Expected flow rate discahrged into the Generator room Oil interceptor is as following
The expected general cleaning water flow rate for the room is equivalent to a service hose bib flow rate, could be used during maintenance.
Service Hose bib maximum WSFU value is 3 WSFU (Taken from Combined flow of a Service Sink as highlighted in attachement)
Drainage fixture Unit Value, based on trap Size as per ASPE Plumbing DATA BOOK (Attached)
1-1/2” 2 15
2” 3 22
2” 4 30
3” 5 37.5
4” 6 45
Proposed intercepor Outlet size is 2" (50mm as per attached data sheet) which can discharge 20 gpm flow rate, hence
Poposed Oil intercptor has a oil/sludge collection capacity of 5 kg as per manufacturer data sheet.