Professional Documents
Culture Documents
Saving Energy in Lab Exhaust Systems: 2 6 ASHRAE Journal J U N e 2 0 1 1
Saving Energy in Lab Exhaust Systems: 2 6 ASHRAE Journal J U N e 2 0 1 1
Figure 1: Relationship of stack and plume heights. Left: good air quality; potential wasted energy. Right: bad air quality; lower energy use.
Saving Energy in
Lab Exhaust Systems
By John J. Carter, Member ASHRAE; Brad C. Cochran, Member ASHRAE; and Jeff D. Reifschneider
ASHRAE Journal
In the past (and even now, its true), particularly for laboratories, the desire was to
keep exhaust stacks as short as possible
to limit the visual impact. This strategy
often results in systems with higher exit
velocities and/or larger volume flow rates
than would otherwise be required. This
is because concentration levels of emitted contaminants typically are inversely
proportional to plume rise: larger plume
rise equals lower concentrations (better air
quality). Plume rise is obtained through
physical stack height and the vertical moAbout the Authors
John J. Carter is a senior associate;
Brad C. Cochran is a senior associate
and a senior project engineer; and Jeff
D. Reifschneider is a senior engineer at
CPP in Fort Collins, Colo.
a s h r a e . o r g
June 2011
mentum of the plume. The shorter the stack, the greater the vertical momentum (i.e., fan power) that is required to achieve the
appropriate plume height (Figure 1 and Equation 1).
Plume Rise = Physical Stack Height
(1)
+
f(Volume FlowVelocity)1/3
= Physical Stack Height+f(ConstantFan Powern)
This high energy demand associated with the shorter stack
heights contradicts the current emphasis on energy conservation in sustainable laboratory design.
The country is focused on methods to save energy with particular focus on turning off lights, riding a bicycle, etc., yet there
is a huge amount of unrealized energy savings available in our
nations research and teaching laboratories. A typical laboratory
consumes up to 10 times the energy per square foot of an office
building, while specialized laboratories may consume up to 100
times more energy.5 Due to the requirements for high air change
rates of 100% outside air, the ventilation system uses a high
percentage of this energy, often up to 80%.6,7 The ventilation of
a laboratory can be broken down into three systems; the outside
air supply system, conditioning (temperature, humidity, filtration, etc.), and the exhaust system.
The supply air and conditioning systems account for approximately 60%6,7 of the ventilation system energy consumption and
have been the focus of laboratory designers for the past several
decades. Variable air volume (VAV) air-handling units have become typical in laboratory design to minimize airflow to match
the buildings ventilation demands, which can vary throughout
the day, depending upon the laboratory occupancy, the fume hood
activity (when VAV fume hoods are installed) and, in some cases,
the quality of the indoor air. Heat recovery systems also are used
regularly, particularly in northern climates, to reduce the energy
consumption of the air-conditioning systems.
Energy saving strategies often overlook the exhaust system,
even though it accounts for the other 40% of the ventilation
systems energy consumption and about 30% of the laboratory
buildings total energy consumption.6,7
Traditionally, laboratories have been designed such that the
exhaust system must operate at full load conditions 24 hours
a day, 365 days a yeara constant volume (CV) exhaust. Full
load often meant the minimum flows to achieve acceptable
air quality, which in some cases could be significantly greater
than the ventilation requirement, particularly for short stacks.
In addition, this air quality setpoint was based on the worstcase wind condition, which typically occurs only for a small
fraction of total hours each year and the assumption that the
exhaust stream actually contains the worst-case contaminants.
We will discuss three strategies that can be used, in part or
in whole, during the design of a new laboratory or renovation
of an existing laboratory. These strategies can safely reduce
the energy consumption of the exhaust system by about 50%
compared to a typical CV system, which equates to a 15% reduction in the laboratorys total energy use. We will also present some case study results.
June 2011
27
ASHRAE Journal
a s h r a e . o r g
June 2011
Concentration (mg/m3)/(g/s)
450
400
350
300
250
200
150
800
100
0
0
900
Concentration (mg/m3)/(g/s)
500
700
600
500
400
300
200
100
0
0 4.5 9.0 13.5 18 22.5 27
Wind Speed
Full Load
60% Load
80% Load
40% Load
Figure 4a (left): Normalized concentration distribution (C/m) versus wind direction. Figure 4b (right): Normalized concentration
distributions (C/m) versus wind speeds for various fan loads.
(Degrees)
(04)
(47)
(79)
0
235
240
245
250
255
260
265
270
275
280
285
290
295
300
305
310
315
320
325
330
335
340
345
350
355
13%
21%
25%
26%
25%
21%
25%
27%
33%
48%
60%
64%
68%
65%
73%
65%
49%
35%
22%
15%
27%
30%
27%
19%
26%
28%
27%
37%
58%
73%
78%
75%
73%
64%
50%
31%
18%
24%
18%
18%
25%
27%
26%
35%
57%
75%
81%
80%
76%
64%
45%
27%
(911) (1113) (1316) (1618) (1820) (2022) (2225) (2527) (2729) (2931) ( >31)
13%
16%
13%
17%
24%
26%
26%
33%
55%
73%
81%
78%
73%
60%
41%
25%
11%
13%
11%
17%
23%
26%
25%
32%
53%
71%
79%
74%
69%
55%
38%
24%
11%
16%
22%
25%
25%
32%
51%
69%
76%
69%
64%
52%
37%
23%
11%
16%
22%
24%
25%
31%
50%
68%
75%
68%
61%
49%
35%
23%
16%
22%
24%
24%
31%
49%
66%
73%
66%
58%
47%
34%
22%
16%
21%
24%
24%
31%
49%
65%
71%
65%
56%
46%
33%
22%
15%
21%
23%
24%
30%
48%
64%
70%
64%
54%
45%
33%
22%
15%
21%
23%
24%
30%
47%
63%
69%
63%
53%
44%
32%
21%
15%
21%
23%
24%
30%
47%
62%
68%
62%
52%
43%
32%
21%
15%
21%
23%
24%
30%
47%
62%
68%
62%
51%
42%
31%
21%
15%
20%
23%
24%
30%
46%
61%
67%
61%
50%
42%
31%
21%
Table 1: Minimum fan load percentages versus anemometer reading (BAS lookup table).
30
ASHRAE Journal
a s h r a e . o r g
June 2011
Total
Per Fan
Total
Per Fan
156,000 cfm
52,000 cfm
78,000
26,000
52,000 cfm
the three configurations versus a constant volume system at the full design
flow. Manufacturer power curves were
used in conjunction with TMY data
(National Renewable Energy Laboratorys Typical Meteorological Year)
and a $0.10 per kWh rate. Table 3
shows a respectable annual cost savings of about $100,000 for the VAV
systems without an anemometer, increasing to about $120,000 per year
for the system with the anemometer.
AHU
400 mg/m3 per g/s
Air Intake
Supply Louvers
Full
Load
Reduced Load
Monitor
Chemical Detected: Exhaust flow rate increased
to achieve more stringent design criterion.
Fume Hood
A S H R A E J o u r n a l
June 2011
Summary
We have shown that using advanced control technologies, including variable air volume exhaust systems, local wind measurements and building automation systems, in
conjunction with state-of-the-art exhaust
dispersion modeling techniques can result
34
160
140
140
120
120
100
100
80
80
60
60
40
20
160
40
20
0
0
160 150 140 130 120 110 100 90 80 70 60
160
160
140
140
120
120
100
100
80
80
60
60
40
20
40
20
0
0
160 150 140 130 120 110 100 90 80 70 60
Building Load (cfm [In Thousands])
160
160
140
140
120
120
100
100
80
80
60
60
40
20
and Bren Hall. The minimum air quality setpoints, both wind and without anemometer
control, were defined as discussed earlier.
Since these buildings have been occupied
for some time, actual building load profiles
were available for predicting electricity costs.
In addition, Southern Cal Edison offered a rebate or $0.24 per kWh saved for the first year,
limited to the cost to implement the system.
Table 4 shows that CNSI was already operating at about 60% of the planned full load
energy consumption prior to conducting
the wind tunnel tests. However, under those
flow conditions, the air quality design criterion was predicted to be exceeded about
7% of the time. By implementing a staged
VAV system with anemometer control, annual energy consumption could be reduced
to about 10% of the existing consumptionall while maintaining acceptable air
quality. This will result in about $81,000 in
annual electricity savings versus the existing operation, with an additional bonus of
about $90,000 from Southern Cal Edison
($0.24 per saved kWh limited by the cost
to upgrade)roughly $80,000 savings the
first year after everything is paid for.
Table 4 shows more modest, but still respectable, performance for the MSRB. Energy consumption could be reduced to about
42% of existing, with an annual electricity
savings of about $14,000. Bren Halls existing
energy consumption, and total exhaust flow
rate, is at lower than the other two buildings,
resulting in much more modest cost savings.
Based on the studies we have conducted to
date, it appears that savings in the range of
$1.06 per L/s ($0.50 per cfm) can be achieved
for many laboratory exhaust systems. In general, it takes systems on the order of 9 439 L/s
to 14 158 L/s (20,000 to 30,000 cfm) before
significant turndown starts to become available. It is likely that smaller systems could
also achieve turndown with favorable surrounding building environments, but annual
costs savings obviously decrease dramatically
as total exhaust flow is reduced.
40
20
0
0
160 150 140 130 120 110 100 90 80 70 60
Building Load (cfm [In Thousands])
Figure 6a (top): Fan load and energy profiles for VAV+Bypass. Figure 6b (center): Staged VAV. Figure 6c (bottom): Staged VAV with anemometer.
A S H R A E J o u r n a l
June 2011
in significantly lower energy consumption, and related electricity costs, for existing and planned laboratories.
Annual Energy
Consumption
Exhaust Configuration
(kWh)
Exhaust
Configuration
Percent Time
Air Quality
Criterion
Is Not Met
Annual
Energy
Consumption
(kWh)
Energy
(kWh)
($)
1,934
VAV+Bypass
962
972
$97,165
VAV+Staged
1,001
933
$93,241
VAV+Staged+Anemometer
709
1,225
$122,494
References
1. Fisk, W.J. 2000. Review of Health and Productivity Gains from
Better IEQ. Proceedings of Healthy Buildings 4:2334.
2. Yates, A. 2001. Quantifying the Business Benefits of Sustainable
Buildings (Draft), Building Research Establishment, Ltd., Project
Report 203995.
3. Kats, G. 2003. The Costs and Financial Benefits of Green
Buildings. Californias Sustainable Building Task Force, Capital E.
4. ANSI/AIHA Standard Z9.5-2003, American National Standard for Laboratory Ventilation. American Industrial Hygiene
Association.
5. EPA. 2000. An Introduction to Low-Energy Design. Laboratories for the 21st Century, U.S. Environmental Protection Agency,
DOE/GO-102000-1112.
6. Laboratories for the 21st Century. 2010. Labs21 Benchmarking
Tool. www.labs21century.gov/toolkit/benchmarking.htm.
7. Kaushansky, J., G. Maine. 2002. Laboratories for the 21st
Century: Case StudiesPharmacia Building Q, Skokie, Illinois.
Laboratories for the 21st Century.
8. 2007 ASHRAE HandbookHVAC Applications, Chapter 44,
Building Air Intake and Exhaust Design.
9. Carter, J., R. Petersen, B.C. Cochran. 2005. Specifying exhaust
Savings vs. CV
($)
(kWh)
First
Year
Return
SCE
Rebate
($)
($)
($)
(Years)
1,839,505
Existing Conditions
7.39%
904,075
Staged Operation
With WD/WS Monitor
0%
94,814
809,260
$80,926
$90,400
$171,326
$90,400
$1,000
0.3
721,823
Existing Conditions
0%
248,229
Staged Operation
With WD/WS Monitor
0%
104,434
143,795
$14,380
$62,800
$48,890
$62,800
$1,000
2.1
0%
159,053
Staged Operation
With WD/WS Monitor
0%
61,875
97,268
$9,727
$23,344
$33,071
$58,300
$1,000
4.0
ASHRAE Journal
a s h r a e . o r g
June 2011