You are on page 1of 69

Shear Behaviour of Large, Lightly-Reinforced

Concrete Beams and One-Way Slabs

CHAPTER 4:

One-Way Slabs

ONE-WAY SLABS

In science, 'fact' can only mean 'confirmed to such a degree that it would be perverse to
withhold provisional assent.' I suppose that apples might start to rise tomorrow, but the possibility
does not merit equal time in physics classrooms. -Stephen Jay Gould

This Chapter reports on two series of experiments that are extensions to beam AT1 described in Chapter 3. The AT-2 series was designed to study the effect of
beam and slab width on shear strength. It is found that the failure shear stress of
slabs is independent of width, and it is inappropriate for the ACI-318 code to
dictate a different level of usable shear before stirrups are required in slabs versus
narrow beams. It is also shown that experimental results from narrow beams can
be applied to the study of wide slabs. The AT-3 series of experiments were
conducted to study the effect of horizontal shrinkage/temperature steel on one-way
shear strength of slabs. It is shown that this type of reinforcement has no effect.

4.1 General
One-way slabs are those slabs with an aspect ratio in plan of 2:1 or greater, in which
bending is primarily about the long axis (Figure 4-1). In heavily loaded slabs, the
thickness is often governed by shear or flexure, while in lightly-loaded slabs, the
thickness is generally chosen based on deflection limitations. Both lightly and heavily
loaded slabs are typically dimensioned so that no shear reinforcement is required, as
placing stirrups in slabs is perceived to be difficult and costly. One-way slabs are
designed for flexure and shear on a per meter width basis, assuming that they act as a
series of independent strips. Thus one-way shear in slabs is often referred to as beam
shear, and design for flexure and shear is carried out using a beam analogy.
The thickness of two-way slabs and plates is typically governed by deflection limitations
or two-way shear at the columns, and one-way shear does not usually govern. However,
two-way slabs must be checked for both one-way and two-way shear, and it is reasonably
straightforward to conceive of a two-way slab system in which one-way shear governs.
90

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Like one-way slabs, design for one-way shear in two-way slabs is usually carried out
using a unit-width beam analogy, assuming the entire slab width is fully effective at
resisting shear.

Figure 4-1: One-Way Slab Supported on Beams on all Four Sides


Because one-way slabs are designed for shear by assuming that they act as a series of
adjacent beams spanning in one direction, it is reasonable to conclude that the size effect
that governs the shear behaviour of thick beams will apply. Furthermore, it is likely that
two-way slabs in which two-way shear governs will exhibit a size effect in one-way shear.
It is also appears (Mitchell et. al. (2005)) that there is a size effect in two-way shear, but
that is beyond the scope of the present study.
Like the wide beam exemption discussed in Chapter 3, Clause 11.5.6.1.(a) of the ACI
318-05 code exempts slabs from requiring minimum shear reinforcement when the
factored shear force, Vu exceeds Vc. See Table 3-1. Thus, the full value of Vc may
be employed in slabs before stirrups are required. Similar to the case of wide beams, the
ACI commentary states that redistribution of loads is possible, resulting in a higher actual
one-way shear strength. In the example shown in Figure 4-1 in which the slab is
supported on stiff beams on all four sides, and where the aspect ratio in plan is not much
greater than 2:1, some redistribution may be possible due to two-way action. However,
in one-way slabs with an aspect ratio considerably greater than 2:1, redistribution due to
91

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

two-way action may be negligible. Furthermore, in one-way slabs supported on stiff


supports along only two sides (Figure 4-2) no redistribution will be possible, and the full
width of the slab may be called upon to resist the full shear.

Figure 4-2: One-Way Slab Supported on Beams on Two Sides


It appears reasonable to assume that one-way slabs will exhibit a size effect in one-way
shear. Because one-way slabs are often dimensioned to avoid the use of stirrups, it would
appear that they would therefore be particularly vulnerable to the size effect.

4.1.1

One-Way Slabs vs. Wide Beams

Beam AT-1 demonstrated that width had no effect on one-way shear stress capacity and
that the ACI wide beam exemption is not appropriate for thick beams. However, it was
designed to investigate the specific case of the ACI wide beam exemption. The major
differences between a beam and a one-way slab include the fact that one-way slabs may
be many times wider than typical beams, and that additional horizontal transverse
reinforcement to control shrinkage and temperature cracking is employed.
Because shallow one-way slabs are thinner than supporting beams, the slab concrete may
exhibit greater shrinkage than the beam concrete at an earlier age (MacGregor and
Bartlett (2000)). This restrained shrinkage may result in shrinkage cracks. Furthermore,
thin slabs have a lower thermal mass than the supporting beams and may therefore
exhibit wider swings in temperature. These different thermal properties can result in
92

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

cracking due to restrained thermal shrinkage. While flexural steel in the spanning
direction will limit the width of these shrinkage and temperature cracks, cracks parallel to
the span may form. To control the width of these potentially wide cracks, building codes
will typically require that additional horizontal steel be placed transverse to the spanning
direction. This additional reinforcement is not unimportant, as shrinkage and temperature
cracks have the potential to become quite wide. MacGregor and Bartlett (2000), for
example, suggest that the purpose of this reinforcement is to hold the slab together
after shrinkage occurs.
In Section 7.12 of the ACI code it is noted that reinforcement for shrinkage and
temperature stresses normal to flexural reinforcement shall be provided in structural slabs
where the flexural reinforcement extends in one direction only. For grade 60ksi
(414MPa) steel, the required amount of shrinkage and temperature steel is 0.18% of the
gross area (width times overall height). In the CSA code, this amount is 0.2% of the
gross area. In situations where considerable restraint is present, reinforcement in addition
to that specifically required by the code may be required. In completely restrained
situations, MacGregor and Bartlett suggest that three times the specified minimum
amount is required. While shrinkage and temperature reinforcement may be placed
anywhere in the slab, it is typically placed directly above the lower layer of steel to
simplify construction.
After publishing the results of beam AT-1, it became apparent that additional studies
were required in the specific case of one-way slabs. In particular, the effects of
horizontal shrinkage and temperature reinforcement perpendicular to the spanning
direction needed to be addressed, as well as the one-way shear behaviour of elements
with widths many times their depths. Lastly, the question of whether the results of oneway shear tests on narrow beams can be applied to one-way slabs needed to be addressed.
A series of specimens were thus designed by the author and tested collaboratively by the
author and Adam Lubell (Lubell (2006)) to complement the results from AT-1. These
specimens are referred to as the AT-2 and AT-3 series of tests.
93

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

4.2 Experimental Program AT-2 Series


4.2.1

Specimen Design and Construction

The design of the AT-2 series of specimens is summarized in Figure 4-3. A total of five
specimens were constructed. The specimens measured nominally 470mm tall and
2900mm long. Two specimens were 250 mm wide, two were 1000mm wide, and one
was 3000mm wide. The 3000mm wide specimen was designed to represent a three-bay
wide transfer slab supporting three point loads at its mid-point. The 1000mm wide
specimens were designed to represent a one-bay wide design strip extracted from the
transfer slab. The 250mm wide specimens were designed to represent typical beam
specimens that are tested to study one-way shear.
They were all reinforced in the longitudinal (N-S) direction with 25M rebars spaced at
125mm at an effective depth of 440mm, for a reinforcement ratio of 0.91%. The
3000mm and 1000mm wide specimens were further reinforced with 15M rebars spaced at
223mm in the transverse (E-W) horizontal direction. These 15M bars were placed as
temperature and shrinkage reinforcement. The provided shrinkage and temperature
reinforcement ratio, s+t, was 0.19%, which is greater than the 0.18% ratio required by the
ACI code. The 250mm wide specimens, representing typical beam-type specimens, did
not have horizontal transverse reinforcement as beams are generally not constructed with
such reinforcement.
Based on the concrete strength of the day of test, and by the ACI code, each specimen
had a nominal flexural capacity of about 765kN-m/m width, with corresponding nominal
one-way shear capacities of between about 450 to 468kN/meter width. One-way shear
governed over two-way shear in all specimens, with the one-way shear capacity being
about 44% of the two-way shear capacity calculated on a critical perimeter located d/2
from the edge of the loading plates. After accounting for self weight, the ACI code
predicted that the specimens would fail in one-way shear at applied loads of between 7679% of the load required to fail them in flexure.
94

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-3: Design of AT-2 Series of Test Specimens


95

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

The formwork for the AT-2 series is shown in Figure 4-4 and Figure 4-5. The formwork
was constructed on a base of multiple layers of 19.1mm (3/4 in.) plywood, and consisted
of 3/4in. formply supported using steel walers and braces. Following casting, the
concrete was cured under wet burlap and plastic sheeting for five days.

Figure 4-4: AT-3 Series Formwork

Figure 4-5: AT-3/3000 Formwork


96

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

4.2.2

One-Way Slabs

Material Properties

Concrete and steel material properties are summarized in Table 4-1 and Table 4-2. The
concrete was ordered from a local ready-mix company with a specified 28-day strength
of 25MPa. The maximum aggregate size was 10mm (3/8 in.), and the coarse aggregate
was obtained from the same quarry as the aggregate used for beam AT-1. On the day of
test, ranging from 55 to 84 days after casting, the measured concrete strength varied from
37.7-40.6MPa. The specimens were removed from their formwork and exposed to
drying on their bottom faces for between two and seven days.
Table 4-1: Concrete Material Properties -AT-2 Series
Specimen

Cast Date

Test Date

f'c (MPa)

'c

-3
Day of Test x10

AT-2/250N

29 July, 2004

Sep. 22, 2004

37.7

--

AT-2/250W

29 July, 2004

Oct. 1, 2004

38.5

1.8

AT-2/1000N

29 July, 2004

Sep. 24, 2004

37.9

--

AT-2/1000W

29 July, 2004

Oct. 8, 2004

39.0

2.0

AT-2/3000

29 July, 2004

Oct. 20/21, 2004

40.6

2.1

Table 4-2: Steel Properties -AT-2 Series

4.2.3

Bar Type

As (mm2)

fy (MPa)

fu (MPa)

15M
25M

200
500

452
465

595
618

Test Setup AT-2 Series

AT-2/250 and AT-2/1000 Series


The test setup for the AT-2/250 and 1000 series is shown in Figure 4-3 and Figures 4-6 to
4-8. Each specimen was tested in three-point bending in the Baldwin test frame in the
Mark Huggins Laboratory at the University of Toronto. Specimen AT-2/3000 was
aligned such that it spanned in the north-south direction, while the 250mm and 1000mm
wide specimens were aligned such that they spanned in the east-west direction. To
97

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

facilitate comparison between specimens, it will be assumed that the 250mm and
1000mm wide specimens were also aligned in the north-south direction. The actual south
faces of the 250 and 1000mm wide specimens correspond to the east face of specimen
AT-2/3000.
The specimens were supported at their north and south ends, 1300mm from the specimen
centerline, at an a/d ratio of 2.95. Specimens AT-2/250W and AT-2/1000W were
supported on 1200mm wide, 152mm long steel plates that were in turn supported on
rollers and steel beams placed directly on the floor of the test frame. These types of
supports will be referred to as wide supports (W). Specimens AT-2/250N and AT2/1000N were supported on 152x152x13mm steel plates placed atop of 152x152x51mm
neoprene bearing pads. The neoprene bearing pads were supported in turn on steel
pedestals placed directly on the floor of the test frame. These types of supports will be
referred to as narrow supports (N). In both the N and W series of specimens, a layer of
plaster-of-paris was placed between the bottom of the specimen and the steel plates to
avoid stress concentrations due to unevenness of the surface finish. The neoprene
bearing pads are of a type commonly used in bridge bearing and other heavy bearing
applications. They have little lateral stiffness, and act and as roller bearings.
Both the N and W series of specimens were loaded though pinned loading blocks that
were free to rotate about the E-W axis. Steel plates measuring 152x152x13mm were
placed between the loading blocks and the top of the specimens. A layer of plaster-ofparis was also placed between the steel plates and the top of the specimens to ensure
uniform load transfer.
Load was applied monotonically to the test specimens. Loading was paused at several
stages during the tests at which point the load was reduced slightly. During these load
stages cracks were marked using a felt-tip pen and photographed. Generally each test
lasted for about four to six hours.

98

One-Way Slabs

Figure 4-6: Test Setup AT-2/250 and AT-2/1000 Series

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

99

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-7: Test Setup: AT-2/250N

Figure 4-8: Test Setup: AT-2/1000W


100

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

AT-2/3000
AT-2/3000 was supported in a manner similar to specimens AT-2/250N and AT-2/1000N.
As shown in Figure 4-9 and Figure 4-10, specimen AT-2/3000 was supported on six steel
plates, neoprene bearing pads and steel pedestals bearing directly on the floor of the test
frame. Plaster-of-paris was placed between the 152x152mm steel plates and the bottom
of the specimen. The pedestals were spaced at 1000mm across the width of the specimen.
Neoprene bearing pads measuring 152x152x51mm and steel plates were placed on top of
the specimen at midspan, spaced at 1000mm on centres across the width. Load was
applied to the specimen through back-to-back steel spreader beams that were bolted
together and load cells spaced at 1000mm and aligned with the neoprene bearing pads.
The steel plates on top of the specimen were placed in a bed of plaster-of-paris prior to
loading. The moment of inertia of the combined spreader beam was about ______mm4.
Load was applied monotonically to the specimen. Loading was paused at several stages
during the test at which point the load was reduced slightly. During these load stages
cracks were marked using a felt-tip pen and photographed. Shortly after the third load
stage on the first day of testing, specimen AT-2/3000 suddenly shifted to the north by
about 25mm and the spreader beam rotated about its longitudinal (east-west) axis.
Because the neoprene bearings had little stiffness in their transverse direction, AT-3/3000
was statically unstable on day 1, and free to move in its horizontal plane. After this shift
occurred, the load was removed and the neoprene bearings on the top of the specimen
were replaced with steel spherical bearings. The test frame spherical head was also
locked against rotation, and this change in the test setup prevented the specimen from
shifting excessively on its supports. Specimen AT-2/3000 was left overnight without any
load applied to it, and loading was resumed the following day (Day 2). The peak load
reached on Day 1 was 2123kN.

101

One-Way Slabs

Figure 4-9: Test Setup AT-2/3000

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

102

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-10: Test Setup: AT-2/3000

4.2.4

Instrumentation AT-2 Series

The instrumentation used for the AT-2 series of specimens is summarized in Figure 4-11
and Figure 4-12.
Five LVDTs were placed at the midspan of specimen AT-2/3000. One LVDT was
placed directly below each of the three load cells, and the remaining two were placed at
either edge of the specimen. Additional LVDTs were placed at the supports. Two
LVDTs were placed at the midspan, quarterspans and supports for the 1000 and 250
series of specimens. Mid-span and quarterspan deflections were then corrected for
support settlement in all of the specimens. Horizontal LVDTs were placed below the
specimens at the supports to monitor north-south horizontal movements and to confirm
that the neoprene bearings allowed horizontal movements to occur, thereby behaving as
103

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

rollers. Side face LVDTs were applied to the 250mm and 1000mm wide specimens to
measure shear strains. No side face LVDTs were installed on specimen AT-2/3000.
A series of 5mm electrical resistance strain gauges was applied to the longitudinal
reinforcing bars in all of the specimens at midspan and quarterspan as shown in Figure
4-12. A series of strain gauges was also applied to the horizontal transverse reinforcing
bars in the 1000mm and 3000mm wide specimens as shown in the figure. These gauges
were set to zero prior to the start of loading. A grid of aluminum zurich targets was not
used in any of the AT-2 series of tests.
Shrinkage strains were measured at various locations in AT-2/1000N, AT-2/1000W and
AT-2/3000 prior to removing the specimens from their formwork using a manual strain
indicator box, and these shrinkage strains are presented in Table 4-3 and Table 4-4.
These strains are calculated based on measurements taken one day prior to removal from
formwork relative to zero-measurements taken about one hour after casting had been
completed. The shrinkage strains measured in the reinforcing bars were all compressive
(negative).

Table 4-3: Shrinkage Strains -AT-2/1000


Specimens
Strain
Gauge

Strain ()
AT-2/1000N AT-2/1000W

EN
EC
ES

-119
-186
-134

-121
-152
-201

MN
MC
MS

-98
-109
-101

-133
-120
-181

TN
TC
TS

-21
-69
-48

-50
-101
-92

Table 4-4: Shrinkage Strains -AT-2/3000


Strain
gauge

Strain ()

1N
1C
1S

-96
-102
-120

3N
3C
3S

-52
-84
-145

TSW
TSCW
TSC
TSCE
TSE

-171
-202
-160
-218
-132

104

One-Way Slabs

Figure 4-11: External Instrumentation AT 2 Series


(See Table 4-5 for as-built dimensions)

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

105

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-12: Reinforcement Strain Gauge Setup AT-2 Series


(See Table 4-5 for as-built dimensions)

106

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

4.3 Experimental Results AT-2 Series


4.3.1

General

All specimens exhibited brittle shear failures prior to reaching their flexural capacities. A
summary of important experimental results, including as-built dimensions, are
summarized in Table 4-5. These results include the following: experimentally
determined failure load, Pexp, the midspan deflection at the failure load, ult, the ratio of
this deflection to one-half of the span-length, ult /0.5L, the shear strain at the failure load
measured using the LVDTs on the east face of the specimen, ult, the average mid-span
steel strain at the failure load, s,ult, and the maximum measured crack width at the load
stage prior to failure. Also shown is the ratio of the peak shear strain ult to ult /0.5L
(shear). Failure shears are listed in Table 4-6.
Photographs of failed specimens are provided in Figure 4-13. The photographs of the
AT-2/250 and /1000 specimens are composite photographs constructed from multiple
photos of the failed specimens. The crack widths shown are from the last load stage prior
to failure. Interestingly, cracks in the 1000mm wide and 3000mm wide specimens
tended to initiate at locations of shrinkage and temperature reinforcement (Figure 4-14).
The AT-2 series of specimens failed at shear stresses ranging from 0.99MPa to 1.07MPa.
Specimen AT-2/250N, supported on a 152mm square neoprene bearing, failed at the
highest shear stress. Its failure shear stress was 2% greater than that of AT-2/250W, the
companion 250mm specimen supported across its full width on a steel plate and roller.
Specimen AT-2/1000N, on the other hand, failed at a shear stress that was 7% less than
the failure shear stress of the companion 1000mm specimen supported across its full
width.
Specimen AT-2/3000 failed at the lowest shear stress and AT-2/1000N failed at the
second lowest shear stress of the AT-2 series of specimens. Both of these specimens
were supported on narrow supports.
107

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Table 4-5: As-Built Properties and Experimental Observations AT-2 Series


Specimen Properties (as built)
Specimen

AT-2/250N
AT-2/250W
AT-2/1000N
AT-2/1000W
AT-2/3000

Experimental Observations

Suport Size

s+t

(mm) (mm) (mm) (w x L, mm)

(%)

(%) (MPa) (mm) (kN) (kN/m) (mm)

h
469
471
470
471
472

bw

437 250 152 x 152


439 252 252 x 152
438 1002 152 x 152
439 1002 1002 x 152
440 3005 152 x 152

f'c

sxe

Pexp Vexp

0.915 - 37.7 529 229


0.904 - 38.5 532 224
0.911 0.191 37.9 531 880
0.909 0.190 39.0 532 942
0.908 0.190 40.6 533 2564

ult ult/0.5L

(1)

458
448
440
471
427

4.53
4.70
4.15
5.00
4.06

ult

x10-3

x10-3

6.97
7.23
6.38
7.69
6.25

1.04
1.01
0.80
0.76
--

shear s,ult(2) wmax


x10-3 (mm)
15%
14%
13%
10%
--

1950
1800
1790
2020
1660

0.35
0.40
0.20
0.25
0.25

Notes:
(1) -Appled shear force per metre width. Does not include self-weight
(2) -Average of mid-span gauges for 250 and 1000 Series. Average of gauges 2C, 4C and 6C for AT-2/3000

Table 4-6: Failure Shears AT-2 Series


(1)

Specimen
AT-2/250N
AT-2/250W
AT-2/1000N
AT-2/1000W
AT-2/3000

(2)

Vexp Vexp
vexp
Vexp
vexp
(kN/m) (kN/m) (MPa) (kN/m) (MPa)
458
448
440
471
427

463
453
445
476
432

1.06
1.03
1.02
1.08
0.98

468
458
450
481
437

1.07
1.04
1.03
1.09
0.99

Notes:
(1) Calculated at d from load, incl. self-weight
(2) Calculated at d from support, incl. self weight

108

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

West Face

West Face

West Face

West Face

East Face

Figure 4-13: Failure Crack Patterns -AT-2 Series


(Crack widths in mm, measured at the last load stage prior to failure)

109

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Longitudinal
Reinforcement
Shrinkage
Reinforcement

Figure 4-14: Initiation of Flexural Cracks at Locations of Shrinkage Reinforcement -AT2/1000N

4.3.2

Load-Displacement Response AT-2/3000

Graphs displaying the load-displacement response from Day 1 and Day 2 area presented
in Figure 4-15. The horizontal instability in the Day 1 test setup is reflected in the loaddisplacement response at a load of about 648kN/m, but no such instability is reflected in
the Day 2 response. After the load was removed at the end of day 1, the vertical LVDTs
were reset to zero, thus day 2 deflections are presented relative to zero on day 2, rather
than zero on day 1.
It is interesting to note that there was significantly greater deflection measured at the
centre of the slab than at the edges. For example, at a load of 648kN/m on day 1, just
prior to considerable increases at VCC and VCW due to the horizontal instability, the
displacement at VCC was 3.4mm, versus an average of 2.7mm at VCE/VCW and 2.3mm
at VCEE/VCWW. The differences in the vertical displacements are demonstrated in
Figure 4-16, in which the VCC displacement is plotted as a percentage of VCE/VCW and
VCEE/VCWW. On day 2, at a load of 648kN/m, the displacement at VCC was 2.8mm,
versus averages of 2.4mm and 2.2mm at VCE/VCW and VCEE/VCWW. At the failure
load, the displacements were 4.2mm, 3.8mm and 3.5mm. There thus appears to have
110

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

been bending about the north-south axis of the slab, indicating two-way bending occurred
in this one-way slab. This out-of-plane bending can be resisted by the shrinkage and
temperature reinforcement.
While it was not possible to accurately measure the deflections after the slab shifted on
day 1, it appears that the specimen was permanently deformed in the two-way bending
direction after the load was removed. This offset is built into the day 2 deflection
readings, and may partly explain why there was a difference of 1.1mm between the centre
and edge deflections on day 1 at 648kN/m, versus only 0.6mm on day 2.
As shown in Figure 4-16, the loads measured were similar in the three load cells. The
centre load cell (LCC) reached a maximum of 37% of the total load applied by the
Baldwin test frame, at which point the loads measured by the east and west load cells
were each about 31.5% of the total load. On the second day of testing, after the neoprene
bearing pads below the load cells had been replaced by spherical bearings, the load
measured by the centre load cell increased gradually from 0% of the total load at an
applied load of 20kN to 33% at the failure load (Figure 4-17).
The load behaviour exhibited by the three load cells on day 2 occurred due to the
permanent deformation in the two-way bending direction and the flexibility of the
spreader beam. That is

XXXXXXXXXXXXXXX

111

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

1000

1000

900

900

800

800

VCE, VCW
VCEE, VCWW
VCC
VCEE

VCWW

VCW

VCE

Applied Load (kN/m width)

Applied Load (kN/m width)

VCC

700

600

500

400

300

700

600

500

400

300

200

200

100

100

0
0.0

1.0

2.0

3.0

4.0

5.0

0.0

6.0

1.0

2.0

3.0

4.0

Displacement (mm)

Displacement (mm)

a) Day 1

b) Day 2

5.0

6.0

Figure 4-15: Day 1 and Day 2 Load-Displacement Response -Specimen AT-2/3000


1000

Load Cell Reading as


Percent of Total Load

Applied Load (kN/m width)

900
800
700

33%
LCE
LCW

Peak Load, Day 1

LCC

VCC Deflection as percent of


Average of VCE, VCW

VCC Deflection as percent of


Average of VCEE, VCWW

LS 3

600
500

LS 2

400
300

LS 1

200
100
0
0%

25%

50%

75%

100%

125%

150%

175%

200%

Percent

Figure 4-16: Load Measured by Load Cells as Percentage of Total Applied Load, and
VCC Deflection as Percent of Other Deflections Day 1

112

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

1000
Failure

Applied Load (kN/m width)

900
800

Load Stage 7

700

Load Stage 6
Load Stage 5

600

LCE
LCW

500
LCC

400
300
200
100

33%

0
0%

20%

40%

60%

80%

100%

Percent of Total Applied Load

Figure 4-17: Load Measured by Load Cells as Percentage of Total Applied Load -Day 2

4.3.3

Longitudinal Steel Strain ResponseAT-2/3000

Strains measured in the longitudinal steel at various load stages in Specimen AT-2/3000
are shown in Figure 4-18. They are plotted as strain profiles across the width of the
specimen at the north quarterspan (Figure 4-18(a)), midspan (Figure 4-18(b)), and south
quarterspans (Figure 4-18(c)). Load stages one to three were taken on the first day, and
stages four to seven were taken on the second day.
At the quarterspans, it can be seen that strains in the longitudinal steel along support lines
(lines 2, 4 and 6) generally were similar to, or smaller than, the adjacent strains outside
the support lines (1, 3, 5 and 7). This is in contrast to the behaviour exhibited by the
strain gauges in the quarterspans of AT-1 in which the longitudinal strains increased
towards the centreline of the beam. With the exception of the strains measured at gauges
4C, 5C and 6C, no strain profiles similar to that exhibited at the quarterspans of beam
AT-1 were observed. It does not appear, therefore, that any effect of loading through
narrow loading points, and supporting the slab on narrow supports, could be found in the
longitudinal strain profiles.
113

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-18: Strain Readings in Longitudinal Rebar Strain Gauges AT-2/3000


114

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

A minor effect of narrow loading points was found in the rate of increase of the strains
measured by the strain gauges. In Figure 4-19 the rates of increase in the strain measured
by gauges 2C, 4C and 6C on the second day of loading are shown as functions of the
applied load. Recall that gauges 2C, 4C and 6C were located directly below load cells
LCW, LCC and LCE. As shown in Figure 4-17, the load measured by load cell LCC,
located directly above gauge 4C was lower than the loads at cells LCW (above gauge 2C)
and LCE (above gauge 6C) up to an applied load of 800kN/m. The loads measured by
LCE and LCW were generally similar to one another throughout loading. In Figure 4-19,
it can be seen that the rates of increase in gauges 2C and 6C follow very similar trends,
and the increase in 6C was slightly higher than in 2C. However, the rate of increase of
strains in 4C increased over the entire loading regime, and this corresponds with the
increasing proportion of the total load measured by load cell LCC. This behaviour was
not noted on day 1, where the ratios of the loads in the load cells to the total load were
closer to 1:3 throughout.
(/kN)
6.0

bar
Papp 3

5.0
4.0
6C
3.0
2.0
1.0
2C

4C

0.0
0

200

400

600

800

1000

Applied Load (kN/m width)

Figure 4-19: Rate of Increase in Measured Strain as a Function of Applied Load (Day 2)
The behaviour described in Figure 4-19 was the only indication found in the longitudinal
rebar strains of an effect caused by loading through individual narrow loading points.

115

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

4.3.4

One-Way Slabs

Transverse Steel Strain ResponseAT-3/3000

It is useful to analyze the measured rebar strains in AT-2/3000 in the shrinkage/


temperature reinforcement to assess its role, if any, in determining one-way shear
behaviour. Strains measured in the shrinkage/temperature steel at various load stages are
shown in Figure 4-20 and Figure 4-21 for Day 1 and Day 2. They are plotted as strain
profiles across the width of the specimen at (a) the north quarterspan, (b) midspan and (c)
south quarterspan.
It can be seen that there was very little strain measured in the gauges on the transverse
steel throughout the loading of the slab. On the north side of the specimen, the largest
tensile (positive) strain measured at the quarterspan was 22 microstrain. The maximum
compressive (negative) strain was -25 microstrain. At midspan, the largest tensile strain
measured was 210 microstrain, and at the south quarterspan it was 90 microstrain. The
strains measured in the transverse rebars generally were negative (compressive) at the
start of the test prior to cracking. This behaviour is due to the Poissons effect in the
bottom of the slab. After flexural cracking due to moments associated with the
longitudinal steel, the strains generally became more positive (tensile).
The shrinkage strains summarized in Table 4-4 indicate that the rebars in AT-2/3000
were slightly precompressed prior to loading. The shrinkage strains in the south
transverse bar are plotted in Figure 4-20(c) and Figure 4-21(c) on the tensile side
(decompression strains). This indicates the required measured tensile strain so as to
decompress the rebar. It can be seen that the maximum tensile strains occurred in the
south transverse bar at the peak load on Day 2, but these strains were, on average, only
about a quarter of the required measured strains to decompress the rebar. In other words,
the bar was likely still slightly compressed at the peak load. On average, the bar was
precompressed by about 177 microstrain prior to removal from the formwork, and at the
peak load, the bar was still precompressed by about 125 microstrain.

116

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

While the shrinkage strains in the northern quarterspan were not measured, based on the
shrinkage strains in the southern span, it is likely that the northern transverse bar was still
compressed at the peak load. Similarly, it is likely that the transverse strains in the
middle bar were small enough such that the bar, on average, was still slightly compressed
at the peak load. It thus appears that there was only a very small internal moment about
the north-south axis associated with the measured bending about the north-south axis.
The strain profiles in the north and south quarterspans in Figure 4-20 show that the outer
gauges (gauges TNW, TNE and TSE) remained compressive for most of the test on Day
1. The inner gauges (TNWC, TNC, TNEC, TSWC, TSC and TSEC), on the other hand,
became tensile after about load stage 2. There is a clear similarity between the shapes of
the profiles in the north and south quarterspans on Day 1. Once the slab started to shift to
the north on Day 1, however, the strain profiles in the north quarterspan were disrupted,
with the inner gauges becoming more compressive. This disruption was not noted in the
south quarterspan. On Day 2, the profiles in the north quarterspan were generally
reversed from their Day 1 shape, with TNEC and TWC showing compressive strains.
Profiles in the south quarterspan on Day 2 resembled the shapes of the Day 1 profiles.
Figure 4-22 shows the average of gauges TNW, TNE and TSE (the transverse strain
gauges located in the east and west bays) and the average of all other gauges on the
transverse rebars at the quarterspans. These averages are shown for both Day 1 and Day
2, with the load stages removed for clarity. It can be seen that the inner gauges are
consistently tensile over the entire course of the test, while the outer gauges, on average,
are compressive, until close to the end of the test.
The behaviour exhibited in Figure 4-22, and the shapes of the quarterspan strain profiles
on Day 1, and on Day 2 in the south quarterspan, can be explained by the fact that the
slab was bending about its north-south axis as well as its primary east-west axis. The
bending about the north-south axis would result in flexural tensile strains in the east-west
direction, and these strains would be larger towards the centre strip of the slab than they
would be in the outer strips.
117

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-20: Strain Readings in Transverse Rebar Strain Gauges AT-2/3000, Day 1
118

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-21: Strain Readings in Transverse Rebar Strain Gauges AT-2/3000, Day 2
119

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

80

Rebar Strain (microstrain)

60

Average of:
TNWC, TNC, TNEC
TSWC, TSC, TSEC

40

20

tens.

0
comp.

-20
Average of:
TNW, TNE, TSE

-40
0

100

200

300

400

500

600

700

800

900

1000

Applied Load (kN/m)

Figure 4-22: Average Strain Readings in Shrinkage Reinforcement -AT-2/3000


It should be noted that the strains in the transverse gauges in the north and south
quarterspans are extremely small, and were well below the shrinkage strains measured
prior to testing. Thus other effects such as the location of cracks with relation to the
instrumented location, and differential shrinkage can not be entirely ruled out. It
certainly appears, however, that the slab exhibited some two-way behaviour in both the
midspan deflections as well as the transverse rebar strains.

4.3.5

Load-Displacement Response -AT-2/250 and AT-2/1000 Series

Plots of the applied load per meter width vs. the mid-span deflection for the 250mm and
1000mm wide specimens are presented in Figure 4-23 and Figure 4-24. It can be seen
that the 250mm wide specimens exhibited very similar responses, failing at similar loads
and deflections. On average, there was about 15% greater deflection in the specimen
supported on the wide supports than the specimen supported on the narrow supports.
This difference was not due to different support settlement between specimens, as
vertical LVDTs were placed at the supports specifically to account for this effect.
The load deflection curves in Figure 4-23 and Figure 4-24 are reproduced in Figure 4-25,
and compared to the measured mid-span deflections in AT-2/3000. The AT-2/3000 loaddisplacement curves have been generated by combining the day 1 and day 2 responses at
120

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

a load of 1866kN. The deflections from AT-2/3000 include the largest deflections
measured (at VCC) the smallest deflections measured (at VCWW) and the average of all
the mid-span LVDT measurements, weighted for the tributary width of the LVDT. It can
be seen that AT-2/1000W, AT-2/250N and W exhibited reasonably similar load
deflection characteristics. The average deflection in AT-2/3000 also was fairly similar to
the deflections measured in these specimens. All the load deflection curves fall within
the envelope bounded by AT-2/3000 VCWW and AT-2/3000 VCC.

4.3.6 Steel Strain Response AT-2/250 and AT-2/1000 Series


Longitudinal Steel Strains AT-2/1000 Series
Strains measured in the longitudinal reinforcement in the 250mm and 1000mm wide
specimens are provided in Figure 4-26. They are presented as strain profiles across the
width of the specimens, and profiles from AT-2/3000 are provided for comparison at
equivalent applied loads. Quarterspan profiles at three loads are shown, and the midspan
profiles at loads corresponding to the peak load of AT-2/3000 are shown. The profiles
for the quarterspans represent the average strains measured in the north and south
quarterspans.
The outer gauges consistently measured higher strains than the centreline gauges at the
midspans of both AT-2/1000N (supported on narrow supports) and AT-2/1000W
(supported on full-width supports). Likewise, at the quarterspans of AT-2/1000W, the
outer gauges measured consistently higher strains than the centreline gauges. At low
loads (at P=400kN/m width, for example) the quarterspan outer gauges measured higher
strains than the centreline gauges in AT-2/1000N, but as the load increased, the centreline
gauges measured higher strains than the outer gauges. This is opposite to the strain
profiles measured elsewhere in the 1000mm wide specimens.

121

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

1000

1000
250N

250W

1000N

900

900

800

800

Applied Load, Papp (kN/m Width)

Applied Load, Papp (kN/m Width)

1000W

700

600

500

400

300

700

600

500

400

300

200

200

100

100

0
0.0

1.0

2.0

3.0

4.0

5.0

6.0

0.0

1.0

2.0

3.0

4.0

5.0

6.0

Mid-Span Displacement, (mm)

Mid-Span Displacement, (mm)

Figure 4-23: Load-Displacement Response Figure 4-24: Load-Displacement Response


AT-2/1000 Series
AT-2/250 Series
1000

900
AT-2/3000 -VCWW

Applied Load (kN/m width)

800

700

600

500
AT-2/3000 -VCC

400

AT-2/3000 -Average mid-span


deflection

300

200

100

0
0.0

1.0

2.0

3.0

4.0

Displacement (mm)

5.0

6.0

Figure 4-25: Load-Displacement


Response -AT-2 Series
122

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-26: Longitudinal Steel Strain Profiles -AT-2 Series


123

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

AT-2/250 Series
It can be seen in Figure 4-26 that consistently higher longitudinal strains were measured
in the quarterspans of the AT-2/250 specimens than in the other specimens. This was not
a result of one or more gauges measuring unusually high strains; all gauges measured
consistently higher strains. Consistently lower strains were measured in AT-2/3000 at
the midspan than in the midspan of other specimens. This is shown in Figure 4-27, in
which the average longitudinal strains at mid-span and quarterspan locations are shown
for all the AT-2 series.
1000
Quarter-span Gauges

Mid-span Gauges

900

Applied Load, Papp (kN/m width)

800

700

600

500

400

300

200
AT-2/3000
AT-2/1000
AT-2/250

100

0
0

400

800

1200

1600

2000

Average Rebar Strain (microstrain)

Figure 4-27: Average Longitudinal Steel Strains -AT-2 Series


Based on the strain gauge response shown in Figure 4-27, it appears that tension
stiffening effects may have been more prominent in the AT-2/3000 longitudinal strains
than in the strains measured in the narrower specimens. Since bars in the corners of
specimens are located close to two faces, these bars may have exhibited less tension
124

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

stiffening than interior bars. In AT-2/3000, with a large number of interior bars, the
reduced tension stiffening in the corner bars is masked in the overall response (Figure
4-27), but can be seen in the individual strain responses (Figure 4-26).
The higher measured strains in the narrow specimens appears to have been a result of
reduced tension stiffening due to a larger percentage of the longitudinal bars being corner
bars.
Comparison with AT-1
It is interesting to compare the longitudinal strain profiles in the AT-2/1000 series to
those in AT-1 (Figure 3-14). Recall that the longitudinal rebar strains at the quarterspans
were larger in the inner gauges than they were in the outer gauges. This pattern is similar
to that exhibited at the quarterspans of AT-2/1000N, but is opposite to the profiles
measured at quarterspans of AT-2/1000W. Also recall that the longitudinal strains
measured at the midspan were generally smaller in the inner gauges than they were in the
outer gauges. This pattern is similar to the midspan profiles measured in both AT-2/1000
specimens. Figure 4-28 presents a plot showing the ratio of the strains in centreline
gauges to the strains in outer gauges at the quarterspans and midspans of both AT-1000
specimens and beam AT-1. It can be seen that the ratios at the midspans of AT-2/1000N,
1000W and AT-1 are all remarkably similar, and are equal to about 0.95 at the peak load.
The ratio at the quarterspans of AT-2/1000W is generally the lowest, reaching a low of
0.55 at P=300kN/m. The ratios at the quarterspans of AT-2/1000N and AT-1, however,
are generally the highest.
Comparison with Shear Strains
Figure 4-29 shows the shear stress vs. shear strain curves for the AT-2/250 and AT2/1000 series of specimens, in which the shear strain shown is the average of the strains
measured in the north and south spans. In this figure it can be seen that the shear stressshear strain curves for specimens AT-2/250N, AT-2/250W and AT-1000W are
remarkably similar up to a shear stress of about 0.9MPa. The shear strains in AT125

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

2/1000N, however, are consistently smaller than the shear strains in the other three
specimens. It appears that, in AT-2/1000N, lower longitudinal steel strains measured
near the side faces of the specimen were associated with lower shear strains measured on
those side faces. It appears reasonable to conclude that the higher longitudinal strains in
the middle of AT-2/1000N were associated with higher shear strains.
It is suggested that this higher shear strain in the interior of AT-2/1000N may have
triggered failure at an overall shear stress that was 93% of the failure shear stress in AT2/1000W. Clearly, though, further work is required to clarify this area, based on the
small sample size used here.
Transverse Shrinkage and Temperature Steel Strains
The strains measured in the gauges on the shrinkage and temperature reinforcement are
shown in Figure 4-30 at an applied load of 854kN/m width. This load corresponds to the
peak load in AT-2/3000. The strain at which, on average, the bars would be
decompressed due to shrinkage is also shown. These decompressed strains are the
average of the shrinkage strains measured in the transverse steel in the specimens.
Transverse rebar strains at the quarterspans of AT-2/1000N were, on average, 1.2 times
the rebar strains at the quarterspans of AT-2/1000W. This is consistent with the higher
strains measured in the longitudinal reinforcement at these locations.
The strains measured at the quarterspans in the AT-2/1000 specimens were small, and
were generally either lower or only slightly higher than the decompression strains. The
strains in the shrinkage reinforcement in the AT-2/1000 specimens were generally larger
than the corresponding strains in AT-2/3000. It is apparent that the shrinkage and
temperature steel in AT-2/3000 was unable to modify the shear behaviour in any
meaningful way.

126

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-28: Ratios of Centreline Strains to Outer Strains AT-2/1000 series and AT-1
127

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

1.2

One-Way Slabs

AT-2/1000W
AT-2/1000N

1.0

Shear Stress (MPa)

0.8
AT-2/250N

AT-2/250W

0.6

0.4
Average of South "X" and North "X"

0.2

0.0
0.0

0.5

1.0

1.5

Average Shear Strain (mm/m)

Figure 4-29: Shear Stress vs. Average Shear Strain-AT-2 Series

Figure 4-30: Shrinkage and Temperature Reinforcement StrainsAT-2/1000N, AT2/1000W and AT-2/3000 (Papp=854kN/m width)
128

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

4.3.7 Failure Photos AT-2 Series


AT-2/250W
A high-resolution digital camera capable of taking 3 to 4 frames per second was used to
photograph the failures of the AT-2 series of specimens. A sequence of photographs
showing the failure of Specimen AT-2/250W is shown in Figure 4-31. The applied loads
are also shown, and on Figures (e) through (n), the times in seconds relative to the time
the peak load is reached are also shown. Cracks have been digitally enhanced for clarity.
Figure 4-32 presents figures showing the (a) measured horizontal displacements, (b)
shear strains, (c) longitudinal rebar strains and (d) vertical displacements. The rebar
strains are the average strains measured by gauges on adjacent bars.
Data presented in Figure 4-32 corresponding to various photos in Figure 4-31 are
identified with an open symbol. In this figure, it can be seen that after the peak load was
reached, the vertical displacements at VS (located just slightly to the north of the critical
crack) started to increase dramatically, while the vertical displacements at VC and VN
increased at lower rates. The portion of concrete to the north of the failure crack (to the
left-hand side, as seen in the failure photos) was therefore rotating in a clock-wise
direction following the peak load.
As the load was increased up to the peak load, positive horizontal movements were
measured at both the north and south ends, indicating that the beam was lengthening. At
the peak load, however, the south end started to move northwards. This movement was
caused by the clockwise rotation of the concrete to the north of the critical crack. This
movement caused the reinforcement to pull the south end of the beam to the north by
dowel action. At final failure (photo m)), the block of concrete to the south of the crack
rotated clockwise and shifted northwards as indicated by the arrows.
The considerable increases in deflection were associated with corresponding increases in
the shear strain. From the peak load to final failure, for example, the shear strain
129

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

increased by about 3.6 times. The vertical deflections were not associated with increases
in the rebar strains, all of which decreased following the peak load (Figure 4-32(c)), and
this is consistent with shear failure. The increases in vertical deflection following the
peak load were therefore a result of increasing shear strain, and were not a result of
flexural action. This shear strain was a result of widening and slip at the critical flexuralshear crack. No crushing was noted at the tip of the crack or in the compression zone at
or after the peak load. Also note that failure was not initiated by a sudden formation of a
crack due to unstable crack growth. Indeed, the final failure crack extended 185mm
between +11 sec. and +66 sec., corresponding to an average velocity of 3.4mm/second.

130

North

South

Figure 4-31: High-Speed Digital Photos of Failure in


South Side of Specimen AT-2/250W (West Face)

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs
One-Way Slabs

131

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-32: Displacements, Shear Strains and Rebar Strains AT-2/250W


132

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

AT-2/1000W
Digital photos of the north end of AT-2/1000W at failure are presented in Figure 4-33.
Figure 4-33a and b were taken at the last two load stages prior to failure. At the peak
load of 942kN (Figure 4-33c) it can be seen that crack (b) had extended slightly towards
the load, and crack (a) had extended slightly towards the support, as the load was
increased from 880kN to 942kN. Both cracks had also widened. After the load dropped,
no continued extension of crack (b) was noted until 16 seconds after the peak load
(Figure 4-33d). From 16 to 18 seconds after the peak load, crack (a) extended, and as it
extended it started to widen (Figure 4-33e and f). By 28 seconds after the peak load,
crack (a) had widened considerably, formed a continuous crack with the upper portion of
crack (b), and extended up towards the load point. Failure is shown in Figure 4-33h.

Figure 4-33: High-Speed Digital Photos of Failure in Specimen AT-2/1000W


133

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

AT-2/3000
Digital photos of AT-2/3000 at failure are presented in Figure 4-34. Failure in this
specimen was more rapid and sudden than the specimens described previously. From
load stage 7 (Figure 4-34b) to the peak load (Figure 4-34c), it can be seen that crack (a)
extended slightly, but after the peak load was reached, no immediate extension of the
crack was observed. See, for example, Figure 4-34(d), taken 7.2 seconds after the peak
load. At 10.4 seconds after the peak load, however, crack (a) rapidly extended up
towards the load points and widened. At 10.8 seconds after the peak load, crack (a)
continued to rapidly extend towards the loads, and started to extend back towards the
supports. Failure occurred 11.2 seconds after the peak load.

Figure 4-34: High-Speed Digital Photos of Failure in Specimen AT-2/3000


No crushing of the concrete above the critical crack or in the compression zone was noted
at or after the peak load in any of the AT-2 specimens. It must also be stressed that, in
the failures described here, the load started to drop prior to the extension of the visible
critical crack towards the loading point. Based on comparing the crack lengths in photos
e) and f) above, the speed of the visible final failure crack propogating towards the load
point was about 1.1m/sec.
134

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

4.3.8

One-Way Slabs

Analysis of AT-2/250N

As described in Chapter 2, there are several theories and analytical studies that describe
the shear behaviour of reinforced concrete beams assuming that there is no aggregate
interlock action at cracks. In these methods, it is assumed that all the vertical shear is
carried in the uncracked compression block.
Beam AT-2/250N can be analyzed to explore the accuracy of these theories. The crack
patterns in this specimen up to failure are shown in Figure 4-35. Photographs of the
beam at, and following, an applied load of 220kN are shown in Figure 4-36. At an
applied load of 220kN (load stage 5), a large crack starting at 395mm from the centre of
the south support and extending up to 95mm from the top of the beam had formed (Crack
(a)). As the load was increased past 220kN, crack (a) slowly widened up to the peak load
(Figure 4-36 (b)). This peak load was held for approximately 8 seconds, after which
failure occurred (Figure 4-36 (c)). If all of the vertical shear was carried in the uncracked
compression zone above crack (a), the maximum shear stress above the tip of crack (a)
would be estimated as: max =

3 V 3 229,000 2
=
= 7.2MPa , excluding self-weight.
2 bh 2 250 95

Based on an average horizontal flexural stress in the compression zone of 7.5MPa


(15MPa at the top of the beam and 0 at the neutral axis), the principal tensile stress would
be 4.4MPa, which greatly exceeds the tensile strength of the concrete. Nevertheless, let
us continue on the assumption that the uncracked concrete can resist this high shear stress.
The author suggests that the only way that the beam might be able to transfer shear
without aggregate interlock or dowel action is by the formation of a direct strut from the
loading plate to the centre of the uncracked compression zone above crack (a), as shown
in Figure 4-37(a). Due to the geometry of the crack, this strut must then rotate so as to
extend to the support plate. Statics requires that a diagonal tie force be present in some
form past crack (a) in order to allow the compressive strut to rotate sufficiently so that it
may extend into the support. As there is no vertical steel placed in the beam, this tie
force must be developed by tensile stresses in the concrete alone. It is difficult to
135

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

imagine how the compressive strut might make a sharp turn towards the support as shown
in Figure 4-37(a), as the tension tie would need to be developed across a crack. Thus, it
is more likely that a gradual change in the angle of inclination of the strut would occur
well past the crack, as shown in Figure 4-37(b). The required tension tie is provided by
tensile stresses developed in the concrete as shown in the figure.

Load Stage 5
Crack (a)

Figure 4-35: Crack Patterns at Load Stages -Specimen AT-2/250N (West Face)
136

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

T=-44sec.

T=0sec.

T=+8sec.
fc=31.7MPa

Figure 4-36: Photos of Failure in Specimen AT-2/250N


A free-body diagram of the portion of concrete to the north of crack (a) is presented in
Figure 4-37(c). Assuming no aggregate interlock, the vertical shear, V, is carried as the
vertical component, Cstrut,y, of the force in the strut, Cstrut. The angle of inclination of the
force in the strut, , is governed by the geometry of the cracking pattern in the beam, and
since crack (a) is located close to the support and extends well up into the beam, this
angle is very shallow. The actual force in the strut, Cstrut, is thus governed by the value of
Cstrut,y required for vertical equilibrium and the angle of inclination of the strut, . For the
specific case of AT-2/250N, the angle of inclination, , is 4.2o, and when
Cstrut,y=229/2=115kN, Cstrut,x=1455kN and Cstrut=1459kN. This would result in a
compressive stress in the compression zone of 61MPa, which is about 1.6fc, and a force
in the tensile steel that is 3 times the maximum force that can be developed by yielding of
the steel.
If the concrete were to crush due to the Cstrut force and the steel were to yield, the freebody diagram in Figure 4-37(c) would not be in static equilibrium. This, combined with
the high shear stress that would be required in the compression zone, should be enough to
show that it is unlikely that the entire shear force is carried in the compression zone. The
maximum horizontal force that can be developed in the compression zone is equal to
137

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

AsFy. Let us assume that the compressive force in the compression zone is equal to AsFy
= (1000*465) = 465kN = Cstrut,x.

Crack (a)

Figure 4-37: Analysis of AT-2/250N Assuming no Aggregate Interlock Action


The compression strut beyond crack (a) is shown in Figure 4-37(d). The vertical
component of the strut at the tip of the crack is equal to the shear force, and is thus equal
to the vertical reaction at the support. Equilibrium requires that horizontal tensile stresses,
t, in combination with the force in the steel at the support, will rotate the strut into the
support. In the figure, it is assumed that the entire cross-section is effective at providing
the required tension.
138

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

As tension cracks do not form past crack (a) where the tension tie is being developed, the
tensile stress in the concrete must remain below the tensile strength of the concrete. For
an angle 1 = 0o, the longitudinal steel at the support would be unstressed, and the
required tensile stresses would be equal to (465,000)/(250*470) = 3.95MPa. This
required tensile strength is about double the tensile strength of the concrete, assuming
that the uniaxial tensile strength of the concrete is equal to 0.33(fc)0.5.
In order to reduce the required tensile stress to the uniaxial tensile strength of the
concrete, the force in the tensile steel would need to be 230kN, resulting in a steel stress
of 230MPa. Rebars that have been instrumented with strain gauges near the supports in
other beam tests (for example, beam AT-1, as well as other beams described later in this
thesis) have consistently shown that rebars near the supports are very lightly stressed, and
are therefore not capable of significantly increasing the angle 1.
The preceeding analysis has shown that it is highly unlikely that the entire shear force
was carried in AT-2/250N by direct strut action above the final failure crack.

139

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

4.4 Experimental Program AT-3 Series


A series of tests designed to complement the results of the AT-2 series was conducted.
The main variable studied in the AT-3 series of tests was the effect of shrinkage and
temperature reinforcement in the form of a horizontal mat of steel placed perpendicular to
the primary flexural reinforcement. This section describes the AT-3 experimental
program.

4.4.1

Specimen Design and Construction

The design of the AT-3 series of specimens is presented in Figure 4-38 A total of four
specimens were constructed and tested. The specimens nominally measured 700mm
wide x 338mm tall x 2800mm long, and were reinforced with four 25M rebars at an
effective depth of 306mm (w=0.93%). In two of the beams (AT-3/T1 and AT-3/T2),
shrinkage and temperature reinforcement consisting of nine 15M bars with standard 180o
hooks at their ends were placed on top of the bottom flexural reinforcement (s+t=0.19%).
No shrinkage and temperature reinforcement was used in the other two specimens (AT3/N1 and AT-3/N2).
The formwork for the AT-3 series is shown in Figure 4-39. The formwork was
constructed on a base of multiple layers of 19.1mm (3/8 in.) plywood, and consisted of
3/8in. formply supported using steel walers and braces. Following casting, the concrete
was cured under wet burlap and plastic sheeting for five days. The concrete for the
specimens was supplied by a local ready mix company with a maximum aggregate size of
20mm (3/4in.) and a 28-day strength of 25MPa. The aggregate was quarried on
Manitoulin Island in Northern Ontario. One batch was used to fill all four forms. On the
day of test, ranging from 42 to 48 days after casting, the concrete strength varied from
37.1 to 37.8MPa (see Table 4-7). Steel material properties are identical to those listed in
Table 4-2.

140

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-38: Specimen Design and Test Setup -AT-3 Series

Figure 4-39: AT-3 Series Formwork


141

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Table 4-7: Concrete Material Properties AT-3 Series


Specimen
AT-3/N1
AT-3/N2
AT-3/T1
AT-3/T2

4.4.2

Cast Date

Test Date

24 June, 2004
24 June, 2004
24 June, 2004
24 June, 2004

Aug 5, 2004
Aug 10, 2004
Aug 6, 2004
Aug 11, 2004

Age
f'c (MPa)
(Days) Day of Test
42
47
43
48

37.5
37.1
37.8
37.1

Instrumentation and Test Setup

Instrumentation used in the AT-3 series is summarized in Figure 4-40. In all four
specimens, two 5mm electrical resistance strain gauges were installed on the longitudinal
steel at midspan (LCE and LCW). In the specimens constructed with horizontal
transverse steel (AT-3/T1 and T2), two of the transverse bars were instrumented with two
5mm electrical resistance strain gauges near the centres of the bars (TNE, TNW and TSE,
TSW). One instrumented transverse bar was located near the north quarterspan, and the
other instrumented bar was located near the south quarterspan. To avoid measuring strain
due to bending of the steel at a crack, the instrumented rebars were oriented such that the
gauges were on the vertical sides of the rebar.
Prior to the test, a total of eleven LVDTs were placed below each specimen to measure
midspan deflection, north and south quarterspan deflection and support settlement.
Additional dial gauges were placed at the supports to measure support settlement.
Horizontal LVDTs (HN and HS) were placed at the level of the steel to measure
horizontal displacements at the supports. Holes were drilled in the end faces to expose
the ends of a longitudinal reinforcing bar, and an LVDT was placed at the exposed rebar
ends to measure rebar slip (SlipN and SlipS). A series of LVDTs were fastened to the
west face of each specimen to measure shear strains. The X-s measured 250mm x
250mm, and were centered at 545mm an 220mm from the centre of the loading, in both
the north and south spans.
A grid of aluminum Zurich targets was not used in the AT-3 series of specimens.
142

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-40: Test Instrumentation -AT-3 Series


The test setup for the AT-3 series is shown in Figure 4-38 and Figure 4-41. Each
specimen was aligned in the north-south direction beneath the Baldwin test frame in the
Mark Huggins Laboratory in the Department of Civil Engineering at the University of
Toronto. The specimens were supported on 152 x 1200mm steel plates and rollers at
their north and south ends, with a layer of plaster placed between the plates and the
soffits of the specimens. The specimens were loaded through two 152 x 1200mm plates
and a steel spreader beam placed on the top of the specimens at midspan. A layer of
plaster was placed between the steel plates and the top of the specimens. The span of the
specimens was 2080mm, corresponding to an a/d ratio of 3.39.

143

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-41: Test Setup -AT-3 Series


Load was applied monotonically to each specimen, and at various stages during the tests
the loading was stopped, and the load reduced slightly, to mark and measure cracks, and
read dial gauges. The specimens were loaded to failure, and each test lasted for about
two to three hours.

4.5 Experimental Results AT-3 Series


As-built specimen properties and experimental results are summarized in Table 4-8.
Load vs. mid-span deflection curves for the AT-3 specimens are presented in Figure 4-42.
The AT-3 specimens failed in shear at applied loads ranging from 475-517kN, which
correspond to shear stresses ranging from 1.12 - 1.20MPa. Failure was preceded by only
small deflections, with ult/L ratios ranging from 1/400 1/370.
The two specimens constructed without shrinkage and temperature reinforcement
exhibited both the lowest and the highest failure shear stresses of the four specimens
tested. The average failure shear stress for the specimen without shrinkage steel was
1.16MPa, while the average for the specimens with shrinkage steel was 1.17MPa, a
difference of 1%. It can be safely concluded, then, that the horizontal transverse mat of
steel had no appreciable effect on the shear strength of these specimens.
144

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Table 4-8: Experimental Results -AT-3 Series


Specimen Properties (as-built)
Specimen

AT-3-N1
AT-3-N2
AT-3-T1
AT-3-T2

bw
h
d
L
(mm) (mm) (mm) (mm)
339
339
338
339

307
306
306
307

697
706
700
706

1080
1080
1080
1080

s+t

(%)

(%) (MPa) (mm) (mm)

0.93
0.93
0.93
0.93

0
0
0.19
0.19

f'c
37.5
37.1
37.8
37.1

ag,eff

sxe

19
19
19
19

276
275
275
276

Experimental Observations
Specimen

AT-3-N1
AT-3-N2
AT-3-T1
AT-3-T2

ult/0.5L

(kN)

ult
(mm)

(x10 )

(x10 )

475
517
506
497

5.25
5.6
5.51
5.38

9.7
10.4
10.2
10.0

1.45
0.66
0.71
0.44

Pexp

-3

ult

shear

s,ult

-3

15%
6%
7%
4%

2205
2728
2414
2730

s+t,ult Vexp(1) vexp(1) Vexp(2) vexp(2)


(kN) (MPa) (kN) (MPa)

--145
229

241.6
262.6
257.1
252.6

1.13
1.22
1.20
1.17

239.2
260.2
254.7
250.2

1.12
1.20
1.19
1.15

Notes:
(1) Calculated at d from support
(2) Calculated at d from load
s+t,ult = Avg. strain at peak load in shrinkage/temperature steel

600
AT-3N2

500
AT-3T1
AT-3T2

Applied Load (kN)

400

AT-3N1

300

200

100

0
0.0

2.0

4.0

6.0

Mid-Span Displacement, (mm)

Figure 4-42: Load Deflection Curves -AT-3 Series


145

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

4.5.1

One-Way Slabs

Transverse Steel Strains

The measured strains in the shrinkage steel are shown in Figure 4-43 at applied loads of
250kN and 497kN. The load of 497kN corresponds to the peak load of AT-3/T2. The
strains shown represent the average of the two strain measurements on each bar. The
data presented in Figure 4-43 indicate that the strains in the horizontal transverse steel
were very small. The largest strains were measured in AT-3/T2 at the peak load (455).
However, this represented only 17% of the midspan longitudinal rebar strain.
Shrinkage strains were measured in a number of the strain gauges placed on the shrinkage
and temperature steel prior to removal from the formwork. The average of these readings
are presented in Figure 4-43, where it can be seen that only the midspan gauges in AT3/T2 significantly exceeded the uncompressed strains. Clearly the horizontal shrinkage
and temperature reinforcement placed transverse to the spanning direction did not play a
role in determining the shear behaviour of the AT-3 specimens.

Figure 4-43: Transverse Steel Strains -AT-3 Specimens


146

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

4.5.2

One-Way Slabs

Failure Photos

The high-speed digital camera used as part of the AT-2 experimental program was used
to photograph the failures in the AT-3 series of specimens. These sequences of photos
are shown in Figure 4-44, Figure 4-45, Figure 4-46 and Figure 4-47. Arrows have been
placed on the final photos in each sequence to indicate the directions of movement when
failure occurred.
In Specimen AT-3/N1, no extensions of existing cracks were observed at the peak load,
or at one second following the peak load. By 1.5 seconds after the peak load, however, a
wide, flat crack formed in the south end that rapidly extended up towards the load and
back towards the support. At failure, the south portion of the beam rotated counterclockwise, caused by dowel action from the downward and northward shift of the north
portion of the specimen.
Like AT-3/N1, specimens AT-3/N2 did not exhibit a sudden extension of the critical
crack at the peak load (Figure 4-45). At twelve seconds after the peak load, a small crack
connected to the critical crack initiated at just above the mid-height of the beam. This
crack gradually extended both upwards towards the load and back towards the support
(Figure 4-45d, e and f). At failure, the portion of the beam to the north of the failure
rotated clockwise due to the downward movement of the longitudinal steel.
Figure 4-46 shows digital photos of specimen AT-3/T1, and it can be seen that no sudden
extension was noted in the critical crack (crack (a)) at the peak load or at 40 seconds past
the peak load. AT 54 seconds past the peak load (Figure 4-46d), a small crack initiated
from crack (a) at mid-height, and this crack gradually extended and widened until failure
occurred. The failure of specimen AT-3/T2 was slightly different than the other AT-3
specimens. A second crack did not initiate at mid-height from the main critical crack.
Rather, the critical crack (crack (a)) started to extend towards the load point at two
seconds after the peak load was reached. The crack widened as it extended, and final
failure occurred at 23.6 seconds after the peak load was reached.
147

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-44: High-Speed Digital Photos of Failure East Face, AT-3/N1

148

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-45: High-Speed Digital Photos of Failure East Face, AT-3/N2

149

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-46: High-Speed Digital Photos of Failure East Face, AT-3/T1


150

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

Figure 4-47: High-Speed Digital Photos of Failure East Face, AT-3/T2

151

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

4.6 Discussion AT Series


Analysis of the results of the AT series provides interesting observations about the effects
of slab width, shrinkage reinforcement, effective depth and the use of narrow supports on
the shear behaviour of reinforced concrete beams and slabs.

4.6.1

Beam/Slab Width

It was found in the AT-2 series of specimens that the failure one-way shear stresses of
beams and slabs tested with widths scaled by the ratios 1:4:12 did not increase. The AT1/DB165 series of specimens also did not show an increase in failure shear stress as the
beam width increased.
Kani (1967) came to a similar conclusion when he tested a series of small scale beams in
which the widths of the beams were increased from 12 in. to 24 in. (152mm to 610mm).
Rajagopalan and Ferguson (1969) also found that width did not significantly affect the
failure shear stress in lightly-reinforced beams/slabs. Kanis series of tests are
summarized in Table 4-9 and predicted shear strengths are presented in Table 4-10. Data
from Kanis tests are plotted in Figure 4-48, along with the data from the DB165/AT-1
series, AT-2 series and Rajagopalan and Ferguson (1969). This figure shows that the
width does not significantly affect the one-way failure shear stress. The ACI exemption
on minimum stirrups for one-way slabs is thus not appropriate. Indeed, as the width was
increased in the AT-2 series, the failure shear stress tended to drop slightly.
The failure crack surface of AT-2/3000, shown in Figure 4-49, was reasonably straight
across the slab width, with only slight undulations between support lines. This supports
the conclusion that slab width has no effect on one-way shear capacity.

4.6.2

Shrinkage and Temperature Steel

It was also discussed previously that the use of shrinkage and temperature steel placed in
a horizontal layer transverse to the spanning direction had no impact on the one-way
152

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

shear strength of reinforced concrete slabs. The ratios of the shear strength of specimens
with shrinkage and temperature steel to the shear strength of companion specimens
without such reinforcement are presented in Figure 4-50.
In this figure, it can be seen that the average strength of the AT-3/T series was 1% greater
than the average strength of the AT-3/N series. In the AT-2 series, the average strength
of AT-2/3000 and the AT-2/1000 series was about 98% that of the average strength of the
AT-2/250 series. This decrease was due to the lower shear strengths of AT-2/1000N and
AT-2/3000.
It can be safely concluded that horizontal shrinkage and temperature reinforcement
placed transverse to the spanning direction does not appreciably affect one-way shear
behaviour. In design situations, one-way slabs must be assumed to have a similar shear
stress capacity to beams, particularly in the absence of significant opportunity to shed
load to the adjacent structure. Because the shear strengths of the AT-2/250 series were
similar to the shear strengths of the wider AT-2 specimens, it can be further concluded
that the results of shear tests of narrow beams can be applied in studying the shear
capacity of wide one-way slabs.

4.6.3

Effect of Slab Depth

Because one-way slabs exhibit similar shear behaviour as narrow beams, the wellestablished size effect can be expected to apply. The failure shear stresses, normalized to
the square root of the concrete strengths, of the AT series of specimens and Kanis
narrow/wide beam test series are presented in Figure 4-51 as a function of the effective
depth. It can be seen that ACI Equation (11-3) can be expected to predict unconservative
shear strengths for very thick slabs, while producing accurate and safe predictions for
shallower slabs. As discussed in Chapter 3, the 1994 CSA simplified expression for Vc
(Equation (2-16)) provides an acceptable prediction of the shear strength of the normal
strength specimens, while overestimating the shear strength of high-strength concrete
specimens. Nevertheless, it does account for the size effect in shear. The data from Kani
153

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

(1967) are very conservatively predicted because their high reinforcement ratio resulted
in lower longitudinal strains in the beam web than were assumed in deriving the CSA
expression. The shear strengths of the AT series, with lower reinforcement ratios, are
better predicted by the 1994 CSA simplified method.
The failure shear stresses of the AT series and Kanis series of specimens normalized by
the square root of the concrete strength and the SMCFT strain effect factor are plotted in
Figure 4-52 vs. the effective crack spacing of the specimens. Also shown is the SMCFT
prediction of the variation of the normalized shear stress as a function of the effective
crack spacing, and this is the SMCFT size effect factor. By accounting for both the use
of high-strength concrete and the effect of the axial stiffness of the longitudinal
reinforcement, the SMCFT produces a clearer picture of the size effect.

4.6.4

Final Remarks

The AT series of specimens have shown that one-way slabs and wide beams without
stirrups exhibit similar shear behaviour to narrow beams. The beam width and use of
shrinkage and temperature reinforcement have been shown to have no significant effect
on the shear stress at failure. The exemption from minimum stirrup requirements
outlined in Clause 11.5.6.1 of the ACI 318 code should not be applicable to thick, wide
beams and thick one-way slabs.
The average failure shear stress of AT-2/1000N and AT-2/3000, both of which were
supported on narrow supports, was 94% that of the average of the other three AT-2
specimens. These results indicate that slabs and wide beams supported on narrow
supports may exhibit a slight decrease in their one-way shear capacity. This difference
accounts for the slight loss of strength exhibited in Figure 4-50 for the AT-2 specimens
with shrinkage steel, and is a far more significant effect than the effect of the shrinkage
steel. The shear strength of AT-2/3000 is identified in Figure 4-51 and Figure 4-52,
where it can be seen that it exhibited a significantly lower shear strength than the other
AT-2 specimens.
154

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

It is suggested that cracks are wider, and shear strains higher, along the support lines of
such elements, thereby initiating failure at a lower overall shear stress than in specimens
supported across their entire widths. In addition to having a shear strength governed by
the size effect, a thick slab or wide beam constructed without stirrups and designed using
the ACI code, may thus be further disadvantaged if supported on narrow supports. The
effect of narrow supports on one-way failure shear stress is greater than the effect of the
slab width and the effect of shrinkage and temperature steel. The reader is referred to
Lubell (2006) who studied this effect in detail.
Table 4-9: Data for Narrow and Wide Beams Tested by Kani (1967)
Specimen Properties
Specimen

Experimental Observations

bw
(mm)

d
(mm)

a/d

w
(%)

152
156
153
151
153
154

276
271
275
271
274
269

2.95
3.00
3.94
4.01
5.94
6.05

2.68
2.73
2.76
2.83
2.76
2.71

27.2
27.4
25.3
27.4
27.5
27.4

19
19
19
19
19
19

612
612
611
611

270
271
271
269

3.02
4.02
5.02
6.06

2.73
2.72
2.72
2.75

27.2
27.2
26.9
26.9

19
19
19
19

f'c
ag,eff
sxe
(MPa) (mm) (mm)

Vexp
(kN/m width)

v exp
(MPa)

248
243
247
243
246
241

411
416
368
367
334
331

1.49
1.54
1.34
1.35
1.22
1.23

243
243
243
241

409
337
373
355

1.51
1.24
1.38
1.32

Series 3.8-2.80-12P
97
83
96
84
81
91
Series W3.8-2.80-12P
274
273
272
271

Table 4-10: Predicted Failure Shears for Beam/Slab Width Series


SMCFT
bw

sxe
vpred
d
f'c
(mm) (mm) (mm) (MPa) (MPa)

vexp
vpred

DB165
AT-1

300
2016

925
916

1404
1330

65.0
64.0

0.80
0.74

AT-2/250N
AT-2/250W
AT-2/1000N
AT-2/1000W
AT-2/3000

250
252
1002
1002
3005

437
439
438
439
440

540
542
541
542
544

37.7
38.5
37.9
39.0
40.6

AT-3/N1
AT-3/N2
AT-3/T1
AT-3/T2

697
706
700
706

307
306
306
307

276
275
275
276

97
83
96
84
81
91

152
156
153
151
153
154

276
271
275
271
274
269

W3.8-2.80-12P
274
273
272
271

612
612
611
611

270
271
271
269

Specimen

ACI Eq. 11-5


vpred

Eq. 2-23
vpred

ACI Eq. 11-3

(MPa)

vexp
vpred

(MPa)

vexp
vpred

vpred

0.82
0.86

1.36
1.33

0.48
0.48

0.69
0.71

0.98
0.93

1.346 0.49
1.336 0.48

0.87
0.87
0.87
0.88
0.89

1.22
1.18
1.17
1.24
1.10

1.05
1.06
1.05
1.07
1.09

1.01
0.97
0.97
1.02
0.90

0.83
0.83
0.83
0.84
0.85

1.30
1.25
1.25
1.30
1.16

1.025
1.036
1.028
1.043
1.064

1.03
1.00
0.99
1.04
0.92

37.5
37.1
37.8
37.1

0.94
0.93
0.94
0.93

1.19
1.29
1.26
1.24

1.03
1.03
1.04
1.03

1.08
1.17
1.15
1.12

0.99
0.99
1.00
0.99

1.14
1.23
1.20
1.18

1.023
1.017
1.027
1.017

1.09
1.18
1.16
1.13

248
243
247
243
246
241

27.2
27.4
25.3
27.4
27.5
27.4

1.26
1.26
1.14
1.17
1.03
1.02

1.19
1.22
1.18
1.15
1.19
1.21

1.06
1.06
0.96
0.99
0.92
0.92

1.40
1.45
1.40
1.37
1.32
1.34

0.87
0.87
0.84
0.87
0.87
0.87

1.72
1.76
1.60
1.55
1.40
1.41

0.871
0.874
0.84
0.874
0.876
0.874

1.71
1.76
1.59
1.55
1.39
1.41

243
243
243
241

27.2
27.2
26.9
26.9

1.26
1.16
1.07
1.01

1.20
1.07
1.28
1.30

1.06
0.98
0.94
0.91

1.43
1.27
1.47
1.45

0.87
0.87
0.86
0.87

1.74
1.43
1.59
1.53

0.871
0.871
0.866
0.866

1.74
1.43
1.59
1.53

(MPa)

vexp
vpred

3.8-2.80-12P

Average: 1.17
Coefficient of Variation: 10%

1.16
24%

1.36
17%

1.25
29%

155

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

0.30

One-Way Slabs

Kani (1967) a/d=2.95-6.06


w=2.74%

Shear Strength (MPa-units)

0.25

AT-2 Series a/d=2.95


w=0.91%

0.20

ACI Eq. 11-3

0.15
Rajagopalan and Ferguson (1968)
a/d=4.16
w=0.63%

0.10

0.05

AT-1/DB165
a/d=2.95
w=0.76-1.01%

0.00
0

500

1000

1500

2000

2500

3000

3500

4000

Beam/Slab Width (mm)

Figure 4-48: Effect of Beam or Slab Width on On-Way Shear Capacity

Figure 4-49: Failure Crack Surface -AT-2/3000


156

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

1.08

Ratio of Shear Capacity to Specimens with s+t=0

1.06

1.04

1.02
AT-3

1.00
AT-2

0.98

0.96

0.94

0.92

0.90

0.88
-0.05

0.05

0.1

0.15

0.2

0.25

Transverse Horizontal Reinforcement Ratio, s+t (%)

Figure 4-50: Effect of Shrinkage/Temperature Steel on Shear Strength of One-Way Slabs


The measured strains in the longitudinal steel have indicated that tension stiffening may
have a greater effect in slabs than in narrow beams. Bars in the middle of slabs would be
expected to exhibit greater tension stiffening than bars at the corners as they are exposed
to only one face. This was the behaviour exhibited in Figure 4-26 and Figure 4-27.
However, the greater tension stiffening in AT-2/3000 did not translate to a higher shear
strength.

157

Shear Behaviour of Large, Lightly-Reinforced


Concrete Beams and One-Way Slabs

One-Way Slabs

0.35
Kani (1967)

Vc

a/d=6
a/d=4
a/d=3

b w d fc'

0.30

Normalized Shear Strength

AT-3 Series

0.25
AT-2 Series

0.20

ACI Eq. 11-3

0.15

Vc = 0.167 fc' bwd

AT-2/3000

CSA-94 Eq. 11-7

0.10
AT-1/DB165

0.05

0.00
-300

300

600

900

1200

1500

1800

Beam/Slab Depth (mm)

Figure 4-51: Effect of Depth on Shear Strength of Wide Beams and Slabs
Kani (1967)

Vc b w d v
0.40
fc'
(1 + 1500 x )

1.4

AT-3 Series

Normalized Shear Strength

1.2

1.0

0.8

a/d=6
a/d=4
a/d=3

AT-2 Series

AT-2/3000

0.6

0.4

AT-1/DB165

SMCFT:

0.2

0.0
-500

500

1300
1000 + s xe

1000 1500 2000 2500 3000 3500

Effective Crack Spacing, sxe (mm)

Figure 4-52: Effect of sxe on Shear Strength of Wide Beams and Slabs
158

You might also like