Professional Documents
Culture Documents
Ref.
Application of VGF Engines EN: 156543
S
at Elevated Jacket Water Temperatures DATE: 10/13
7790-1
GE Power & Water
Distributed Power Cooling Systems
1) Alarm & Shutdown Setpoints, S8382 (or latest revision); found in General Tech Data Book under the “Control
Systems” tab,
2) Coolant Rate of Change Shutdown Control, PSA-1211M; reference Waukesha Power Systems Price Book,
Engomatic Control System Model 1105.
b) Coolant Flow and Circuit Restrictions: Table 1 and Table 2 below depict the minimum and maximum flows and
restrictions for VGF jacket water circuits and auxiliary water circuits. Note: The restriction data below reflects jacket
water and auxiliary water circuits without thermostats, as these devices are supplied by the customer.
TABLE 2. VGF Auxiliary Water Flows and Restrictions (intercooler in series with oil cooler; without thermostats);
applies to intercooler water inlet temperatures 130°F (54°C) or less.
AUXILIARY WATER
CIRCUIT RESTRICTION AUXILIARY WATER
MINIMUM AUX COOLANT (PSI) AT MINIMUM MAXIMUM AUX COOLANT CIRCUIT RESTRICTION
ENGINE FLOW (GPM) AUX FLOW FLOW (GPM) (PSI) AT MAXIMUM AUX COOLANT
MODEL 1500 / 1800 RPM 1500 / 1800 RPM ALL RPM’S FLOW
F18 25 / 35 1.2 / 2.4 70 9.6
H24 25 / 35 1.2 / 2.4 70 9.6
L36 52 / 62 4.6 / 6.5 105 18.6
P48 71 / 87 8.5 / 12.8 105 18.6
NOTES:
1. liters per minute = gpm x 3.785
2. kPa = psi x 6.894
c) Cooling System Pressures: To maintain proper cooling system performance, the following cooling system static
pressures must be maintained:
1) Pressure at engine jacket water inlet connection flange:
a) Minimum: 45 psia (310 kPa).
b) Maximum: 75 psia (517 kPa).
2) Pressure at intercooler water inlet connection flange:
a) Maximum: 90 psia (621 kPa).
These minimum and maximum pressures are achieved through proper sizing of external restrictions (heat exchangers,
piping, thermostats, etc.) combined with proper expansion tank design. For information on expansion tank design, including
pressure cap rating selection, reference the latest revisions of Cooling Systems, Chapter 4 of the Waukesha Installation
Manual (Form 1091), and Cooling System Guidelines for Waukesha Engines, S6699-7 (or latest version).
Page 2 of 5
Ref.
Application of VGF Engines EN: 156543
S
at Elevated Jacket Water Temperatures DATE: 10/13
7790-1
GE Power & Water
Distributed Power Cooling Systems
Note: In addition to meeting the above system pressure requirements, the expansion tanks are also required to meet the
net positive suction head (NPSH) requirements of the customer-supplied water pumps. The customer is advised to consult
with their pump manufacturer regarding net positive suction head requirements.
d) Cooling System Design and Layout: Elevated jacket water cooling systems can be relatively complex cooling
systems, incorporating exhaust heat recovery units, waste dump heat exchangers, multiple water pumps and
multiple temperature controls. In addition, the high jacket water temperatures encountered in these systems will
cause the coolant to flash to steam unless maintained at proper pressure levels. Thus, the complexity of the system,
combined with the potential for the coolant to flash to steam, dictates that special measures be taken to assure
proper cooling system performance. The documents listed below contain information vital to the proper design of
elevated jacket water cooling systems:
1) Cooling Systems, Waukesha Installation Manual, Form 1091 (or latest revision),
2) Cooling System Guidelines for Waukesha Engines, S6699-7 (or latest revision); found in General Tech Data Book
under the “Cooling Systems” tab,
3) Elevated Temperature Cooling Systems, WPS 7/90; found in the General Tech Data Book under the “Application
Notes” tab.
The suggested minimum jacket water circuit return delta temperature into a warm engine is 30°F (16.6°C) less than the
designed jacket water outlet temperature with a maximum rate-of-change return temperature of 18°F (10°C) per minute
while between the minimum and maximum operating temperatures. See Waukesha Installation Manual, Form 1091, (or
latest revision), for more information.
Figures 1 and 2 depict typical elevated temperature cooling system layouts using a water-to-water heat exchanger for
isolation of the jacket water coolant circuit and recovery of engine heat for use in a process thermal requirement. A waste
dump heat exchanger can be included in the process loop to allow continued engine operation during periods when there is
little or no process thermal requirement. The waste dump heat exchanger can be a remote fan-cooled radiator, a cooling
tower, or some other type of heat exchanger device. As is typical of the VGF engine family, the auxiliary water circuit
(intercooler and lube oil cooler) require a separate source of cooling water, as aux water temperatures are significantly less
than jacket water temperatures.
Figure 2 is similar to Figure 1, with the addition of a heat recovery silencer. Note that in either schematic, the process loop
requires its own circulating water pump. The exhaust gas temperature exiting the heat recovery silencer should be kept to a
minimum of 100°F (55°C) above the engine jacket water outlet temperature to prevent condensation within the silencer.
Figures 1 and 2 are generic high temperature cooling systems, and do not depict all valving, air bleeds, orifices, balance
lines, bypasses, etc. Reference Cooling Systems, Waukesha Installation Manual, Form 1091 (or latest revision), for complete
cooling system component details.
Page 3 of 5
Ref.
Application of VGF Engines EN: 156543
S
at Elevated Jacket Water Temperatures DATE: 10/13
7790-1
GE Power & Water
Distributed Power Cooling Systems
Page 4 of 5
Ref.
Application of VGF Engines EN: 156543
S
at Elevated Jacket Water Temperatures DATE: 10/13
7790-1
GE Power & Water
Distributed Power Cooling Systems
*Trademark of General Electric Company. All other trademarks are the property of their respective owners.
Page 5 of 5
Ref.
Application of VGF Engines EN: 156543
S
at Elevated Jacket Water Temperatures DATE: 10/13
7790-1