Professional Documents
Culture Documents
LUSAIL - QATAR
ARCHITECTURE CONCEPT REPORT
REVISION 00 – NOV. 2019
ARCHITECTURE ....................................................................................................................................................... 3 - 35
LANDSCAPE ................................................................................................................................................................... 36 - 47
Selection Parameters
The selection of materials shall be based on the following parameters:
Aesthetic requirements
Durability
Maintenance requirements
The Plot will be used for AL ERKYAH MIXED USE building the building consists of:
- Two basements (Parking & Service)
- Ground floor (Retail, Anchors)
- First podium (FEC, Shops and Cinemas)
- Service floor (MEP, Serviced Apartments & Podium LSC)
- Second podium (Service)
- Typical floor plans (12 Floors Serviced Apartment)
- Roof plan
Building design, materials and safety shall be controlled and complied with the following Design requirements for architectural form
respectable codes and standards: a. Maximum height 18m for Podium , 45m for Towers
b. Maximum Built-up ratio 50%.
Qatar Fire and Life safety Guidelines, 2015 edition c. Setbacks 5m from all sides. except piazza side 0m
NFPA - National Fire Protection Association NFPA 101, 2015 edition.
NFPA - National Fire Protection Association NFPA 5000, 2015 edition 2.3 Goals of Design
IBC - International Building Code IBC, 2012 edition. a. The design objective is to achieve harmony between the various parts of the project as
ASTM - American Society for Testing Materials ASTM. well as achieving harmony between the building and the district as a whole through
several axes of design, which are:
SCDB - Qatari Civil Defense Bureau.
- Efficiency in operating the building and protecting it from accidents through
ADA - American Disabled Association ADA.
applying codes and regulations governing the design work, and using building
Other related codes mentioned in the Engineering Design Criteria. materials suitable for urban environment and the exploitation of natural resources
available to provide energy and achieve sustainability.
- Realism by using international standards, which provide modernity with ease in
Standard of Measurements
reviewing and obtaining the necessary approvals and permits. This is through the
The modern metric system, System International (SI), will be applied. All dimensions will be in integration of local requirements and the application of local codes with reference
Millimeters & elevation levels in Meters. to international codes for modern elements not covered by local codes and
regulations.
- Flexibility in design that speeds the completion of construction process with
minimal impact and cost on creativity and innovation.
Wall types will be used to indicate all internal walls in terms of:
1. Fire rating & separation as per the IBC code. 3.2 Internal Finishes
2. Sound transmission class (STC) as per Architectural Graphic Standards -10th Edition
In addition to architectural and interior design requirements, the room environment,
, based on the following sound isolation criteria:
room temperature, illumination, noise level and sound transmission class shall be kept
cinema Vs all others. STC 60 at the acceptable levels
Normal offices, meeting Vs Adjacent offices and similar activities. STC 47
The selection of material dimension shall be studied carefully. Nominal sizes shall be
Entertement spacse Vs corridors. STC 47 of first priority. Integration between the finishing material and the adequacy to design
shops Vs other Toilets STC 47 and to maintenance requirements shall be the most important in selecting the material
dimensions.
MEP spaces Vs all others. STC 60
IBC Code Chapter 8 for the interior finishes will be used to control the selection of the
Internal Finishes. In general, the interior finishes shall match the existing.
2. Granite
Approved natural granite slabs to ASTM C615 with finish indicated on drawings,
obtained from one strata of one quarry, free from faults and to the shaped, sizes, and
patterns shown on the Drawings. Granite slabs to have the following minimum
properties:
1. Density: 160 lbs. /ft3
2. Compression strength: 19,000 psi
3. Water absorption: 0.4 % max.
4. Modulus of rupture: 1,500 psi.
5. Abrasion resistance ASTM C241, Ha: 25
- Accessories:
o Sealants within the panel system shall be as per manufacturer's standards to
meet performance requirements.
o Internal Flashing: sheet metal flashing which may be required at base or
penetration conditions will be produced in the same material finish as the adjacent
panels.
o Coping: Wall copings will be produced with the same material as the wall panel
system unless otherwise noted. Sheet Metal flashing extensions will be
acceptable in non- viewing areas in accordance with Manufacturer’s
recommended details.
o Furring/Supports.
o Fasteners: Type 304 Stainless Steel or Cadmium plated as recommended for
- Insulation
specific application.
The insulation needs to be non-combustible, rot and vermin proof and non-absorbent. The
o Shims: High impact plastic shims will be used to maintain planar surfaces.
insulation shall have a foil layer to act a vapor control layer or a breather membrane applied to
the outer face to control condensation.
4. EIFS system
This EIFS system is based on using EPS (Expanded Polystyrene) as the insulation material.
A lightweight system, is comprised of a polystyrene insulation board secured to the exterior wall
with an adhesive or mechanical fasteners, then reinforced with an acrylic plaster and fiberglass
mesh on top, and finished with an acrylic and polymer coat that is both colorfast and crack-
resistant.
Expanded Polystyrene (G-EPS) offers approximately 10% more thermal efficiency and is
especially suited to renovation work as thinner boards can be used 3.4 Building Thermal & Moisture Protections
Toilet fixtures & accessories shall be selected according the selection parameters of
the interior designs and color schemes.
Minimum plumbing fixtures will be calculated in reference to IBC code Table 2902.1
The selection of tea room equipment for different types shall be studied to achieve
project requirements.
3.7 Electro-Mechanical:
A preliminary study has been made during the conceptual design stage, considering
an easy approach for the handicapped persons in the projects’ buildings.
Using ramps (slope not steeper than 1:12) and providing special toilets at all public
toilets units.
All designs shall be reviewed as per the (ADA) standards in the forthcoming phases.
Table 2902.1, IBC 2012 provides the required rates to provide the number of toilets and drinking Male & Female prayer room: 2 WC, 2 Lav., 1 Service Sink and 1 Drinking fountain.
water fountains for all occupations. Stores & services: 2WC, 2Lav, 1 Service Sink and 1 Drinking fountain.
Basement Total WC. =4, Total Lav. =4, Total Service Sink=2, Total Drinking fountain=2
Ground Podium
Hyper market & shops: 9 WC, 5 Lav., 1 Service Sink and 5 Drinking fountain.
Lounge & entrance Tower B: 1 WC, 1 Lav. 1 Service Sink.
Ground Total WC. =10, Total Lav. =6, Total Service Sink=2, Total Drinking fountain=5
First Podium
Food court: 8 WC, 3 Lav., 1 Service Sink and 1 Drinking fountain.
F&B, Shops and mercantile space: 1 WC, 1 Lav. and 1 Service Sink.
FEC: 12 WC, 5 Lav., 1 Service Sink and.
Bowling hall: 3 WC, 2 Lav., and 1 Service Sink.
MGT. Office: 1 WC, 1 Lav. and 1 Service Sink.
Cinema: 11 WC. 5 Lav., 1 Service Sink and 1 Drinking fountain.
First Floor Total WC. =36, Total Lav. =17, Total Service Sink=6, Total Drinking fountain=2
Second Podium
GYM & SPA: 2 WC, 1 Lav., 1 Service Sink.
Swimming pools 28 WC, 7 Lav., 1 Service Sink and 1 Drinking fountain.
Second Floor Total WC. =30 Total Lav. =8, Total Service Sink=1, Total Drinking fountain=1
This Building is classified as an “Apartment & Mercantile occupancy” according to Qatari fire
building. The design will apply the life safety requirement and fire resistance according to this
classification With regard to spaces of a special nature (assembly / high hazard).
Design Criteria:
- Assembly Occupancies > 300<1000 (FEC & Cinema) shall be separated 2 HRs fire rated
with Mercantile Occupancies.
- Assembly Occupancies < 300 (such as bowling hall) shall be separated 2 HRs fire rated with
Mercantile Occupancies.
- Assembly Occupancies > 1000 (such as Swimming pools Area) shall be separated 3 HRs
fire rated with Storage Occupancies.
- Assembly Occupancies > 300<1000 (FEC & Cinema) shall be separated 2 HRs fire rated
Business Occupancy – Revisions B_2015- with Apartment Occupancies.
Qatari fire and Life Safety Guideline - Apartment occupancies shall be separated 2 HRs fire rated with Storage low/ordinary
6.2 Separate Occupancies: Hazard occupancies at basement floor.
The building contains some other occupations such as garage, Cafeterias and assembly zones
such as FEC, Food court and Cinema hall.
Required Separation of Occupancies (hours), will follow Table 6.1.14.4.1 (a) & (b) at NFPA 101,
2015 Edition.
Item Requirements
*Minimum unobstructed width for less 1120 mm
than 2000 people 1140 mm
*Minimum unobstructed width for more
than 2000 people
Fig. 7.1.1.C. Minimum required width Maximum riser height 180 mm
Minimum Riser Height 100 mm
Minimum Tread depth 280 mm
All doors which are located within walls constructed of fire resistant material shall be Minimum Headroom 2030 mm
provided with self-closing devices. Self-closing devices shall comply with the requirements Maximum height between landings 3660 mm
Maximum tread and landing slope 21 mm (1 in 48)
of NFPA 101 Chapter 7.2.1.8
Table 7.1.3: Exit Stair Specifications
Door shall swing in the direction of egress, when serving an occupant load of 50 persons
(*) refers to the total cumulative occupant load assigned to a stair
or more.
The exit door at the point of discharge from a stair shall open outwards, in the direction of
travel. The minimum stair width should be clear of all obstructions except projections not more
than 114 at or below handrail height on each side of the stair (Chapter 7.2.2.2.1.2 of NFPA
The calculation for the width capacity of door shall be based on 5mm per person.
101)
The minimum required unobstructed clearance with door leaf encroaching into a landing
7.1.2 Corridors is shown in Fig. 7.1.1.C the minimum width of stair used in the project is 1150mm.
As per NFPA 101, Assembly Occupancy, Mercantile Occupancy & Business Occupancy, Tread and Landing surfaces shall be as per Chapter
corridor and lobby protection shall not be required in buildings protected throughout by an 7.2.2.3.3 of NFPA 101.
approved, supervised automatic sprinkler system in accordance with Chapter 9.7 of NFPA
Measurement of headroom clearance is shown in Fig.7.1.3 and in accordance with
101.
Chapter 7.2.2.2.1.1 of NFPA 101.
Corridors with a required capacity of more than 50 persons will be required to be of
sufficient width to accommodate the required occupant load but have a width of not less
than 1120mm as per NFPA 101. Corridors with a required capacity of not more than 50
persons will be required to be not less than 915mm width for general public areas unless
specific occupancy chapter requires different corridor width. However, based on
operational constraints corridors in this project may be required to exceed the minimum
width requirements noted above.
The minimum width of corridor used in the project is 1200mm .
Occupant load factor for each usage as per Qatari fire and life safety guideline: Minimum clear width for escape Stairs needed according to Qatari fire and life safety guide-line
is 1420mm.
Residential: 18.6 m2/Person
Residential:
Assembly:
Table 7.4.1 Allowable Building Height and Area – NFPA 5000, 2015
Conclusion:
- The current Design doesn’t cover the needed number of Escape stairs in (cinema zone &
food court) and required escape Exits in (hyper market & Lounge in Tower B). According to table 7.4.1, for buildings protected with an automatic sprinkler system and for
buildings with built-up area exceeding 23000 sq. ft. that considered as un-limited classification
the construction type shall be determined as shown above.
Fire Resistance Ratings for Type I Construction (hr.) – NFPA 5000, 2015
Conclusion:
- Columns supporting more than one floor or columns, shall be 3hr fire resistance ratings for
type I construction. Ramp Landings; Ref. “ADA code, 2010”
- Beams, Girders, Trusses, and Arches supporting more than one floor or columns, shall be
3hr fire resistance ratings for type I construction. Curb Ramps:
- Floor / Ceiling assemblies, shall be 2hr fire resistance ratings for type I construction. Counter Slope. Counter slopes of adjoining gutters and road surfaces immediately adjacent to
- Roof / Ceiling Assemblies, shall be 11/2hr fire resistance ratings for type I construction. the curb ramp shall not be steeper than 1:20.
The adjacent surfaces at transitions at curb ramps to walks, gutters, and streets shall be at the
same level.
LANDSCAPE
CONCEPT REPORT
5 5
9 1
5 8
3
6
7
Pure Rounded Mica Stone Hardscape Patterns
Pebbles Cladding GROUND FLOOR
LAYOUT
2-SOFTSCAPE PALLET
1 RETAIL ENTRANCE 5
2 RESIDENTIAL
ENTRANCE 2
4
3 GATES
7
4 BICYCLE RACK 4
BLOCK C
9
Delonix Regia Chamaerops Humilis Plumeria Obtusa Cassia Fistula 5 SHADED PARKING 7 6
1
AREAS
3 9
6 VIP PARKING
7 SERVICE PARKING
8 OUTDOOR
SITTING AREA
Phoenix Lantana Camara Pennisetum Nerium Oleander Wedelia Trilobata Washingtonia
9 WATER FEATURE
Dactylifera Setaceum robusta
3-5-Parking Shades
5-WATER FEATURE
BLOCK A BLOCK B
6 4
8
5 1
Granite Flooring Beige Porcelain Brownish Gray Dark Brown
Wooden Texture Porcelain Granite 7
2
7 5
Dark Blue Red EPDM Yellow EPDM Blue EPDM 4 EXTERNAL SHOWER 8 GREEN WALLS
Mosaic Tiles Rubber Tiles Rubber Tiles Rubber Tiles
BLOCK C
2-SOFTSCAPE PALLET
Plumeria Obtusa Rhapis Excelsa Cycas Revoluta Lantana Camara Cortaderia Selloana Leucophyllum
Frutescens
4-KIDS PLAYGROUND
Green Walls
BLOCK A BLOCK B
BLOCK C
SECTION (A – A)
1
3
3
1 4
Granite Flooring Beige Porcelain Light Beige Pure Rounded 2
Wooden Texture Granite Pebbles
2- WATER PRESERVATION BY USE RAIN WATER TANKS & DROPED IRRIGATION SYSTEM
5- PROVIDE HANDICAPPED PARKING AND PATHWAY FOR THEM WITH SUITABLE WIDTH AND SLOPE
LIGHT EMPERADOR MARBLE CREMA MAFRIL MARBLE OFF WHITE PAINT OAK WOOD/VENEER STAINLESS HAIRLINE FINISH
LIGHT EMPERADOR MARBLE CREMA MAFRIL MARBLE OFF WHITE PAINT OAK WOOD/VENEER STAINLESS HAIRLINE FINISH
LIGHT EMPERADOR MARBLE CREMA MAFRIL MARBLE OFF WHITE PAINT OAK WOOD/VENEER POLISHED BRUSHED COPPER
LIGHT EMPERADOR MARBLE CREMA MAFRIL MARBLE OFF WHITE PAINT OAK WOOD/VENEER POLISHED BRUSHED COPPER
PORCILAIN TILES WOOD EFFECT CREMA MAFRIL MARBLE OFF WHITE PAINT OAK WOOD/VENEER MIXED TYPES FLOOR
PORCELIAN TILES -OFFWHITE PORCELIAN TILES –LIGH GREY PORCELIAN TILES – OFF WHITE PORCELIAN TILES – MARBLE EFFECT GREY WHITE PAINT
NOVO RUVINIA MARBLE CREMA MAFRIL MARBLE DOUBLE BLACK MARBLE OAK WOOD/VENEER WALL PAPER
DARK EMPERADOR MARBLE CREMA MAFRIL MARBLE DOUBLE BLACK MARBLE WALL PAPER POLISHED BRUSHED BRASS
PORCELAIN TILES (MARBLE EFFECT) WALL PAPER OAK WOOD/VENEER DOUBLE BLACK MARBLE
PORCILAIN TILES WOOD EFFECT OFF WHITE PAINT LIGHT GREY PAINT WALL PAPER
PORCILAIN TILES WOOD EFFECT OFF WHITE PAINT OAK WOOD/VENEER WALNUT WOOD/VENEER
PORCILAIN TILES PORCELIAN TILES -OFFWHITE OFF WHITE PAINT LIGHT GREY PAINT
PORCILAIN TILES PORCILAIN TILES -BEIGE OFF WHITE PAINT GREY PAINT
CALACATTA MARBLE PORCILAIN TILES WOOD EFFECT GRIGIO SAN MARCO MARBLE OFF WHITE PAINT GRAY PAINTED WOOD
8.1. DEAD LOADS AND SUPERIMPOSED DEAD LOADS ......................................................................... 76 14. CONEPTUAL STRUCTURAL PLAN .................................................................................................. 92
8.2. LIVE LOADS ........................................................................................................................................ 76 14.1. EXPANSION JOINTS LOCATION ........................................................................................................ 92
8.4. EARTH AND GROUNDWATER PRESSURE ....................................................................................... 77 14.3. BASMENT 01 FLOOR PLAN ................................................................................................................ 94
9.1. SERVICEABILITY LIMIT STATE COMBINATIONS .............................................................................. 80 14.7. PODIUM 02 FLOOR PLAN ................................................................................................................... 98
The project is the construction of ERKYAH MIXED USE DEVELOPMENT project at Serviceability limit state will be used for deflection criteria.
Qatar. The building consists of: Both safety and serviceability design conditions will be accounted for.
Two basements (Parking & Service), Ground floor (Retail, Anchors), First podium (FEC, Shops
and Cinemas), Service floor (MEP, Serviced Apartments & Podium LSC), Second podium
(Service), Typical floor plans (12 Floors Serviced Apartment), and Roof plan 6. CODES AND STANDARDS
SCOPE OF THE REPORT All design and details will be prepared in accordance with the following codes:
This report summarizes the design criteria, assumptions and approaches that are adopted in
Code,
structural engineering design of the project. Standard or
The proposed values have been established as being the most appropriate for the project, in full Description
Reference
compliance with international standards and excellent practice taking into consideration (Primary list)
constrains and limitations associated with the project.
QCS 2014 Qatar Construction Specifications.
3. DESIGN OBJECTIVE Building Code - American Concrete Institute Requirements for
Our objective is to fulfill the architectural design intent, with the safest and the most cost effective ACI 318-14 Structural Concrete ACI Manuals of Concrete Practice 2001
and economical design. Taking into consideration the constructability aspects and safety. American Concrete Institute.
ASCE 7- 10 Minimum Design loads for building and other structures.
4. DESIGN WORKING LIFE
AISC Manual of Steel Construction - American Institute of Steel
The design working life of the building structures considered 50 years as per QCS 2014 AISC
Construction.
The following is the QCS 2014 recommendations for the design life:
Building structure design working life shall be minimum as specified below: AWS Code American Welding Society.
DESIGN INDICATIVE
WORKING LIFE DESIGN WORKING EXAMPLES
CATEGORY LIFE (YEARS) The following codes of practice and standards could be used when needed:
Code, Standard or
1 10 TEMPORARY STRUCTURES (a)
Reference Description
REPLACAPLE STRUCTURAL PARTS, eg. (Secondary list)
2 10 TO 25
GANTRY GIRDERS, BEARINGS
UBC 1997 Uniform Building Code, USA.
3 15 TO 30 STORAGE AND SIMILAR STRUCTURES
PCI Design Handbook for Precast / Prestressed Concrete,
BUILDING STRUCTURES AND OTHER PCI
4 50 TO 75 Fourth Edition - Precast / Prestressed Concrete Institute.
COMMON STRUCTURES
CRSI 2002 Concrete Reinforcing Steel Institute.
CIVIL ENGINEERING STRUCTURES LIKE
5 120
BRIDGES, TUNNEL etc BS 4 Structural steel sections.
BS 6031 Code of practice for earthwork. Reinforcing and Structural Steel (Yield strength)
Welded Structural Steel tubes for General Engineering Minimum
BS EN 10296 Material description
Purposes. strength
Loading for building Part 1 code of practice for dead and
BS 6399 Non-Prestressed Deformed Bars 500 MPa
imposed loads.
BS 8004 Code of practice for foundations. Prestressed Strands 1690 MPa
Code of practice for design of concrete structures for
BS 8007 Structural Steel 355 MPa
retaining aqueous liquid.
BS 8110 Structural use of concrete. Bolts and Nuts Grade 8.8 640 MPa
BS 5950 Structural Use of steelwork in building. Headed Shear Studs 350 MPa
Code of basic data for the design of buildings for Wind
BS 6399 Part 2
loads.
CIRIA Guide to concrete construction in Gulf region.
1.2(D+F+T) +1.6(L+H) +0.5(Lr or S or R), It means modifier of temperature the same modifier for
dead load.
For verifying the inter-story drift limit state due to seismic load, the following load Not supporting or attached to
combinations are considered: Flat nonstructural elements likely to be
Immediate deflection due to maximum of L, S, R L/180 (1)
roofs damaged by large deflections
# Load Combination
Edrift Immediate deflection due to L
ID
S1010 / ±
S1020 1.00 Not supporting or attached to
For verifying the long-term serviceability limit state of concrete slabs, the following long- nonstructural elements likely to be
Floors L/360
term parameter and load combinations are considered: damaged by large deflections
Long-term Immediate deflection due to L
Value
Parameter
λ 2.00 That part of total deflection occurring after
Supporting or attached to attachment of nonstructural elements, which is
Roof or
nonstructural elements likely to be the sum of the time dependent deflection due to L/480 (3)
Type of floors
Type of Slab Load Combination damaged by large deflections all sustained loads and the immediate due to any
Analysis
additional live load (2)
Immediate deflection due to all gravity
That part of total deflection occurring after
loads
Supporting or attached to attachment of nonstructural elements, which is
(Cracked) Roof or
nonstructural elements NOT likely to the sum of the time dependent deflection due to L/240 (4)
- Immediate deflection due to floors
Traditional be damaged by large deflections all sustained loads and the immediate due to any
Non-Linear sustained gravity loads
RC additional live load (2)
(Cracked)
(1)Limit not intended to safeguard against ponding. Ponding shall be checked by calculations of deflection, including added
+ Long-Term deflection due to
deflections due to ponded water, and considering time- dependent effects of sustained loads, camber, construction tolerances,
sustained gravity loads and reliability of provisions for drainage.
(Cracked + Long-Term) (2)Time-dependent deflection shall be calculated in accordance with 24.2.4, but shall be permitted to be reduced by amount of
λ x Dead Loads deflection calculated to occur before attachment of nonstructural elements. This amount shall be calculated on basis of accepted
+ (0.25 x λ + 0.75) x Live Loads engineering data relating to time-deflection characteristics of members similar to those being considered.
PT Linear (3)Limit shall be permitted to be exceeded if measures are taken to prevent damage to supported or attached elements.
+ λ x Final PT Load
(4)Limit shall not exceed tolerance provided for nonstructural elements.
(Un-cracked)
λ x Dead Loads
Traditional
Linear + (0.25 x λ + 0.75) x Live Loads
RC
(Cracked)
# Load
Combination D1 D2 F L1 L2 L3 L4 L5 Lr W E H T
ID
U0100-TP / ±
1.20 1.20 1.20 1.60 1.60 1.60 1.60 1.60 1.60 NA NA NA
U0100-TN 1.00
U0200 1.20 1.20 1.20 1.60 1.60 1.60 1.60 1.60 0.50 NA NA NA NA
U0310 1.20 1.20 1.20 1.00 1.00 1.00 1.00 1.00 1.60 NA NA NA NA
U0320 1.20 1.20 1.20 1.00 0.50 1.00 1.00 1.00 1.60 NA NA NA NA
U0331 / ±
1.20 1.20 1.20 NA NA NA NA NA 1.60 NA NA NA
U0332 0.50
U0411 / ±
1.20 1.20 1.20 1.00 1.00 1.00 1.00 1.00 0.50 NA NA NA
U0412 1.00
U0421 / ±
1.20 1.20 1.20 1.00 0.50 1.00 1.00 1.00 0.50 NA NA NA
U0422 1.00
U0511 / ±
1.20 1.20 1.20 1.00 1.00 1.00 1.00 1.00 NA NA NA NA
U0512 1.00
U0521 / ±
1.20 1.20 1.20 1.00 0.50 1.00 1.00 1.00 NA NA NA NA
U0522 1.00
U0611 / ±
0.90 0.90 NA NA NA NA NA NA NA NA NA NA
U0612 1.00
U0621 / ±
0.90 0.90 NA NA NA NA NA NA NA NA 1.60 NA
U0622 1.00
U0711 / ±
0.90 0.90 0.90 NA NA NA NA NA NA NA NA NA
U0712 1.00
U0721 / ±
0.90 0.90 0.90 NA NA NA NA NA NA NA 1.60 NA
U0722 1.00
Parameter Limit
Maximum Allowable Liquid Limit 35% (Maximum)
Ground
Building Foundation Immediate Net
Water Plasticity Index 10% (Maximum)
Title Level* Elastic Bearing
Table** Material Passing 0.075
Settlement Capacity 20% (Maximum)
mm Sieve
Organic Matter Content 2% (Maximum)
ERKYA
8.00-9.00 +1.00
MIXED 25 mm 475 KPa Soaked CBR value 15% (Minimum)
m QND
USE 5% (Maximum)by weight of dry
ERKYA Water soluble salts
12.00- +1.00 soil
MIXED 25 mm 500 KPa
13.00 m QND Rock Particles Size 75 mm (Maximum)
USE
Structural fill should not contain any roots, construction debris, salts, deleterious material, organic
*Below existing ground level.
matters, cobbles or boulders (size 80mm). Recommended backfill material can be specified within
**The groundwater table highest level to be +1.00 QND .
granular non-cohesive soils. Well-graded material is preferred.
Lateral earth pressure developed by compacted backfill are calculated using an
For uplift Design Check using safe we would use the following equation for this check:
angle of internal friction of phi and the corresponding at rest, active, and passive
pressure coefficients are as follows:
0.9 x (Own Weight) – Uplift Load shall be greater than or equal to zero
Phi = 30 Phi = 45 Phi = 40
Coefficient
degree degree degree
At Rest 0.5 0.292 0.357
Active 0.33 0.171 0.217
Passive 3.00 5.83 4.59
2D modeling, analysis and Rigid diaphragms have infinite in-plane stiffness properties, and therefore they neither exhibit membrane
Ultimate tool for designing deformation nor report the associated forces, whereas semi-rigid diaphragms simulate actual in-plane stiffness
design of reinforced
CSI SAFE concrete floor and properties and behavior. For most reinforced-concrete slab systems, in which the slab is sufficiently thick and
concrete foundations and
foundation systems. membrane deformation due to lateral loading is negligible, rigid diaphragms produce results nearly identical to
slabs
those of semi-rigid diaphragms, while taking advantage of faster computation. Semi-rigid diaphragms should be
Calculation pad for Structural analysis and modeled when significant in-plane deformation does occur, or when required by code.
structural analysis and design of structural Primary differences;
PROKON
design of structural elements Formulation – The infinite in-plane stiffness components of a rigid diaphragm allows the stiffness matrix to
elements. (General purpose) condense, decreasing computational time.
Eccentricity – For rigid diaphragms, the accidental eccentricity associated with auto seismic loading is
concentrated and applied at the center of mass, whereas for semi-rigid diaphragms, accidental eccentricity is
12.2. P-Delta Analysis
applied to every node for auto seismic loads. If no diaphragm is assigned eccentricity will not be applied to any
As per ASCE-7-10 section no 12.8.7 we ought to calculate (Ɵ) actual from Etabs node. For auto wind load cases and rigid diaphragm, loading is applied at geometric centroid, in case of semi-rigid
model and compare it with the maximum allowable sway as following; diaphragm auto wind loads are distributed in 10 nodes, so that the summation of these forces with respect to
centroid will be equivalent to lateral and torsional wind cases.
Ɵ max = (0.5/ (Beta x Cd), where Beta = 1, Cd equal 4 for selected lateral Reporting forces – In-plane chord, shear, and collector forces are only reported when using semi-rigid diaphragms.
resisting system for example
Using the TABLE (12.12-1) we could find that the required allowable drift
depends on the risk category which is (I, II, III and IV) and the type of structure
which found as all other structures that represent our statical system case of
ordinary reinforced concrete with shear wall
12.6. MATERIALS
Concrete specified Compressive strength fc’ as per ACI-318M-14 is nearly
equal 80% of the Fcu.
Beams (R Sec) 0.50 (M2 and M3) Table 6.6.3.1.1(a) Moment of inertia and cross-sectional area permitted for
0.50 X 1.50 = 0.75 Elastic analysis at factored level
Beams (L Sec) (Modeled as R Sec)
(M2 and M3)
Cross sectional Cross sectional
0.50 X 2.00 = 1.00 Moment of
Beams (T Sec) (Modeled as R Sec) Member and condition area for axial area for shear
(M2 and M3) inertia
deformations deformations
0.35 (m11 and
Slabs (Traditional RC)
m22) Columns 0.70 Ig
1.00 (m11 and
Slabs (PT)
m22) Un-cracked 0.70 Ig
Beams (R Sec) 1.00 (M2 and M3)
Cracked 0.35 Ig
Beams (L Sec) (Modeled as R Sec) 1.50 (M2 and M3)
Beams 0.35 Ig
Beams (T Sec) (Modeled as R Sec) 2.00 (M2 and M3)
1.00 (m11 and Flat plates and flat slabs 0.25 Ig
Slabs (Traditional)
m22)
Slabs (PT) NA
0.10 x Torsional
Columns and Beams (Torsional Stiffness)
Constant
Walls and Slabs (Torsional Stiffness) 0.10 (m12)
1.1 This concept report is intended to describe the various electrical systems that will
be designed for the project. This report also aims / intends to illustrate / define While achieving the design objectives, other important factors will have to be
the scope and extent of electrical works / supporting information / criteria that will considered carefully as summarized below:
serve the Project, and to highlight the essential guidelines and backbone that will
be implemented in the preparation of the Electrical drawings / design. a) Cost effectiveness
b) Efficiency and energy conservation.
1.2 The electrical installations shall be laid, based on /considering / complying with c) Co-ordination with other design elements
applicable codes and standards including local regulation/Authorities. d) Flexibility of installation
e) Simplifying installations, operations and maintenance.
2. Basic design criteria 2.3 Equipment & Materials
2.1 Overall Concept / Strategy All Equipment and materials will be specified to comply with the latest relevant
standards of IEC, BS and QCS as applicable, where not in contradiction with
Kahramaa / Owner / operator requirements.
a) All Electrical engineering systems necessary for the full operation of the
project will be provided while emphasizing on sustainable green design for 2.4 Codes & Standards
the project reflecting the design intent of the client / Operator.
All electrical installations will be designed in compliance with the latest edition of
the following codes and standards as applicable:
b) The project aims to achieve GSAS (Global Sustainability Assessment
System) building requirements of 2-stars target score. The GSAS rating will a) Qatar General Electricity & Water Corporation (KAHRAMAA), latest edition.
be considered while designing the lighting, lighting control and other items
as applicable. b) Ministry of Interior (MOI-QCDD), Local Civil Defense Authorities Codes and
Practices.
c) For all electrical systems, which are explained in this report, any other
disciplines change during the next project stages may result in an impact c) Ministry of Interior (MOI-QSSD), Local Security Surveillance Dept. Codes
on the explained concept mentioned herein in this report. and Practices
2.2 Objectives, Constraints And Other Considerations: d) Lusail City Design Criteria Report.
From the above, the maximum demand power allocated for the project
from the utility is around 9.5 MVA. However, the estimated maximum
demand load is 12.588 MVA which means there is a shortage of about 3
MVA.
The estimated demand power does not include the pending area, which
is part of plot H-1/HA-1 (i.e. the indicated power shortage does not
include the expected load of the pending area as well).
The utility allocated power from the six MV intake points will be used
through points HC-1 and HA-3 as shown in figure E-1.
2- Electrical substation 2;
- This substation will also be located in basement 1 floor opposite to the two MV
intake points HA-2 & HA-3 close to the east boundary of the basement and it
consists of one 11 KV switchgear inside the MV room 2 (19.3m x 7.2m
dimensions. This room has bigger dimensions compare with MV room 1 due to
the structural elements / geometry in this location). The switchgear will be
connected to the 11 KV intake HA-3 from the other loop of the 66/11 KV
Boulevard 1 primary substation.
3.7 Metering & Kwh Meters Connection d) Meeting KM latest regulation, Capacitor banks shall be provided as a
a) In coordination with KM regulations and subject to their approval, standalone panel(s) beside the main LV panels within the respective LV
independent KM’ KWHM metering system located in the LV / electrical room.
room shall be provided for Landlord. The landlord’s LVPs will include
the main KM meters. There will be dedicated LVPs for the towers to
feed all residential towers and their parking in basement 2 floor and the
other LVPs dedicated for the mall and its parking on site and basement
d) The generators backup time is 8 hours for three days (i.e. the daily
h) The conduits will be galvanized steel for surface runs while, high fuel tank capacity shall be for 8 hours and the bulk fuel tank shall be
impact PVC conduits will be installed where concealed within the for 24 hours).
building fabric.
e) The generators will be accommodated with acoustic treatment to keep
i) All steel wire armored cables will be fixed to heavy duty galvanized the noise at 1m outside the generators room limited to 85 dBA.
steel cable trays / ladders for all horizontal and vertical runs.
f) Fire resistant cables /wires shall be used to ensure emergency power
supply is maintained under fire conditions for the whole Emergency
j) The Enclosed Bus Duct shall be constructed with extruded aluminum Power Distribution.
housing and Copper Bus Bars, with openings for duct plug-in units for
feeding the towers’ apartments. The Enclosed Bus Duct shall be complete
with all hangers, cable tap boxes, bus plugs and accessories required for g) The location of the generators room (23m x 13.5m dimensions) is in
the complete installation. The Enclosed Bus Duct shall be rated as 415 basement 1 floor as shown in figure E-2 above. The room shall
volt, 3 phases, neutral, and earth, 5 wires, 50 Hz with full capacity neutral. accommodate three generators with ratings according to the
The Enclosed Bus Duct shall be built to match with the BS and have Local estimated emergency load.
Authority approval.
a) The separate conduits, wire ways, cable trays will be dedicated for f) The clean earthing system for main telecom room equipment and all other low
normal circuits, emergency circuits and low current circuits. current equipment shall be provided with dedicated earth pits and
conductor(s).
b) The separate conduits and trunking will be dedicated for normal lighting
and emergency lighting circuits. g) All metalwork associated with the electrical installation shall be bonded
together and shall be solidly and effectively earthed to achieve equipotential
c) The flexible galvanized steel conduits will be used for terminating all grounding network.
connections to motors and vibrating equipment.
h) The earthing termination shall comprise a set of earth electrodes enclosed
d) The cable trays or ladder will be of galvanized sheet steel, supported either in inspectional hand holes to achieve the minimum earth resistance value.
from ceiling or walls.
i) Interconnection for earthing pits to each other shall be through a minimum
e) The type of conduits (PVC or galvanized steel conduits) according to its of two (2) pvc insulated copper cables and shall be of the loop / ring type
use will be as per QCS. (bonding the earth pits together and returning back to the main earth pit(s)).
m) The resistance of any point in the earth continuity system to the main e) Fan coil units shall be connected (for each one) to its own 13A switch
earth electrode shall not exceed 1 ohm, unless approved otherwise by fused spur unit mounted adjacent to the unit and as per Kahramaa
Kahramaa. regulations.
n) All non-current carrying metallic parts of electrical / mechanical f) Wall mounted extract / exhaust fans shall be controlled from a
installations shall be bonded to the earthing system. separate switch of the same type as the light switch and as per
Kahramaa regulations.
o) All metallic parts of the water tank, pump rooms including the g) All 13A socket outlets shall be switched type, flush mounted and
reinforcing steel, all forming shells, and all metal fittings within or conform to BS 1363.
attached to tank structure and all metal parts of electric equipment
shall be bonded together with the earthing system.
h) Power supply to the landscape, garbage chute, Lifts, BMU and any
other general purpose services shall be designed and provided as
p) Earth electrodes to be not less than 3.6 m long, in 1.2 m sections per the requirement of the project.
coupled by strong bronze couplers, and 16 mm diameter, steel core
copper jacketed type.
i) The wiring devices shall be selected based on the Architect or ID
requirements in coordination with furniture layout(s).
q) Full technical details shall be submitted during the shop drawing
stage, along with final locations of earthing pits and final earthing
conductor size calculations with exact routing. j) In Kitchen, pantry, or tea rooms, the followings will be considered in
design:
3.14 Small Power System Installations Cooker : Spur outlet with separate DP switch
Refrigerator: 20A Socket Outlet with separate switch
a) The general power installations will comprise socket outlets, flex
outlets, double pole switches, distribution boards and associated
conduits and wiring. Micro-wave Oven: 20A Socket Outlet with separate switch
Kettle: 13A Switched Socket outlet
b) The circulation / general areas shall be provided with 13A switched Hood: 13A Spur outlet with separate switch
a) Wiring devices will be selected based on the Architect or ID h) The illumination levels for various areas/spaces and general service
requirements in coordination with furniture layout. areas will be calculated based on CIBSE recommendations.
b) The face plate finish will be determined in conjunction with Some examples are shown in table below.
architectural details in interior area and will be stainless steel
metal clad finish in plant rooms, switchboard room, etc.
c) The lighting control switches will be rated 20A, grid type and
modular construction.
d) The light fittings for internal, external façade and emergency escape j) All light fittings used shall be of energy saving applicable types / LED
route lighting distribution shall be designed and provided in line with (wherever applicable) to be compatible with the concept of green
interior designer by taking into consideration both functional and buildings approach / GSAS certification requirements.
aesthetic aspects.
k) The lighting for garden, landscape, building facade …etc. shall be
e) The General arrangement and type of lighting fixtures will be selected provided with wiring connections to the lighting points which to be
to suit the specific area requirements. designed / determined along with the types of light fittings by the
exterior designer / specialist lighting consultant.
b) The external area lighting will be controlled through photocells, f) The central battery system shall be sized for 1.5 hours operation and
contactors and timers. shall be connected to the emergency generator.
d) The Aircraft warning lights on the towers will be fed from the
respective floor central battery panel.
a) The state-of-the-art structured cabling network will be designed c) Two main telecom rooms (one for the mall and the other one for the
and provided based on latest technology for telephone, data, residential towers) are provided with 7.2x5 m2 dimensions attached
voice and video distribution networks. with two GSM rooms (for the mall and towers as well) (7.2x4.8 m2
dimensions) in basement 1 floor.
b) The telephone & data cabling system will comprise service
provider main distribution frame (MDF), intermediate distribution
frames (IDFs), cable trays, trunking, telephone cables, Cat 6 d) Each telecom room will include two isolators 63 ampere for telecom
cables, junction boxes, back boxes, telephone face plates, equipment and each GSM room will include one isolator 63 ampere
conduits and all other required associated accessories. for GSM equipment.
e) The project will have two separate systems one for the h) The low current room will accommodate the intermediate distribution
commercial mall and the other for the residential towers. The frames (IDF) which will feed all data and telephone outlets & Floor
MDF of the commercial mall will be accommodated within a distribution box (FDB) which will serve each primary home
centralized LC room in basement 1 while; the three MDFs of the distribution box (PHDB) in each tenant area (apartments, shops,
towers will be accommodated within three LC rooms attached to F&B, Hyper Market, etc.).
the towers’ cores in the service floor.
4.2 Telecommunications System a) The CCTV surveillance security system will be designed and provided to
monitor the movement of the people based on IP technology and using
a) The telecom service provider Main Distribution Frame (MDF) room shall be structured cabling network as per MOI-QSSD requirements.
established as an incoming and distribution point for main
telecommunications cabling of the project. b) The CCTV surveillance security system will comprise main CCTV racks,
central monitoring station, IP colored cameras (fixed / PTZ (pan tilt zoom)),
c) Two CCTV control rooms (one for the commercial mall and the other for
the residential towers) with 7.1m x 4.8m dimensions each will
accommodate the security console desk(s) and screens that will be
monitored by operators.
e) The CCTV system’s main racks will be located within a dedicated two
CCTV rack rooms (one for the commercial mall and the other for the
residential towers) as per MOI-QSSD requirements. The rack room
dimensions is 7 x 3.7 m2 located directly beside the CCTV control room in
basement 1 floor.
g) Each CCTV system will have a dedicated UPS backup power supply to run
the whole system for not less than one hour in case of power failure
h) CCTV data outlet will be energized through dedicated IDF and the length
between the rack and outlet will not exceed 90 meter.
j) Each CCTV system shall have sufficient storage for all camera recordings
for a period of 120 days, in MPEG-4 or H.264 format or better quality
compression techniques.
b) This system will form part of the door access control system described
a) The door entry and car parking barrier access control system
above. The system will include Drop arm barriers, vehicle detection
will be designed and provided based on proximity card
loops, parking sensor, counter screens, indications lamps.
technology and TCP/IP network protocol to restrict / control
entry of people or vehicles to the respective area / room inside
c) Security guards shall be able to control the drop barriers from the
the building.
remote location. Drop barriers are recommended for entry and exit
areas of the car parking only.
b) The card access system shall be provided to control the access
to the building through common card reader or card keys and d) Parking Control System shall be automatic operation at entrance and
shall be integrated with gate barrier(s) and building entrance(s). automatic operation at exit.
c) Two separate access control systems will be provided ( one for e) Entry, Automatic Gate Arm Control Electrically operated upon insertion
the commercial mall and the other for the residential towers) of coded card / insertion of pass key. Activate automatic arm reversing
switch if an obstacle is sensed in the down motion.
d) The door access system will be provided for electric rooms, low f) Exit, Automatic Gate Arm Control: Electrically operated upon insertion
current rooms, utility / mechanical rooms, security offices, fire of coded card / insertion of pass key. Activate automatic arm reversing
command center, CCTV rack room …etc. and any other switch if an obstacle is sensed in the down motion.
strategic areas that require the use of authorized cards / keys.
e) All strategic doors will be provided with magnetic door contacts 4.6 Sound System And Voice Evacuation
to detect unauthorized passage and generate alarm / notification
signals. a) The PA system shall be deployed/provided in the public areas to
provide public address announcement and emergency evacuation
f) Each access control system shall have provision for integration messages complying / in coordination with the NFPA & QCDD
with its respective building management system (BMS). It shall requirements and to their approval.
be integrated also with the respective fire alarm system control
panel for releasing the required doors / exits in case of fire.
b) The PA & background (BG) music system will comprise main rack,
amplifier(s), CD player, radio tuner, microphone(s), sound speakers
g) The two access control systems will be as follows: and all other required associated accessories.
One for mall services and mall parking (basement 1). The mall
services room doors shall be accessed through authorized
persons. c) The public address system shall be integrated with the main fire alarm
control panel(s) to be utilized for the emergency evacuation and
The other one is for the residential towers; this one shall prevent warning purposes in the case of fire or emergency.
accessibility to the residential parking (basement 2) and to allow
accessibility from mall to residential towers for the towers’ d) Emergency evacuation (EVC) announcements shall be broadcasted
residents only. from the FCC (fire command center) of the building in ground floor.
4.5 Car Parking Management System e) Emergency evacuation (EVC) announcements shall be broadcasted
to all areas (either as a common announcement or according to the
zoning and staging of any evacuation based on the fire management
a) The system shall be provided within parking spaces related to the strategy for the building).
g) All cables of the EVC system will be of fire resistant type similar to the
fire alarm system’s cables. Six Satellite panels (SFACP) for the three towers (two
SFACP for each tower located at the tower’s entrance in
the ground floor) and connected to MFACP.
h) The PA & BGM main rack and console will be accommodated inside
the control room of the mall in basement 2 floor. MIMIC panel which shall monitor all fire alarm devices,
Addressable smoke detectors,
Heat detectors,
4.7 Building Management System Multi detectors,
Transmitter & receiver beam detectors,
a) A comprehensive and effective two building management Monitor / interface modules for sprinkler supervised
systems (BMS) will be provided (one for the commercial mall valves, sprinkler flow / tamper switches,
and the other for the residential towers) for various control &
monitoring functions of HVAC, electrical, plumbing, sanitary Fire & sprinkler pumps and diesel generator.
drainage systems and any other required building services.
b) Each BMS shall also be interfaced with the fire alarm system to Fire alarm Panels are provided strategically
enhance the safety management of the building. serving/emphasizing the separation concept, with an
interconnection between the different panels to ensure a
homogeneous/centralized fire alarm control for the whole
c) Dedicated vertical cable tray will be provided in low current project.
rooms for BMS system’s cables.
The fire alarm system shall protect all risk areas within the
d) Each BMS main station will be located within the respective premises by giving warning of a fire condition when
BMS room (3 x 4m2 dimensions) in basement 1 floor for the detected by an automatic detector or by the manual
commercial mall and in basement 2 floor for the residential operation of a break glass call point. The risk area shall be
towers. divided into zones as per the life safety fire zoning.
Total Total
Air Conditioning Lighting Small Power Water Heater Cooker Misc. Loads (Pumps, Fans, refregirator, etc.) Normal Emergency Fire Mode
Normal Emergency
Mode (KVA) Mode (KVA) (KVA)
load (KVA) load (KVA)
FLOOR PLAN ROOM NAME AREA (m2) VA/m2 Total Load (KVA) Normal (KVA) Emergency (KVA) VA/m2 Total Load (KVA) Normal (KVA) Emergency (KVA) VA/m2 Total Load (KVA) VA/m2 Total Load (KVA) VA/m2 Total Load (KVA) VA/m2 Total Load (KVA) Normal (KVA) Emergency (KVA)
Parking 32525 0 0 0.00 0.00 3 97.58 73.18 24.39 2 65.05 0 0.00 0 0.00 0 0.00 0.00 0.00 138.23 24.39 162.63 24.39 24.39
BASEMENT 01 FLOOR Services 2805 0 0 0.00 0.00 6 16.83 12.62 4.21 10 28.05 0 0.00 0 0.00 0 0.00 0.00 0.00 40.67 4.21 44.88 4.21 4.21
Stair 326 0 0 0.00 0.00 6 1.96 0.00 1.96 0 0.00 0 0.00 0 0.00 0 0.00 0.00 0.00 0.00 1.96 1.96 1.96 1.96
Services 5696 0 0 0.00 0.00 6 34.18 25.63 8.54 10 56.96 0 0.00 0 0.00 0 0.00 0.00 0.00 82.59 8.54 91.14 8.54 8.54
shops 3995 0 0 0.00 0.00 10 39.95 39.95 0.00 36 143.82 0 0.00 0 0.00 0 0.00 0.00 0.00 183.77 0.00 183.77 0.00 0.00
Stair & elev. 437 0 0 0.00 0.00 6 2.62 0.00 2.62 0 0.00 0 0.00 0 0.00 0 0.00 0.00 0.00 0.00 2.62 2.62 2.62 2.62
Toilets 126 0 0 0.00 0.00 6 0.76 0.57 0.19 2 0.25 0 0.00 0 0.00 33 4.16 4.16 0.00 4.98 0.19 5.17 0.19 0.19
GROUND FLOOR Offices 78 0 0 0.00 0.00 6 0.47 0.35 0.12 24 1.87 0 0.00 0 0.00 20 1.56 1.56 0.00 3.78 0.12 3.90 0.12 0.12
kiosk 76 0 0 0.00 0.00 0 0.00 0.00 0.00 6 0.46 0 0.00 0 0.00 69 5.24 5.24 0.00 5.70 0.00 5.70 0.00 0.00
CAFÉ (F&B) 873 0 0 0.00 0.00 7 6.11 6.11 0.00 15 13.10 0 0.00 110 96.03 107 93.41 93.41 0.00 208.65 0.00 208.65 0.00 0.00
open space 26689 0 0 0.00 0.00 2 53.38 53.38 0.00 0 0.00 0 0.00 0 0.00 5 133.45 133.45 0.00 186.82 0.00 186.82 0.00 0.00
hyper market 3160 44.9 141.884 141.88 0.00 10 31.60 31.60 0.00 40 126.40 0 0.00 0 0.00 47 148.52 148.52 0.00 448.40 0.00 448.40 0.00 0.00
Services 5797 0 0 0.00 0.00 6 34.78 26.09 8.70 10 57.97 0 0.00 0 0.00 0 0.00 0.00 0.00 84.06 8.70 92.75 8.70 8.70
Stair & elev. 431 0 0 0.00 0.00 6 2.59 0.00 2.59 0 0.00 0 0.00 0 0.00 0 0.00 0.00 0.00 0.00 2.59 2.59 2.59 2.59
Toilets 205 0 0 0.00 0.00 6 1.23 0.92 0.31 2 0.41 0 0.00 0 0.00 33 6.77 6.77 0.00 8.10 0.31 8.41 0.31 0.31
Offices 149 0 0 0.00 0.00 6 0.89 0.67 0.22 24 3.58 0 0.00 0 0.00 20 2.98 2.98 0.00 7.23 0.22 7.45 0.22 0.22
353- Erkyah Mixed Use development
CINEMA 3187 42 133.854 133.85 0.00 10 31.87 31.87 0.00 20 63.74 0 0.00 0 0.00 30 95.61 95.61 0.00 325.07 0.00 325.07 0.00 0.00
FOOD COURT 849 0 0 0.00 0.00 6 5.09 3.82 1.27 10 8.49 0 0.00 0 0.00 0 0.00 0.00 0.00 12.31 1.27 13.58 1.27 1.27
1ST PODIUM FLOOR
kiosk 56 0 0 0.00 0.00 0 0.00 0.00 0.00 6 0.34 0 0.00 0 0.00 69 3.86 0.00 0.00 0.34 0.00 0.34 0.00 0.00
COLD STORE 90 0 0 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0 0.00 0 0.00 330 29.70 29.70 0.00 29.70 0.00 29.70 0.00 0.00
FEC 4605 50.6 233.013 233.01 0.00 10 46.05 46.05 0.00 20 92.10 0 0.00 0 0.00 60 276.30 276.30 0.00 647.46 0.00 647.46 0.00 0.00
shops 620 0 0 0.00 0.00 10 6.20 6.20 0.00 36 22.32 0 0.00 0 0.00 0 0.00 0.00 0.00 28.52 0.00 28.52 0.00 0.00
CAFÉ (F&B) 51 0 0 0.00 0.00 7 0.36 0.36 0.00 15 0.77 0 0.00 110 5.61 107 5.46 5.46 0.00 12.19 0.00 12.19 0.00 0.00
F&B 395 0 0 0.00 0.00 7 2.77 2.77 0.00 15 5.93 0 0.00 110 43.45 107 42.27 42.27 0.00 94.41 0.00 94.41 0.00 0.00
Elevators & Escalator / Travellator Mall 390.00 0.00 390.00 0.00 0.00
Telecom. & Security loads Mall 0 120 120.00 120.00 120.00
Fire Pump Mall 0 260 260.00 0.00 260.00
Jockey Pump 0 22 22.00 22.00 22.00
Water Transfer Pump 11 0 11.00 0.00 0.00
Water Booster Pump 0 15 15.00 15.00 15.00
Heat Pump 55 0 55.00 0.00 0.00
Submersible Pumps 0 0 0.00 0.00 0.00
Chilled Water Pump Mall 220 0 220.00 0.00 0.00
Parking Exhaust and supply fans 0 1318 1318.00 1318.00 1318.00
Ground floor Fan Coil Units 93.42 0 93.42 0.00 0.00
Ground floor Air Handling Units 100 0 100.00 0.00 0.00
First Podium floor Fan Coil Units 43.8 0 43.80 0.00 0.00
First Podium floor Air Handling Units 33.33 0 33.33 0.00 0.00
First Podium floor ERUs (Ventilation) 100 0 100.00 0.00 0.00
Service Level Air Handling Units 208.45 0 208.45 0.00 0.00
Service Level FAHUs, ERUs, FAFs, EXAFs (Ventilation) 79.23 0 79.23 0.00 0.00
DX A/C units for Electrical Substation 0 111 111.00 111.00 0.00
DX A/C units for Main Telecom, CCTV & Low Current rooms 0 50.1 50.10 50.10 0.00
Public Toilets Water Heaters 28 0 28.00 0.00 0.00
Misc. Loads (Pumps, Fans, refregirator, etc.)
Air Conditioning Lighting Small Power Water Heater Cooker
Total Connected load 1386.98 161.10 362.13 55.12 691.59 83.00 145.09 1235.42 1735.00 3904.21 1951.22 5855.42 1691.22 1790.12
Demand Factors 0.9 0.9 0.6 0.9 0.6 0.3 0.4 0.5 0.8 0.66 0.81 0.71 0.80 0.82
Total Demad Load 1248.28 144.99 217.28 49.60 414.95 24.90 58.04 617.71 1388.00 2581.16 1582.59 4163.75 1352.97 1471.59
Total Demand Load on Transformers (KVA) 4163.75
Total Demand Load on Transformers (KW) 3747.38
Air Conditioning Water Heater Cooker General Others Total Load (KVA)
MALL
Total Load (KVA) Total Load (KVA) Total Load (KVA) Total Load (KVA) Total Load (KVA)
Air Conditioning Water Heater Cooker General Others Total Load (KVA)
TOWER (EXCEPT RESIDENTIAL APPARTMENT)
Total Load (KVA) Total Load (KVA) Total Load (KVA) Total Load (KVA) Total Load (KVA)
CONNECTED LOAD (KVA) 1342.13 532.00 0.00 787.74 1693.96 4355.83
DEMAND FACTOR 0.90 0.30 0.40 0.70 0.77 0.74
MAX. DEMAND LOAD (KVA) 1207.92 159.60 0.00 548.11 1304.35 3219.98
Air Conditioning Water Heater Cooker General Others Total Load (KVA)
TOWER RESIDENTIAL APPARTMENT
Total Load (KVA) Total Load (KVA) Total Load (KVA) Total Load (KVA) Total Load (KVA)
CONNECTED LOAD (KVA) 817.38 3268.89 0.00 1562.00 5482.33 11130.60
DEMAND FACTOR 0.90 0.30 0.40 0.60 0.50 0.48
MAX. DEMAND LOAD (KVA) 735.64 980.67 0.00 937.20 2741.17 5394.67
Air Conditioning Water Heater Cooker General Others Total Load (KVA)
ALL PROJECT LOAD
Total Load (KVA) Total Load (KVA) Total Load (KVA) Total Load (KVA) Total Load (KVA)
CONNECTED LOAD (KVA) 3707.59 3883.89 145.09 3458.57 10146.71 21341.85
DEMAND FACTOR 0.90 0.30 0.40 0.63 0.60 0.60
MAX. DEMAND LOAD (KVA) 3336.83 1165.17 58.04 2167.15 6050.54 12777.72
1.2 Design Criteria ....................................................................................................................... 130 1.4.2 Fresh and exhaust air system for mall facilities ...................................................................................... 147
1.2.1 Doha Orientation Data ............................................................................................................................ 130 1.4.3 Toilets ..................................................................................................................................................... 147
1.2.2 Outside Temperatures ............................................................................................................................. 130 1.4.4 Storage Area .......................................................................................................................................... 147
1.2.3 Indoor Design Conditions ........................................................................................................................ 131 1.4.5 Kitchen .................................................................................................................................................... 147
1.2.4 Internal Heat Gain Design Criteria .......................................................................................................... 131 1.5 Smoke control systems ......................................................................................................... 148
1.2.5 Equipment Power Densities ..................................................................................................................... 132 1.5.1 Parking Garage Ventilation & Smoke Management Plan ..................................................................... 148
1.2.6 Lighting Power Densities ......................................................................................................................... 132 1.5.2 Large space smoke evacuation system .................................................................................................. 149
1.2.7 Ventilation ............................................................................................................................................... 133 1.5.3 Atrium smoke evacuation system .......................................................................................................... 149
1.2.8 Ductwork ................................................................................................................................................. 133 1.5.4 Pressurization system ............................................................................................................................. 149
1.2.9 Pipe Work ................................................................................................................................................ 134
1.6 HVAC Zoning .......................................................................................................................... 153
1.2.10 Building Construction U values .............................................................................................................. 134
1.2.11 Occupancy Basic Criteria ....................................................................................................................... 134 1.7 Fresh & Exhaust riser ............................................................................................................ 159
1.2.12 Cooling & Heating Load ......................................................................................................................... 134 1.8 Outline Specifications ............................................................................................................ 167
The latest editions of publications and standards listed here are intended as guidelines for design. They
1.2.2 Outside Temperatures
are mandatory only where referenced as such in the text of this chapter or in applicable codes. The list is
not meant to restrict the use of additional guides or standards. Summer
ASHRAE: Standard 62: Ventilation for Acceptable Indoor Air Quality. Summer: 31.9°C wet bulb, 34°C mean coincident dry bulb.
ASHRAE: Standard 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings. Used in the design of all outdoor air treatment plant
Sheet Metal and Air Conditioning Contractors’ National Association, Inc. (SMACNA): – SMACNA HVAC
Duct Construction Standards: Metal and Flexible. – SMACNA HVAC Air Duct Leakage Test Manual. –
SMACNA Fire, Smoke and Radiation Damper Installation Guide for HVAC Systems. – Seismic Restraint
Manual Guidelines for Mechanical Systems.
All applicable regulations and requirements of local utility companies having jurisdiction.
The design of HVAC system will be based on the following design criteria.
23 50
WORKSHOP
1.2.3 Indoor Design Conditions.
Indoor design conditions temperatures and relative humidity requirements shall be according to the
following table:
BOWLING AREA 23 50
INDOOR CINEMA 23 50
RELATIVE
DESIGN
HUMIDITY PRAYER HALL 23 50
FUNCTION TEMPERATURE
(SUMMER) HYPER MARKET 23 50
(SUMMER) 0C
%RH (±5%) FEC(FAMILY ENTERTAINMENT
(±1) 23 50
CENTER)
1.2.7 Ventilation
The minimum required fresh air supply has been based on ASHRAE requirements and has also considered
GSAS requirements:
45 10.2 19.8 Building external glazing type shall be chosen to conserve energy and to minimize the air
35 7.4 13.2 conditioning load.
25 4.8 8.6 External windows, low-e tinted double-glazed, with U = 1.8 W/M2.K & Shading coefficient of 0.25
shall be used in the HVAC cooling load calculation
1.2.9 Pipe Work
The pipe works sizing will be done in accordance with ASHRAE Handbook 1.2.11 Occupancy Basic Criteria
Fundamentals - Chapter 22 Pipe Sizing" along with recommendations of Carrier
Systems Design Manual, Part 3, Piping Design. Friction loss and velocities will be
generally as follows: The design will incorporate the occupancy as per Arch furniture layout or will be taken occupant density
from ASHRAE standard 62.1 Table 6.2.2.1.
Friction loss through pipe works shall not exceed 4 ft/100 ft. of equivalent pipe length.
1.2.12 Cooling & Heating Load
Water velocities will not exceed the following:
Air conditioning load is calculated using a computer program based on ASHRAE methods developed
by carrier for Engineering Consultants, the program is hourly analysis program (HAP 4.9), USA.
WATER VELOCITY Computer printouts indicate input design conditions used for cooling and heating load calculations and
SERVICE output showing individual room peak load, air quantities and zone and building block loads.
FPS
As AL ERKYAH is a part of a LUSAIL city, chilled water Generation System will be based on the district
Cooling system, which will be provided by MARAFEQ Building, will contain Energy Transfer Stations
1.2.10 Building Construction U values.
(ETS) located in basement -1 and the following are the main zoning.
The building will be serving by 2 NOS of ETS based on the operation
The following parameter of building construction u values which will considered and achieved in Arch.
Specification and final approved by GSAS specialist. 1- ETS with approximate capacity 3465 TR for serving the mall.
2- ETS with approximate capacity 4050 TR for serving residential towers and related spaces.
1. External Walls U value:
External wall shall be heavy construction, medium/light external colour, U-value not to exceed 0.30 The chilled water provided from MRAFEQ (primary side) to the main Energy Transfer Stations
W/M2.K. (ETS rooms) located in 1st basement
Chilled Water Supply Temperature: 5.0 oC
2. Roof U value:
Chilled Water Return Temperature: 14.0 oC
Roof shall be heavy-construction, medium colour, U-value not to exceed 0.25 W/M2.K.
Chilled water will be directly provided to Towers via (5 NOS including one standby) variable speed
secondary chilled water pumps connected to the heat exchangers in towers ETS Room located in
Basement 1, and serving apartment floors from second podium to tower Roof floor.
Chilled Water Supply Temperature: 6.2 oC
Chilled Water Return Temperature: 15.2 oC
B- Mall area
Chilled water will be directly provided to mall area (podiums retails) via (4 NOS including one standby)
variable speed secondary chilled water pumps connected to the heat exchangers in mall ETS Room
located in Basement 1, and serving mall floors from Basement 2 to second podium floor.
Chilled Water Supply Temperature: 6.2 oC
Chilled Water Return Temperature: 15.2 oC
Heat exchangers
1. Apartments(towers):
Apartment’s room shall be provided with dedicated 2 pipes concealed fan coil unit located
above room lobby.
100% filtered and tempered outside fresh air should be ducted directly into the Apartment
room and maintaining positive pressure.
Digital thermostat with 3 speeds located near to return air outlet.
Fan coil units shall be provided with PICV valve for cooling circuit with on/off position.
Centralized exhaust system for toilet and kitchens connected to energy recovery unit. Exhaust
air shall be not less than 30 L/s for toilet and 50 L/s for kitchen.
2. Mall area :
Public areas shall be air conditioned by total recirculate constant air volume air handling unit
and fresh air for this spaces will be supplied with treated fresh air handling units.
Individual temperature control for each public space shall be provided.
3. Computer Rooms:
Computer rooms shall be cooled by self-contained. These units shall be specifically designed
for this purpose and contain compressors, filters, humidifiers and controls. They shall be sized
to allow for a minimum of 50 % redundancy, either two units at 75 % load or three units at 50
%. Heat rejection from these self-contained units shall be by air-cooled condensers or chilled
water.
5. Hypermarket
Proposed AC system for Hypermarket will provide chilled water with a BTU meter and treated
Fresh air.
Proposed Hood exhaust and fresh air system for hypermarket will provide.( provide exhaust
hood duct with ecology unit)
Outdoor air quantities, pressurization relationship to adjacent areas and minimum total air change
rates will be computed in accordance with ASHRAE Standard 62.1 recommendations.
Fresh Air ventilation rates should be designed at 5% above ASHRAE 62.1 minimum requirements
As much as possible design of the ventilation system shall be such that it provides air movement
from clean to less clean areas.
The number of people should be based on normal occupancy or as per the furniture layout in
sitting areas as per ASHRAE 62.1.
1.4.1 Fresh and exhaust air system for apartments tower (A, B, C).
The fresh air will be centrally treated and tempered using Energy Recovery Units that will
filter and cool/heat air to specific requirement prior circulating to different air conditioned
zones. Energy Recovery Unit with heat wheel
Exhausted air from the toilets will be collected and passed to energy recovery units in 1.4.3 Toilets:
which the recovered energy will be used to pre-cool the fresh air. The thermal wheel
energy recovery units shall have 80% sensible heat efficiency, 60% latent heat efficiency
and these will amount to a maximum 70% total energy recovery from the exhausted air Toilets shall be provided with general exhaust systems at the rate 35 l/s per toilet for public toilets and
quantity. 30 l/s for Private toilet.
Exhaust from kitchens, kitchenettes and pantries shall be directly discharged to outside 1.4.4 Storage Area
the building by using Exhaust fans(one duty and one standby).
Garbage exhaust which is not permitted to mix with energy recovery will be directly Generally, storage rooms located adjacent to or within air-conditioned areas will be air-conditioned,
discharged using exhaust fans to outside the building. unless otherwise identified.
1.4.5 Kitchen
1.4.2 Fresh and exhaust air system For mall facilities Kitchens with cooking ranges, steam kettles, ovens and dishwashers shall be provided with
Dedicated filtered make-up air (uncooled) and exhaust hoods/exhaust systems in accordance with
(Hypermarket, cinema, FEC (family entertainment center), Kitchen, Shops, food and beverage …) NFPA Standard 96 and ASHRAE Applications Handbook. All components OF the ventilation system
shall be designed to operate in balance with each other, even under variable loads, to properly capture,
The fresh air will be centrally treated and tempered using fresh air handling unit(s) with contain, and remove the cooking effluent and heat, and maintain proper temperature and pressurization
heat pipes that will filter and cool/heat air to specific requirement prior circulating to control in the spaces in an efficient and economic manner. The operation of the kitchen exhaust
different air Conditioned zones.
systems shall not affect the pressure relation between the kitchen and surrounding spaces.
Kitchen exhaust will be filtered by ecology units then discharged to outside the building.
• Hoods shall be double skin Air curtain type to allowing the introduction of make-up fresh air to
Kitchen make up air will be provided to each hood using fresh air fans. Ensure minimum velocity in the hood surface for proper and effective exhaust.
All Fresh air handling units FAHU with heat pipes used for mall facilities provided by
landlord.
Hood exhaust air shall be sized as per ASHRAE standard 154 or as per hood
manufacturer
A ceiling hung fan coil and/or air handling shall be used for air conditioning.
For F&B Provision for Kitchen Exhaust & Fresh Air: Follow supplier requirements if not
available consider kitchen area to be 30% of F&B area, and exhaust flow rate 35l/s/m2,
and makeup air 90% of exhaust flow rate.
Jet fan shall be used instead of distributing duct which will give a high performance in air
movement and increase system efficiency.
The fans will be rated to operate at a temperature of 250°C for two hour and will be
connected to generator.
For any area exceed 1115 sqm will be provided with smoke ventilation, as per QCDD The staircases, smoke stop lobbies and fire fighting lobbies shall be pressurized to offer a
requirement a mechanical extract system will be provided to this area . Smoke will be evacuated tenable area for civil defines fire fighting and escape of the building.
via fire rated duct and fans to operate at a temperature 250°C for two hour located in mechanical
service floor The fans will be connected to the standby generator. The makeup air required for
this area will be thru opening doors to building outside. Each stair or fire fighting lobby will be pressurized by independent and separate fans.
Chilled water pipes will be schedule 40 black steel with appropriate elastomeric type insulation.
Chilled water pumps will be variable speed, horizontal split case or vertical type.
Air Handling Units will be double skin, draw through, central station with filter sections, cooling coil,
Fans, heat recovery unit (for 100% F.A) and sound attenuator on both supply and return.
Fan coil units will be provided with cooling coils only.
DRAINAGE SYSTEM
The drainage systems will be designed in accordance with the requirements of the following Minimum flow velocity 0.6 m/sec
2.3 Introduction
The buildings will be equipped with all necessary drainage installations of appropriate kind,
size and function.
The design criteria established for drainage systems is to ensure a high level of cleanliness,
hygiene and property within the building with systems designed for minimum maintenance,
efficient operation and reliability.
Estimated flow rate for drainage system will be calculated based on BS-EN-12056-2:2000
according to usage of appliances and system type
Horizontal sloped pipe for specific size shall be calculated according to manning equation
as the following:
Where:
Q = Quantity rate of flow in cubic feet per second (cfs)
A = Cross-sectional area of flow (ft2)
n = Coefficient representing roughness of pipe surface, degree of fouling and pipe diameter
R = Hydraulic radius (hydraulic mean depth of flow) (ft.)
A Double stack for soil (toilets, bidets & urinals) and waste (lavatories, showers, floor drain, Gray wastewater shall be provided in this project to collect the wastewater generated
service sink….etc.) with vent piping to prevent pressure fluctuation shall be provided to the from Showers, Lavatory, baths and floor drains, then to be discharged and gathered in
project as follows: gray water tank.
Vent piping, where called by codes, is provided to protect the system against loss of the trap Gray water tank shall be calculated based on 85% of total daily potable water demand and
seal. will be sufficient for one day storage.
All green area above building structure will be drained through planter drain and discharged Gray water tank over flow will be pumped and connected to external sewage network.
into the storm water tank.
Commercial Podiums:
All piping, fittings and pipe risers will be located in service shafts, which will be accommodated
Waste water pipes and stacks from commercial podiums will be collected into the Gray water
in the layout in view of easy accessibility and maintenance. All shafts will be provided with
tank to be treated, transfer to non-potable water tank and re-use it in the water closet (WC)
access doors/hatch.
flushing. Gray water tank has capacity 130 m³ enough for one day storage.
Drainage pipes, stacks…will be accommodated and suspended at the basement floor to gray
Residential Towers:
wastewater, storm water tanks and foul water sewage network.
Waste water pipes and stacks from residential towers will be collected into the Gray water
Clean out will be provided in every change of direction in the suspended pipes to ensure
tank to be treated, transfer to non-potable water tank and re-use it in the water closet (WC)
proper cleaning and maintenance of the system.
flushing & irrigation system with capacity 350 m³ enough for one day storage.
Inspection chambers/manhole shall be provided in every change of direction of the buried
piping system and in lower basement floor to minimize the cause and effect of any
consequential damage due to pipe clogging and to ensure accessibility for inspection and 2.6.4 Kitchen Drainage
maintenance.
A single kitchen waste stack for kitchens and F&B areas with vent piping to prevent
pressure fluctuation shall be provided to the project as follows:
2.6.2 Foul Sewage Drainage Commercial Podiums:
Foul sewage effluents produced through WC’s flushing will be collected through soil stacks A separate kitchen drainage pipes and stakes for commercial podiums (Service, Podium1
and pipes to be discharged in the external sewage networks. and ground floors) will be collected and connected directly to external sewage network
through separate grease interceptors located in reasonable area to facilitate inspection and
Commercial Podiums: maintenance.
A separate soil drainage pipes and stakes for commercial podiums will be connected
directly to external sewage network. Residential Towers:
A separate kitchen drainage pipes and stakes for residential Towers apartments and
Residential Towers:
podium-2 level will be collected and connected directly to external sewage network through
A separate soil drainage pipes and stakes for commercial podiums will be connected separate grease interceptors located in reasonable area to facilitate inspection and
directly to external sewage network. maintenance.
All sanitary fixtures and drains under road level will be drained to dedicated sump pits and
pumped as the following.
- Toilets drainage will be collected to sewage sump pits and pumped into external sewage
network through slow down chamber.
- All lift pit and pump rooms will be collected to sump pits and pumped into storm water tank
as per ASHGHAL requirement.
Minimum two submersible pumps will be provided as one duty + one standby each 100% of
the load and both working together in case of emergency.
Sum pit minimum effective volume will be calculated according to the equation below
Where:
Pump flow-rate [l/s]
Vh: necessary, minimum accumulated volume between start and stop.
Zmax: maximum number of starts per hour and should be specified by the
pump or motor manufacture.
Commercial Podiums:
A separate condensate drainage pipes and stakes for commercial podiums will be collected
into non-potable water tank.
Residential Towers:
A separate group of stacks will collect from residential towers apartments and podium-2
condensate (a/c condensate) drainage pipes. They will be independent of any drainage and
waste system and will be accommodated to non-potable water tank
TANK 1 TANK 2
CASE(1) As Per ASHGHAL (Vol. 8) CASE(1) As Per ASHGHAL (Vol. 8)
Total Project Area (m2) = 22494 Total Project Area (m2) = 19979
Total Project Area (ha) = 2.25 Total Project Area (ha) = 2.00
Storm water Storage Requirements (m3/ha) = 390 Storm water Storage Requirements (m3/ha) = 390
Requird total Storm water storage (m3) = 877.3 Requird total Storm water storage (m3) = 779.2
3.1 Codes and Regulations The sizing of water supply piping will be based on the demand weight of fixtures units
(WFU) in accordance with (IPC) Tables E103.3(2) & E103.3(3)
The water supply systems will be designed in accordance with the requirements of the
following codes and local regulation:
- Qatar General Electricity & Water Corporation KAHRAMAA,
- International Plumbing Code IPC,
- Uniform Plumbing Code UPC,
- National Plumbing Code Handbook,
- American Water Works Association,
- American Society of Plumbing Engineers,
3.2.2 The water supply system will be designed to maintain the following maximum design
flow velocity.
Maximum Design Flow Velocity (m/s)
Mains 2.4
Riser 2.0
Branche 1.5
s
OWNER / DEVELOPER: LEAD CONSULTANT:
189
OWNER / DEVELOPER: LEAD CONSULTANT:
190
3.3 Potable Cold Water System Description
3.3.1 General
The building will be supplied with fresh water from the municipality potable water Tower-A
network tie-in points through main water meters located at the plot boundary.
Two elevated potable water tanks will be provided for tower A, to supply the tower wet areas
The Water supply system shall be provided to the project as follows: as per following:
- Tower floors from roof until 10th floor through pressure boosting pumps with variable
Commercial Podiums: frequency motor set.
Main concrete potable water tank will be provided with capacity sufficient for 2 days of water - Tower floors from 9th floor until 1st floor through gravity line.
demand. The tank will be located on 2nd basement floor.
Pressure reducing valve PRV will be provided before sub meters to maintain the pressure less
Main potable water tank capacity will be approximately 310 m³. than or equal 3 bar for water meters accuracy.
The main potable water tank will be supplied the elevated water tanks through lifting pumps A dedicated water meters room in each floor level of the tower to serve each
as the following: apartment.
- Elevated water tanks will be adequately sized for water storage for a minimum period Tower-B
of 1 day.
Two elevated potable water tank will be provided for tower B, to supply the tower wet areas
as per following:
Residential Towers: - Tower floors from roof until 10th floor through pressure boosting pumps with variable
frequency motor set.
Main concrete potable water tank will be provided with capacity sufficient for 2 days of water
demand. The tank will be located on 2nd basement floor. - Tower floors from 9th floor until podium-2 floor through gravity line.
Main potable water tank capacity will be approximately 810 m³. Pressure reducing valve PRV will be provided before sub meters to maintain the pressure less
than or equal 3 bar for water meters accuracy.
The main potable water tank will be supplied the elevated water tanks through lifting pumps
as the following: A dedicated water meters room in each floor level of the tower to serve each apartment
Elevated water tanks will be adequately sized for water storage for a minimum period of 1
day.
A constant speed transfer pumps set will be provided at main water tank pump room to fill the
elevated water tanks from main potable water tank at 2nd basement within 8 hours.
Two elevated potable water tank will be provided for tower C, to supply the tower wet areas 3.5 Water Hammer Arrestors
as per following:
Water hammer arrestors are required to prevent the effect of water hammering.
- Tower floors from roof until 10th floor through pressure boosting pumps with variable
frequency motor set. Water hummer arrestor will be provided between the quick shut-off valve or faucet and
the incoming water supply.
- Tower floors from 9th floor until 1st floor through gravity line.
Pressure reducing valve PRV will be provided before sub meters to maintain the
pressure less than or equal 3 bar for water meters accuracy. 3.6 Automatic Air Vent
A dedicated water meters room in each floor level of the tower to serve each apartment Automatic air vents will be provided for each water supply riser to prevent air binding
during filling operation and allow the continual release of air during normal operation.
Multimedia filters will be provided on the feeding line at each elevated water tank to filter
the domestic water from any particles or impurities can effect on the people health.
Non-potable water system shall be provided to this project and it shall be subjected to GSAS - Flow Equalization
assessment. - Settling
The non-potable water system can be described as the treated gray wastewater to - Chlorination
produce water which can be used for irrigation and W/C flushing as well.
- Filtration
Gray water treatment plant will be provided to treat gray wastewater which collected
from wash basins, floor drains, bathtubs and showers. 3.8.3 Flow Equalization
Waste water will be collected in grey water tank and then is drawn by grey water feed The tank which receives raw grey wastewater generated from bathtubs, showers and
pump then treatment process is applied through the grey water treatment plant. And wash basins in the Raw Grey Water Collection Tank.
After treatment, the water will be stored in non-potable water tank. The Raw grey waste water is collected to dampen the variation in hydraulic & organic
load. Odor control dosing is given in to it to prevent the smell.
The wastewater is kept in Agitated condition to avoid settling of suspended solids along
with acid dosing to maintain the pH Value. Air is injected through submersible aerators in
the aeration tank.
Sodium hypochlorite solution is dosed in the chlorine contact tank then to the Final
settling tank. The aerated / settled grey wastewater is pumped into the media / carbon
Filters via the Filter Feed/ back wash Pumps. Level switches actuate the pumps.
3.8.4 Coagulant Dosing
Coagulant dosing system is considered as, in order to form the better flocs, which can be
easily separated in the Media filters. This improves the efficiency of media filters in
removal of suspended impurities
3.8.5 Automatic Multimedia Filter
The filtered water then passes through the Multimedia Filter before passing through
Activated Carbon Filter. As solids accumulate in the sand bed the pressure loss through
the Media rises & periodically reaches a value above which the plant will not further as
Designed. At this time the filter needs to be backwashed clear of accumulated solids. The
Media is backwashed by controlled flow of tertiary waste water delivered from the Treated
Grey Waste Water Tank by using the back wash pumps. The backwash water is sent to
the Drain.
3.8.6 Automatic Activated Carbon Filter
The effluent of the Multimedia Filter then passes through a bed of Activated Carbon.
The Porous carbon media having large surface area helps in absorption of dissolved
organic Matter on the surface
Provision is made for backwashing of filter media to limit head loss build up due to
Accumulation of suspended solids. The backwash water is sent to the drain.
The non-potable water tank will be supplied from the following: Hot water supply will be at temperature of 60⁰C
- Treated gray water through treatment unit.
- Makeup line from municipality potable water network through irrigation water meter. Individual hot water heaters will be provided for Pool & GYM toilets at podium-2 level,
Branch Lines (lines that run from the recirculation loop to the fixture) will be the shortest
- HVAC unit’s condensate drainage. possible length from the recirculation loop to the fixture outlet with a maximum distance
The main non-potable water tank will supply the elevated non-potable water tanks through of 15 meters.
lifting pumps.
Balancing valves shall be provided for all hot water circulating line.
Elevated non potable water tanks will be adequately sized for water storage for a minimum
period of one day located at roof floors for each residential towers
3-BR 52 4 1 1 1 1 1 4 - 52 208 -
3-BR( DUPLEX) 2 4 1 1 1 1 1 4 - 2 8 -
Two water tube gas type boilers will be provided for the building, each boiler will be
sufficient for 75% of total heating load.
A Group of calorifiers at roof level will be provided to supply each residential tower.
The hot water storage tanks (Calorifiers) will be heated via hot water boilers located at roof
floor for each tower.
Pressure zoning by using a separate hot water calorifiers for group of floors and PRVs will
be provided to maintain the pressure less than or equal 4.5 bar at any point in the system
Hot water will be circulated at minimum temperatures 50°C to prevent the colonization of
Legionella bacteria.
Valves will be installed for each feeding and return pipe. Control valves are wedge-gate
type and constructed so that they could be repacked while open and under pressure.
Hot water calorifiers will be equipped with positive means of safety devices (pressure
release valve which shall be connected to the nearest drain point) that guard the system
against dangers of excessive pressure and temperature.
The following table per ASHRAE shall be used to determine hot water demand:
Boiler
No. of UNITS Thermal Power - Each (KW) Total Gas consumption (m3/hr)
2 1024 178
Residential Towers:
Separate non-potable water meter shall be provided for each apartment.
Non-potable water meters shall be located at the same potable water meter rooms or at
the entrance of each apartment and shall be connected to building billing system.
Residential Towers:
Separate Hot water meter shall be provided for each apartment in case of using central hot
water system by gas boilers.
Hot water meters shall be located at the same potable water meter rooms or at the
entrance of each apartment and shall be connected to building billing system.
3.12.1 System Description • Design capacity of the main drain line shall be 100% of the pumps flow rates.
Landscape green areas will be provided with automatically controlled irrigation system. • Main drain pipe sizing shall be based on the min. velocity of 0.75 m/s and design
It will be divided into zones in order to irrigate the whole site in one day. velocity of 1.25 m/s.
The system will be provided with booster pumps, central controller, solenoid valves, 3.13.5 Main drain points:
sprinkles, bubblers, emitters and miscellaneous appurtenances for a complete
automatic operation network • Design capacity of the main drain points shall be 100% of the pumps flow rates.
Non-potable water tank will be the water source for the irrigation system. • The velocity through the main drain points shall not exceed 0.305 m/s
3.12.2 Piping Material • Drain points shall be spaced max. 9.2 m apart and max 4.6m from wall.
Material will be UPVC pressure pipes to BS 3505:1986, Class “E” and fittings will be
solvent welded to BS 4346, the lock ring type. 3.13.6 Vacuum cleaning points:
• Inlet network pipe sizing shall be based on the Velocity of 1.5 m/s.
• Design capacity of the main gutter line shall be 100% of the pumps flow rates.
• Outlet network pipe sizing shall be based on the min. velocity of 0.75 m/s and design
velocity of 1.25 m/s.
The size and shape of a pool can be determined by the fountain effects or, the fountain
effect may be designed to fit the pool. Water depth should be no more than 300mm to
avoid the water feature to be classified as a swimming pool with all the requisite fencing
legislation
It is a general rule of thumb that the water feature effect height is the equivalent of half
of the radius of the pool. Some jets require a non-turbulent water supply in order to work
properly. Others require wave suppression when installed in circular pools in order to
prevent wave amplification
Pumps for water features are selected based on water and pressure requirements for
the combined fountain effects. Submersible pumps or dry pumps are available for use on
fountains. Dry pumps should be equipped with suction strainers.
Overflow drains can remove excess water brought on by rainfall or accidental overfilling
of the fountain. Overflow drains have two functions; they provide a means for removing
water in case water makeup should malfunction and they provide a means for removing
storm water. The preferable location for an overflow drain is in the wall of the pool where
it can be hidden. All overflow drains are designed to prevent large debris from clogging
the drain pipe.
Estimated No. of
Estimated No. of Occupants: Water consumption
Occupants
Commercial (No. of Occupants)-Staff 1896 60 / stuff
Commercial (No. of Occupants)-Visitor 5686 20 / visitor
Residential (No. of Occupants) 1850 300 / person
Podium 2 (No. of Occupants)-Staff 389 60 / stuff
Podium 2 (No. of Occupants)-Visitor 1168 20 / visitor
Estimated potable and non-potable water demand will be calculated based on the
following:
m3 / day 601.7
Estimated potable and non-potable water demand will be calculated based on the
following
Total Non-Potable Water Tank =Non-potable water requirement application A (2 Days Storage)+ Irrigation water requirement((1 Day Storage))
COMMERCIAL PODIUMS
Mall Lobby - - - - - - -
Shops - - - - - - -
Administration Offices - - - - - - -
Hypermarket √ - √ - √ - √
Garbage Rooms √ - - - √ - -
Public Toilets √ √ √ - √ √ -
Spa √ √ √ √ √ √ √
Male Gym √ √ √ √ √ √ √
Female Gym √ √ √ √ √ √ √
CAFÉ √ - √ - √ - √
PANTRY √ - √ - √ - -
Mechanical room √ - - - √ - -
Pump room √ - - - √ - -
WORKSHOP - - - - - - -
Food Court - - - - - - -
Bowling - - - - - - -
Cinema √ √ √ - √ √ -
Dinning √ - √ - √ - √
Corridors - - - - - - -
Service - - - - - - -
ELEC ROOM - - - - - - -
IDF ROOM - - - - - - -
TELECOM ROOM - - - - - - -
GSM ROOM - - - - - - -
CCTV ROOM - - - - - - -
PRAYER ROOM - - - - - - -
ANCHOR STORE - - - - - - -
STORE - - - - - - -
RESIDENTAIL TOWERS
Tower A apartments from (1-12)Floor √ √ √ √ √ √ √
4.2 General Description All normal usage areas (except Transformer, Wet sprinkler system
Electrical, & TEL rooms, etc.).
The fire protection system will be designed in accordance with the National Fire
Protection Association NFPA and the local fire safety code and will mainly consider the All normal usage areas. Wet riser system supplying water to the
following: various landing valves and hose reels.
The project is overall classified as Ordinary Hazard for basement and mechanical floors,
extra hazard for fire pump room and light hazard for the rest as per NFPA regulations. All normal usage areas. Fire hose cabinets complete with hose reel,
The whole project is protected by water suppression system include fire hose cabinet, fire extinguisher and landing valve.
sprinkler system in addition to the fire extinguishers where required.
All normal usage areas. Portable fire extinguishers, dry powder as
System shall be hydraulically sized using software “Fire Elite” for most remote area and per specific area requirements.
most demand.
A total flooding system shall also be used where needed. An adequate water reserve is GSM & Telecom rooms FM-200
provided to feed the system.
Generator and fuel rooms. Foam System.
Siamese connection will be providing and coordinated with local civil defence
department.
Sub-station rooms. Aerosol
Four way Connections will be provided as per NFPA14 requirements
Electrical rooms more than 5.1m2 Automatic Sprinkler System
The wet sprinkler system shall be designed based on the following data:
4.5.1 General
Wet sprinkler system protection will be provided throughout the building in all normal
usage areas.
The system is designed in accordance with NFPA-13, "Wet Type" with sprinklers zones
controlled by multiple main valves. The sprinkler heads will be of the correct type and
temperature rating for each location and will be provided. Where required with metal
guards to prevent accidental damage.
Concealed type sprinklers to be used in all area with false ceiling to maintain an
ecstatic interior look.
Multiple sprinkler types are used in the project, depending on protected area, and raging
form exposed, pendent, upright, Wall hung extended coverage and decorative sprinklers.
One Jockey pump will be provided to pressurize the sprinkler system serving the
building. Main fire and Jockey pump will be located in the main plant room close to the
storage water tank in the first basement.
The water demand for fire protection in the building will be calculated hydraulically and
4.6.1 General the storage tank will be sized based on 1st fire scenario (Fire Pump Room Sprinklers) for
90 minutes’ storage.
The standpipe system comprises of a Wet Class I, II & III installation as defined in NFPA
14. Fire pumps will be sized to provide 6.9 bars at the farthest landing valve. The pump in
will be sufficient to deliver 1000 gpm.
The standpipes provide water for the sprinkler installation at each floor level and will also
serve hose reels and landing valves for building, Occupant use No part of the buildings System will be designed to have a max of 12.1 bar pressure at any branch serving a
will be farther than 30 m from a hose reel and 38 m from landing valve. sprinkler system.
- float switches, • Fire Hose Stations will be selected to cover all areas using 30 meters’ length and
25 mm diameter hose
- Control valves,
• Fire Hose Cabinets class III and landing valves Ø63 mm (2 1/2'') (Dry / Wet) shall
- Drain and test valves, Etc. be located in order of priority according to QCDD requirements for fire brigade
usage:
4.6.3 Class I and Class III Systems.
1- Within a fire-fighting lobby.
For Class I and Class III systems, the minimum flow rate for the hydraulically most
remote standpipe shall be 500 gpm (1893 L/min), through the two most remote 21⁄2 in. 2- In a smoke-stop lobby or common lobby in close proximity to the exit staircase.
(65 mm) outlets. The minimum flow rate for additional standpipes shall be 500 gpm (1893
L/min) 3- Where firefighting lobby, smoke-stop lobby are not provided, landing valve to be
located in each exit stairway.
For the second standpipe and 250 gpm
(946 L/min) for the third standpipe per
standpipe for buildings with floor areas
that exceed 80,000 ft2 (7432 m2) per floor.
Siamese connection are installed at a convenient height from finished side walk level The automatic clean agent system shall include the following:
and shall be chrome plated extra heavy cast brass complete with the following:
• Agent cylinders with electrical or pressure operated valves
- 6" x 2 1/2" x 2 1/2" x 2 1/2" x 2 1/2" (150x65x65x65x65 mm) Siamese connection with
drain cock and check valves to suit local practice. • Flexible hose
- All chains, caps and screws used for fixing. • Discharge header
- Recessed wall box housing the Siamese connection with wired glass door marked in • Piping network including pipes, fittings and supports.
red from inside: "FIRE BRIGADE CONNECTION" in both English and Arabic.
• Discharge nozzles
4.7 Clean Agent Fire Extinguishing Systems • Supervisory pressure switch
The systems shall consist of agent storage cylinders permanently connected to fix piping • Abort switch
by sectional valves to reduce cost of the system, with fixed nozzles arranged to discharge
the suppression agent within the protected room. The systems shall be designed for • Heat and smoke detectors
automatic operation using suitable detectors and for manual operation using a manual
• Electronic sounder
pull station fixed at each room exit. Walls surrounding protected areas shall be extended
full height. • Control panel (release panel)
The system shall utilize the FM-200 as the clean extinguishing agent. The system shall • Necessary wiring
be designed as per the requirements of NFPA 2001.
• Sectional Valves
Each system shall consist of main and reserve cylinders, nozzles, control system and
piping network of galvanized seamless steel schedule 40.
4.7.3 Design Criteria
In a major project. This system does not cause any damage to equipment in all areas
mentioned above; it deploys quickly and cleanly and won't leave behind oily residue, The clean agent systems shall be designed based on the total flooding method with a
particulate, or water. minimum concentration of 7%.
FM-200 fire suppressant is safe when used where people are present.
Foam deluge and foam sprinkler systems are utilized to protect specialist risks involving
the storage and handling of flammable and combustible liquids.
Type of Foam Concentrate Application Rate
Areas to including generator and fuel room firefighting foams suppress fire by forming a
blanket across the surface of the liquid fuel and separating it from the air (oxygen) that it AFFF 0.1 gpm/ft2 (4.1 lpm/m2)
needs to burn.
In addition to smothering the fire the foam blanket also cools the fuel and suppresses the Fluoroprotein 0.16 gpm/ft2 (6.5 lpm/m2)
release of flammable vapors Foam system shall be designed as per (NFPA) 16 –
Standard for Low, Medium and High Expansion Foam.
Protein 0.20 pm/ft2 (8.1 lpm/m2)
A low expansion foam firefighting system shall be installed for generator room which will
be used is a fixed proportioning system permanently piped to monitors of fixed spray
nozzles strategically located around the landing pad.
All-purpose dry powder extinguishers are provided. The dry powder will be all purpose
type able to extinguish electrical, paper, wood and textile type fires.
Positioning of the extinguishers is important and care will be taken to ensure that a
person intending to use an extinguisher will not be brought into a "dead-end" situation
where escape from a fire would be difficult. The extinguishers will be located on or close
to escape routes. Generally, the dry powder extinguishers will be located within hose reel
recesses to make a complete fire-fighting package.
All extinguishers will have the operating instructions prominently displayed on the
extinguisher body in English and Arabic.
Aerosol has been certified as having Zero Ozone Depleting Potential (ODP) & Zero
Global Warming Potential (GWP). It is officially listed by the US Environmental Protection
The extinguishers will contain approximately 6 kg (13 lb.) weight of Authority under its Halon replacement ‘Significant New Alternatives Program’ (SNAP).
all-purpose dry powder, will have a discharge time of approximately
10 seconds and will have a discharge jet with a range of Aerosol system shall be used in electrical rooms, control rooms and all relevant areas.
approximately 6m.
The fire extinguishers are distributed thru out the building to provide
a maximum walking distance of 77ft form any locations as per NFPA-
10.
The system will be design and installed as per NFPA and specialist recommendation.
Fire extinguishers will be wall mounted, 4.5 kg dry chemical, where required.
Fire hose cabinets will be provided with swinging type, 25mm diameter, and 30m length
hose.
Fire pumps and equipment shall be approved by factory manual research (FM) and
underwriter
(SNG) SYSTEM
Emergency switch, and domestic gas leak Gas regulator in the building shall be able to
Provision shall be made to incorporate means of controlling the gas flow within the be operated with
building gas piping system including isolation of damaged facilities or components.
75mbar incoming pressure from the main Pressure Reducing and Metering Station.
The gas supply source pressure considered in the design shall be determined based on Detection system as minimum.
the upstream design conditions. System shall be designed to supply a forecast hourly
peak demand 5.7.2 System Components
The load that shall be applied during design shall be diversified. Considerations in Pressure reducing and metering station,
determining the load diversity shall include the nature of the facility being designed, the
type of load and the number of consumers. Gas box units,
Designs shall minimize the types and size range of materials and use only material items Gas regulators,
for which approved Material Specifications exist.
Gas hoses,
All materials shall be suitable for local climatic conditions.
Solenoid valves,
All materials, assemblies and installations shall ensure correct functionality and full
operability taking into accounts the ambient conditions of the location. Gas leak detectors,
All piping and fittings as well as other components and accessories shall be suitable for Under/over pressure shutoff device.
both NG usages.
All gas shafts within a building preferred to be dedicated for gas with a minimum size
suitable for accessing the shaft for maintenance purposes.
5.8 Outline Specification
5.7 Building Installation Pipework Pipe fittings and component shall be designed and installed in accordance with relevant
standards.
5.7.1 General
Material shall have the physical properties suitable to the proposed duty considering all
Specialist designer shall ensure the gas pipes service to the plot is accurate. surrounding forces, operating temperature and pressure.
Customer Installation Pipework extends from the outlet valve of the Pressure Reducing Steel pipe:
& Metering Station
Carbon steel or wrought iron pipe shall be at least of Schedule 40 Grade B.
(Customer Primary Meter) to the consumer appliances.
Copper:
At the initial stages of building design and planning the specialist designer/Installer needs
to ensure that the Copper tube install in the building (inside kitchen only) shall be rigid type.
Customer Internal Piping connected to the meter outlet valve are adequately designed Annealed-Temper or Drawn-Temper Copper Tube
in order to provide a
Polyethylene:
safe supply of gas to the point of use. Residential and unit apartment pipe work in the
kitchen shall be installed PE pipe shall be for buried used only.
with shutoff valve, solenoid valve, low pressure regulator with UPSO, auto-shutoff valve, PE pipe must not be used within building, for entry or exit sit shall be sleeved with special
requirement.
MECHNICAL ROOMS -
HYPER MARKET √
F&B √
CAFÉ √
PUMP ROOM -
GENERATOR ROOM -
PUBLIC TOILET -
JANITOR -
SPA -
GYM -
SWIMMING POOL TOILET -
GARBAGE ROOMS -
RESIDETAIL APARTMENT √
MV
N=408500.663 Missing
HA3 25483 HA4 HA-2(21023)&R-13(21021) E= 227493.482
N=408463.185 E= 227506.040
HA-4 21022 A170 HA-3 TOP LEV = 5.610
TEL
N= 408569.957 E= 227441.642
END PIPE NSC-1/HC-1
N= 408577.742 E= 227483.480
N= 408569.955 E= 227480.274
END PIPE HA-2
N= 408522.408 E= 227490.383
HVAC
(END CAP) CONNECTION TO PLOT HA1 N 408546.474 E 227359.684 TOP LEV = 4.047 Missing
(END CAP) CONNECTION TO PLOT HA2 N 408531.984 E 227488.411 TOP LEV = 5.204 Ø 200mm
(END CAP) CONNECTION TO PLOT HA3 N 408519.437 E 227491.096 TOP LEV = 5.204 Missing
(END CAP) CONNECTION TO PLOT HA3 N 408496.729 E 227496.036 TOP LEV = 5.498 Missing
(END CAP) CONNECTION TO PLOT HA4 N 408458.675 E 227504.349 TOP LEV = 5.280 Missing
FS
ST
GAS NETWORK
GAS TIE IN NO. TIE IN COORDINATES ELEVATION
LOW (END CAP) CONNECTION TO PLOT H-1/HA-1 N= 408523.026 E= 227281.045 TOP LEV = 4.858
N= 408546.112 E= 227365.860 TOP LEV = 5.116
LOW (END CAP) CONNECTION TO PLOT NSC-1-HC-1 N= 408562.720 E= 227424.649 TOP LEV = 5.298
LOW (END CAP) CONNECTION TO HA-2 N= 408524.795 E= 227487.764 TOP LEV = 5.290
LOW (END CAP) CONNECTION TO HA-3 N= 408491.526 E= 227494.837 TOP LEV = 5.693
LOW (END CAP) CONNECTION TO HA-4 N= 408452.517 E= 227505.090 TOP LEV = 5.475
Av. Foul
Cooling Av. Potable
PWC Sewer
S.No Plot GFA (m2) Demand GAS (KWh) water
(Kg/day) Generated
(TR) demand (L/S)
(L/S)
HA-2(21023)&R-
HA3 25483 HA4 13(21021) 1167.49 875.43
HA-4 21022 A170 HA-3 1056.72 792.38
49,760 120,329 13039.7 9502.33
Utility Required
Existing Pipe Required Pipe
allocation People 2-days Storage Volume (L) Avg. Flow
Size (mm) Size (mm)
(Ave. l/s) (Avg. l/s)
Assumptions
1. Based on 300 L/person/day for Residential and 60 L/person/day for commercial
2. Based on 8 hour refill of one day storage volume
Not Used
Assumptions
1. The average flowrate is based on a 10 hour working day.
2. Based on 1:100 pipe fall
GAS NETWORK
GAS TIE IN NO. TIE IN COORDINATES
LOW (END CAP) CONNECTION TO PLOT H-1/HA-1 Not Used
Used
LOW (END CAP) CONNECTION TO PLOT NSC-1-HC-1 Used
LOW (END CAP) CONNECTION TO HA-2 Used
LOW (END CAP) CONNECTION TO HA-3 Used
LOW (END CAP) CONNECTION TO HA-4 Used (In Case of Central Heating Boiler)