053-069
ISSUE 1
Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset
Press the
button.
button the first digit will flash to enable the pin to be entered.
(up) or
Press
Press
(right) when the first digit is correctly entered. The digit you have just entered will now
show # for security.
Repeat this process for the other digits off the PIN number. You can press (left) if you need to move
back to adjust one of the previous digits.
When
is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is
not correct, you must re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed :
EDITING A PARAMETER
Press the
or
or
Press
DIMENSIONS
240.0mm x 181.1mm x 41.7mm (9.4 x 7.1 x 1.6)
PANEL CUTOUT:
220mm x 160mm (8.7 x 6.3)
to save the value. The parameter ceases flashing to indicate that it has been
bee saved.
or
button.
NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to
ensure security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or
automatically) to ensure security.
NOTE: More comprehensive module configuration is possible
possible using the 86xx
86xx series PC
configuration software.
software. Please contact us for further details
NOTE: The contents of the tables overleaf may differ depending on the actual module
configuration.
ADJUSTABLE PARAMETERS
Front Panel Configuration Editor (Factory default settings are shown in bold italicised text)
Section
Values
Display
Contrast
Language
Current Date and Time
LCD Page Timer
Scroll Delay
Engine Pre Heat Timer
Engine Crank Duration
Engine Crank Rest Time
Engine Safety On Delay
Engine Smoke Limiting
Engine Smoke Limiting Off
Engine Warm Up Time
Engine Cool Down Time
Engine Speed Overshoot Delay
Engine Failed To Stop
Battery Under Voltage Warning Delay
Battery Over Voltage Warning Delay
Return Delay
Generator Transient Delay
Under Voltage Shutdown
Under Voltage Pre-Alarm
Nominal Voltage
Over Voltage Pre-Alarm
Over Voltage Shutdown
Under Frequency Shutdown
Under Frequency Pre-Alarm
Nominal frequency
Over Frequency Pre-Alarm
Over Frequency Shutdown
Full Load Rating
kW Overload Trip
Delayed Over current
Delayed Over Current
AC System
CT Primary
CT Secondary
Short Circuit Trip
Earth CT Primary
Earth Fault Trip
Earth Fault Trip
Transient Delay
Gen Reverse Power Delay
Full kW rating
Full kVAr rating
Load Ramp Rate
Load Level For More Sets
Load Level For Less Sets
Load Demand Priority
Gen Reverse Power
Insufficient Capacity Delay
Insufficient Capacity Action
Reactive Load CTL Mode
Load Parallel Power
Load Power factor
Oil Pressure Low shutdown
Oil Pressure Low Pre-Alarm
Coolant Temp High Pre-Alarm
Coolant Temp High Electrical Trip
Coolant Temp High Shutdown
Start Delay Off load
Start Delay on load
Start Delay Telemetry
Pre Heat Timer
Crank Duration
Crank rest Time
Safety On Delay
Smoke Limiting
Smoke limiting off
Warm Up Time
Cool Down Time
Speed Overshoot Delay
Speed Overshoot
Fail To Stop Delay
Battery Under Volts Warning
Battery Under Volts Warning Delay
Battery Under Volts Warning
Battery Over Volts Warning
Battery Over Volts Warning Delay
Battery Over Volts Warning
Charge Alternator Failure Warning
53%
English, others.
hh:mm
5m
2s
0s
10s
10s
10s
0s
0s
0s
1m
0s
30s
1m
1m
30s
0s
184v
196v
230v
265v
277v
40Hz
42Hz
50Hz
54Hz
57Hz
500A
100%
Active
100%
3 Phase 4 Wire
600A
5A
200%
500A
Active
10%
0s
2s
345kW
258kVAr
3%
80%
70%
1
35kW
1s
None
VAr Share
172kW
When
0%
When
1.03bar
1.24bar
90C
92C
95C
5s
5s
5s
0s
10s
10s
10s
0s
0s
0s
1m
0s
0%
30s
Active
1m
10v
Active
1m
30v
Active
Timers
Generator
Engine
Continued Overleaf
Section
Values
Engine (Continued)
Charge
Charge
Charge
Charge
Charge
Scheduler
Scheduler
6.0v
5s
Inactive
4.0v
(When Enabled)
5s
(When Enabled)
Active, Inactive. Electronic engines only when
droop is enabled.
Active, Inactive
Active , Inactive (Only Available When
Scheduler Is Active)
Weekly, Monthly (Only Available When
Scheduler Is Active)
Alternator
Alternator
Alternator
Alternator
Alternator
Failure Warning
Warning Delay
Failure Shutdown
Failure Shutdown
Shutdown Delay
Droop %
Schedule On Load
Schedule Period
Press
Schedule Time & Date Selection
(1-16)
The running editor can be entered while the engine is running. All protections remain active if the
engine is running while the running editor is entered.
Press the up
Press the up
Press the
saved.
or down
or down
button to save the value. The parameter ceases flashing to indicate that it has been
(When Enabled)
button.
Running Editor
Factory Settings
DISPLAY
53%
English
(1)
0-100% (0)
0-100% (50)
Inactive, Active
Inactive, Active
0-100 % (0)
0-100 % (0)
Inactive Active
Contrast
Language
Load Demand priority
Load Power factor
Load parallel power
Commissioning screens
Override starting alarms
Voltage adjust (manual mode only engine running breaker open)
Frequency adjust (manual mode only engine running breaker open)
Mains decoupling test mode (Stop mode only)
or