4-26 TB4-27
CB-104 50
CB-105 50 P2A (CB TROUBLE) TRIP LOCKOUT
(SF6/OIL/N2) NA
CB-106 50 P2A

CB-107 50 P2A (CB TROUBLE) CB OPERATION


L/O GRA / (AR L/O OIL PR) TB4-22 TB4-23
CB-108 50 P2A

CB-109 50 P2A (CB TROUBLE) CB DC SUP2


FAIL/DC2 FAIL TB4-30 TB4-31
CB-110 50 P2A
CB-111 50 P2A (CB TROUBLE) SF6 GAS
REPLENISHMENT ALARM/ TB4-20 TB4-21
CB-112 50 P2A (LOSS OF SF6 GAS POLEA/ B/C)
CB-113 50 P2A (CB TROUBLE) LOW AIR
PRESSURE/PD RELAY TRIP NA
CB-114 50 P2A
CB-115 50 P2A
63AR
CB-116 TB4-18 TB4-19
50 P2A

CB-117 50 P2A (CB TROUBLE)SPRING CHARGE TB1-35 TB1-36


MOTOR START/COMPRESSOR START TB2-35 TB2-36
CB-118 50 P2A
TB2-35 TB3-36
CB-119 50 P2A (CB TROUBLE)NA/SPRING CHARGE TB1-29 TB1-30
MOTOR STOP(SPRING CHARGED TB2-29 TB2-30
CB-120 50 P2A /COMPRESSOR STOP
TB3-29 TB3-30
CB-121
SPARE
CB-122

CB-123 NO CONTACT TB5-07

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871260
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC CB (202-52) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 60 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR ALSTOM MAKE

CB-124 NO CONTACT TB5-08

CB-125 NO CONTACT TB6-07

CB-126 NO CONTACT TB6-08

CB-127 NO CONTACT TB7-07

CB-128 NO CONTACT TB7-08

CB-129 NO CONTACT TB5-17

CB-130 NO CONTACT TB5-18

CB-131 NO CONTACT TB6-17

CB-132 NO CONTACT TB6-18

CB-133 NO CONTACT TB7-17

CB-134 NO CONTACT TB7-18

CB-135 NO CONTACT TB5-21

CB-136 NO CONTACT TB5-22

CB-137 NO CONTACT TB6-21

CB-138 NO CONTACT TB6-22

CB-139 NO CONTACT TB7-21

CB-140 NO CONTACT TB7-22

CB-141 NO CONTACT TB5-23

CB-142 NO CONTACT TB5-24

CB-143 NO CONTACT TB6-23

CB-144 NO CONTACT TB6-24

CB-145 NO CONTACT TB7-23

CB-146 NO CONTACT TB7-24

CB-147 NO CONTACT TB5-25

CB-148 NO CONTACT TB5-26

CB-149 NO CONTACT TB6-25

CB-150 NO CONTACT TB6-26

CB-151 NO CONTACT TB7-25

CB-152 NO CONTACT TB7-26

CB-153 NO CONTACT TB5-27

CB-154 NO CONTACT TB5-28

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871261
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC CB (202-52) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 61 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR ALSTOM MAKE

CB-155 NO CONTACT TB6-27

CB-156 NO CONTACT TB6-28

CB-157 NO CONTACT TB7-27

CB-158 NO CONTACT TB7-28

CB-159 NC CONTACT TB5-36

CB-160 NC CONTACT TB5-36

CB-161 NC CONTACT TB6-35

CB-162 NC CONTACT TB6-36

CB-163 NC CONTACT TB7-35

CB-164 NC CONTACT TB7-36

CB-165 NC CONTACT TB5-37

CB-166 NC CONTACT TB5-38

CB-167 NC CONTACT TB6-37

CB-168 NC CONTACT TB6-38

CB-169 NC CONTACT TB7-37

CB-170 NC CONTACT TB7-38

CB-171 NC CONTACT

CB-172 NC CONTACT

CB-173 NC CONTACT

CB-174 NC CONTACT

CB-175 NC CONTACT

CB-176 NC CONTACT

CB-177 NO CONTACT

CB-178 NO CONTACT

CB-179 NO CONTACT

CB-180 NO CONTACT

CB-181 NO CONTACT

CB-182 NO CONTACT

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871262
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC CB (202-52) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 62 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS1-01 32 P2A DC SUPPLY-1, +VE TB1-01
IS1-02 32 P2A DC SUPPLY-1, -VE TB1-02
IS1-03 32 P2A COMMON TB1-03
IS1-04 32 P2A OPEN TB1-05
IS1-05 32 P2A CLOSE TB1-04
IS1-06 32 P2A +VE OF INTERLOCK COIL TB1-06
IS1-07 32 P2A -VE OF INTERLOCK COIL TB1-07
IS1-08 50 P2A NO CONTACT TB3-101

IS1-09 50 P2A NO CONTACT TB3-102

IS1-10 41 P2A NO CONTACT TB3-105

IS1-11 41 P2A NO CONTACT TB3-106

IS1-12 NO CONTACT TB3-109

IS1-13 NO CONTACT TB3-110

IS1-14 NO CONTACT TB3-113

IS1-15 NO CONTACT TB3-114

IS1-16 NO CONTACT TB3-117


IS1-17 NO CONTACT TB3-118
IS1-18 NO CONTACT TB3-121
IS1-19 NO CONTACT TB3-122
IS1-20 NO CONTACT TB3-125
IS1-21 NO CONTACT TB3-126
IS1-22 NO CONTACT TB3-129
IS1-23 NO CONTACT TB3-130

IS1-24 NO CONTACT TB3-133

IS1-25 NO CONTACT TB3-134

IS1-26 NO CONTACT TB3-137

IS1-27 NO CONTACT TB3-138

IS1-28 NO CONTACT TB3-141

IS1-29 NO CONTACT TB3-142

IS1-30 NO CONTACT TB3-145

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871263
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89A) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 63 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS1-31 NO CONTACT TB3-146
IS1-32 NO CONTACT TB3-149
IS1-33 NO CONTACT TB3-150
IS1-34 NO CONTACT TB3-153
IS1-35 NO CONTACT TB3-154
IS1-36 50 P2A NC CONTACT TB3-103
IS1-37 50 P2A NC CONTACT TB3-104
IS1-38 41 P2A NC CONTACT TB3-107
IS1-39 41 P2A NC CONTACT TB3-108
IS1-40 NC CONTACT TB3-111
IS1-41 NC CONTACT TB3-112
IS1-42 NC CONTACT TB3-115
IS1-43 NC CONTACT TB3-116
IS1-44 NC CONTACT TB3-119
IS1-45 NC CONTACT TB3-120
IS1-46 NC CONTACT TB3-123
IS1-47 NC CONTACT TB3-124
IS1-48 NC CONTACT TB3-127
IS1-49 NC CONTACT TB3-128
IS1-50 NC CONTACT TB3-131
IS1-51 NC CONTACT TB3-132
IS1-52 NC CONTACT TB3-135
IS1-53 NC CONTACT TB3-136
IS1-54 NC CONTACT TB3-139
IS1-55 NC CONTACT TB3-140

IS1-56 NC CONTACT TB3-143

IS1-57 NC CONTACT TB3-144

IS1-58 NC CONTACT TB3-147

IS1-59 NC CONTACT TB3-148

IS1-60 NC CONTACT TB3-151

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871264
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89A) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 64 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS1-61 NC CONTACT TB3-152
IS1-62 NC CONTACT TB3-155
IS1-63 NC CONTACT TB3-156
IS1-64 SPARE TB TB3-161
IS1-65 SPARE TB TB3-162
IS1-66 SPARE TB TB3-163
IS1-67 SPARE TB TB3-164
IS1-68 SPARE TB TB3-165
IS1-69 SPARE TB TB3-166
IS1-70 SPARE TB TB3-167
IS1-71 SPARE TB TB3-168
IS1-72 SPARE TB TB4-169
IS1-73 SPARE TB TB4-170
IS1-74 SPARE TB TB4-171
IS1-75 SPARE TB TB4-172
IS1-76 SPARE TB TB4-173
IS1-77 SPARE TB TB4-174
IS1-78 SPARE TB

IS1-79 SPARE TB

IS1-80 SPARE TB

IS1-81 SPARE TB

IS1-82 SPARE TB

IS1-83 SPARE TB

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871265
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89A) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 65 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS2-01 32 P2A DC SUPPLY-1, +VE TB1-01
IS2-02 32 P2A DC SUPPLY-1, -VE TB1-02
IS2-03 32 P2A COMMON TB1-03
IS2-04 32 P2A OPEN TB1-05
IS2-05 32 P2A CLOSE TB1-04
IS2-06 32 P2A +VE OF INTERLOCK COIL TB1-06
IS2-07 32 P2A -VE OF INTERLOCK COIL TB1-07
IS2-08 50 P2A NO CONTACT TB3-101

IS2-09 50 P2A NO CONTACT TB3-102

IS2-10 41 P2A NO CONTACT TB3-105

IS2-11 41 P2A NO CONTACT TB3-106

IS2-12 NO CONTACT TB3-109

IS2-13 NO CONTACT TB3-110

IS2-14 NO CONTACT TB3-113

IS2-15 NO CONTACT TB3-114

IS2-16 NO CONTACT TB3-117


IS2-17 NO CONTACT TB3-118
IS2-18 NO CONTACT TB3-121
IS2-19 NO CONTACT TB3-122
IS2-20 NO CONTACT TB3-125
IS2-21 NO CONTACT TB3-126
IS2-22 NO CONTACT TB3-129
IS2-23 NO CONTACT TB3-130

IS2-24 NO CONTACT TB3-133

IS2-25 NO CONTACT TB3-134

IS2-26 NO CONTACT TB3-137

IS2-27 NO CONTACT TB3-138

IS2-28 NO CONTACT TB3-141

IS2-29 NO CONTACT TB3-142

IS2-30 NO CONTACT TB3-145

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871266
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89B) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 66 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS2-31 NO CONTACT TB3-146
IS2-32 NO CONTACT TB3-149
IS2-33 NO CONTACT TB3-150
IS2-34 NO CONTACT TB3-153
IS2-35 NO CONTACT TB3-154
IS2-36 50 P2A NC CONTACT TB3-103
IS2-37 50 P2A NC CONTACT TB3-104
IS2-38 41 P2A NC CONTACT TB3-107
IS2-39 41 P2A NC CONTACT TB3-108
IS2-40 NC CONTACT TB3-111
IS2-41 NC CONTACT TB3-112
IS2-42 NC CONTACT TB3-115
IS2-43 NC CONTACT TB3-116
IS2-44 NC CONTACT TB3-119
IS2-45 NC CONTACT TB3-120
IS2-46 NC CONTACT TB3-123
IS2-47 NC CONTACT TB3-124
IS2-48 NC CONTACT TB3-127
IS2-49 NC CONTACT TB3-128
IS2-50 NC CONTACT TB3-131
IS2-51 NC CONTACT TB3-132
IS2-52 NC CONTACT TB3-135
IS2-53 NC CONTACT TB3-136
IS2-54 NC CONTACT TB3-139
IS2-55 NC CONTACT TB3-140

IS2-56 NC CONTACT TB3-143

IS2-57 NC CONTACT TB3-144

IS2-58 NC CONTACT TB3-147

IS2-59 NC CONTACT TB3-148

IS2-60 NC CONTACT TB3-151

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871267
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89B) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 67 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR ELPRO (SIEMENS)

DRG.No. PGCIL-0M-0502

IS2-61 NC CONTACT TB4-152, TB4-183

IS2-62 NC CONTACT TB4-155

IS2-63 NC CONTACT TB4-156, TB4-184

IS2-64 SPARE TB TB3-185

IS2-65 SPARE TB TB3-186

IS2-66 SPARE TB TB3-187

IS2-67 SPARE TB TB3-188

IS2-68 SPARE TB TB3-189

IS2-69 SPARE TB TB3-190

IS2-70 SPARE TB TB3-191

IS2-71 SPARE TB TB3-192

IS2-72 SPARE TB TB4-193

IS2-73 SPARE TB TB4-194

IS2-74 SPARE TB TB4-195

IS2-75 SPARE TB TB4-196

IS2-76 SPARE TB TB4-197

IS2-77 SPARE TB TB4-198

IS2-78 SPARE TB TB4-199

IS2-79 SPARE TB TB4-200

IS2-80 SPARE TB

IS2-81 SPARE TB

IS2-82 SPARE TB

IS2-83 SPARE TB

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871268
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89B) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 68 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS3-01 32 P2A DC SUPPLY-1, +VE TB1-01

IS3-02 32 P2A DC SUPPLY-1, -VE TB1-02

IS3-03 32 P2A COMMON TB1-03

IS3-04 32 P2A OPEN TB1-05

IS3-05 32 P2A CLOSE TB1-04

IS3-06 32 P2A +VE OF INTERLOCK COIL TB1-06

IS3-07 32 P2A -VE OF INTERLOCK COIL TB1-07

IS3-08 51 P2A NO CONTACT TB3-101

IS3-09 51 P2A NO CONTACT TB3-102

IS3-10 NO CONTACT TB3-105

IS3-11 NO CONTACT TB3-106

IS3-12 NO CONTACT TB3-109

IS3-13 NO CONTACT TB3-110

IS3-14 NO CONTACT TB3-113

IS3-15 NO CONTACT TB3-114

IS3-16 NO CONTACT TB3-117

IS3-17 NO CONTACT TB3-118

IS3-18 NO CONTACT TB3-121

IS3-19 NO CONTACT TB3-122

IS3-20 NO CONTACT TB3-125

IS3-21 NO CONTACT TB3-126

IS3-22 NO CONTACT TB3-129

IS3-23 NO CONTACT TB3-130

IS3-24 NO CONTACT TB3-133

IS3-25 NO CONTACT TB3-134

IS3-26 NO CONTACT TB3-137

IS3-27 NO CONTACT TB3-138

IS3-28 NO CONTACT TB3-141

IS3-29 NO CONTACT TB3-142

IS3-30 NO CONTACT TB3-145

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871269
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89C) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 69 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS3-31 NO CONTACT TB3-146
IS3-32 NO CONTACT TB3-149
IS3-33 NO CONTACT TB3-150
IS3-34 NO CONTACT TB3-153
IS3-35 NO CONTACT TB3-154
IS3-36 51 P2A NC CONTACT TB3-103
IS3-37 51 P2A NC CONTACT TB3-104
IS3-38 NC CONTACT TB3-107
IS3-39 NC CONTACT TB3-108
IS3-40 NC CONTACT TB3-111
IS3-41 NC CONTACT TB3-112
IS3-42 NC CONTACT TB3-115
IS3-43 NC CONTACT TB3-116
IS3-44 NC CONTACT TB3-119
IS3-45 NC CONTACT TB3-120
IS3-46 NC CONTACT TB3-123
IS3-47 NC CONTACT TB3-124
IS3-48 NC CONTACT TB3-127
IS3-49 NC CONTACT TB3-128
IS3-50 NC CONTACT TB3-131
IS3-51 NC CONTACT TB3-132
IS3-52 NC CONTACT TB3-135
IS3-53 NC CONTACT TB3-136
IS3-54 NC CONTACT TB3-139
IS3-55 NC CONTACT TB3-140

IS3-56 NC CONTACT TB3-143

IS3-57 NC CONTACT TB3-144

IS3-58 NC CONTACT TB3-147

IS3-59 NC CONTACT TB3-148

IS3-60 NC CONTACT TB3-151

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871270
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89C) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 70 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS3-61 NC CONTACT TB3-152

IS3-62 NC CONTACT TB3-155

IS3-63 NC CONTACT TB3-156

IS3-64 SPARE TB TB3-161

IS3-65 SPARE TB TB3-162

IS3-66 SPARE TB TB3-163

IS3-67 SPARE TB TB3-164

IS3-68 SPARE TB TB3-165

IS3-69 SPARE TB TB3-166

IS3-70 SPARE TB TB3-167

IS3-71 SPARE TB TB3-168

IS3-72 SPARE TB TB4-169

IS3-73 SPARE TB TB4-170

IS3-74 SPARE TB TB4-171

IS3-75 SPARE TB TB4-172

IS3-76 SPARE TB TB4-173

IS3-77 SPARE TB TB4-174

IS3-78 SPARE TB

IS3-79 SPARE TB

IS3-80 SPARE TB

IS3-81 SPARE TB

IS3-82 SPARE TB

IS3-83 SPARE TB

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871271
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89C) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 71 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS4-01 33 P2A DC SUPPLY-1, +VE TB1-01
IS4-02 33 P2A DC SUPPLY-1, -VE TB1-02
IS4-03 33 P2A COMMON TB1-03
IS4-04 33 P2A OPEN TB1-05
IS4-05 33 P2A CLOSE TB1-04
IS4-06 33 P2A +VE OF INTERLOCK COIL TB1-06
IS4-07 33 P2A -VE OF INTERLOCK COIL TB1-07
IS4-08 50 P2A NO CONTACT TB3-101

IS4-09 50 P2A NO CONTACT TB3-102

IS4-10 41 P2A NO CONTACT TB3-105

IS4-11 41 P2A NO CONTACT TB3-106

IS4-12 NO CONTACT TB3-109

IS4-13 NO CONTACT TB3-110

IS4-14 NO CONTACT TB3-113

IS4-15 NO CONTACT TB3-114

IS4-16 NO CONTACT TB3-117


IS4-17 NO CONTACT TB3-118
IS4-18 NO CONTACT TB3-121
IS4-19 NO CONTACT TB3-122
IS4-20 NO CONTACT TB3-125
IS4-21 NO CONTACT TB3-126
IS4-22 NO CONTACT TB3-129
IS4-23 NO CONTACT TB3-130

IS4-24 NO CONTACT TB3-133

IS4-25 NO CONTACT TB3-134

IS4-26 NO CONTACT TB3-137

IS4-27 NO CONTACT TB3-138

IS4-28 NO CONTACT TB3-141

IS4-29 NO CONTACT TB3-142

IS4-30 NO CONTACT TB3-145

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871272
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89T) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 72 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS4-31 NO CONTACT TB3-146
IS4-32 NO CONTACT TB3-149
IS4-33 NO CONTACT TB3-150
IS4-34 NO CONTACT TB3-153
IS4-35 NO CONTACT TB3-154
IS4-36 50 P2A NC CONTACT TB3-103
IS4-37 50 P2A NC CONTACT TB3-104
IS4-38 41 P2A NC CONTACT TB3-107
IS4-39 41 P2A NC CONTACT TB3-108
IS4-40 NC CONTACT TB3-111
IS4-41 NC CONTACT TB3-112
IS4-42 NC CONTACT TB3-115
IS4-43 NC CONTACT TB3-116
IS4-44 NC CONTACT TB3-119
IS4-45 NC CONTACT TB3-120
IS4-46 NC CONTACT TB3-123
IS4-47 NC CONTACT TB3-124
IS4-48 NC CONTACT TB3-127
IS4-49 NC CONTACT TB3-128
IS4-50 NC CONTACT TB3-131
IS4-51 NC CONTACT TB3-132
IS4-52 NC CONTACT TB3-135
IS4-53 NC CONTACT TB3-136
IS4-54 NC CONTACT TB3-139
IS4-55 NC CONTACT TB3-140

IS4-56 NC CONTACT TB3-143

IS4-57 NC CONTACT TB3-144

IS4-58 NC CONTACT TB3-147

IS4-59 NC CONTACT TB3-148

IS4-60 NC CONTACT TB3-151

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871273
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89T) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 73 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9040458
DRG.No. STD-9046159
IS4-61 NC CONTACT TB3-152

IS4-62 NC CONTACT TB3-155

IS4-63 NC CONTACT TB3-156

IS4-64 SPARE TB TB3-161

IS4-65 SPARE TB TB3-162

IS4-66 SPARE TB TB3-163

IS4-67 SPARE TB TB3-164

IS4-68 SPARE TB TB3-165

IS4-69 SPARE TB TB3-166

IS4-70 SPARE TB TB3-167

IS4-71 SPARE TB TB3-168

IS4-72 SPARE TB TB4-169

IS4-73 SPARE TB TB4-170

IS4-74 SPARE TB TB4-171

IS4-75 SPARE TB TB4-172

IS4-76 SPARE TB TB4-173

IS4-77 SPARE TB TB4-174

IS4-78 SPARE TB

IS4-79 SPARE TB

IS4-80 SPARE TB

IS4-81 SPARE TB

IS4-82 SPARE TB

IS4-83 SPARE TB

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871274
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89T) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 74 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9043561
DRG.No. STD-9046162
ES1-01 32 P2A DC SUPPLY-1, +VE TB1-01

ES1-02 32 P2A DC SUPPLY-1, -VE TB1-02

ES1-03 32 P2A +VE INTERLOCK TB1-11

ES1-04 32 P2A -VE INTERLOCK TB1-12

ES1-05 50 P2A NO CONTACT TB3-101

ES1-06 50 P2A NO CONTACT TB3-102

ES1-07 30 P2A NO CONTACT TB3-105

ES1-08 30 P2A NO CONTACT TB3-106

ES1-09 NO CONTACT TB3-109

ES1-10 NO CONTACT TB3-110

ES1-11 NO CONTACT TB3-113

ES1-12 NO CONTACT TB3-114

ES1-13 NO CONTACT TB3-117

ES1-14 NO CONTACT TB3-118

ES1-15 NO CONTACT TB3-121

ES1-16 NO CONTACT TB3-122

ES1-17 50 P2A NC CONTACT TB3-103


ES1-18 50 P2A NC CONTACT TB3-104
ES1-19 NC CONTACT TB3-107
ES1-20 NC CONTACT TB3-108
ES1-21 NC CONTACT TB3-111
ES1-22 NC CONTACT TB3-112
ES1-23 NC CONTACT TB3-115
ES1-24 NC CONTACT TB3-116
ES1-25 NC CONTACT TB3-119
ES1-26 NC CONTACT TB3-120
ES1-27 NC CONTACT TB3-123
ES1-28 NC CONTACT TB3-124
ES1-29 SPARE TB TB3-125

ES1-30 SPARE TB TB3-126

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871275
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89AE) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 75 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9043561
DRG.No. STD-9046162
ES1-31 SPARE TB TB3-127
ES1-32 SPARE TB TB3-128
ES1-33 SPARE TB

ES1-34 SPARE TB

ES1-35 SPARE TB

ES1-36 SPARE TB

ES1-37 SPARE TB

ES1-38 SPARE TB

ES1-39

ES1-40

ES1-41

ES1-42

ES1-43

ES1-44

ES1-45

ES1-46

ES1-47

ES1-48

ES1-49

ES1-50

ES1-51

ES1-52

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871276
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC ISOLATOR (202-89AE) TERMINALS DRG. NO.: CPD KR87 SC12 SHT 76 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9043561
DRG.No. STD-9046162
ES2-01 32 P2A DC SUPPLY-1, +VE TB1-01

ES2-02 32 P2A DC SUPPLY-1, -VE TB1-02

ES2-03 32 P2A +VE INTERLOCK TB1-11

ES2-04 32 P2A -VE INTERLOCK TB1-12

ES2-05 51 P2A NO CONTACT TB3-101

ES2-06 51 P2A NO CONTACT TB3-102

ES2-07 30 P2A NO CONTACT TB3-105

ES2-08 30 P2A NO CONTACT TB3-106

ES2-09 NO CONTACT TB3-109

ES2-10 NO CONTACT TB3-110

ES2-11 NO CONTACT TB3-113

ES2-12 NO CONTACT TB3-114

ES2-13 NO CONTACT TB3-117

ES2-14 NO CONTACT TB3-118

ES2-15 NO CONTACT TB3-121

ES2-16 NO CONTACT TB3-122

ES2-17 51 P2A NC CONTACT TB3-103


ES2-18 51 P2A NC CONTACT TB3-104
ES2-19 NC CONTACT TB3-107
ES2-20 NC CONTACT TB3-108
ES2-21 NC CONTACT TB3-111
ES2-22 NC CONTACT TB3-112
ES2-23 NC CONTACT TB3-115
ES2-24 NC CONTACT TB3-116
ES2-25 NC CONTACT TB3-119
ES2-26 NC CONTACT TB3-120
ES2-27 NC CONTACT TB3-123
ES2-28 NC CONTACT TB3-124
ES2-29 SPARE TB TB3-125

ES2-30 SPARE TB TB3-126

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871277
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC EARTH SWITCH(202-89CE1) TERMINALS
DRG. NO.: CPD KR87 SC12 SHT 77 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9043561
DRG.No. STD-9046162
ES2-31 SPARE TB TB3-127
ES2-32 SPARE TB TB3-128
ES2-33 SPARE TB

ES2-34 SPARE TB

ES2-35 SPARE TB

ES2-36 SPARE TB

ES2-37 SPARE TB

ES2-38 SPARE TB

ES2-39

ES2-40

ES2-41

ES2-42

ES2-43

ES2-44

ES2-45

ES2-46

ES2-47

ES2-48

ES2-49

ES2-50

ES2-51

ES2-52

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871278
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC EARTH SWITCH(202-89CE1) TERMINALS
DRG. NO.: CPD KR87 SC12 SHT 78 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9043561
DRG.No. STD-9046162
ES3-01 32 P2A DC SUPPLY-1, +VE TB1-01

ES3-02 32 P2A DC SUPPLY-1, -VE TB1-02

ES3-03 32 P2A +VE INTERLOCK TB1-11

ES3-04 32 P2A -VE INTERLOCK TB1-12

ES3-05 51 P2A NO CONTACT TB3-101

ES3-06 51 P2A NO CONTACT TB3-102

ES3-07 NO CONTACT TB3-105

ES3-08 NO CONTACT TB3-106

ES3-09 NO CONTACT TB3-109

ES3-10 NO CONTACT TB3-110

ES3-11 NO CONTACT TB3-113

ES3-12 NO CONTACT TB3-114

ES3-13 NO CONTACT TB3-117

ES3-14 NO CONTACT TB3-118

ES3-15 NO CONTACT TB3-121

ES3-16 NO CONTACT TB3-122

ES3-17 51 P2A NC CONTACT TB3-103


ES3-18 51 P2A NC CONTACT TB3-104
ES3-19 NC CONTACT TB3-107
ES3-20 NC CONTACT TB3-108
ES3-21 NC CONTACT TB3-111
ES3-22 NC CONTACT TB3-112
ES3-23 NC CONTACT TB3-115
ES3-24 NC CONTACT TB3-116
ES3-25 NC CONTACT TB3-119
ES3-26 NC CONTACT TB3-120
ES3-27 NC CONTACT TB3-123
ES3-28 NC CONTACT TB3-124
ES3-29 SPARE TB TB3-125

ES3-30 SPARE TB TB3-126

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871279
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC EARTH SWITCH(202-89CE2) TERMINALS
DRG. NO.: CPD KR87 SC12 SHT 79 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION TERMINAL FOR S&S MAKE
DRG.No. STD-9043561
DRG.No. STD-9046162
ES3-31 SPARE TB TB3-127
ES3-32 SPARE TB TB3-128
ES3-33 SPARE TB

ES3-34 SPARE TB

ES3-35 SPARE TB

ES3-36 SPARE TB

ES3-37 SPARE TB

ES3-38 SPARE TB

ES3-39

ES3-40

ES3-41

ES3-42

ES3-43

ES3-44

ES3-45

ES3-46

ES3-47

ES3-48

ES3-49

ES3-50

ES3-51

ES3-52

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871280
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC EARTH SWITCH(202-89CE2) TERMINALS
DRG. NO.: CPD KR87 SC12 SHT 80 OF 82
TERMINAL REF. SHT No. FROM/TO PANEL DESCRIPTION

PL-01,PL-02 16 PXA CH-1(CODE-1) CS COMMAND

PL-03,PL-04 16 PXA CH-1(CODE-1) CR COMMAND

PL-05,PL-06 16 PXA CH-1CARRIER FAIL

PL-07,PL-08 16 PXA CH-1(CODE-2) CS COMMAND

PL-09,PL-10 16 PXA CH-1(CODE-2) CR COMMAND

PL-11,PL-12 25 PXA CH-1DIRECT TRIP RECEIVE

PL-13,PL-14 26 PXB CH-1DIRECT TRIP SEND

PL-21,PL-22 22 PXB CH-2(CODE-1) CS COMMAND

PL-23,PL-24 22 PXB CH-2(CODE-1) CR COMMAND

PL-25,PL-26 22 PXB CH-2CARRIER FAIL

PL-27,PL-28 22 PXB CH-2(CODE-2) CS COMMAND

PL-29,PL-30 22 PXB CH-2(CODE-2) CR COMMAND

PL-31,PL-32 25 PXA CH-2DIRECT TRIP RECEIVE

PL-33,PL-34 27 PXB CH-2DIRECT TRIP SEND

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871281
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 MAKE SPECIFIC PLCC TERMINALS DRG. NO.: CPD KR87 SC12 SHT 81 OF 82
STANDARD REFERENCE DRAWING FOR CIRCUIT BREAKER STANDARD REFERENCE DRAWING FOR ISOLATOR

EQUIPMENT MAKE DRAWING NUMBER EQUIPMENT MAKE DRAWING NUMBER

SWITCHGEARS & STRUCTURALS DRG.No. STD-9040458


CIRCUIT BREAKER ALSTOM DRG.NO:-E1611000 ISOLATOR
DRG.No. STD-9046159

STANDARD REFERENCE DRAWING FOR EARTH SWITCH STANDARD REFERENCE DRAWING FOR PLCC

EQUIPMENT MAKE DRAWING NUMBER EQUIPMENT MAKE DRAWING NUMBER

DRG.No. STD-9043561
EARTH SWITCH SWITCHGEARS & STRUCTURALS DRG.No. STD-9046162

FOR ALSTOM REF: ENGG.REF.NO.: KR87 PREPARED BY: MB REVISION: Z


SCHEME TYPE: LINE
CUSTOMER: POWERGRID CORPORATION OF INDIA LTD
PROJECT: POWERGRID 400/220kV DALTONGANJ S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: P2A, P2B FILE: DR871282
CHECKED BY: JKK DATE: 29.08.2013
BASE FILE: P.O.NO.: LOA/5427PK067/ PCP/ 01 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE-1 PROTECTION APPROVED BY: SSS SCALE: --

SALES ORDER: 3269020733 Dated 23.03.12 PALLAVARAM CHENNAI 600043 STANDARD DRAWING REFERENCE DRG. NO.: CPD KR87 SC12 SHT 82 OF 82
CUSTOMER : M/s POWERGRID CORPORATION OF INDIA Ltd.,
SUB-STATION : 765/400/220KV S/s
CIRCUIT : 220KV LINE
BAY REF :BAY-2-X
DRAWINGS REF : GENERAL ARRANGEMENT -PXA,PXB
LEGEND/Bill of Materials -PXA,PXB
SCHEMATIC DRAWING -CPD KR90 SC31

APPLICABLE FOR TECH SPECIFICATION, SECTION :CRP


A.) C/ENGG/SPEC/C&R REV NO:06 (Part-II)
B.) C/ENGG/SPEC/CRP REV NO: 07
C.) C/ENGG/SPEC/CRP REV NO: 08

PROJECT REF : PROJECT SPECIFIC

PO REF : PROJECT SPECIFIC

PO DATE : PROJECT SPECIFIC

CONTRACTOR: PROJECT SPECIFIC


ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2A


Cust. PGCIL Panel type P2A Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


CIL 1 H3 CSS1 2P4 K183 195B 14 K35

CIL 2 H4 CSS1 3P1 K205 195B 21 K3

TH 1 H5 CSS1 3P2 K247 195B 22 K3C

TH 2 H7 CSS1 3P3 K131C 195B 27 K1

52CS 1P1 K19 CSS1 3P4 K131 195B 28 K2

52CS 1P2 K29 CSS1 4P3 K205 195B E EARTH

52CS 1P3 K135 CSS1 4P4 K277 80DC1 2 S101

52CS 1P4 K133 195R 1 S101 80DC1 4 S107

52CS 2P3 K235 195R 3 S113 80DC1 13 J13

52CS 2P4 K233 195R 5 U57 80DC1 14 J14

52CS 3P1 K205A 195R 7 U58 80DC1 E EARTH

52CS 3P2 K219 195R 13 K32 86LO 1 K10

52CS 4P1 K105A 195R 14 K31 86LO 3 K19

52CS 4P2 K163 195R 21 K3 86LO 5 K3

52CS 5P1 S101 195R 22 K3A 86LO 6 K53

52CS 5P2 S103 195R 27 K1 86LO 7 K3A

52CS 5P3 S101 195R 28 K2 86LO 8 K53B

52CS 5P4 S105 195R E01 EARTH 86LO 9 K3

52CS 6P1 U149 195R E02 ELOOP 86LO 10 K53

52CS 6P2 U151 195Y 1 S101 86LO 11 K3B

52CS 6P3 K1A 195Y 3 S113 86LO 12 K53C

52CS 6P4 K21 195Y 5 U57 86LO 13 K3

52CS 7P1 K1A 195Y 7 U60 86LO 14 S101

52CS 7P2 K23 195Y 13 K34 86LO 15 K3C

52CS 7P3 K1A 195Y 14 K33 86LO 16 S111

52CS 7P4 K25 195Y 21 K3 86LO 17 K53

52CS 8P1 K51A 195Y 22 K3B 86LO 18 P105

52CS 8P2 K87 195Y 27 K1 86LO 19 K53A

52CS 8P3 K51A 195Y 28 K2 86LO 20 P123

52CS 8P4 K89 195Y E EARTH 86LO 25 K409A

52CS 9P1 K51A 195B 1 S101 86LO 26 K402

52CS 9P2 K91 195B 3 S113 86LO 27 K407

CSS1 1P3 K105 195B 5 U57 86LO 28 K402

CSS1 1P4 K171 195B 7 U62 86LO E EARTH

CSS1 2P3 K101 195B 13 K35A TTX4 1 K131

CSS1 2P4 K183 195B 14 K35 TTX4 2 S119C

Page 1 of 9
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2A


Cust. PGCIL Panel type P2A Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


TTX4 3 K135 TTX3 15 E51 TTX2 E EARTH

TTX4 4 S119 TTX3 16 P115T TTX1 1 K105

TTX4 5 K219T TTX3 17 E371 TTX1 2 S101

TTX4 6 K453B TTX3 18 P137T TTX1 3 K105A

TTX4 7 K219 TTX3 19 E71 TTX1 4 S119A

TTX4 8 K455B TTX3 20 P123T TTX1 5 K105

TTX4 10 K453C TTX3 25 K192 TTX1 6 K147

TTX4 12 K455C TTX3 26 K102 TTX1 7 K105T

TTX4 13 K441T TTX3 27 K191 TTX1 8 K147T

TTX4 14 S103T TTX3 28 K102 TTX1 9 K129T

TTX4 15 K441 TTX3 E EARTH TTX1 10 K149

TTX4 16 S105T TTX2 1 K205 TTX1 11 K155

TTX4 17 K453A TTX2 2 S119A TTX1 12 K149T

TTX4 18 K561 TTX2 3 K205A TTX1 13 K163

TTX4 19 K455A TTX2 4 S119B TTX1 14 K151

TTX4 20 K401A TTX2 5 K133 TTX1 15 K143T

TTX4 25 K192 TTX2 6 K205 TTX1 16 K151T

TTX4 26 K102 TTX2 7 K137T TTX1 17 K165

TTX4 27 K191 TTX2 8 K205T TTX1 18 K131

TTX4 28 K102 TTX2 9 K231 TTX1 19 K145T

TTX4 E EARTH TTX2 10 K403A TTX1 20 K135T

TTX3 1 K231 TTX2 11 K235T TTX1 25 K192

TTX3 2 S119B TTX2 12 K405A TTX1 26 K102

TTX3 3 K235 TTX2 13 S147 TTX1 27 K191

TTX3 4 S119C TTX2 14 K403B TTX1 28 K102

TTX3 5 E311 TTX2 15 S145 TTX1 E EARTH

TTX3 6 P131T TTX2 16 K405B COX1 3 K407A

TTX3 7 E11 TTX2 17 K233 COX1 4 K553

TTX3 8 P111T TTX2 18 K403C COX1 5 K407B

TTX3 9 E331 TTX2 19 K237T COX1 6 K557

TTX3 10 P133T TTX2 20 K405C COX1 7 K105

TTX3 11 E31 TTX2 25 K192 COX1 9 K119

TTX3 12 P113T TTX2 26 K102 COX1 11 K173

TTX3 13 E351 TTX2 27 K191 COX1 14 K106

TTX3 14 P135T TTX2 28 K102 COX1 E EARTH

TTX3 15 E51 TTX2 E EARTH RX1 1 K143

Page 2 of 9
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2A


Cust. PGCIL Panel type P2A Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


RX1 2 K103 86A 32 K449T 21M1 D5 K106

RX1 3 K105 86A 33 K53 21M1 D6 K115

RX1 4 K101 86A 34 K453 21M1 D7 K106

RX1 7 U11 86A 35 K53A 21M1 D8 K117

RX1 8 K201 86A 36 K455A 21M1 D9 K106

RX1 9 U12 86A 37 K53 21M1 D10 K119

RX1 10 K203 86A 38 K453 21M1 D11 K106

RX1 11 K185 86A 39 K53B 21M1 D12 K121

RX1 14 K102 86A 40 K455B 21M1 D13 K106

RX1 E EARTH 86A 41 K53 21M1 D14 K123

86A 2 P105 86A 42 K453 21M1 D15 K106

86A 4 P123 86A 43 K53C 21M1 D16 K125

86A 5 K3 86A 44 K455C 21M1 E EARTH

86A 6 K403 86A 45 S101 21M1 E1 K106

86A 7 K3A 86A 46 S101T 21M1 E2 K127

86A 8 K405A 86A 47 S149 21M1 E3 K106

86A 9 K3 86A 48 S147 21M1 E4 K129

86A 10 K403 86A E EARTH 21M1 E5 K106

86A 11 K3B 21M1 +N2 K105 21M1 E6 K141

86A 12 K405B 21M1 C2 A172 21M1 E7 K106

86A 13 K3 21M1 C3 A112 21M1 E8 K143

86A 14 K403 21M1 C5 A172 21M1 E9 K106

86A 15 K3C 21M1 C6 A132 21M1 E10 K145

86A 16 K405C 21M1 C8 A172 21M1 E11 K106

86A 17 K105 21M1 C9 A152 21M1 E12 K147

86A 18 P105T 21M1 C11 A179 21M1 E13 K106

86A 19 K117 21M1 C12 A180 21M1 E14 K149

86A 20 P137T 21M1 C19 E113 21M1 E15 K106

86A 25 K109 21M1 C20 E133 21M1 E16 K151

86A 26 K102 21M1 C21 E153 21M1 F1 K106

86A 27 K103 21M1 C22 E173 21M1 F3 K106

86A 28 K102 21M1 D1 K106 21M1 F4 K155

86A 29 K9 21M1 D2 K111 21M1 F5 K106

86A 30 K443 21M1 D3 K106 21M1 F6 K157

86A 31 K10 21M1 D4 K113 21M1 F7 K106

86A 32 K449T 21M1 D5 K106 21M1 F8 K159

Page 3 of 9
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2A


Cust. PGCIL Panel type P2A Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


21M1 F9 K106 21M1 K2 K106 21M1 M7 K53D

21M1 F10 K161 21M1 K3 K179B 21M1 M8 K53A

21M1 F11 K106 21M1 K4 K106 21M1 M9 K53D

21M1 F12 K163 21M1 K5 K454 21M1 M10 K53B

21M1 F13 K106 21M1 K6 K455A 21M1 M11 K53D

21M1 F14 K165 21M1 K7 K454 21M1 M12 K53C

21M1 F15 K103 21M1 K8 K455B 21M1 M14 K103

21M1 F16 K103A 21M1 K9 K454 21M1 M15 K104

21M1 H1 K401F 21M1 K10 K455C 21M1 M17 K203

21M1 H2 K407A 21M1 K11 P105B 21M1 M18 K203D

21M1 H3 K501A 21M1 K12 P111 21M1 N13 K205

21M1 H4 K553 21M1 K14 P113 21M1 N14 K243

21M1 H5 S101E 21M1 K15 P105B 21M1 -N1 K106

21M1 H6 S139 21M1 K17 P115 BCU 3 D72

21M1 H8 S141 21M1 K18 P105B BCU 4 D73

21M1 H9 S101E 21M1 L1 K415 BCU 7 D54

21M1 H11 S143 21M1 L2 K405A BCU 8 D73

21M1 H12 S101E 21M1 L3 K415 BCU 11 D34

21M1 J1 U27 21M1 L4 K405B BCU 12 D73

21M1 J2 U29 21M1 L5 K415 BCU 15 D14

21M1 J3 U31 21M1 L6 K405C BCU 16 D73

21M1 J4 U33 21M1 L7 U101 BCU 19 E635B

21M1 J5 P105A 21M1 L8 U103 BCU 20 E672B

21M1 J6 P131T 21M1 L9 U105 BCU 21 E313

21M1 J7 P105A 21M1 L10 U107 BCU 22 E373

21M1 J8 P133T 21M1 L14 K133 BCU 23 E333

21M1 J9 P105A 21M1 L15 K131A BCU 24 E373

21M1 J10 P135T 21M1 L17 K233 BCU 25 E353

21M1 J11 S101A 21M1 L18 K231A BCU 26 E373

21M1 J12 S145A 21M1 M1 K3D BCU 27 E635A

21M1 J14 S145B 21M1 M2 K3A BCU 28 E672A

21M1 J15 S101A 21M1 M3 K3D BCU A4 K223

21M1 J17 S145C 21M1 M4 K3B BCU A6 K205

21M1 J18 S101A 21M1 M5 K3D BCU A23 S101

21M1 K1 K175B 21M1 M6 K3C BCU A24 S102

21M1 K2 K106 21M1 M7 K53D BCU E EARTH

Page 4 of 9
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2A


Cust. PGCIL Panel type P2A Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


BLKA R1 K3D BLKB S6 E172 BB1 11 E371

BLKA R2 K105 BLKB S7 K201 BB1 12 E372

BLKA R3 A112 BLKB S8 K453 BB1 13 K101

BLKA R4 A132 BLKB S9 K179 BB1 14 K103

BLKA R5 A152 BLKB S10 K231 BB1 15 K105

BLKA R6 A172 BLKF R1 E635A BB1 16 K105A

BLKA R7 K104 BLKF R2 E635B BB1 17 K121

BLKA R8 K415 BLKF R3 E313 BB1 18 K123

BLKA R9 K175B BLKF R4 E333 BB1 19 K127

BLKA R10 K131A BLKF R5 E353 BB1 20 K129

BLKA S1 K3 BLKF R6 E373 BB1 21 K131

BLKA S2 K101 BLKF R7 D14 BB1 22 K133

BLKA S3 A111 BLKF R8 D34 BB1 23 K135

BLKA S4 A131 BLKF R9 D54 BB1 24 K141

BLKA S5 A151 BLKF R10 D72 BB2 1 K145

BLKA S6 A177 BLKF S1 E632A BB2 2 K155

BLKA S7 K101 BLKF S2 E632B BB2 3 K177

BLKA S8 K403 BLKF S3 E312 BB2 4 K19

BLKA S9 K175 BLKF S4 E332 BB2 5 K1A

BLKA S10 K131 BLKF S5 E352 BB2 6 K201

BLKB R1 K53D BLKF S6 E372 BB2 7 K202

BLKB R2 K106 BLKF S7 D13 BB2 8 K203

BLKB R3 E113 BLKF S8 D33 BB2 9 K205

BLKB R4 E133 BLKF S9 D53 BB2 10 K205A

BLKB R5 E153 BLKF S10 D71 BB2 11 K207

BLKB R6 E173 BB1 1 D13 BB2 12 K21

BLKB R7 K203D BB1 2 D33 BB2 13 K219

BLKB R8 K454 BB1 3 D53 BB2 14 K223

BLKB R9 K179B BB1 4 D71 BB2 15 K23

BLKB R10 K231A BB1 5 E311 BB2 16 K231

BLKB S1 K53 BB1 6 E312 BB2 17 K233

BLKB S2 K102 BB1 7 E331 BB2 18 K235

BLKB S3 E112 BB1 8 E332 BB2 19 K243

BLKB S4 E132 BB1 9 E351 BB2 20 K247

BLKB S5 E152 BB1 10 E352 BB2 21 K25

BLKB S6 E172 BB1 11 E371 BB2 22 K277

Page 5 of 9
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2A


Cust. PGCIL Panel type P2A Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


BB2 23 K29 BB4 10 P131T BB11 21 H1

BB2 24 K3 BB4 11 P133T BB11 22 H2

BB3 1 K3A BB4 12 P135T BB11 23 J13

BB3 2 K3B BB4 13 P137T BB11 24 J14

BB3 3 K3C BB4 14 S101 BB12 1 J23

BB3 4 K401 BB4 15 S102 BB12 2 J24

BB3 5 K402 BB4 16 S103T BB12 3 K801A

BB3 6 K405A BB4 17 S109 BB12 4 K833T

BB3 7 K405B BB4 18 S115 BB12 5 K403

BB3 8 K405C BB4 19 S117 BB12 6 K403A

BB3 9 K407 BB4 20 S145A BB12 7 K403B

BB3 10 K407A BB4 21 S145B BB12 8 K403C

BB3 11 K407B BB4 22 S145C BB12 9 K453

BB3 12 K441 BB4 23 S147 BB12 10 K453A

BB3 13 K443 BB4 24 S149 BB12 11 K453B

BB3 14 K455A BB11 1 E411A BB12 12 K453C

BB3 15 K455B BB11 2 E431A BB12 13 K105T

BB3 16 K455C BB11 3 E451A BB12 14 K129T

BB3 17 K51A BB11 4 E471A BB12 15 K143T

BB3 18 K53 BB11 5 E611A BB12 16 K145T

BB3 19 K53A BB11 6 E631A BB12 17 K157T

BB3 20 K53B BB11 7 E651A BB12 18 K135T

BB3 21 K53C BB11 8 E671A BB12 19 K137T

BB3 22 K557 BB11 9 E411B BB12 20 K205T

BB3 23 K561 BB11 10 E431B BB12 21 K219T

BB3 24 K7 BB11 11 E451B BB12 22 K235T

BB4 1 K87 BB11 12 E471B BB12 23 K237T

BB4 2 K89 BB11 13 E611B BB13 1 K441T

BB4 3 K9 BB11 14 E631B BB13 2 K449T

BB4 4 K91 BB11 15 E651B BB13 3 K401A

BB4 5 P105 BB11 16 E671B BB13 4 K409

BB4 6 P111 BB11 17 E11 BB13 5 K553

BB4 7 P113 BB11 18 E31 BB13 6 P105T

BB4 8 P115 BB11 19 E51 BB13 7 P111T

BB4 9 P123 BB11 20 E71 BB13 8 P113T

BB4 10 P131T BB11 21 H1 BB13 9 P115T

Page 6 of 9
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2A


Cust. PGCIL Panel type P2A Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


BB13 10 P123T LK1A 2 J13 TB5 1 K403

BB13 11 S101T LK2A 1 J12 TB5 2 K403A

BB13 12 S145 LK2A 2 J14 TB5 3 K403B

BB13 13 S105T FS11 1 J13 TB5 4 K403C

BB13 14 S139 FS11 2 K1 TB5 5 K453

BB13 15 S141 FS12 1 J14 TB5 6 K453A

BB13 16 S143 FS12 2 K2 TB5 7 K453B

HS 1 H3 FS13 1 J13 TB5 8 K453C

HS 2 H5 FS13 2 K101 TB5 9 K441T

LKM1 1 P105 FS14 1 J14 TB5 10 K449T

LKM1 2 P105B FS14 2 K102 TB5 11 S105T

LKM1-A 1 P105T FS15 1 J13 TB5 12 S139

LKM1-A 2 P105A FS15 2 K801 TB5 13 S141

LKM1-B 1 S101 FS16 1 J14 TB5 14 S143

LKM1-B 2 S101A FS16 2 K802 TB5 15 K409

LKM1-C 1 K401 FS111 1 E111 TB5 16 K553

LKM1-C 2 K401F FS111 2 E112 TB5 17 K401A

LKM1-D 1 K561 FS131 1 E131 TB5 18 S101T

LKM1-D 2 K501A FS131 2 E132 TB5 19 S145

LKM1-E 1 S103T FS151 1 E151 TB5 21 P105T

LKM1-E 2 S101E FS151 2 E152 TB5 22 P111T

LKDT1 1 K101 LK171 1 E171 TB5 23 P113T

LKDT1 2 K131C LK171 2 E172 TB5 24 P115T

LKT1 1 K1A FS631A 1 E631A TB5 25 P123T

LKT1 2 K3 FS631A 2 E632A TB5 31 K105T

PS 1 H3 LK671A 1 E671A TB5 32 K129T

PS 2 H4 LK671A 2 E672A TB5 34 K105T

PS E EARTH FS631B 1 E631B TB5 35 K143T

R86A 1 K101 FS631B 2 E632B TB5 36 K145T

R86A 2 K103A LK671B 1 E671B TB5 37 K105T

FS91 1 H1 LK671B 2 E672B TB5 38 K147T

FS91 2 H3 ETL2 1 A171S TB5 39 K149T

LK91 1 H2 ETL2 E EARTH TB5 40 K151T

LK91 2 H4 ETLP1 1 E171 TB5 41 K205T

LK1A 1 J11 ETLP1 E EARTH TB5 42 K219T

LK1A 2 J13 TB5 1 K403 TB5 45 K135T

Page 7 of 9
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2A


Cust. PGCIL Panel type P2A Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


TB5 46 K137T TB2 7 K159 TB1 5 A151

TB5 47 K235T TB2 8 K161 TB1 7 A171

TB5 48 K237T TB2 19 K183 TB1 8 A171S

TB3 1 K1 TB2 20 K185 TB1 9 A179

TB3 2 K2 TB2 21 K171 TB1 10 A180

TB3 3 K1A TB2 22 K129 TB1 11 A177

TB3 4 K3A TB2 23 K175 TB1 12 A171

TB3 5 K3B TB2 24 K105 TB1 21 E111

TB3 6 K3C TB2 25 K173 TB1 22 E131

TB3 7 K31 TB2 26 K177 TB1 23 E151

TB3 8 K32 TB2 27 K125 TB1 24 E171

TB3 9 K33 TB2 28 K179 TB1 31 E11

TB3 10 K34 TB2 31 K101 TB1 32 E31

TB3 11 K35 TB2 32 K102 TB1 33 E51

TB3 12 K35A TB2 33 K133 TB1 34 E71

TB3 13 K21 TB2 37 K101 TB1 41 H1

TB3 14 K23 TB2 38 K103 TB1 42 H2

TB3 15 K25 TB2 39 S101 TBOH 16 K109

TB3 16 K7 TB2 40 S102 TBOH 19 K207

TB3 17 K27 TB2 46 U101 TBOD 1 K407A

TB3 18 K29 TB2 47 U103 TBOD 2 K407

TB3 19 K3 TB2 48 U105 TBOD 3 K105A

TB3 20 K3A TB2 49 U107 TBOD 4 K165

TB3 21 K3B TB2 50 U27 TBOD 5 K401

TB3 22 K3C TB2 51 U29 TBOD 6 K407

TB3 47 U149 TB2 52 U31 TBOD 7 K19

TB3 48 U151 TB2 53 U33 TBOD 8 K27

TB8 1 J11 TB2 54 U11 TBOE 1 K19

TB8 2 J12 TB2 55 U12 TBOE 2 K29

TB2 1 K105A TB2 56 U57 TBOE 3 K1A

TB2 2 K111 TB2 57 U58 TBOE 4 K21

TB2 3 K113 TB2 58 U60 TBOE 5 K1A

TB2 4 K115 TB2 59 U62 TBOE 6 K23

TB2 5 K105 TB1 1 A111 TBOE 7 K1A

TB2 6 K157 TB1 3 A131 TBOE 8 K25

TB2 7 K159 TB1 5 A151 TBOE 9 K51A

Page 8 of 9
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2A


Cust. PGCIL Panel type P2A Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


TBOE 10 K87 TBOG 22 K233
TBOE 11 K51A TBOG 24 K231
TBOE 12 K89 TBOG 25 K801
TBOE 13 K51A TBOG 26 K802
TBOE 14 K91 TBOG 27 K801
TBOE 19 K191 TBOG 28 K802
TBOE 21 K101 TBIP 1 S101
TBOE 22 K192 TBIP 21 S102
TBOE 24 K101 TBIO 1 S101
TBOE 25 K801 TBIO 21 S102
TBOE 26 K802 TBIN 1 S101
TBOE 27 K801 TBIN 15 S145A
TBOE 28 K802 TBIN 16 S145B
TBOF 1 K805 TBIN 17 S145C
TBOF 3 K805 TBIN 21 S102
TBOF 5 K801 TBIM 1 S101
TBOF 7 K801 TBIM 5 S103
TBOF 9 K835 TBIM 6 S105
TBOF 11 K835 TBIM 7 S107
TBOF 13 K801 TBIM 8 S109
TBOF 15 K101 TBIM 9 S111
TBOF 21 K201 TBIM 10 S113
TBOF 22 K409A TBIM 11 S115
TBOF 24 K401 TBIM 12 S117
TBOG 1 K815 TBIM 13 S119
TBOG 3 K815 TBIM 14 S149
TBOG 5 K801 TBIM 17 K133
TBOG 7 K801 TBIM 19 K233
TBOG 9 K801 TBIM 21 S102
TBOG 11 K825 TBIM 23 K102
TBOG 13 K825 TBIM 24 K202
TBOG 15 K833T HT 1 H7
TBOG 16 K801A HT 2 H4
TBOG 19 K133 EBAR 1 EARTH
TBOG 21 K131 EBAR 2 ELOOP
TBOG 22 K233

Page 9 of 9
ALSTOM T&D INDIA LTD.

Job no. KR87 Wire Wise Schedule


Cust. PGCIL
Panel type P2A
Wire no. Colour Connection pattern
A111 RD BLKA(S3)- TB1(1)
A112 RD 21M1(C3)- BLKA(R3)
A131 YL BLKA(S4)- TB1(3)
A132 YL 21M1(C6)- BLKA(R4)
A151 BL BLKA(S5)- TB1(5)
A152 BL 21M1(C9)- BLKA(R5)
A171 BK TB1(7)- TB1(12)
A171S BK ETL2(1)- TB1(8)
A172 BK 21M1(C2)- 21M1(C5)- 21M1(C8)- BLKA(R6)
A177 BK BLKA(S6)- TB1(11)
A179 BK 21M1(C11)- TB1(9)
A180 BK 21M1(C12)- TB1(10)
D13 RD BLKF(S7)- BB1(1)
D14 RD BCU(15)- BLKF(R7)
D33 YL BLKF(S8)- BB1(2)
D34 YL BCU(11)- BLKF(R8)
D53 BL BLKF(S9)- BB1(3)
D54 BL BCU(7)- BLKF(R9)
D71 BK BLKF(S10)- BB1(4)
D72 BK BCU(3)- BLKF(R10)
D73 BK BCU(4)- BCU(8)- BCU(12)- BCU(16)
E11 RD TTX3(7)- BB11(17)- TB1(31)
E111 RD FS111(1)- TB1(21)
E112 RD BLKB(S3)- FS111(2)
E113 RD 21M1(C19)- BLKB(R3)
E131 YL FS131(1)- TB1(22)
E132 YL BLKB(S4)- FS131(2)
E133 YL 21M1(C20)- BLKB(R4)
E151 BL FS151(1)- TB1(23)
E152 BL BLKB(S5)- FS151(2)
E153 BL 21M1(C21)- BLKB(R5)
E171 BK LK171(1)- ETLP1(1)- TB1(24)
E172 BK BLKB(S6)- LK171(2)
E173 BK 21M1(C22)- BLKB(R6)
E31 YL TTX3(11)- BB11(18)- TB1(32)
E311 RD TTX3(5)- BB1(5)
E312 RD BLKF(S3)- BB1(6)
E313 RD BCU(21)- BLKF(R3)
E331 YL TTX3(9)- BB1(7)
E332 YL BLKF(S4)- BB1(8)
E333 YL BCU(23)- BLKF(R4)
E351 BL TTX3(13)- BB1(9)
E352 BL BLKF(S5)- BB1(10)
E353 BL BCU(25)- BLKF(R5)
E371 BK TTX3(17)- BB1(11)
E372 BK BLKF(S6)- BB1(12)
E373 BK BCU(22)- BCU(24)- BCU(26)- BLKF(R6)
E411A RD BB11(1)
E411B RD BB11(9)
E431A YL BB11(2)
E431B YL BB11(10)
E451A BL BB11(3)
E451B BL BB11(11)
E471A BK BB11(4)
E471B BK BB11(12)
E51 BL TTX3(15)- BB11(19)- TB1(33)
E611A RD BB11(5)
E611B RD BB11(13)
E631A YL BB11(6)- FS631A(1)
E631B YL BB11(14)- FS631B(1)
E632A YL BLKF(S1)- FS631A(2)
E632B YL BLKF(S2)- FS631B(2)
E635A YL BCU(27)- BLKF(R1)
E635B YL BCU(19)- BLKF(R2)
E651A BL BB11(7)
E651B BL BB11(15)
E671A BK BB11(8)- LK671A(1)
E671B BK BB11(16)- LK671B(1)
E672A BK BCU(28)- LK671A(2)

Page 1 of 5
ALSTOM T&D INDIA LTD.

Job no. KR87 Wire Wise Schedule


Cust. PGCIL
Panel type P2A
Wire no. Colour Connection pattern
E672B BK BCU(20)- LK671B(2)
E71 BK TTX3(19)- BB11(20)- TB1(34)
195R(E01)- 195Y(E)- 195B(E)- 80DC1(E)- 86LO(E)- TTX4(E)- TTX3(E)- TTX2(E)- TTX1(E)- COX1(E)- RX1(E)- 86A(E)-
EARTH GN 21M1(E)- BCU(E)- PS(E)- ETL2(E)- ETLP1(E)- EBAR(01)
ELOOP GN 195R(E02)- EBAR(02)
H1 BK BB11(21)- FS91(1)- TB1(41)
H2 BK BB11(22)- LK91(1)- TB1(42)
H3 BK CIL(1)- HS(1)- PS(1)- FS91(2)
H4 BK CIL(2)- PS(2)- LK91(2)- HT(2)
H5 BK TH(1)- HS(2)
H7 BK TH(2)- HT(1)
J11 GY LK1A(1)- TB8(1)
J12 GY LK2A(1)- TB8(2)
J13 GY 80DC1(13)- BB11(23)- LK1A(2)- FS11(1)- FS13(1)- FS15(1)
J14 GY 80DC1(14)- BB11(24)- LK2A(2)- FS12(1)- FS14(1)- FS16(1)
J23 GY BB12(1)
J24 GY BB12(2)
K1 GY 195R(27)- 195Y(27)- 195B(27)- FS11(2)- TB3(1)
K10 GY 86LO(1)- 86A(31)
CSS1(2P3)- RX1(4)- BLKA(S2)- BLKA(S7)- BB1(13)- LKDT1(1)- R86A(1)- FS13(2)- TB2(31)- TB2(37)- TBOE(21)-
K101 GY TBOE(24)- TBOF(15)
TTX4(26)- TTX4(28)- TTX3(26)- TTX3(28)- TTX2(26)- TTX2(28)- TTX1(26)- TTX1(28)- RX1(14)- 86A(26)- 86A(28)-
K102 GY BLKB(S2)- FS14(2)- TB2(32)- TBIM(23)
K103 GY RX1(2)- 86A(27)- 21M1(F15)- 21M1(M14)- BB1(14)- TB2(38)
K103A GY 21M1(F16)- R86A(2)
K104 GY 21M1(M15)- BLKA(R7)
CSS1(1P3)- TTX1(1)- TTX1(5)- COX1(7)- RX1(3)- 86A(17)- 21M1(+N2)- BLKA(R2)- BB1(15)- TB2(5)- TB2(24)
K105 GY
K105A GY 52CS(4P1)- TTX1(3)- BB1(16)- TB2(1)- TBOD(3)
K105T GY TTX1(7)- BB12(13)- TB5(31)- TB5(34)- TB5(37)
COX1(14)- 21M1(D1)- 21M1(D3)- 21M1(D5)- 21M1(D7)- 21M1(D9)- 21M1(D11)- 21M1(D13)- 21M1(D15)-
21M1(E1)- 21M1(E3)- 21M1(E5)- 21M1(E7)- 21M1(E9)- 21M1(E11)- 21M1(E13)- 21M1(E15)- 21M1(F1)-
21M1(F3)- 21M1(F5)- 21M1(F7)- 21M1(F9)- 21M1(F11)- 21M1(F13)- 21M1(K2)- 21M1(K4)- 21M1(-N1)-
K106 GY BLKB(R2)
K109 GY 86A(25)- TBOH(16)
K111 GY 21M1(D2)- TB2(2)
K113 GY 21M1(D4)- TB2(3)
K115 GY 21M1(D6)- TB2(4)
K117 GY 86A(19)- 21M1(D8)
K119 GY COX1(9)- 21M1(D10)
K121 GY 21M1(D12)- BB1(17)
K123 GY 21M1(D14)- BB1(18)
K125 GY 21M1(D16)- TB2(27)
K127 GY 21M1(E2)- BB1(19)
K129 GY 21M1(E4)- BB1(20)- TB2(22)
K129T GY TTX1(9)- BB12(14)- TB5(32)
K131 GY CSS1(3P4)- TTX4(1)- TTX1(18)- BLKA(S10)- BB1(21)- TBOG(21)
K131A GY 21M1(L15)- BLKA(R10)
K131C GY CSS1(3P3)- LKDT1(2)
K133 GY 52CS(1P4)- TTX2(5)- 21M1(L14)- BB1(22)- TB2(33)- TBOG(19)- TBIM(17)
K135 GY 52CS(1P3)- TTX4(3)- BB1(23)
K135T GY TTX1(20)- BB12(18)- TB5(45)
K137T GY TTX2(7)- BB12(19)- TB5(46)
K141 GY 21M1(E6)- BB1(24)
K143 GY RX1(1)- 21M1(E8)
K143T GY TTX1(15)- BB12(15)- TB5(35)
K145 GY 21M1(E10)- BB2(1)
K145T GY TTX1(19)- BB12(16)- TB5(36)
K147 GY TTX1(6)- 21M1(E12)
K147T GY TTX1(8)- TB5(38)
K149 GY TTX1(10)- 21M1(E14)
K149T GY TTX1(12)- TB5(39)
K151 GY TTX1(14)- 21M1(E16)
K151T GY TTX1(16)- TB5(40)
K155 GY TTX1(11)- 21M1(F4)- BB2(2)
K157 GY 21M1(F6)- TB2(6)
K157T GY BB12(17)
K159 GY 21M1(F8)- TB2(7)
K161 GY 21M1(F10)- TB2(8)

Page 2 of 5
ALSTOM T&D INDIA LTD.

Job no. KR87 Wire Wise Schedule


Cust. PGCIL
Panel type P2A
Wire no. Colour Connection pattern
K163 GY 52CS(4P2)- TTX1(13)- 21M1(F12)
K165 GY TTX1(17)- 21M1(F14)- TBOD(4)
K171 GY CSS1(1P4)- TB2(21)
K173 GY COX1(11)- TB2(25)
K175 GY BLKA(S9)- TB2(23)
K175B GY 21M1(K1)- BLKA(R9)
K177 GY BB2(3)- TB2(26)
K179 GY BLKB(S9)- TB2(28)
K179B GY 21M1(K3)- BLKB(R9)
K183 GY CSS1(2P4)- TB2(19)
K185 GY RX1(11)- TB2(20)
K19 GY 52CS(1P1)- 86LO(3)- BB2(4)- TBOD(7)- TBOE(1)
K191 GY TTX4(27)- TTX3(27)- TTX2(27)- TTX1(27)- TBOE(19)
K192 GY TTX4(25)- TTX3(25)- TTX2(25)- TTX1(25)- TBOE(22)
K1A GY 52CS(6P3)- 52CS(7P1)- 52CS(7P3)- BB2(5)- LKT1(1)- TB3(3)- TBOE(3)- TBOE(5)- TBOE(7)
K2 GY 195R(28)- 195Y(28)- 195B(28)- FS12(2)- TB3(2)
K201 GY RX1(8)- BLKB(S7)- BB2(6)- TBOF(21)
K202 GY BB2(7)- TBIM(24)
K203 GY RX1(10)- 21M1(M17)- BB2(8)
K203D GY 21M1(M18)- BLKB(R7)
K205 GY CSS1(3P1)- CSS1(4P3)- TTX2(1)- TTX2(6)- 21M1(N13)- BCU(A6)- BB2(9)
K205A GY 52CS(3P1)- TTX2(3)- BB2(10)
K205T GY TTX2(8)- BB12(20)- TB5(41)
K207 GY BB2(11)- TBOH(19)
K21 GY 52CS(6P4)- BB2(12)- TB3(13)- TBOE(4)
K219 GY 52CS(3P2)- TTX4(7)- BB2(13)
K219T GY TTX4(5)- BB12(21)- TB5(42)
K223 GY BCU(A4)- BB2(14)
K23 GY 52CS(7P2)- BB2(15)- TB3(14)- TBOE(6)
K231 GY TTX3(1)- TTX2(9)- BLKB(S10)- BB2(16)- TBOG(24)
K231A GY 21M1(L18)- BLKB(R10)
K233 GY 52CS(2P4)- TTX2(17)- 21M1(L17)- BB2(17)- TBOG(22)- TBIM(19)
K235 GY 52CS(2P3)- TTX3(3)- BB2(18)
K235T GY TTX2(11)- BB12(22)- TB5(47)
K237T GY TTX2(19)- BB12(23)- TB5(48)
K243 GY 21M1(N14)- BB2(19)
K247 GY CSS1(3P2)- BB2(20)
K25 GY 52CS(7P4)- BB2(21)- TB3(15)- TBOE(8)
K27 GY TB3(17)- TBOD(8)
K277 GY CSS1(4P4)- BB2(22)
K29 GY 52CS(1P2)- BB2(23)- TB3(18)- TBOE(2)
195R(21)- 195Y(21)- 195B(21)- 86LO(5)- 86LO(9)- 86LO(13)- 86A(5)- 86A(9)- 86A(13)- BLKA(S1)- BB2(24)-
K3 GY LKT1(2)- TB3(19)
K31 GY 195R(14)- TB3(7)
K32 GY 195R(13)- TB3(8)
K33 GY 195Y(14)- TB3(9)
K34 GY 195Y(13)- TB3(10)
K35 GY 195B(14)- TB3(11)
K35A GY 195B(13)- TB3(12)
K3A GY 195R(22)- 86LO(7)- 86A(7)- 21M1(M2)- BB3(1)- TB3(4)- TB3(20)
K3B GY 195Y(22)- 86LO(11)- 86A(11)- 21M1(M4)- BB3(2)- TB3(5)- TB3(21)
K3C GY 195B(22)- 86LO(15)- 86A(15)- 21M1(M6)- BB3(3)- TB3(6)- TB3(22)
K3D GY 21M1(M1)- 21M1(M3)- 21M1(M5)- BLKA(R1)
K401 GY BB3(4)- LKM1-C(1)- TBOD(5)- TBOF(24)
K401A GY TTX4(20)- BB13(3)- TB5(17)
K401F GY 21M1(H1)- LKM1-C(2)
K402 GY 86LO(26)- 86LO(28)- BB3(5)
K403 GY 86A(6)- 86A(10)- 86A(14)- BLKA(S8)- BB12(5)- TB5(1)
K403A GY TTX2(10)- BB12(6)- TB5(2)
K403B GY TTX2(14)- BB12(7)- TB5(3)
K403C GY TTX2(18)- BB12(8)- TB5(4)
K405A GY TTX2(12)- 86A(8)- 21M1(L2)- BB3(6)
K405B GY TTX2(16)- 86A(12)- 21M1(L4)- BB3(7)
K405C GY TTX2(20)- 86A(16)- 21M1(L6)- BB3(8)
K407 GY 86LO(27)- BB3(9)- TBOD(2)- TBOD(6)
K407A GY COX1(3)- 21M1(H2)- BB3(10)- TBOD(1)
K407B GY COX1(5)- BB3(11)
K409 GY BB13(4)- TB5(15)
K409A GY 86LO(25)- TBOF(22)

Page 3 of 5
ALSTOM T&D INDIA LTD.

Job no. KR87 Wire Wise Schedule


Cust. PGCIL
Panel type P2A
Wire no. Colour Connection pattern
K415 GY 21M1(L1)- 21M1(L3)- 21M1(L5)- BLKA(R8)
K441 GY TTX4(15)- BB3(12)
K441T GY TTX4(13)- BB13(1)- TB5(9)
K443 GY 86A(30)- BB3(13)
K449T GY 86A(32)- BB13(2)- TB5(10)
K453 GY 86A(34)- 86A(38)- 86A(42)- BLKB(S8)- BB12(9)- TB5(5)
K453A GY TTX4(17)- BB12(10)- TB5(6)
K453B GY TTX4(6)- BB12(11)- TB5(7)
K453C GY TTX4(10)- BB12(12)- TB5(8)
K454 GY 21M1(K5)- 21M1(K7)- 21M1(K9)- BLKB(R8)
K455A GY TTX4(19)- 86A(36)- 21M1(K6)- BB3(14)
K455B GY TTX4(8)- 86A(40)- 21M1(K8)- BB3(15)
K455C GY TTX4(12)- 86A(44)- 21M1(K10)- BB3(16)
K501A GY 21M1(H3)- LKM1-D(2)
K51A GY 52CS(8P1)- 52CS(8P3)- 52CS(9P1)- BB3(17)- TBOE(9)- TBOE(11)- TBOE(13)
K53 GY 86LO(6)- 86LO(10)- 86LO(17)- 86A(33)- 86A(37)- 86A(41)- BLKB(S1)- BB3(18)
K53A GY 86LO(19)- 86A(35)- 21M1(M8)- BB3(19)
K53B GY 86LO(8)- 86A(39)- 21M1(M10)- BB3(20)
K53C GY 86LO(12)- 86A(43)- 21M1(M12)- BB3(21)
K53D GY 21M1(M7)- 21M1(M9)- 21M1(M11)- BLKB(R1)
K553 GY COX1(4)- 21M1(H4)- BB13(5)- TB5(16)
K557 GY COX1(6)- BB3(22)
K561 GY TTX4(18)- BB3(23)- LKM1-D(1)
K7 GY BB3(24)- TB3(16)
FS15(2)- TBOE(25)- TBOE(27)- TBOF(5)- TBOF(7)- TBOF(13)- TBOG(5)- TBOG(7)- TBOG(9)- TBOG(25)-
K801 GY TBOG(27)
K801A GY BB12(3)- TBOG(16)
K802 GY FS16(2)- TBOE(26)- TBOE(28)- TBOG(26)- TBOG(28)
K805 GY TBOF(1)- TBOF(3)
K815 GY TBOG(1)- TBOG(3)
K825 GY TBOG(11)- TBOG(13)
K833T GY BB12(4)- TBOG(15)
K835 GY TBOF(9)- TBOF(11)
K87 GY 52CS(8P2)- BB4(1)- TBOE(10)
K89 GY 52CS(8P4)- BB4(2)- TBOE(12)
K9 GY 86A(29)- BB4(3)
K91 GY 52CS(9P2)- BB4(4)- TBOE(14)
P105 GY 86LO(18)- 86A(2)- BB4(5)- LKM1(1)
P105A GY 21M1(J5)- 21M1(J7)- 21M1(J9)- LKM1-A(2)
P105B GY 21M1(K11)- 21M1(K15)- 21M1(K18)- LKM1(2)
P105T GY 86A(18)- BB13(6)- LKM1-A(1)- TB5(21)
P111 GY 21M1(K12)- BB4(6)
P111T GY TTX3(8)- BB13(7)- TB5(22)
P113 GY 21M1(K14)- BB4(7)
P113T GY TTX3(12)- BB13(8)- TB5(23)
P115 GY 21M1(K17)- BB4(8)
P115T GY TTX3(16)- BB13(9)- TB5(24)
P123 GY 86LO(20)- 86A(4)- BB4(9)
P123T GY TTX3(20)- BB13(10)- TB5(25)
P131T GY TTX3(6)- 21M1(J6)- BB4(10)
P133T GY TTX3(10)- 21M1(J8)- BB4(11)
P135T GY TTX3(14)- 21M1(J10)- BB4(12)
P137T GY TTX3(18)- 86A(20)- BB4(13)
52CS(5P1)- 52CS(5P3)- 195R(1)- 195Y(1)- 195B(1)- 80DC1(2)- 86LO(14)- TTX1(2)- 86A(45)- BCU(A23)- BB4(14)-
S101 GY LKM1-B(1)- TB2(39)- TBIP(1)- TBIO(1)- TBIN(1)- TBIM(1)
S101A GY 21M1(J11)- 21M1(J15)- 21M1(J18)- LKM1-B(2)
S101E GY 21M1(H5)- 21M1(H9)- 21M1(H12)- LKM1-E(2)
S101T GY 86A(46)- BB13(11)- TB5(18)
S102 GY BCU(A24)- BB4(15)- TB2(40)- TBIP(21)- TBIO(21)- TBIN(21)- TBIM(21)
S103 GY 52CS(5P2)- TBIM(5)
S103T GY TTX4(14)- BB4(16)- LKM1-E(1)
S105 GY 52CS(5P4)- TBIM(6)
S105T GY TTX4(16)- BB13(13)- TB5(11)
S107 GY 80DC1(4)- TBIM(7)
S109 GY BB4(17)- TBIM(8)
S111 GY 86LO(16)- TBIM(9)
S113 GY 195R(3)- 195Y(3)- 195B(3)- TBIM(10)
S115 GY BB4(18)- TBIM(11)
S117 GY BB4(19)- TBIM(12)

Page 4 of 5
ALSTOM T&D INDIA LTD.

Job no. KR87 Wire Wise Schedule


Cust. PGCIL
Panel type P2A
Wire no. Colour Connection pattern
S119 GY TTX4(4)- TBIM(13)
S119A GY TTX2(2)- TTX1(4)
S119B GY TTX3(2)- TTX2(4)
S119C GY TTX4(2)- TTX3(4)
S139 GY 21M1(H6)- BB13(14)- TB5(12)
S141 GY 21M1(H8)- BB13(15)- TB5(13)
S143 GY 21M1(H11)- BB13(16)- TB5(14)
S145 GY TTX2(15)- BB13(12)- TB5(19)
S145A GY 21M1(J12)- BB4(20)- TBIN(15)
S145B GY 21M1(J14)- BB4(21)- TBIN(16)
S145C GY 21M1(J17)- BB4(22)- TBIN(17)
S147 GY TTX2(13)- 86A(48)- BB4(23)
S149 GY 86A(47)- BB4(24)- TBIM(14)
U101 GY 21M1(L7)- TB2(46)
U103 GY 21M1(L8)- TB2(47)
U105 GY 21M1(L9)- TB2(48)
U107 GY 21M1(L10)- TB2(49)
U11 GY RX1(7)- TB2(54)
U12 GY RX1(9)- TB2(55)
U149 GY 52CS(6P1)- TB3(47)
U151 GY 52CS(6P2)- TB3(48)
U27 GY 21M1(J1)- TB2(50)
U29 GY 21M1(J2)- TB2(51)
U31 GY 21M1(J3)- TB2(52)
U33 GY 21M1(J4)- TB2(53)
U57 GY 195R(5)- 195Y(5)- 195B(5)- TB2(56)
U58 GY 195R(7)- TB2(57)
U60 GY 195Y(7)- TB2(58)
U62 GY 195B(7)- TB2(59)

Page 5 of 5
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2B


Cust. PGCIL Panel type P2B Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


CIL 1 H3 21M2 312 K204B 21M2 4105 K1E

CIL 2 H4 21M2 313 K213 21M2 4107 K405A

TH 1 H5 21M2 314 K204C 21M2 4108 K407P

TH 2 H7 21M2 315 K215 21M2 4109 K405B

CSS2 1P3 K205 21M2 316 K204D 21M2 4110 K405C

CSS2 1P4 K271 21M2 317 K217 21M2 4111 K407Q

CSS2 2P3 K201 21M2 318 K204E 21M2 4113 K53A

CSS2 2P4 K283 21M2 319 K219 21M2 4114 K53E

CSS2 3P1 K205 21M2 321 K227 21M2 4115 K53B

CSS2 3P2 K249 21M2 322 K204J 21M2 4116 K53C

CSS2 3P3 K231C 21M2 323 K251 21M2 4117 K53F

CSS2 3P4 K231 21M2 324 K204K 21M2 4201 K455A

CSS2 4P3 K105 21M2 325 K241 21M2 4202 K453E

CSS2 4P4 K177 21M2 326 K204L 21M2 4203 K455B

21M2 1 A213 21M2 327 K243 21M2 4204 K455C

21M2 2 A277A 21M2 328 K204M 21M2 4205 K453F

21M2 3 A233 21M2 329 K245 21M2 4207 P111

21M2 4 A277B 21M2 3110 K204F 21M2 4208 P105C

21M2 5 A253 21M2 3111 K221 21M2 4209 P113

21M2 6 A277C 21M2 3112 K204G 21M2 4210 P115

21M2 7 A277D 21M2 3113 K223 21M2 4211 P105D

21M2 8 A275 21M2 3114 K204H 21M2 4213 K103

21M2 9 A279 21M2 3115 K225 21M2 4214 K101B

21M2 10 A280 21M2 3116 K204I 21M2 4216 K203

21M2 13 E213 21M2 3210 K204N 21M2 4217 K102B

21M2 14 E273 21M2 3211 K247 21M2 5101 P131T

21M2 15 E233 21M2 3212 K204O 21M2 5102 P105F

21M2 16 E273A 21M2 3213 K249 21M2 5103 P133T

21M2 17 E253 21M2 3214 K204P 21M2 5104 P135T

21M2 18 E273B 21M2 3215 K229 21M2 5105 P105G

21M2 111 K105 21M2 3216 K203 21M2 5107 S145A

21M2 112 K127 21M2 4101 K3A 21M2 5108 S101B

21M2 114 K205 21M2 4102 K1D 21M2 5109 S145B

21M2 115 K204A 21M2 4103 K3B 21M2 5110 S145C

21M2 311 K211 21M2 4104 K3C 21M2 5111 S101C

21M2 312 K204B 21M2 4105 K1E 21M2 5113 S139

Page 1 of 8
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2B


Cust. PGCIL Panel type P2B Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


21M2 5114 S101E TXS1 30 K53F 80DC2 13 J23

21M2 5115 S141 TXS1 31 K453E 80DC2 14 J24

21M2 5116 S143 TXS1 32 K453F 80DC2 E EARTH

21M2 5117 S101F TXS1 33 P105C 295B 1 S101

21M2 5201 K279 TXS1 34 P105D 295B 3 S115

21M2 5202 K205H TXS1 35 P105F 295B 5 U63

21M2 5203 K275 TXS1 36 P105G 295B 7 U68

21M2 5204 K233 TXS1 37 S101B 295B 13 K85A

21M2 5205 K231B TXS1 38 S101C 295B 14 K85

21M2 5207 K553 TXS1 C1 K204 295B 21 K53

21M2 5208 K561A TXS1 2CA K204D 295B 22 K53C

21M2 5210 K407A TXS1 3CA K204H 295B 27 K51

21M2 5211 K401D TXS1 4CA K204L 295B 28 K52

21M2 5213 K121 TXS1 5CA K204P 295B E EARTH

21M2 5214 K105 TXS1 2CB K204E 295Y 1 S101

21M2 5216 K133 TXS1 3CB K204I 295Y 3 S115

21M2 5217 K131B TXS1 4CB K204M 295Y 5 U63

21M2 E01 EARTH TXS1 P1 K204A 295Y 7 U66

21M2 E02 ELOOP TXS1 2PB K204C 295Y 13 K84

TXS1 1 A277A TXS1 3PB K204G 295Y 14 K83

TXS1 2 A277B TXS1 4PB K204K 295Y 21 K53

TXS1 3 A277C TXS1 5PB K204O 295Y 22 K53B

TXS1 4 A277D 80CO 3 J23 295Y 27 K51

TXS1 5 E273 80CO 4 J24 295Y 28 K52

TXS1 6 E273A 80CO 5 J17 295Y E EARTH

TXS1 7 E273B 80CO 6 J18 295R 1 S101

TXS1 8 K204B 80CO 7 J13 295R 3 S115

TXS1 9 K204F 80CO 8 J14 295R 5 U63

TXS1 10 K204J 80CO 9 J17 295R 7 U64

TXS1 11 K204N 80CO 10 J18 295R 13 K82

TXS1 25 K1D 80CO 11 J13 295R 14 K81

TXS1 26 K1E 80CO 14 J14 295R 21 K53

TXS1 27 K407P 80CO E EARTH 295R 22 K53A

TXS1 28 K407Q 80DC2 2 S101 295R 27 K51

TXS1 29 K53E 80DC2 4 S109 295R 28 K52

TXS1 30 K53F 80DC2 13 J23 295R E EARTH

Page 2 of 8
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2B


Cust. PGCIL Panel type P2B Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


86B 1 K205 86B 42 K453 PU A9 B53

86B 2 P105 86B 43 K53C PU A11 B73

86B 3 K227 86B 44 K455C PU A12 B77

86B 4 P123 86B 45 S101 PU B1 P104

86B 5 K3 86B 46 S101T PU B2 P107

86B 6 K403 86B 47 S149 PU B3 P104

86B 7 K3A 86B 48 S147 PU B4 P109

86B 8 K405A 86B E EARTH PU B5 P104

86B 9 K3 RX2 1 K145 PU B6 P111

86B 10 K403 RX2 2 K203 PU B7 P104

86B 11 K3B RX2 3 K105 PU B8 P113

86B 12 K405B RX2 4 K201 PU B9 P104

86B 13 K3 RX2 7 U13 PU B10 P115

86B 14 K403 RX2 8 K101 PU B11 P104

86B 15 K3C RX2 9 U14 PU B12 P123

86B 16 K405C RX2 10 K103 PU B13 P104

86B 18 P105T RX2 11 K285 PU B15 P104

86B 20 P137T RX2 14 K202 PU B16 P119

86B 25 K207 RX2 E EARTH PU C1 P104

86B 26 K202 COX2 3 K407B PU C2 P121

86B 27 K203 COX2 4 K557 PU C3 P104

86B 28 K202 COX2 5 K407 PU C4 P125

86B 29 K6 COX2 6 K409 PU C5 P104

86B 30 K441 COX2 7 K105 PU C6 P127

86B 31 K9 COX2 8 K205 PU C7 P104

86B 32 K443 COX2 9 K141 PU C8 P129

86B 33 K53 COX2 10 K225 PU C9 P104

86B 34 K453 COX2 11 K273 PU C10 P131

86B 35 K53A COX2 14 K204 PU C11 P104

86B 36 K455A COX2 E EARTH PU C12 P133

86B 37 K53 PU A2 B77 PU C13 P104

86B 38 K453 PU A3 B13 PU C14 P135

86B 39 K53B PU A5 B77 PU C15 P104

86B 40 K455B PU A6 B33 PU C16 P137

86B 41 K53 PU A8 B77 PU E EARTH

86B 42 K453 PU A9 B53 PU E1 K105

Page 3 of 8
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2B


Cust. PGCIL Panel type P2B Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


PU E2 K123 TBEM 7 E315 BLKE S5 B51

PU E3 K105A TBEM 8 E335 BLKE S6 B71

PU E4 K155 TBEM 9 E355 BLKE S7 K3

PU E5 S101D TBEM 10 E375 BLKE S8 K53

PU E6 S149 TTB 1 D12 BLKE S9 K131

PU E7 U21 TTB 2 D11 BLKE S10 K231

PU E8 U22 TTB 3 D13 BLKD R1 K1D

PU E13 K6 TTB 4 D32 BLKD R2 K204

PU E15 K7 TTB 5 D31 BLKD R3 E213

PU F1 K11 TTB 6 D33 BLKD R4 E233

PU F2 K3A TTB 7 D52 BLKD R5 E253

PU F3 K11 TTB 8 D51 BLKD R6 E273

PU F4 K3B TTB 9 D53 BLKD R7 K205H

PU F5 K11 TTB A1 E315 BLKD R8 K231B

PU F6 K3C TTB A2 E312 BLKD R10 K131B

PU F7 K61 TTB B1 E335 BLKD S1 K3

PU F8 K53A TTB B2 E332 BLKD S2 K202

PU F9 K61 TTB C1 E355 BLKD S3 E212

PU F10 K53B TTB C2 E352 BLKD S4 E232

PU F11 K61 TTB N1 E375 BLKD S5 E252

PU F12 K53C TTB N2 E372 BLKD S6 E272

PU F14 K133 BLKE R1 P104 BLKD S7 K204

PU F15 K131D BLKE R2 P105 BLKD S8 K231

PU F17 K233 BLKE R3 B13 BLKD S10 K131

PU F18 K231D BLKE R4 B33 BLKC R1 K407P

PU G1 P104 BLKE R5 B53 BLKC R2 K201

PU G2 P105 BLKE R6 B73 BLKC R3 A213

PU G13 K205 BLKE R7 K11 BLKC R4 A233

PU G14 K241 BLKE R8 K61 BLKC R5 A253

TBEM 1 D12 BLKE R9 K131D BLKC R6 A275

TBEM 2 D13 BLKE R10 K231D BLKC R7 K53E

TBEM 3 D32 BLKE S1 P102 BLKC R8 K453E

TBEM 4 D33 BLKE S2 P101 BLKC R9 K101B

TBEM 5 D52 BLKE S3 B11 BLKC R10 K102B

TBEM 6 D53 BLKE S4 B31 BLKC S1 K403

TBEM 7 E315 BLKE S5 B51 BLKC S2 K205

Page 4 of 8
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2B


Cust. PGCIL Panel type P2B Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


BLKC S3 A211 BB2 4 K19 BB3 15 K455B

BLKC S4 A231 BB2 5 K1A BB3 16 K455C

BLKC S5 A251 BB2 6 K201 BB3 17 K51A

BLKC S6 A277 BB2 7 K202 BB3 18 K53

BLKC S7 K53 BB2 8 K203 BB3 19 K53A

BLKC S8 K453 BB2 9 K205 BB3 20 K53B

BLKC S9 K101 BB2 10 K205A BB3 21 K53C

BLKC S10 K201 BB2 11 K207 BB3 22 K557

BB1 1 D13 BB2 12 K21 BB3 23 K561

BB1 2 D33 BB2 13 K219 BB3 24 K7

BB1 3 D53 BB2 14 K223 BB4 1 K87

BB1 4 D71 BB2 15 K23 BB4 2 K89

BB1 5 E311 BB2 16 K231 BB4 3 K9

BB1 6 E312 BB2 17 K233 BB4 4 K91

BB1 7 E331 BB2 18 K235 BB4 5 P105

BB1 8 E332 BB2 19 K243 BB4 6 P111

BB1 9 E351 BB2 20 K247 BB4 7 P113

BB1 10 E352 BB2 21 K25 BB4 8 P115

BB1 11 E371 BB2 22 K277 BB4 9 P123

BB1 12 E372 BB2 23 K29 BB4 10 P131T

BB1 13 K101 BB2 24 K3 BB4 11 P133T

BB1 14 K103 BB3 1 K3A BB4 12 P135T

BB1 15 K105 BB3 2 K3B BB4 13 P137T

BB1 16 K105A BB3 3 K3C BB4 14 S101

BB1 17 K121 BB3 4 K401 BB4 15 S102

BB1 18 K123 BB3 5 K402 BB4 16 S103T

BB1 19 K127 BB3 6 K405A BB4 17 S109

BB1 20 K129 BB3 7 K405B BB4 18 S115

BB1 21 K131 BB3 8 K405C BB4 19 S117

BB1 22 K133 BB3 9 K407 BB4 20 S145A

BB1 23 K135 BB3 10 K407A BB4 21 S145B

BB1 24 K141 BB3 11 K407B BB4 22 S145C

BB2 1 K145 BB3 12 K441 BB4 23 S147

BB2 2 K155 BB3 13 K443 BB4 24 S149

BB2 3 K177 BB3 14 K455A BB11 1 E411A

BB2 4 K19 BB3 15 K455B BB11 2 E431A

Page 5 of 8
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2B


Cust. PGCIL Panel type P2B Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


BB11 3 E451A BB12 14 K129T LKM2-E 2 K561A

BB11 4 E471A BB12 15 K143T LKM2-F 1 K401

BB11 5 E611A BB12 16 K145T LKM2-F 2 K401D

BB11 6 E631A BB12 17 K157T LKPU-1 1 S101

BB11 7 E651A BB12 18 K135T LKPU-1 2 S101D

BB11 8 E671A BB12 19 K137T ETL1 1 D70

BB11 9 E411B BB12 20 K205T ETL1 E EARTH

BB11 10 E431B BB12 21 K219T ETL3 1 A271S

BB11 11 E451B BB12 22 K235T ETL3 E EARTH

BB11 12 E471B BB12 23 K237T ETL4 1 B75S

BB11 13 E611B BB13 1 K441T ETL4 E EARTH

BB11 14 E631B BB13 2 K449T ETLP2 1 E271

BB11 15 E651B BB13 3 K401A ETLP2 E EARTH

BB11 16 E671B BB13 4 K409 ETLP3 1 E371

BB11 17 E11 BB13 5 K553 ETLP3 E EARTH

BB11 18 E31 BB13 6 P105T HS 1 H3

BB11 19 E51 BB13 7 P111T HS 2 H5

BB11 20 E71 BB13 8 P113T PS 1 H3

BB11 21 H1 BB13 9 P115T PS 2 H4

BB11 22 H2 BB13 10 P123T PS E EARTH

BB11 23 J13 BB13 11 S101T R86B 1 K201

BB11 24 J14 BB13 12 S145 R86B 2 K229

BB12 1 J23 BB13 13 S105T FS92 1 H1

BB12 2 J24 BB13 14 S139 FS92 2 H3

BB12 3 K801A BB13 15 S141 LK92 1 H2

BB12 4 K833T BB13 16 S143 LK92 2 H4

BB12 5 K403 LKM2-A 1 P105 LK1B 1 J21

BB12 6 K403A LKM2-A 2 P105C LK1B 2 J23

BB12 7 K403B LKM2-B 1 P105T LK2B 1 J22

BB12 8 K403C LKM2-B 2 P105F LK2B 2 J24

BB12 9 K453 LKM2-C 1 S101 FS21 1 J23

BB12 10 K453A LKM2-C 2 S101B FS21 2 K51

BB12 11 K453B LKM2-D 1 S103T FS22 1 J24

BB12 12 K453C LKM2-D 2 S101E FS22 2 K52

BB12 13 K105T LKM2-E 1 K561 FS23 1 J23

BB12 14 K129T LKM2-E 2 K561A FS23 2 K201

Page 6 of 8
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2B


Cust. PGCIL Panel type P2B Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


FS24 1 J24 TB1 9 A279 TB2 11 K251

FS24 2 K202 TB1 10 A280 TB2 19 K283

FS31 1 J17 TB1 11 A277 TB2 20 K285

FS31 2 S101 TB1 12 A271 TB2 21 K271

FS32 1 J18 TB1 21 B11 TB2 22 K217

FS32 2 S102 TB1 23 B31 TB2 23 K275

FS33 1 J17 TB1 25 B51 TB2 24 K205

FS33 2 K401 TB1 27 B71 TB2 25 K273

FS34 1 J18 TB1 28 B75S TB2 26 K277

FS34 2 K402 TB1 31 D11 TB2 27 K245

FS211 1 E211 TB1 33 D31 TB2 28 K279

FS211 2 E212 TB1 35 D51 TB2 29 S101

FS231 1 E231 TB1 37 D71 TB2 30 S117

FS231 2 E232 TB1 38 D70 TB2 31 K201

FS251 1 E251 TB1 41 E311 TB2 32 K202

FS251 2 E252 TB1 42 E331 TB2 33 K233

LK271 1 E271 TB1 43 E351 TB2 37 K201

LK271 2 E272 TB1 44 E371 TB2 38 K203

FS311 1 E311 TB1 45 E211 TB9 8 K205

FS311 2 E312 TB1 46 E231 TB9 39 S101E

FS331 1 E331 TB1 47 E251 TB9 40 S101F

FS331 2 E332 TB1 48 E271 TB3 1 K51

FS351 1 E351 TB1 51 E631A TB3 2 K52

FS351 2 E352 TB1 52 E671A TB3 3 K51A

LK371 1 E371 TB1 53 E631B TB3 4 K53A

LK371 2 E372 TB1 54 E671B TB3 5 K53B

LKT2 1 K51A TB2 1 K205 TB3 6 K53C

LKT2 2 K53 TB2 2 K211 TB3 7 K81

LKDT2 1 K201 TB2 3 K213 TB3 8 K82

LKDT2 2 K231C TB2 4 K215 TB3 9 K83

TB1 1 A211 TB2 5 K221 TB3 10 K84

TB1 3 A231 TB2 6 K205 TB3 11 K85

TB1 5 A251 TB2 8 K247 TB3 12 K85A

TB1 7 A271 TB2 9 K205 TB3 13 K87

TB1 8 A271S TB2 10 K249 TB3 14 K89

TB1 9 A279 TB2 11 K251 TB3 15 K91

Page 7 of 8
ALSTOM T&D INDIA LTD.

Job no. KR87 Equipment Wise Schedule File ER87P2B


Cust. PGCIL Panel type P2B Date 30/08/13

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


TB3 16 K53 EBAR 2 ELOOP
TB3 17 K53A
TB3 18 K53B
TB3 19 K53C
TB4 1 P101
TB4 2 P102
TB4 3 P105
TB4 4 P107
TB4 5 P109
TB4 6 P105
TB4 7 P119
TB4 8 P121
TB4 9 P125
TB4 10 P105
TB4 11 P127
TB4 12 P129
TB4 13 P105
TB4 14 P131
TB4 15 P133
TB4 16 P105
TB4 17 P135
TB4 18 P137
TB4 41 U13
TB4 42 U14
TB4 43 U63
TB4 44 U64
TB4 45 U66
TB4 46 U68
TB4 49 U21
TB4 50 U22
TB8 1 J21
TB8 2 J22
HT 1 H7
HT 2 H4
EBAR 1 EARTH
EBAR 2 ELOOP

Page 8 of 8
ALSTOM T&D INDIA LTD.

Job no. KR87 Wire Wise Schedule


Cust. PGCIL
Panel type P2B
Wire no. Colour Connection pattern
A211 RD BLKC(S3)- TB1(1)
A213 RD 21M2(1)- BLKC(R3)
A231 YL BLKC(S4)- TB1(3)
A233 YL 21M2(3)- BLKC(R4)
A251 BL BLKC(S5)- TB1(5)
A253 BL 21M2(5)- BLKC(R5)
A271 BK TB1(7)- TB1(12)
A271S BK ETL3(1)- TB1(8)
A275 BK 21M2(8)- BLKC(R6)
A277 BK BLKC(S6)- TB1(11)
A277A BK 21M2(2)- TXS1(1)
A277B BK 21M2(4)- TXS1(2)
A277C BK 21M2(6)- TXS1(3)
A277D BK 21M2(7)- TXS1(4)
A279 BK 21M2(9)- TB1(9)
A280 BK 21M2(10)- TB1(10)
B11 RD BLKE(S3)- TB1(21)
B13 RD PU(A3)- BLKE(R3)
B31 YL BLKE(S4)- TB1(23)
B33 YL PU(A6)- BLKE(R4)
B51 BL BLKE(S5)- TB1(25)
B53 BL PU(A9)- BLKE(R5)
B71 BK BLKE(S6)- TB1(27)
B73 BK PU(A11)- BLKE(R6)
B75S BK ETL4(1)- TB1(28)
B77 BK PU(A2)- PU(A5)- PU(A8)- PU(A12)
D11 RD TTB(2)- TB1(31)
D12 RD TBEM(1)- TTB(1)
D13 RD TBEM(2)- TTB(3)- BB1(1)
D31 YL TTB(5)- TB1(33)
D32 YL TBEM(3)- TTB(4)
D33 YL TBEM(4)- TTB(6)- BB1(2)
D51 BL TTB(8)- TB1(35)
D52 BL TBEM(5)- TTB(7)
D53 BL TBEM(6)- TTB(9)- BB1(3)
D70 ETL1(1)- TB1(38)
D71 BK BB1(4)- TB1(37)
E11 RD BB11(17)
E211 RD FS211(1)- TB1(45)
E212 RD BLKD(S3)- FS211(2)
E213 RD 21M2(13)- BLKD(R3)
E231 YL FS231(1)- TB1(46)
E232 YL BLKD(S4)- FS231(2)
E233 YL 21M2(15)- BLKD(R4)
E251 BL FS251(1)- TB1(47)
E252 BL BLKD(S5)- FS251(2)
E253 BL 21M2(17)- BLKD(R5)
E271 BK ETLP2(1)- LK271(1)- TB1(48)
E272 BK BLKD(S6)- LK271(2)
E273 BK 21M2(14)- TXS1(5)- BLKD(R6)
E273A BK 21M2(16)- TXS1(6)
E273B BK 21M2(18)- TXS1(7)
E31 YL BB11(18)
E311 RD BB1(5)- FS311(1)- TB1(41)
E312 RD TTB(A2)- BB1(6)- FS311(2)
E315 RD TBEM(7)- TTB(A1)
E331 YL BB1(7)- FS331(1)- TB1(42)
E332 YL TTB(B2)- BB1(8)- FS331(2)
E335 YL TBEM(8)- TTB(B1)
E351 BL BB1(9)- FS351(1)- TB1(43)
E352 BL TTB(C2)- BB1(10)- FS351(2)
E355 BL TBEM(9)- TTB(C1)
E371 BK BB1(11)- ETLP3(1)- LK371(1)- TB1(44)
E372 BK TTB(N2)- BB1(12)- LK371(2)
E375 BK TBEM(10)- TTB(N1)
E411A RD BB11(1)
E411B RD BB11(9)
E431A YL BB11(2)
E431B YL BB11(10)

Page 1 of 5
ALSTOM T&D INDIA LTD.

Job no. KR87 Wire Wise Schedule


Cust. PGCIL
Panel type P2B
Wire no. Colour Connection pattern
E451A BL BB11(3)
E451B BL BB11(11)
E471A BK BB11(4)
E471B BK BB11(12)
E51 BL BB11(19)
E611A RD BB11(5)
E611B RD BB11(13)
E631A YL BB11(6)- TB1(51)
E631B YL BB11(14)- TB1(53)
E651A BL BB11(7)
E651B BL BB11(15)
E671A BK BB11(8)- TB1(52)
E671B BK BB11(16)- TB1(54)
E71 BK BB11(20)
21M2(E01)- 80CO(E)- 80DC2(E)- 295B(E)- 295Y(E)- 295R(E)- 86B(E)- RX2(E)- COX2(E)- PU(E)- ETL1(E)- ETL3(E)-
EARTH GN ETL4(E)- ETLP2(E)- ETLP3(E)- PS(E)- EBAR(01)
ELOOP GN 21M2(E02)- EBAR(02)
H1 BK BB11(21)- FS92(1)
H2 BK BB11(22)- LK92(1)
H3 BK CIL(1)- HS(1)- PS(1)- FS92(2)
H4 BK CIL(2)- PS(2)- LK92(2)- HT(2)
H5 BK TH(1)- HS(2)
H7 BK TH(2)- HT(1)
J13 GY 80CO(7)- 80CO(11)- BB11(23)
J14 GY 80CO(8)- 80CO(14)- BB11(24)
J17 GY 80CO(5)- 80CO(9)- FS31(1)- FS33(1)
J18 GY 80CO(6)- 80CO(10)- FS32(1)- FS34(1)
J21 GY LK1B(1)- TB8(1)
J22 GY LK2B(1)- TB8(2)
J23 GY 80CO(3)- 80DC2(13)- BB12(1)- LK1B(2)- FS21(1)- FS23(1)
J24 GY 80CO(4)- 80DC2(14)- BB12(2)- LK2B(2)- FS22(1)- FS24(1)
K101 GY RX2(8)- BLKC(S9)- BB1(13)
K101B GY 21M2(4214)- BLKC(R9)
K102B GY 21M2(4217)- BLKC(R10)
K103 GY 21M2(4213)- RX2(10)- BB1(14)
K105 GY CSS2(4P3)- 21M2(111)- 21M2(5214)- RX2(3)- COX2(7)- PU(E1)- BB1(15)
K105A GY PU(E3)- BB1(16)
K105T GY BB12(13)
K11 GY PU(F1)- PU(F3)- PU(F5)- BLKE(R7)
K121 GY 21M2(5213)- BB1(17)
K123 GY PU(E2)- BB1(18)
K127 GY 21M2(112)- BB1(19)
K129 GY BB1(20)
K129T GY BB12(14)
K131 GY BLKE(S9)- BLKD(S10)- BB1(21)
K131B GY 21M2(5217)- BLKD(R10)
K131D GY PU(F15)- BLKE(R9)
K133 GY 21M2(5216)- PU(F14)- BB1(22)
K135 GY BB1(23)
K135T GY BB12(18)
K137T GY BB12(19)
K141 GY COX2(9)- BB1(24)
K143T GY BB12(15)
K145 GY RX2(1)- BB2(1)
K145T GY BB12(16)
K155 GY PU(E4)- BB2(2)
K157T GY BB12(17)
K177 GY CSS2(4P4)- BB2(3)
K19 GY BB2(4)
K1A GY BB2(5)
K1D GY 21M2(4102)- TXS1(25)- BLKD(R1)
K1E GY 21M2(4105)- TXS1(26)
K201 GY CSS2(2P3)- RX2(4)- BLKC(R2)- BLKC(S10)- BB2(6)- R86B(1)- FS23(2)- LKDT2(1)- TB2(31)- TB2(37)
K202 GY 86B(26)- 86B(28)- RX2(14)- BLKD(S2)- BB2(7)- FS24(2)- TB2(32)
K203 GY 21M2(3216)- 21M2(4216)- 86B(27)- RX2(2)- BB2(8)- TB2(38)
K204 GY TXS1(C1)- COX2(14)- BLKD(R2)- BLKD(S7)
K204A GY 21M2(115)- TXS1(P1)
K204B GY 21M2(312)- TXS1(8)
K204C GY 21M2(314)- TXS1(2PB)

Page 2 of 5
ALSTOM T&D INDIA LTD.

Job no. KR87 Wire Wise Schedule


Cust. PGCIL
Panel type P2B
Wire no. Colour Connection pattern
K204D GY 21M2(316)- TXS1(2CA)
K204E GY 21M2(318)- TXS1(2CB)
K204F GY 21M2(3110)- TXS1(9)
K204G GY 21M2(3112)- TXS1(3PB)
K204H GY 21M2(3114)- TXS1(3CA)
K204I GY 21M2(3116)- TXS1(3CB)
K204J GY 21M2(322)- TXS1(10)
K204K GY 21M2(324)- TXS1(4PB)
K204L GY 21M2(326)- TXS1(4CA)
K204M GY 21M2(328)- TXS1(4CB)
K204N GY 21M2(3210)- TXS1(11)
K204O GY 21M2(3212)- TXS1(5PB)
K204P GY 21M2(3214)- TXS1(5CA)
CSS2(1P3)- CSS2(3P1)- 21M2(114)- 86B(1)- COX2(8)- PU(G13)- BLKC(S2)- BB2(9)- TB2(1)- TB2(6)- TB2(9)-
K205 GY TB2(24)- TB9(8)
K205A GY BB2(10)
K205H GY 21M2(5202)- BLKD(R7)
K205T GY BB12(20)
K207 GY 86B(25)- BB2(11)
K21 GY BB2(12)
K211 GY 21M2(311)- TB2(2)
K213 GY 21M2(313)- TB2(3)
K215 GY 21M2(315)- TB2(4)
K217 GY 21M2(317)- TB2(22)
K219 GY 21M2(319)- BB2(13)
K219T GY BB12(21)
K221 GY 21M2(3111)- TB2(5)
K223 GY 21M2(3113)- BB2(14)
K225 GY 21M2(3115)- COX2(10)
K227 GY 21M2(321)- 86B(3)
K229 GY 21M2(3215)- R86B(2)
K23 GY BB2(15)
K231 GY CSS2(3P4)- BLKE(S10)- BLKD(S8)- BB2(16)
K231B GY 21M2(5205)- BLKD(R8)
K231C GY CSS2(3P3)- LKDT2(2)
K231D GY PU(F18)- BLKE(R10)
K233 GY 21M2(5204)- PU(F17)- BB2(17)- TB2(33)
K235 GY BB2(18)
K235T GY BB12(22)
K237T GY BB12(23)
K241 GY 21M2(325)- PU(G14)
K243 GY 21M2(327)- BB2(19)
K245 GY 21M2(329)- TB2(27)
K247 GY 21M2(3211)- BB2(20)- TB2(8)
K249 GY CSS2(3P2)- 21M2(3213)- TB2(10)
K25 GY BB2(21)
K251 GY 21M2(323)- TB2(11)
K271 GY CSS2(1P4)- TB2(21)
K273 GY COX2(11)- TB2(25)
K275 GY 21M2(5203)- TB2(23)
K277 GY BB2(22)- TB2(26)
K279 GY 21M2(5201)- TB2(28)
K283 GY CSS2(2P4)- TB2(19)
K285 GY RX2(11)- TB2(20)
K29 GY BB2(23)
K3 GY 86B(5)- 86B(9)- 86B(13)- BLKE(S7)- BLKD(S1)- BB2(24)
K3A GY 21M2(4101)- 86B(7)- PU(F2)- BB3(1)
K3B GY 21M2(4103)- 86B(11)- PU(F4)- BB3(2)
K3C GY 21M2(4104)- 86B(15)- PU(F6)- BB3(3)
K401 GY BB3(4)- LKM2-F(1)- FS33(2)
K401A GY BB13(3)
K401D GY 21M2(5211)- LKM2-F(2)
K402 GY BB3(5)- FS34(2)
K403 GY 86B(6)- 86B(10)- 86B(14)- BLKC(S1)- BB12(5)
K403A GY BB12(6)
K403B GY BB12(7)
K403C GY BB12(8)
K405A GY 21M2(4107)- 86B(8)- BB3(6)
K405B GY 21M2(4109)- 86B(12)- BB3(7)

Page 3 of 5
ALSTOM T&D INDIA LTD.

Job no. KR87 Wire Wise Schedule


Cust. PGCIL
Panel type P2B
Wire no. Colour Connection pattern
K405C GY 21M2(4110)- 86B(16)- BB3(8)
K407 GY COX2(5)- BB3(9)
K407A GY 21M2(5210)- BB3(10)
K407B GY COX2(3)- BB3(11)
K407P GY 21M2(4108)- TXS1(27)- BLKC(R1)
K407Q GY 21M2(4111)- TXS1(28)
K409 GY COX2(6)- BB13(4)
K441 GY 86B(30)- BB3(12)
K441T GY BB13(1)
K443 GY 86B(32)- BB3(13)
K449T GY BB13(2)
K453 GY 86B(34)- 86B(38)- 86B(42)- BLKC(S8)- BB12(9)
K453A GY BB12(10)
K453B GY BB12(11)
K453C GY BB12(12)
K453E GY 21M2(4202)- TXS1(31)- BLKC(R8)
K453F GY 21M2(4205)- TXS1(32)
K455A GY 21M2(4201)- 86B(36)- BB3(14)
K455B GY 21M2(4203)- 86B(40)- BB3(15)
K455C GY 21M2(4204)- 86B(44)- BB3(16)
K51 GY 295B(27)- 295Y(27)- 295R(27)- FS21(2)- TB3(1)
K51A GY BB3(17)- LKT2(1)- TB3(3)
K52 GY 295B(28)- 295Y(28)- 295R(28)- FS22(2)- TB3(2)
295B(21)- 295Y(21)- 295R(21)- 86B(33)- 86B(37)- 86B(41)- BLKE(S8)- BLKC(S7)- BB3(18)- LKT2(2)- TB3(16)
K53 GY
K53A GY 21M2(4113)- 295R(22)- 86B(35)- PU(F8)- BB3(19)- TB3(4)- TB3(17)
K53B GY 21M2(4115)- 295Y(22)- 86B(39)- PU(F10)- BB3(20)- TB3(5)- TB3(18)
K53C GY 21M2(4116)- 295B(22)- 86B(43)- PU(F12)- BB3(21)- TB3(6)- TB3(19)
K53E GY 21M2(4114)- TXS1(29)- BLKC(R7)
K53F GY 21M2(4117)- TXS1(30)
K553 GY 21M2(5207)- BB13(5)
K557 GY COX2(4)- BB3(22)
K561 GY BB3(23)- LKM2-E(1)
K561A GY 21M2(5208)- LKM2-E(2)
K6 GY 86B(29)- PU(E13)
K61 GY PU(F7)- PU(F9)- PU(F11)- BLKE(R8)
K7 GY PU(E15)- BB3(24)
K801A GY BB12(3)
K81 GY 295R(14)- TB3(7)
K82 GY 295R(13)- TB3(8)
K83 GY 295Y(14)- TB3(9)
K833T GY BB12(4)
K84 GY 295Y(13)- TB3(10)
K85 GY 295B(14)- TB3(11)
K85A GY 295B(13)- TB3(12)
K87 GY BB4(1)- TB3(13)
K89 GY BB4(2)- TB3(14)
K9 GY 86B(31)- BB4(3)
K91 GY BB4(4)- TB3(15)
P101 GY BLKE(S2)- TB4(1)
P102 GY BLKE(S1)- TB4(2)
PU(B1)- PU(B3)- PU(B5)- PU(B7)- PU(B9)- PU(B11)- PU(B13)- PU(B15)- PU(C1)- PU(C3)- PU(C5)- PU(C7)- PU(C9)-
P104 GY PU(C11)- PU(C13)- PU(C15)- PU(G1)- BLKE(R1)
P105 GY 86B(2)- PU(G2)- BLKE(R2)- BB4(5)- LKM2-A(1)- TB4(3)- TB4(6)- TB4(10)- TB4(13)- TB4(16)
P105C GY 21M2(4208)- TXS1(33)- LKM2-A(2)
P105D GY 21M2(4211)- TXS1(34)
P105F GY 21M2(5102)- TXS1(35)- LKM2-B(2)
P105G GY 21M2(5105)- TXS1(36)
P105T GY 86B(18)- BB13(6)- LKM2-B(1)
P107 GY PU(B2)- TB4(4)
P109 GY PU(B4)- TB4(5)
P111 GY 21M2(4207)- PU(B6)- BB4(6)
P111T GY BB13(7)
P113 GY 21M2(4209)- PU(B8)- BB4(7)
P113T GY BB13(8)
P115 GY 21M2(4210)- PU(B10)- BB4(8)
P115T GY BB13(9)
P119 GY PU(B16)- TB4(7)
P121 GY PU(C2)- TB4(8)

Page 4 of 5
ALSTOM T&D INDIA LTD.

Job no. KR87 Wire Wise Schedule


Cust. PGCIL
Panel type P2B
Wire no. Colour Connection pattern
P123 GY 86B(4)- PU(B12)- BB4(9)
P123T GY BB13(10)
P125 GY PU(C4)- TB4(9)
P127 GY PU(C6)- TB4(11)
P129 GY PU(C8)- TB4(12)
P131 GY PU(C10)- TB4(14)
P131T GY 21M2(5101)- BB4(10)
P133 GY PU(C12)- TB4(15)
P133T GY 21M2(5103)- BB4(11)
P135 GY PU(C14)- TB4(17)
P135T GY 21M2(5104)- BB4(12)
P137 GY PU(C16)- TB4(18)
P137T GY 86B(20)- BB4(13)
S101 GY 80DC2(2)- 295B(1)- 295Y(1)- 295R(1)- 86B(45)- BB4(14)- LKM2-C(1)- LKPU-1(1)- FS31(2)- TB2(29)
S101B GY 21M2(5108)- TXS1(37)- LKM2-C(2)
S101C GY 21M2(5111)- TXS1(38)
S101D GY PU(E5)- LKPU-1(2)
S101E GY 21M2(5114)- LKM2-D(2)- TB9(39)
S101F GY 21M2(5117)- TB9(40)
S101T GY 86B(46)- BB13(11)
S102 GY BB4(15)- FS32(2)
S103T GY BB4(16)- LKM2-D(1)
S105T GY BB13(13)
S109 GY 80DC2(4)- BB4(17)
S115 GY 295B(3)- 295Y(3)- 295R(3)- BB4(18)
S117 GY BB4(19)- TB2(30)
S139 GY 21M2(5113)- BB13(14)
S141 GY 21M2(5115)- BB13(15)
S143 GY 21M2(5116)- BB13(16)
S145 GY BB13(12)
S145A GY 21M2(5107)- BB4(20)
S145B GY 21M2(5109)- BB4(21)
S145C GY 21M2(5110)- BB4(22)
S147 GY 86B(48)- BB4(23)
S149 GY 86B(47)- PU(E6)- BB4(24)
U13 GY RX2(7)- TB4(41)
U14 GY RX2(9)- TB4(42)
U21 GY PU(E7)- TB4(49)
U22 GY PU(E8)- TB4(50)
U63 GY 295B(5)- 295Y(5)- 295R(5)- TB4(43)
U64 GY 295R(7)- TB4(44)
U66 GY 295Y(7)- TB4(45)
U68 GY 295B(7)- TB4(46)

Page 5 of 5