Design calculation sheet

Project Asmakh Heritage Village

Subject Oil Interceptor Calculation

Area Generator Room Substation 02

Determining Oil interceptor Flow Rate

Expected flow rate discahrged into the Generator room Oil interceptor is as following

The expected general cleaning water flow rate for the room is equivalent to a service hose bib flow rate, could be used during maintenance.

1)Calculate Service Hose flow rate

As per IPC 2018, Water fixture load values for fixtures

Service Hose bib maximum WSFU value is 3 WSFU (Taken from Combined flow of a Service Sink as highlighted in attachement)

Equivalent Flowrate in GPM 6.5 gpm

Drainage fixture Unit Value, based on trap Size as per ASPE Plumbing DATA BOOK (Attached)

Fixture Outlet (Trap Drainage Fixture GPM Equivalent


Size) Unit Value
1-1/4” 1 7.5

1-1/2” 2 15

2” 3 22

2” 4 30

3” 5 37.5

4” 6 45

Proposed intercepor Outlet size is 2" (50mm as per attached data sheet) which can discharge 20 gpm flow rate, hence

the interceptor size is acceptable.

Poposed Oil intercptor has a oil/sludge collection capacity of 5 kg as per manufacturer data sheet.