Professional Documents
Culture Documents
Specified Conditions As Per Heat Load Calculations Requirement
Specified Conditions As Per Heat Load Calculations Requirement
SPECIFIED CONDITIONS
SN.
Location
UNIT TYPE
TMBH
(NOM)
CFM
QTY
TMBH
SMBH
DCFM
TR
AC-GF-FCU-01
Ducted
18
480
17.99
15.8
685
1.499
AC-GF-FCU-02
Ducted
18
640
17.46
16.36
779
1.455
AC-GF-FCU-03
Ducted
32
640
30.9
25.29
981
2.575
AC-GF-FCU-04
Ducted
72
1920
67.36
61
2757
5.613
AC-GF-FCU-05
Ducted
60
1600
55.28
51.44
2426
4.607
AC-FF-FCU-01
Ducted
18
480
19.06
17.97
862
1.588
AC-FF-FCU-02
Ducted
24
480
25.41
24.31
1189
2.118
AC-FF-FCU-03
Ducted
12
480
13.04
11.94
551
1.087
AC-FF-FCU-04
Ducted
24
640
11.2
10.83
494
0.933
10
AC-FF-FCU-05
Ducted
36
960
29.84
28.75
1418
2.487
11
AC-FF-FCU-06
Ducted
32
800
28.9
27.25
588
2.408
55
Note:
1. Selected Capacities are based on the following conditions:
Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB
Design conditions selected based on 27/19 air on coil & 46 deg C ambient temp.
Apparatus dew point temperature 55 deg F, Bypass factor 0.1
Ambient Temperature 115 F
Refrigerent Type: R-407 C
FIT-410.01 R0 D01/06/2010
SPECIFIED CONDITIONS
SN.
Location
UNIT TYPE
TMBH
(NOM)
CFM
QTY
TMBH
SMBH
DCFM
TR
AC-GF-FCU-01
Ducted
18
480
20
14.62
13.72
896
1.22
AC-GF-FCU-02
Ducted
18
480
20
15.78
15.33
1001
1.32
AC-GF-FCU-03
Ducted
24
640
20
22.88
20.84
1361
1.91
AC-GF-FCU-04
Ducted
60
1600
20
63.15
61.8
4037
5.26
AC-GF-FCU-05
Ducted
36
960
20
38.1
36.06
2355
3.18
AC-FF-FCU-01
Ducted
30
800
20
27.97
27.52
1798
2.33
AC-FF-FCU-02
Ducted
24
640
20
20.23
19.78
1292
1.69
AC-FF-FCU-03
Ducted
30
800
20
27.27
26.82
1752
2.27
AC-FF-FCU-04
Ducted
36
1120
20
38.71
38026
2499
3.23
10
AC-FF-FCU-05
Ducted
36
1120
20
38.23
37.1
2423
3.19
200
Note:
1. Selected Capacities are based on the following conditions:
Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB
Apparatus dew point temperature 55 deg F, Bypass factor 0.1
Ambient Temperature 115 F
Refrigerent Type: R-407 C
FIT-410.01 R0 D01/06/2010
SPECIFIED CONDITIONS
SN.
Location
UNIT TYPE
TMBH
(NOM)
CFM
QTY
TMBH
SMBH
DCFM
AC-GF-FCU-01
Ducted
18
480
23
14.62
13.72
896
1.22
AC-GF-FCU-02
Ducted
18
480
23
15.78
15.33
1001
1.32
AC-GF-FCU-03
Ducted
24
640
23
22.88
20.84
1361
1.91
AC-GF-FCU-04
Ducted
72
1600
23
63.15
61.8
4037
5.26
AC-GF-FCU-05
Ducted
36
960
23
38.1
36.06
2355
3.18
AC-FF-FCU-01
Ducted
24
800
23
14.22
13.12
612
1.19
AC-FF-FCU-02
Ducted
18
480
23
18.66
17.56
841
1.56
AC-FF-FCU-03
Ducted
42
1120
23
23.82
22.72
1107
1.99
AC-FF-FCU-04
Ducted
48
1280
23
31.47
27.62
1198
2.62
207
Note:
1. Selected Capacities are based on the following conditions:
Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB
Apparatus dew point temperature 55 deg F, Bypass factor 0.1
Ambient Temperature 115 F
Refrigerent Type: R-407 C
FIT-410.01 R0 D01/06/2010
SPECIFIED CONDITIONS
SN.
Location
UNIT TYPE
TMBH
(NOM)
CFM
QTY
TMBH
SMBH
DCFM
TR
AC-GF-SP-01
Split
160
61
8.04
6.94
293
0.67
AC-GF-FCU-02
Ducted
24
640
61
29.59
27.39
1283
2.47
AC-GF-FCU-03
Ducted
72
1920
61
61.4
57
2681
5.12
AC-FF-FCU-01
Ducted
36
960
61
30.75
29.11
1404
2.56
AC-FF-FCU-02
Ducted
42
1120
61
45.34
42.05
1974
3.78
AC-FF-FCU-03
Ducted
18
480
61
16.51
15.42
730
1.38
366
Note:
1. Selected Capacities are based on the following conditions:
Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB
Apparatus dew point temperature 55 deg F, Bypass factor 0.1
Ambient Temperature 115 F
Refrigerent Type: R-407 C
FIT-410.01 R0 D01/06/2010
SPECIFIED CONDITIONS
SN.
Location
UNIT TYPE
TMBH
(NOM)
CFM
QTY
TMBH
SMBH
DCFM
TR
AC-GF-FCU-01
Split
12
320
48
10.95
9.85
443
0.91
AC-GF-FCU-02
Ducted
42
1280
48
58.66
53.17
2418
4.89
AC-FF-FCU-01
Ducted
18
480
48
17.6
16.5
786
1.47
AC-FF-FCU-02
Ducted
30
800
48
22.81
17.87
630
1.90
AC-FF-FCU-03
Ducted
24
640
48
24.96
22.77
1045
2.08
240
Note:
1. Selected Capacities are based on the following conditions:
Entering Air Temperature 70 F (21.1 C) DB / 60 F (15.60 C) WB
Apparatus dew point temperature 55 deg F, Bypass factor 0.1
Ambient Temperature 115 F
Refrigerent Type: R-407 C
FIT-410.01 R0 D01/06/2010