1.2 CS31 System Bus: Advant Controller 31 / Issued: 05.2001
1.2 CS31 System Bus: Advant Controller 31 / Issued: 05.2001
Wiring
Bus line
construction
conductor cross section
recommendation
twisting rate
core insulation
resistance per core
characteristic impedance
Capacitance between the cores
terminating resistors
bus length
Remarks
1-3
Bus configurations
A CS31 system bus always contains only one bus master (basic unit or coupler) which controls all actions on the
bus. Up to 31 slaves can be connected to the bus, e.g.
remote modules or slave-configured basic units.
Fig. 1.2-1:
direct
earthing
with clip
on cabinet
steel plate
CS31
slave
CS31
slave
Bus configuration for CS31 system bus (bus master at one end of the bus line)
This configuration is
not possible for the
couplers 07 CS 61
and 35 CS 91.
CS31
slave
CS31
slave
direct
earthing
with clip
Fig. 1.2-2:
Bus configuration for CS31 system bus (bus master within the bus line)
This configuration is only possible for bus masters that do not contain internal bus terminating resistors.
Therefore, this configuration is not allowed with the couplers 07 CS 61 and 35 CS 91.
1-4
RIGHT!
Bus line is looped through
from module to module.
CS31 system bus
CS31
slave
Fig. 1.2-3:
CS31
slave
Earthing
In order to avoid disturbance, the cable shields must be earthed directly.
Case a:
Several switch-gear cabinets: If it can be guaranteed that no potential differences can occur between the switch-gear
cabinets by means of current-carrying metal connections (earthing bars, steel constructions etc.), the direct earthing is
chosen.
CS31
slave
CS31
slave
Cabinet 1
CS31
slave
Cabinet 2
Current-carrying connection
Fig. 1.2-4:
Current-carrying connection
Direct earthing
1-5
Case b:
Several switch-gear cabinets: If potential differences can occur between the switch-gear cabinets, the capacitive earthing is chosen in order to avoid circulating currents on the cable shields.
Switch-gear cabinet 1
CS31 system bus
CS31
master
CS31
slave
Earthing bar
cabinet 1
Cabinet earthing
Switch-gear cabinet 2
capacitive earthing with 0,1 F X-type capacitor directly on the cabinet's steel plate
CS31
slave
CS31
slave
Earthing bar
cabinet 2
Cabinet earthing
Fig. 1.2-5:
Earthing concept with several switch-gear cabinets: direct earthing of cable shields when cables
enter the first switch-gear cabinet (containing the master), and capacitive earthing at the modules
Note: The total length of the earthing connections shield-module and module-earthing bar must be as short as possible
(max. 25 cm). The conductor cross section must be at least 2.5 mm2.
VDE 0160 requires, that the shield must be earthed directly at least once per system.
_____________________________________________________________________________________________________
1.3
see volume 5