Version: V100R002
Report No: SYBH (A)074112010
TEST REPORT
IEC 60950-1: 2005 (2nd Edition) and/or EN 60950-1:2006
Safety of information technology equipment
Report reference No......................... : SYBH(A)074112010
Compiled by
Maggie Zhang
(printed name and signature) .......... :
...........................
Reviewed by
Kelvin Shi
(printed name and signature) .......... :
......................
Approved by
Zhang Guoqing
(printed name and signature) .......... :
.................
st
nd
Serial number :
Report No.:
SYBH(A)074112010
N/A
Page 1 of 49
Summary of testing:
Tests performed (name of test and test clause):
The submitted samples were found to comply with the requirements of:
IEC 60950-1:2005 (2nd Edition) and/or
EN 60950-1:2006 + A11:2009
Report No.:
SYBH(A)074112010
Page 2 of 49
Report No.:
SYBH(A)074112010
Page 3 of 49
Report No.:
SYBH(A)074112010
Page 4 of 49
Report No.:
SYBH(A)074112010
Page 5 of 49
VDC;
For HX04-22DH heat exchanger: 38 VDC58VDC;
For direct cooling fan: 30 VDC-56 VDC;
For TEC: 38.4 VDC-57.6 VDC
Tested for IT power systems ....................................
N/A :
IT testing, phase-phase voltage (V) .........................
N/A :
Class of equipment ...................................................
Class:I
Considered current rating (A) ...................................
Refer: to general product information
Pollution degree (PD) ...............................................
For IP55
: cabinets, pollution degree is PD 2
For IP34 cabinets, pollution degree is PD 3
IP protection class ....................................................
Refer: to general product information
Altitude during operation (m) ....................................
4000m
:
Altitude of test laboratory (m) ...................................
500m
:
Mass of equipment (kg) ............................................
Refer: to general product information
Maximum operation ambient
40C
temperature(C) ......................................................... :
Possible test case verdicts:
- test case does not apply to the test object .................
N/A :
- test object does meet the requirement .......................
P (Pass)
:
- test object does not meet the requirement .................
F (Fail):
Testing .......................................................................... :
Date of receipt of test item ............................................
2010-11-20
:
Date(s) of performance of tests ....................................
2010-11-20
:
to 2010-11-23
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing
laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Note: This TRF includes EN Group Differences together with National Differences and Special
National Conditions, if any. All Differences are located in the Appendix to the main body of
this TRF.
Throughout this report a comma is used as the decimal separator.
Report No.:
SYBH(A)074112010
Page 6 of 49
Model name
Rating
IPXX
MassKg
Inside equipment
ITS1000M-FMS11-G1002
48VDC; 3.1A
IP55
204
HX02
ITS1000M-FMS11-G1006
48VDC; 9.5A
IP55
231
HX04(ETSI)
ITS1000M-FMS11-G1009
48VDC; 9.5A
IP55
251
HX04(BTS)
ITS1000M-FMS11-G1013
48VDC; 9.5A
IP34
251
HX04+Fan
ITS1000M-FMS11-G1003
48VDC; 1.0A
IP34
194
Fan
ITS1000M-FMS11-H1002
48VDC; 7.9A
IP55
200
TEC
ITS1000M-FMS12-G1002
48VDC; 4.1A
IP34
228
HX02+Fan
ITS1000M-FMS12-G1001
48VDC; 11A
IP55
233
HX02+TEC
ITS1000M-FMS23-G1001
48VDC; 11A
IP34
446
HX04+HX02+Fan
10
ITS1000M-FMS23-G1002
48VDC; 20.5A
IP55
454
HX04+HX02+TEC
11
ITS1000M-FMS33-G1009
48VDC; 13.6A
IP34
602
HX04+HX02+Fan
12
ITS1000M-FMS33-G1010
48VDC; 20.5A
IP55
610
HX04+HX02+TEC
13
ITS1000M-FMS11-G1016
48VDC; 3.1A
IP55
195
HX021.6m
14
ITS1000M-FMS11-G1017
48VDC; 7.9A
IP55
190
TEC1.6m
HX02 is short for HX02-22DH heat exchanger; HX04 is short for HX04-22DH heat
exchanger; Fan is short for direct cooling fan; TEC is short for Air condition
2. For IP34 cabinets, only PD 3 equipment can be put inside.
3. The maximum operation temperature is 40 C
4. The equipment is intended to be operated at altitude up to 4000 m.
5. EUT is supposed to be recognized certified. Other tests such as heating test should be
considered in the final system.
6. There are five single configured doors: HX02 Cabinet, HX04 Cabinet, TEC Cabinet, Direct
Cooling Cabinet, and Nature Cooling Cabinet. Tests performed on these five configurations were
considered to be representative of combination configurations of these five single one.
Report No.:
SYBH(A)074112010
Page 7 of 49
Report No.:
SYBH(A)074112010
Page 8 of 49
Requirement + Test
GENERAL
Pass
1.5
Components
Pass
1.5.1
General
Pass
Pass
1.5.2
Pass
1.5.3
Thermal controls
See 1.5.1.
Pass
1.5.4
Transformers
Pass
1.5.5
Interconnecting cables
No such components.
N/A
1.5.6
No such components.
N/A
1.5.7
1.5.7.1
Only functional.
Pass
1.5.7.2
No resistors bridging
double or reinforced
insulation.
N/A
1.5.7.3
No such component.
N/A
1.5.8
N/A
1.5.9
Surge suppressors
No such component.
N/A
1.5.9.1
General
N/A
1.5.9.2
Protection of VDRs
N/A
1.5.9.3
N/A
1.5.9.4
N/A
1.5.9.5
N/A
1.6
Power interface
Pass
1.6.1
N/A
1.6.2
Input current
Pass
1.6.3
N/A
1.6.4
Neutral conductor
N/A
Report No.:
SYBH(A)074112010
Result - Remark
Verdict
Pass
Page 9 of 49
Requirement + Test
Result - Remark
1.7
1.7.1
Power rating
Verdict
Pass
The required marking is
located on the inside
surface of the door.
Pass
Pass
Pass
used
N/A
Pass
Pass
Pass
N/A
1.7.2
Pass
1.7.2.1
General
Pass
1.7.2.2
Disconnect devices
1.7.2.3
1.7.2.4
1.7.2.5
Pass
1.7.2.6
Ozone
N/A
1.7.3
N/A
1.7.4
No voltage selector.
N/A
Pass
Pass
Pass
N/A
N/A
1.7.5
No such outlets
N/A
1.7.6
Pass
Report No.:
SYBH(A)074112010
Page 10 of 49
Requirement + Test
Result - Remark
1.7.7
Wiring terminals
Refer below:
Pass
1.7.7.1
Protective earthing
indicated by the symbol
60417-5019
Pass
1.7.7.2
1.7.7.3
Pass
1.7.8
Refer below:
Pass
1.7.8.1
Pass
1.7.8.2
Colours ................................................................:
N/A
1.7.8.3
Pass
1.7.8.4
None
N/A
1.7.9
Pass
1.7.10
1.7.11
Durability
Pass
1.7.12
Removable parts
Pass
1.7.13
It should be considered in
the final system.
N/A
Language(s) ......................................................... :
1.7.14
Pass
2.1
Pass
2.1.1
Refer below:
Pass
2.1.1.1
No operator access to
energized parts.
Pass
N/A
N/A
Verdict
N/A
Pass
Page 11 of 49
2.1.1.2
2.1.1.3
Requirement + Test
Result - Remark
Test with test finger (Figure 2A) ............................: The test finger was unable
to contact bare hazardous
parts, basic insulation, or
ELV circuits.
Test with test pin (Figure 2B) .................................: The test pin was unable to
contact bare hazardous
parts.
Test with test probe (Figure 2C) ............................: Intended for using in
restricted access locations.
See 2.1.3
No battery is accessible
Battery compartments
when the door is closed;
Access to ELV wiring
No internal wiring at ELV
accessible to the operator.
Verdict
Pass
Pass
Pass
Pass
N/A
2.1.1.4
2.1.1.5
Pass
2.1.1.6
Manual controls
Pass
2.1.1.7
Pass
Pass
Pass
a) Capacitor connected to the d.c. mains supply ..: Considered in the end
system
N/A
N/A
2.1.1.9
N/A
2.1.2
Checked by inspection,
unintentional contact is
unlikely during service
operations.
Pass
2.1.3
N/A
2.1.1.8
Report No.:
SYBH(A)074112010
Page 12 of 49
Requirement + Test
Result - Remark
Verdict
2.2
SELV circuits
2.2.1
General requirements
2.2.2
Pass
2.2.3
Pass
2.2.4
Pass
2.3
TNV circuits
2.3.1
Limits
Pass
SELV limits are not
exceeded under normal
condition and after a single
fault.
Pass
N/A
No TNV circuits.
N/A
2.3.2
N/A
2.3.2.1
General requirements
N/A
2.3.2.2
N/A
2.3.2.3
Protection by earthing
N/A
2.3.2.4
N/A
2.3.3
N/A
N/A
N/A
2.4
N/A
2.4.1
General requirements
2.4.2
Limit values
N/A
N/A
2.4.3
N/A
2.5
N/A
N/A
Page 13 of 49
Requirement + Test
Result - Remark
N/A
N/A
N/A
2.6
2.6.1
Protective earthing
2.6.2
Functional earthing
2.6.3
2.6.3.1
General
2.6.3.2
Pass
Accessible conductive parts
are reliably connected to
protective earth.
Pass
Pass
Refer below:
Pass
Pass
Refer below:
2
Verdict
2
Rated current: 20.5 A MAX.
Rated current (A), cross-sectional area (mm ),
AWG ...................................................................... : Cross-sectional area (mm 2):
2
2.5 mm Minimum
Pass
Pass
Pass
2.6.3.5
Pass
2.6.4
Terminals
Refer below:
Pass
2.6.4.1
General
Refer below:
Pass
2.6.4.2
Pass
Report No.:
SYBH(A)074112010
Pass
Page 14 of 49
Requirement + Test
Result - Remark
Verdict
2.6.5
Refer below:
2.6.5.1
Interconnection of equipment
2.6.5.2
Pass
2.6.5.3
Pass
2.6.5.4
Pass
2.6.5.5
Pass
2.6.5.6
Corrosion resistance
Pass
2.6.5.7
Pass
2.6.5.8
Pass
2.7
N/A
2.7.1
Basic requirements
N/A
Pass
Pass
DC mains supply
N/A
2.7.2
N/A
2.7.3
N/A
2.7.4
N/A
2.7.5
N/A
2.7.6
N/A
2.8
Safety interlocks
2.8.1
General principles
N/A
N/A
2.8.2
Protection requirements
Report No.:
SYBH(A)074112010
No LPS.
N/A
Page 15 of 49
Requirement + Test
Result - Remark
Verdict
2.8.3
Inadvertent reactivation
N/A
2.8.4
Fail-safe operation
N/A
2.8.5
Moving parts
N/A
2.8.6
Overriding
N/A
2.8.7
N/A
2.8.7.1
N/A
2.8.7.2
Overload test
N/A
2.8.7.3
Endurance test
N/A
2.8.7.4
N/A
2.8.8
Mechanical actuators
N/A
2.9
Electrical insulation
2.9.1
2.9.2
Humidity conditioning
Pass
The application of
insulating materials is
suitable for the electrical,
thermal and mechanical
strength, and the working
environment (temperature,
pressure, humidity and
pollution).
Natural rubber,
hygroscopic and material
containing asbestos not
used as insulation
Pass
N/A
2.9.3
Grade of insulation
2.9.4
Pass
N/A
2.10
N/A
2.10.1
General
2.10.1.1
Frequency ............................................................. :
N/A
N/A
2.10.1.2
N/A
2.10.1.3
N/A
2.10.1.4
N/A
2.10.1.5
N/A
2.10.1.6
N/A
2.10.1.7
N/A
Report No.:
SYBH(A)074112010
Page 16 of 49
Requirement + Test
Result - Remark
Verdict
2.10.2
2.10.2.1
General
N/A
N/A
2.10.2.2
N/A
2.10.2.3
N/A
2.10.3
Clearances
N/A
2.10.3.1
General
N/A
2.10.3.2
N/A
N/A
N/A
N/A
N/A
2.10.3.3
N/A
2.10.3.4
N/A
2.10.3.5
N/A
2.10.3.6
N/A
2.10.3.7
N/A
2.10.3.8
N/A
2.10.3.9
N/A
N/A
N/A
N/A
Creepage distances
N/A
N/A
2.10.4.1
General
N/A
2.10.4.2
N/A
2.10.4.3
N/A
2.10.5
Solid insulation
N/A
2.10.5.1
General
N/A
2.10.5.2
N/A
2.10.5.3
N/A
2.10.5.4
Semiconductor devices
N/A
2.10.5.5.
Cemented joints
N/A
2.10.5.6
N/A
2.10.5.7
N/A
Page 17 of 49
Requirement + Test
Result - Remark
Verdict
2.10.5.8
N/A
2.10.5.9
N/A
N/A
N/A
2.10.5.12
N/A
N/A
N/A
N/A
N/A
N/A
N/A
2.10.5.13
N/A
N/A
N/A
N/A
N/A
2.10.6
N/A
2.10.6.1
N/A
2.10.6.2
N/A
2.10.6.3
N/A
2.10.6.4
N/A
N/A
N/A
2.10.7
N/A
2.10.8
N/A
2.10.8.1
N/A
2.10.8.2
Thermal conditioning
N/A
2.10.8.3
N/A
2.10.8.4
N/A
2.10.9
Thermal cycling
N/A
2.10.5.14
Report No.:
SYBH(A)074112010
Page 18 of 49
Requirement + Test
Result - Remark
Verdict
2.10.10
N/A
2.10.11
N/A
2.10.12
N/A
Pass
3.1
General
Pass
3.1.1
Pass
3.1.2
Pass
3.1.3
Pass
3.1.4
Insulation of conductors
Insulation on internal
conductors is considered
to be of adequate quality
and suitable for the
application and the
working voltage involved.
Pass
3.1.5
No beads or similar
ceramic insulators on
conductors.
N/A
3.1.6
Pass
3.1.7
No such materials in
electrical connections
N/A
3.1.8
None
N/A
Report No.:
SYBH(A)074112010
Page 19 of 49
Requirement + Test
Result - Remark
Termination of conductors
Terminations cannot
become displaced so
that clearances and
creepage distances can
be reduced
Verdict
Pass
10 N pull test
Pass
3.1.10
Sleeving on wiring
N/A
3.2
Pass
3.2.1
Means of connection
3.2.1.1
3.2.1.2
3.2.2
N/A
3.2.3
N/A
Refer below:
Pass
N/A
Need to be considered in
the end system, A set of
terminals complied with
Cl.3.3 is provided by
approved
N/A
Appliance inlets
Approved appliance
inlets used, but this
appliance inlets not used
in the end system
Pass
3.2.5
N/A
3.2.5.1
N/A
Type ...................................................................... :
2
N/A
3.2.6
N/A
3.2.7
N/A
3.2.8
Cord guards
N/A
3.2.9
Report No.:
SYBH(A)074112010
N/A
Page 20 of 49
Requirement + Test
Result - Remark
Verdict
3.3
Pass
3.3.1
Wiring terminals
Pass
3.3.2
3.3.3
Screw terminals
Pass
3.3.4
N/A
N/A
Refer below:
3.3.6
No damage to
conductors, see 3.3.3
and 3.3.4
3.3.7
N/A
3.3.8
Stranded wire
N/A
3.4
N/A
3.4.1
General requirement
3.4.2
Disconnect devices
N/A
N/A
3.4.3
N/A
3.4.4
N/A
3.4.5
N/A
3.4.6
N/A
3.4.7
N/A
3.4.8
N/A
3.4.9
N/A
3.4.10
Interconnected equipment
N/A
3.4.11
N/A
3.5
Interconnection of equipment
Pass
3.5.1
General requirements
Pass
Report No.:
SYBH(A)074112010
DC mains supply
Pass
Pass
Page 21 of 49
Requirement + Test
Result - Remark
Verdict
3.5.2
Pass
3.5.3
No ELV circuit
N/A
3.5.4
N/A
PHYSICAL REQUIREMENTS
Pass
4.1
Stability
Pass
Fixed equipment.
Angle of 10
N/A
N/A
4.2
Mechanical strength
Pass
4.2.1
General
Pass
4.2.2
No hazard
Pass
4.2.3
No hazard.
Pass
4.2.4
No hazard.
Pass
4.2.5
Impact test
Refer below:
Pass
Fall test
Pass
Swing test
Pass
4.2.6
N/A
4.2.7
No thermal plastic
materials used as
enclosure of the products
contained in this report
N/A
4.2.8
N/A
N/A
4.2.9
4.2.10
4.3
Report No.:
SYBH(A)074112010
N/A
N/A
Pass
Page 22 of 49
Requirement + Test
Result - Remark
Verdict
4.3.1
Pass
4.3.2
N/A
4.3.3
Adjustable controls
No hazardous adjustable
controls.
N/A
4.3.4
Securing of parts
Pass
4.3.5
N/A
4.3.6
N/A
Torque .................................................................. :
N/A
4.3.7
No heating elements
provided.
N/A
4.3.8
Batteries
Need to be considered in
the end system
N/A
N/A
N/A
N/A
N/A
4.3.9
N/A
4.3.10
Not produced
N/A
4.3.11
N/A
4.3.12
N/A
N/A
N/A
4.3.13
Radiation
Refer below:
Pass
4.3.13.1
General
Refer below:
Pass
4.3.13.2
Ionizing radiation
N/A
Report No.:
SYBH(A)074112010
Page 23 of 49
4.3.13.3
Requirement + Test
Result - Remark
Verdict
N/A
N/A
4.3.13.4
N/A
4.3.13.5
Pass
CLASS I
4.3.13.6
4.4
Pass
4.4.1
General
Pass
4.4.2
4.4.3
4.4.4
4.5
Thermal requirements
Pass
4.5.1
General
Pass
4.5.2
Temperature tests
Report No.:
SYBH(A)074112010
N/A
Pass
N/A
A metal net reduced the
access to moving fans.
Pass
Pass
Page 24 of 49
Requirement + Test
Result - Remark
Verdict
4.5.3
Pass
4.5.4
Pass
4.5.5
Only approved
components used in
hazardous voltage.
Pass
4.6
Openings in enclosures
4.6.1
Pass
No openings in top area.
Pass
Door is interlocked.
4.6.4
4.6.4.1
N/A
Pass
N/A
N/A
N/A
4.6.4.3
N/A
4.6.5
No barrier secured by
adhesive inside
enclosure.
4.7
Resistance to fire
4.7.1
4.7.2
N/A
Pass
Method 1 is used.
Pass
Pass
N/A
Report No.:
SYBH(A)074112010
Pass
Page 25 of 49
Requirement + Test
Result - Remark
Verdict
4.7.2.1
Pass
4.7.2.2
Pass
4.7.3
Materials
4.7.3.1
General
Appropriate use of
components and suitable
construction. Components
are mounted on material of
flammability V-1. See 1.5.1
Pass
4.7.3.2
Metal
Pass
4.7.3.3
4.7.3.4
4.7.3.5
Rated HF-1
4.7.3.6
N/A
Pass
5.1
N/A
5.1.1
General
5.1.2
N/A
5.1.2.1
N/A
5.1.2.2
N/A
5.1.2.3
N/A
5.1.3
Test circuit
N/A
5.1.4
N/A
5.1.5
Test procedure
N/A
Report No.:
SYBH(A)074112010
Pass
N/A
Pass
Pass
N/A
Page 26 of 49
Requirement + Test
Result - Remark
Test measurements
Verdict
N/A
264V/60Hz
5.1.7
N/A
5.1.7.1
General ................................................................ :
N/A
5.1.7.2
N/A
5.1.8
N/A
5.1.8.1
N/A
5.1.8.2
N/A
N/A
N/A
5.2
Electric strength
Pass
5.2.1
General
Pass
5.2.2
Test procedure
No insulation breakdown
detected during the test.
(see appended table 5.2)
Pass
5.3
5.3.1
Pass
5.3.2
Motors
No motors used.
N/A
5.3.3
Transformers
N/A
Report No.:
SYBH(A)074112010
Pass
Page 27 of 49
Requirement + Test
Result - Remark
Verdict
5.3.4
Pass
5.3.5
Electromechanical components
No electromechanical
components in secondary
circuits.
N/A
5.3.6
N/A
5.3.7
Simulation of faults
Pass
5.3.8
Unattended equipment
5.3.9
Pass
5.3.9.1
Pass
5.3.9.2
No reduction of clearance
and creepage distances.
Electric strength test is
made on basic,
supplementary and
reinforced insulation.
Pass
N/A
6.1
N/A
6.1.1
N/A
6.1.2
N/A
6.1.2.1
Requirements
N/A
6.1.2.2
N/A
Exclusions ............................................................ :
N/A
Report No.:
SYBH(A)074112010
Page 28 of 49
Requirement + Test
Result - Remark
Verdict
6.2
N/A
6.2.1
Separation requirements
N/A
6.2.2
N/A
6.2.2.1
Impulse test
N/A
6.2.2.2
Steady-state test
N/A
6.2.2.3
Compliance criteria
N/A
6.3
N/A
N/A
7.1
General
N/A
7.2
N/A
7.3
N/A
7.4
N/A
7.4.1
General
N/A
7.4.2
N/A
7.4.3
Impulse test
N/A
Report No.:
SYBH(A)074112010
No connection to cable
distribution
Page 29 of 49
Requirement + Test
Result - Remark
Verdict
N/A
A.1
N/A
A.1.1
Samples ................................................................ :
A.1.2
N/A
A.1.3
N/A
A.1.4
N/A
Flame A, B, C or D ............................................... :
A.1.5
Test procedure
N/A
A.1.6
Compliance criteria
N/A
A.2
Flammability test for fire enclosures of movable equipment having a total mass
not exceeding 18 kg, and for material and components located inside fire
enclosures (see 4.7.3.2 and 4.7.3.4)
A.2.1
A.2.2
N/A
A.2.3
N/A
A.2.4
N/A
Flame A, B or C .................................................... :
N/A
A.2.5
Test procedure
N/A
A.2.6
Compliance criteria
N/A
A.2.7
N/A
A.3
N/A
A.3.1
Mounting of samples
N/A
A.3.2
Test procedure
N/A
A.3.3
Compliance criterion
N/A
Report No.:
SYBH(A)074112010
Page 30 of 49
Requirement + Test
Result - Remark
Verdict
N/A
B.1
General requirements
N/A
Position ................................................................ :
Manufacturer ........................................................ :
Type ..................................................................... :
Test conditions
N/A
B.3
Maximum temperatures
N/A
B.4
N/A
B.5
N/A
N/A
B.6
B.6.1
General
N/A
B.6.2
Test procedure
N/A
B.6.3
N/A
B.6.4
N/A
B.7
N/A
B.7.1
General
N/A
B.7.2
Test procedure
N/A
B.7.3
N/A
B.7.4
N/A
B.8
N/A
B.9
N/A
B.10
N/A
N/A
In approved power supply
Manufacturer ........................................................ :
Type ..................................................................... :
Report No.:
SYBH(A)074112010
Page 31 of 49
Requirement + Test
Result - Remark
Verdict
C.1
Overload test
N/A
C.2
Insulation
N/A
N/A
N/A
D.1
Measuring instrument
N/A
D.2
N/A
N/A
N/A
N/A
G.1
Clearances
G.1.1
General
N/A
N/A
G.1.2
N/A
G.2
N/A
G.2.1
N/A
G.2.2
N/A
G.2.3
N/A
G.2.4
N/A
G.3
N/A
G.4
N/A
G.4.1
N/A
G.4.2
N/A
G.4.3
Combination of transients
N/A
G.4.4
N/A
G.5
N/A
N/A
N/A
N/A
Report No.:
SYBH(A)074112010
Page 32 of 49
Requirement + Test
Result - Remark
Verdict
N/A
G.6
N/A
N/A
Pass
N/A
K.1
N/A
K.2
N/A
K.3
N/A
K.4
N/A
K.5
N/A
K.6
Stability of operation
N/A
N/A
L.1
Typewriters
N/A
L.2
N/A
L.3
Erasers
N/A
L.4
Pencil sharpeners
N/A
L.5
N/A
L.6
Motor-operated files
N/A
L.7
N/A
N/A
M.1
Introduction
N/A
M.2
Method A
N/A
M.3
Method B
N/A
M.3.1
Ringing signal
N/A
M.3.1.1
Report No.:
SYBH(A)074112010
Page 33 of 49
Requirement + Test
Result - Remark
Verdict
M.3.1.2
M.3.1.3
M.3.1.4
M.3.2
N/A
M.3.2.1
N/A
M.3.2.2
Tripping device
N/A
M.3.2.3
N/A
N/A
N.1
N/A
N.2
N/A
N/A
N/A
N/A
N/A
N/A
R.1
N/A
R.2
N/A
N/A
S.1
Test equipment
S.2
Test procedure
N/A
N/A
S.3
N/A
N/A
Waveform recorded.
Report No.:
SYBH(A)074112010
N/A
Page 34 of 49
Requirement + Test
Result - Remark
Verdict
N/A
V.1
Introduction
N/A
V.2
N/A
N/A
W.1
N/A
W.1.1
Floating circuits
N/A
W.1.2
Earthed circuits
N/A
W.2
N/A
W.2.1
Isolation
N/A
W.2.2
N/A
W.2.3
N/A
N/A
X.1
N/A
X.2
N/A
N/A
Y.1
N/A
Y.2
N/A
Y.3
N/A
Y.4
N/A
Pass
AA
N/A
BB
Report No.:
SYBH(A)074112010
Page 35 of 49
Pass
General
Delete all the country notes in the reference document according to the
following list:
1.4.8
Note 2
1.5.1
Note 2 & 3
1.5.7.1
Note
1.5.8
Note 2
1.5.9.4
Note
1.7.2.1
Note 4, 5 & 6
2.2.3
Note
2.2.4
Note
2.3.2
Note
2.3.2.1 Note 2
2.3.4
Note 2
2.6.3.3
Note 2 & 3
2.7.1
Note
2.10.3.2 Note 2
2.10.5.13 Note 3
3.2.1.1 Note
3.2.4
Note 3.
2.5.1
Note 2
4.3.6
Note 1 & 2
4.7
Note 4
4.7.2.2
Note
4.7.3.1 Note 2
5.1.7.1
Note 3 & 4
5.3.7
Note 1
6
Note 2 & 5
6.1.2.1
Note 2
6.1.2.2
Note
6.2.2
Note 6.
2.2.1
Note 2
6.2.2.2
Note
7.1
Note 3
7.2
Note
7.3
Note 1 & 2
G.2.1
Note 2
Annex H Note 2
Pass
1.3.Z1
N/A
1.5.1
Pass
NOTE Z1 The use of certain substances in electrical and electronic equipment is restricted
within the EU: see Directive 2002/95/EC
1.7.2.1
N/A
NOTE Z1 In addition, the instructions shall include, as far as applicable, a warning that
excessive sound pressure from earphones and headphones can cause hearing loss
Report No.:
SYBH(A)074112010
Page 36 of 49
N/A
2.7.2
Pass
3.2.3
Delete the NOTE in Table 3A, and delete also in this table the conduit sizes in
parentheses.
Pass
3.2.5.1
Replace
N/A
3.3.4
In Table 3D, delete the fourth line: conductor sizes for 10 to 13 A, and replace
with the following:
| Over 10 up to and including 16
|
1,5 to 2,5
|
1,5 to 4
|
Delete the fifth line: conductor sizes for 13 to 16 A.
Pass
4.3.13.6
N/A
Annex H
N/A
Delete NOTE 2.
Bibliography
Additional EN standards.
Report No.:
SYBH(A)074112010
Page 37 of 49
ZA
ZB
1.2.4.1
N/A
1.5.7.1
N/A
1.5.8
In Norway, due to the IT power system used (see annex V, Figure V.7),
capacitors are required to be rated for the applicable line-to-line voltage (230 V).
N/A
1.5.9.4
In Finland, Norway and Sweden, the third dashed sentence is applicable only to
equipment as defined in 6.1.2.2 of this annex.
N/A
1.7.2.1
N/A
1.7.5
N/A
2.2.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1 and 6.1.2.2 of this annex.
N/A
2.3.2
In Finland, Norway and Sweden there are additional requirements for the
insulation. See 6.1.2.1 and 6.1.2.2 of this annex.
N/A
2.3.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1 and 6.1.2.2 of this annex.
N/A
2.6.3.3
In the United Kingdom, the current rating of the circuit shall be taken as 13 A,
not 16 A.
N/A
2.7.1
N/A
2.10.5.13
In Finland, Norway and Sweden, there are additional requirements for the
insulation, see 6.1.2.1 and 6.1.2.2 of this annex.
N/A
Report No.:
SYBH(A)074112010
Refer
below
Page 38 of 49
N/A
3.2.1.1
N/A
3.2.1.1
N/A
3.2.1.1
In the United Kingdom, apparatus which is fitted with a flexible cable or cord and
is designed to be connected to a mains socket conforming to BS 1363 by means
of that flexible cable or cord and plug, shall be fitted with a standard plug in
accordance with Statutory Instrument 1768:1994 - The Plugs and Sockets etc.
(Safety) Regulations 1994, unless exempted by those regulations.
N/A
NOTE Standard plug is defined in SI 1768:1994 and essentially means an approved plug
conforming to BS 1363 or an approved conversion plug.
3.2.1.1
In Ireland, apparatus which is fitted with a flexible cable or cord and is designed
to be connected to a mains socket conforming to I.S. 411 by means of that
flexible cable or cord and plug, shall be fitted with a 13 A plug in accordance with
Statutory Instrument 525:1997 - National Standards Authority of Ireland (section
28) (13 A Plugs and Conversion Adaptors for Domestic Use) Regulations 1997.
N/A
3.2.4
Pass
3.2.5.1
In the United Kingdom, a power supply cord with conductor of 1,25 mm2 is
allowed for equipment with a rated current over 10 A and up to and including 13
A.
N/A
Report No.:
SYBH(A)074112010
Page 39 of 49
N/A
4.3.6
In the United Kingdom, the torque test is performed using a socket outlet
complying with BS 1363 part 1:1995, including Amendment 1:1997 and
Amendment 2:2003 and the plug part of DIRECT PLUG-IN EQUIPMENT shall be
assessed to BS 1363: Part 1, 12.1, 12.2, 12.3, 12.9, 12.11, 12.12, 12.13, 12.16
and 12.17, except that the test of 12.17 is performed at not less than 125 C.
Where the metal earth pin is replaced by an Insulated Shutter Opening Device
(ISOD), the requirements of clauses 22.2 and 23 also apply.
N/A
4.3.6
N/A
5.1.7.1
N/A
Report No.:
SYBH(A)074112010
Page 40 of 49
In Finland, Norway and Sweden, add the following text between the first and
second paragraph of the compliance clause:
If this insulation is solid, including insulation forming part of a component, it shall
at least consist of either
two layers of thin sheet material, each of which shall pass the electric
strength test below, or
one layer having a distance through insulation of at least 0,4 mm, which
shall
pass the electric strength test below.
If this insulation forms part of a semiconductor component (e.g. an optocoupler),
there is no distance through insulation requirement for the insulation consisting of
an insulating compound completely filling the casing, so that CLEARANCES and
CREEPAGE DISTANCES do not exist, if the component passes the electric
strength test in accordance with the compliance clause below and in addition
passes the tests and inspection criteria of 2.10.11 with an electric
strength
test of 1,5 kV multiplied by 1,6 (the electric strength test of 2.10.10 shall
be
performed using 1,5 kV), and
is subject to ROUTINE TESTING for electric strength during
manufacturing,
using a test voltage of 1,5 kV.
It is permitted to bridge this insulation with a capacitor complying with
EN 132400:1994, subclass Y2.
A capacitor classified Y3 according to EN 132400:1994, may bridge this
insulation under the following conditions:
the insulation requirements are satisfied by having a capacitor classified
Y3
as defined by EN 132400, which in addition to the Y3 testing, is tested
with
an impulse test of 2,5 kV defined in EN 60950-1:2006, 6.2.2.1;
the additional testing shall be performed on all the test specimens as
described in EN 132400;
the impulse test of 2,5 kV is to be performed before the endurance test in
EN 132400, in the sequence of tests as described in EN 132400.
N/A
6.1.2.2
N/A
7.2
In Finland, Norway and Sweden, for requirements see 6.1.2.1 and 6.1.2.2 of this
annex.
The term TELECOMMUNICATION NETWORK in 6.1.2 being replaced by the
term CABLE DISTRIBUTION SYSTEM.
N/A
7.3
In Norway and Sweden, there are many buildings where the screen of the
coaxial cable is normally not connected to the earth in the building installation.
N/A
7.3
N/A
ZC
A-DEVIATIONS (informative)
Report No.:
SYBH(A)074112010
Refer
below
Page 41 of 49
N/A
1.5.1
N/A
NOTE In Switzerland, switches containing mercury such as thermostats, relays and level
controllers are not allowed.
1.7.2.1
N/A
eller
If essential for the safety of the equipment, the tag must in addition be provided
with a diagram, which shows the connection of the other conductors, or be
provided with the following text:
For tilslutning af de vrige ledere, se medflgende installationsvejledning.
1.7.2.1
Pass
1.7.5
N/A
1.7.13
N/A
5.1.7.1
N/A
Report No.:
SYBH(A)074112010
Page 42 of 49
object/part No.
manufacturer/
trademark
type/model
technical data
standard
mark(s) of
1
conformity )
TEC
21160927
AVC
ZNUC00R001
Input: 48Vdc,
max. 6.9A
EN 60950-1
TUV Rheinland
Alternative
Laird
AA-200-48HUAW1-00
Input: 48Vdc,
max. 6.9A
EN 60950-1
TUV-PS
Fan
32030057
DELTA
ELECTRONIC
S INC
PFB1248EHE6F58
48 V, 0.45 A,
5.133 m3/min,
181.27 CFM
UL 507
UL E132003
-alternative
DELTA
ELECTRONIC
S IN
PFB1248EHE6F58
48 V, 0.45 A,
5.133 m3/min,
181.27 CFM
UL 507
UL E132003
Fuse on Heat
LITTELFUSE
exchanger
INC
HX02-22DH and
HX04-22DH
19040096
0451001.MRL
UL, E10480
-alternative
CONQUER
ELECTRONIC
S CO LTD
SEF001
125 Vac, 1 A
UL, E82636
-alternative
UL, E20624
Fuse on on
LITTELFUSE
Heat exchanger INC
HX02-22DH and
HX04-22DH
19040105
0451012.MRL
65 V ac/dc, 12
A
UL, E10480
-alternative
CONQUER
ELECTRONIC
S CO LTD
SEF012
125 Vac, 12 A
UL, E82636
-alternative
125ac/86dc, 12
A
UL, E20624
Transformer on ShenZhen
Heat exchanger HAIGUANG
HX02-22DH and
HX04-22DH
09040334
SMD653
1:1.1
0.80 W
UL
UL
Gasket
Meteor
EPDM
Tested
according to
EN60950-22
EN60950-22
TUV-PS
PCB
Various
Various
94V-0,
Min 105(C
UL94
UL
Report No.:
SYBH(A)074112010
Page 43 of 49
--
--
--
7.9
--
--
U (V)
P (W)
I (mA)
P
Ifuse (mA) condition/status
-38.4
2.7
0.1
--
-48
304.0
6.3
--
-57.6
433.7
7.5
--
--
--
7.9
--
--
-38.4
3.0
0.1
--
-48
299.8
6.2
--
-57.6
430.4
7.5
--
U (V)
P (W)
I (mA)
P
Ifuse (mA) condition/status
--
--
-30
2.7
0.09
--
--
1.0
-48
12.8
0.32
--
--
--
-56
14.4
0.29
--
U (V)
P (W)
I (mA)
P
Ifuse (mA) condition/status
--
--
-38
268.2
7.08
--
--
9.5
-48
367.3
7.82
--
--
--
-58
459.9
8.18
--
--
--
--
3.1
--
--
U (V)
P (W)
I (mA)
P
Ifuse (mA) condition/status
-38.4
36.0
1.22
--
-48
39.3
1.16
--
-57.6
39.8
0.96
--
Report No.:
SYBH(A)074112010
Page 44 of 49
N/A
VA
Limit
Meas.
Limit
Normal condition
Single fault: ..
Single fault: ..
Single fault: ..
supplementary information:
S-c=Short circuit, O-c=Open circuit
2.10.2
N/A
Location
supplementary information:
2.10.3 and
2.10.4
U peak
(V)
U r.m.s.
(V)
Required cl
(mm)
N/A
cl
(mm)
Required cr
(mm)
cr
(mm)
Basic/supplementary:
Supplementary information:
Report No.:
SYBH(A)074112010
Page 45 of 49
U peak
(V)
N/A
U rms
(V)
Test
voltage
(V)
Required DTI
(mm)
DTI
(mm)
Supplementary information:
4.3.8
TABLE: Batteries
N/A
Max.
current
during
fault
condition
Manuf.
Specs.
Unintentional
charging
Rechargeable batteries
Charging
Meas.
current
Discharging
Manuf.
Specs.
Meas.
current
Reversed charging
Manuf.
Specs.
Meas.
current
Manuf.
Specs.
Test results:
Verdict
- Chemical leaks
- Explosion of the battery
- Emission of flame or expulsion of molten metal
- Electric strength tests of equipment after completion of tests
Supplementary information:
4.5
-58V
-38V
-58V
--
--
--
--
--
--
Report No.:
SYBH(A)074112010
allowed
Tmax (C)
T (C)
24.7
24.8
40
40
--
Page 46 of 49
25.4
25.9
40.7
41.1
90
25.4
26.0
40.7
41.2
90
4.Winding of T1 on HECA
26.3
26.9
41.6
42.1
90
5.Core of T1 on HECA
26.0
26.6
41.3
41.8
90
6. Winding of L1 on HECA
27.3
27.9
42.6
43.1
90
25.8
26.3
41.1
41.5
85
26.3
26.9
41.6
42.1
105
9.Surface of heater
25.5
26.0
40.8
41.2
70
26.6
26.0
41.9
41.2
85
11.Surface of EUT
24.9
24.9
40.2
40.1
70
supplementary information
Tested with HX04-22DH
maximum temperature T of part/at::
allowed
Tmax (C)
T (C)
1.Ambient
23.9
23.7
40
40
--
55.8
84.5
71.9
100.8
90
30.7
35.0
46.8
51.3
90
4.Winding of T1 on HECA
26.0
26.6
42.1
42.9
90
5.Core of T1 on HECA
25.9
26.5
42
42.8
90
6. Winding of L1 on HECA
26.2
27.1
42.3
43.4
90
24.4
24.9
40.5
41.2
85
24.7
25.2
40.8
41.5
105
9.Surface of heater
24.7
25.2
40.8
41.5
70
24.5
24.9
40.6
41.2
85
11.Surface of EUT
23.0
22.6
39.1
38.9
70
supplementary information
Tested with HX02-22DH
4.5.5
Part
N/A
2 mm
Supplementary information:
Report No.:
SYBH(A)074112010
Page 47 of 49
Pass
Manufacturer of
material
Type of material
Thickness Flammability
(mm)
class
Evidence
Supplementary information:
5.2
TABLE: Electric strength tests, impulse tests and voltage surge tests
DC
1002V
Breakdown
Yes / No
NO
NO
NO
component fault
No.
test voltage
(V)
Openings
of HX0422DH
Openings
blocked
-48Vdc
210
--
--
Fan of
HX0422DH
Fan
disconnected
-48Vdc
117
--
--
DC input
of HX0422DH
Short circuit
-48Vdc
5mins
--
--
DC input
of HX0222DH
Short circuit
-48Vdc
5mins
--
--
DC input
of TEC
Short circuit
-48Vdc
5mins
--
--
DC input
of TEC
Short circuit
-48Vdc
5mins
--
--
Report No.:
SYBH(A)074112010
test time
fuse
No.
fuse current
(A)
result
Page 48 of 49
Report No.:
SYBH(A)074112010
Page 49 of 49
Attachment No. 1
Attachment contains
Cover page:
1 page
National Differences:
16 pages
Total:
17 pages
Attachment 1 to
SYBH(A)074112010
Page 1 of 17
Requirement Test
Result - Remark
1.5.101
Attachment 1 to
SYBH(A)074112010
Verdict
N/A
N/A
Page 2 of 17
Requirement Test
Result
Verdict
CA
Canada and the United States of America have adopted a single, bi-national standard, CAN/CSA C22.2
No. 60950-1/UL60950-1, Second Edition, which is based on IEC 60950-1, Second Edition. This bi-national
standard should be consulted for further details on the national conditions and differences summarized
below.
SPECIAL NATIONAL CONDITIONS
The following is a summary of the key national differences based on national regulatory requirements,
such as the Canadian Electrical Code (CEC) Part and the Canadian Building Code, which are referenced
in legislation and which form the basis for the rules and practices followed in electrical and building
installations.
1.1.1
1.4.14
1.5.5
N/A
N/A
N/A
Attachment 1 to
SYBH(A)074112010
N/A
N/A
Page 3 of 17
Requirement Test
Result
Verdict
1.7.7
N/A
2.5
N/A
2.7.1
N/A
N/A
3.2
N/A
3.2.1
N/A
3.2.1.2
N/A
3.2.3
N/A
3.2.5
N/A
3.2.9
N/A
Attachment 1 to
SYBH(A)074112010
Page 4 of 17
Requirement Test
Result
Verdict
3.3
N/A
3.3.3
N/A
3.3.4
N/A
3.4.2
N/A
3.4.8
N/A
3.4.11
N/A
4.3.12
N/A
4.3.13.5
N/A
4.7
N/A
4.7.3.1
N/A
Attachment 1 to
SYBH(A)074112010
Page 5 of 17
Requirement Test
Result
Annex H
Verdict
N/A
The following key national differences are based on requirements other than national regulatory requirements.
1.5.1
1.6.1.2
2.3.1
2.3.2.1
Attachment 1 to
SYBH(A)074112010
N/A
N/A
N/A
N/A
N/A
Page 6 of 17
Requirement Test
2.6.3.4
4.2.8.1
4.2.11
4.3.2
5.1.8.3
5.3.7
6.4
M.2
Annex NAD
Attachment 1 to
SYBH(A)074112010
Result
Verdict
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Page 7 of 17
Requirement Test
Annex NAF
Attachment 1 to
SYBH(A)074112010
Result
Verdict
N/A
Page 8 of 17
Requirement Test
1.1
N/A
1.1.1
N/A
1.1.2
N/A
1.1.2
N/A
1.4.14
N/A
1.5.1
N/A
1.5.1
N/A
1.5.5
N/A
1.5.5
N/A
1.5.5
N/A
1.5.5
N/A
1.5.5
N/A
1.5.5
N/A
1.6.1.2
N/A
Attachment 1 to
SYBH(A)074112010
Result
Verdict
Page 9 of 17
Requirement Test
Result
Verdict
1.6.1.2
N/A
1.7
N/A
1.7.1
N/A
1.7.1
N/A
1.7.6
N/A
1.7.7
N/A
1.7.7
N/A
1.7.7
N/A
2.1.1.1
N/A
2.3.1.b
N/A
2.3.1.b
N/A
2.3.1.b
N/A
2.3.2.1
N/A
2.3.2.4
N/A
Attachment 1 to
SYBH(A)074112010
Page 10 of 17
Requirement Test
Result
Verdict
2.5
N/A
2.6
N/A
2.6.3.3
N/A
2.6.3.4
N/A
2.6.4.1
N/A
2.7.1
N/A
2.7.1
N/A
2.7.1
N/A
2.7.1
N/A
2.7.1
N/A
N/A
3.1.1
N/A
3.1.1
N/A
Attachment 1 to
SYBH(A)074112010
Page 11 of 17
Requirement Test
Result
Verdict
3.2
N/A
3.2.1
N/A
3.2.1
N/A
3.2.1
N/A
3.2.1.2
N/A
3.2.1.2
N/A
3.2.1.2
N/A
3.2.1.2
N/A
3.2.1.2
N/A
3.2.1.2
N/A
3.2.3
N/A
3.2.3
N/A
Attachment 1 to
SYBH(A)074112010
Page 12 of 17
Requirement Test
3.2.3
N/A
3.2.3
N/A
3.2.5
N/A
3.2.5
N/A
3.2.5
N/A
3.2.6
N/A
3.2.9
N/A
3.2.9
N/A
3.3
N/A
3.3
N/A
3.3.1
N/A
3.3.3
N/A
3.3.4
N/A
3.3.4
N/A
Attachment 1 to
SYBH(A)074112010
Result
Verdict
Page 13 of 17
Requirement Test
3.3.6
N/A
3.3.6
N/A
3.3.6
N/A
3.4.2
N/A
3.4.8
N/A
3.4.11
N/A
4.2.8.1
N/A
4.2.9
N/A
4.2.11
N/A
4.3.2
N/A
4.3.6
N/A
4.3.12
N/A
4.3.12
N/A
Result
Verdict
N/A
Page 14 of 17
Requirement Test
Result
Verdict
N/A
4.7
N/A
4.7.3.1
N/A
4.7.3.1
N/A
4.7.3.4
N/A
5.1.8.2
N/A
5.1.8.3
N/A
5.3.7
N/A
5.3.7
N/A
5.3.9.1
N/A
N/A
N/A
Attachment 1 to
SYBH(A)074112010
Page 15 of 17
Requirement Test
6.3
N/A
6.3
N/A
6.4
N/A
6.4
N/A
N/A
N/A
M.2
N/A
M.4
N/A
NAC
N/A
NAC
N/A
NAD
N/A
NAD
N/A
NAF
N/A
NAF.1.7
N/A
Attachment 1 to
SYBH(A)074112010
Result
Verdict
Page 16 of 17
Requirement Test
Result
Verdict
N/A
NAF.3.4
N/A
NAF.4.4
N/A
Attachment 1 to
SYBH(A)074112010
Page 17 of 17
Attachment No. 2
National and Group Differences for
IEC 60950-1 1st edition (2001)
as per IEC Bulletin 112A (2006)
Countries Included: See overview on
following page
Attachment contains
Cover page:
1 page
Total:
7 pages
9 pages
Attachment 2 to
SYBH(A)074112010
Page 1 of 9
COUNTRIES
Country
Group differ.
National differ.
National standard
AU Australia
SAI Global
Yes
Yes
AS/NZS 60950.1-2003
Attachment 2 to
SYBH(A)074112010
Tested
Yes
Page 2 of 9
Requirement - Test
Result - Remark
Verdict
AU
1.2
Annex ZZ
(normative)
Variations to IEC 60950-1:2001 for application
in Australia and New Zealand
ZZ1 Introduction This Annex sets out variations between this Standard and IEC
60950-1:2001. These variations indicate national variations for purposes of the
IECEE CB Scheme and will be published in the IECEE CB Bulletin. These variations
are indicated within the body of the Standard.
ZZ.2 Variations
The variations are as follows:
Considered.
Pass
Pass
1.5.1
Pass
1.5.2.
Add the following to the end of first and third dash Considered
items: or the relevant Australian/New Zealand
Standard.
Pass
2.1
Deleted
Pass
3.2.3
Delete Note 2.
Deleted
Pass
3.2.5.1
Attachment 2 to
SYBH(A)074112010
Pass
Page 3 of 9
Requirement - Test
Result - Remark
Verdict
No such device.
N/A
4.3.13.5
Considered
Pass
4.7
N/A
4.7.201
N/A
Attachment 2 to
SYBH(A)074112010
Page 4 of 9
Requirement - Test
Result - Remark
Attachment 2 to
SYBH(A)074112010
Verdict
N/A
Page 5 of 9
Requirement - Test
Result - Remark
Verdict
N/A
Change
5 Severities
Replace with:
The duration of application of the
test flame shall be 30 s 1 s.
N/A
8 Test procedure
8.2
8.4
8.5
Replace with:
The test shall be made on one
specimen. If the specimen does
not withstand the test, the test
may be repeated on two further
specimens, both of which shall
then withstand the test.
Replace with:
The duration of burning (tb) shall
not exceed 30 s. However, for
printed circuit boards, it shall not
exceed 15 s.
Attachment 2 to
SYBH(A)074112010
Page 6 of 9
Requirement - Test
Result - Remark
Verdict
The needle-flame test shall not be carried out on parts of material classified as V-0
or V-1 according to IEC 60695-11-10, provided that the sample tested was not
thicker than the relevant part.
4.7.201.4 Testing in the event of non-extinguishing material If parts, other than
enclosures, do not withstand the glow wire tests of 4.7.201.3, by failure to extinguish
within 30 s after the removal of the glow-wire tip, the needle-flame test detailed in
4.7.201.3 shall be made on all parts of non-metallic material which are within a
distance of 50 mm or which are likely to be impinged upon by flame during the tests
of 4.7.201.3. Parts shielded by a separate barrier which meets the needle-flame test
need not be tested.
NOTE 1 - If the enclosure does not withstand the glow-wire test the equipment is
considered to have failed to meet the requirements of Clause 4.7.201 without the
need for consequential testing.
NOTE 2 - If other parts do not withstand the glow-wire test due to ignition of the
tissue paper and if this indicates that burning or glowing particles can fall onto an
external surface underneath the equipment, the equipment is considered to have
failed to meet the requirements of Clause 4.7.201 without the need for consequential
testing.
NOTE 3 - Parts likely to be impinged upon by the flame are considered to be those
within the envelope of a vertical cylinder having a radius of 10 mm and a height
equal to the height of the flame, positioned above the point of the material
supporting, in contact with, or in close proximity to, connections.
4.7.201.5 Testing of printed boards
The base material of printed boards shall be subjected to the needle-flame test of
Clause 4.7.201.3. The flame shall be applied to the edge of the board where the heat
sink effect is lowest when the board is positioned as in normal use. The flame shall
not be applied to an edge, consisting of broken perforations, unless the edge is less
than 3 mm from a POTENTIAL IGNITION SOURCE.
The test is not carried out if the Printed board does not carry any POTENTIAL
IGNITION SOURCE; Base material of printed boards, on which the available
apparent power at a connection exceeds 15 VA operating at a voltage exceeding 50
V and equal or less than 400 V (peak) a.c. or d.c. under normal operating conditions,
is of flammability category FV-1 or better according to AS/NZS 4695.707, or the
printed boards are protected by an enclosure meeting the flammability category FV-0
according to AS/NZS 4695.707, or made of metal, having openings only for
connecting wires which fill the openings completely; or Base material of printed
boards, on which the available apparatus power at a connection exceeds 15 VA
operating at a voltage exceeding 400 V (peak) a.c. or d.c. under normal operating
conditions, and base material of printed boards supporting spark gaps which
provides protection against overvoltages, is of flammability category FV-0 according
to AS/NZS 4695.707 or the printed boards are contained in a metal enclosure,
having openings only for connecting wires which fill the openings completely.
Compliance shall be determined using the smallest thickness of the material.
NOTE Available apparent power is the maximum apparent power which can be
drawn from the supplying circuit through a resistive load whose value is chosen to
maximise the apparent power for more than 2 min when the circuit supplied is
disconnected.
Attachment 2 to
SYBH(A)074112010
Page 7 of 9
Requirement - Test
6.2.2
N/A
6.2.2.1
N/A
6.2.2.2
N/A
Attachment 2 to
SYBH(A)074112010
Result - Remark
Verdict
Page 8 of 9
Requirement - Test
Annex P
N/A
Index
N/A
Attachment 2 to
SYBH(A)074112010
Result - Remark
Verdict
Page 9 of 9
Attachment No. 3
National and Group Differences
for
IEC 60950 3rd Ed. as per CB Bulletin
No. 112A (2006)
Countries Included: See overview on
following page
Attachment contains
Cover page:
1 page
Total:
8 pages
10 pages
Attachment 3 to
SYBH(A)074112010
Page 1 of 10
GROUP DIFFER.
UA Ukraine
NATL DIFFER.
NATL
STANDARD
TESTED
YES
DSTU 4113-2001
YES
CN China
YES
YES
JP Japan
YES
J60950(H14)
YES
Attachment 3 to
SYBH(A)074112010
Page 2 of 10
Requirement Test
Result Remark
Verdict
1.4.5
DC power supply
N/A
1.5.8
N/A
1.7.2
Pass
2.3.3
6.2.2
N/A
6.2.2.1
N/A
6.2.2.2
Annex N
Attachment 3 to
SYBH(A)074112010
No TNV circuits
N/A
N/A
N/A
Page 3 of 10
Requirement Test
Result Remark
Verdict
1.4.5
DC power supply
N/A
1.7.1
N/A
1.7.12
N/A
3.2.1
Attachment 3 to
SYBH(A)074112010
No such device.
N/A
Page 4 of 10
Requirement Test
Result Remark
1.2
Added.
Pass
Class I equipment.
Pass
Considered.
See appended table 1.5.1.
Pass
1.2.4.101
1.2.12.1
Verdict
Attachment 3 to
SYBH(A)074112010
Page 5 of 10
Attachment 3 to
SYBH(A)074112010
Result Remark
Verdict
Pass
Considered
Pass
Pass
N/A
Pass
Pass
Page 6 of 10
3.2.5
4.2.8
4.5.1
4.7.3.2
Requirement Test
Result Remark
Addition:
Earthing of CLASS 0I EQUIPMENT
Plugs with a lead wire for earthing shall not be
used for equipment having a rated voltage
exceeding 150V.
For plugs with a lead wire for earthing, the lead
wire shall not be earthed by a clip.
CLASS 0I EQUIPMENT shall be provided with an
earthing terminal or lead wire for earthing in the
external where easily visible.
Delete 1) in Table 3B.
Addition:
Add the following informative remark after the last
sentence.
Remark - IEC 61965 is also applicable instead of
IEC 60065.
Addition:
Considered.
Add the following to suffix 5) as specified in
Conditions applicable to Table 4A, Parts 1 and
2.
With regard to Table 4A, insulating materials
complying with Japanese requirements (refer to
Japanese differences for the current IEC 60335-1
(3rd Edition) in CB Bulletin 101B) are also
acceptable.
Add a suffix 7) in Conditions applicable to Table
4A, Parts 1 and 2. In the right column of Table
4A, Part 1, add suffix 7) to 50 (K),
corresponding to - without T marking in the left
column so as to become 50 7).
Add 7) to Table 4A, Part 2 as follows. 7) This
value shall apply only to wiring or cords
complying with relevant IEC standards. Others
shall comply with Japanese
requirements (refer to Japanese differences for
the current IEC 60335-1 (3rd Edition) in CB
Bulletin 101B).
Addition:
No such flexible printed board
Add the following in 7th paragraph.
used.
- for thin materials, e.g., flexible printed boards,
etc., used inside equipment, be of
FLAMMABILITY CLASS VTM-2 or better.
Attachment 3 to
SYBH(A)074112010
Verdict
N/A
Pass
N/A
Pass
N/A
Page 7 of 10
5.3.8.2
Annex A
Annex G
Annex P
Annex U
U.2.1
Requirement Test
Replacement: Replace Table 5A.
Result Remark
Considered.
Replacement:
Replace 3rd Item as follows.
- BASIC INSULATION between the PRIMARY
CIRCUIT and accessible conductive parts of
CLASS I or 0I EQUIPMENT;
Addition:
Add the subclause A.101with the title
Flammability tests for classifying materials VTM
and the following:
Thin sheet materials shall comply with ISO 9773.
Addition:
Add the following to the Note for Table G.1.
2. In Japan, MAINS TRANSIENT VOLTAGE for
equipment with a Nominal AC MAINS SUPPLY
VOLTAGE of 100V is to be decided based on the
column where Nominal AC MAINS SUPPLY
VOLTAGE in Table G.1 is 150V.
Addition:
Add IEC 61965:2000, Mechanical Safety for
Cathode Ray Tubes.
Replacement:
Replace 2nd paragraph.
This annex covers to round winding wires having
diameters between 0.05 mm and 5.00 mm.
Replacement:
Electric strength
The test sample is prepared according to IEC
60851-5:1996, 4.4.1 (for a twisted pair). The
sample is then subjected to the test of 5.2.2 of
this standard, with a test voltage not less than
twice the appropriate voltage in table 5B (see
5.2.2) of this standard. However, the minimum
values shall be as follows:
- for BASIC INSULATION or SUPPLEMENTARY
INSULATION, 3000 V, or; - for REINFORCED
INSULATION, 6000 V.
Attachment 3 to
SYBH(A)074112010
Verdict
Pass
N/A
N/A
N/A
N/A
N/A
N/A
Page 8 of 10
Table U.1
U.2.3
U.2.4
Requirement Test
Result Remark
Replacement:
Flexibility and adherence
Test 8 of IEC 60851-3:1996, 5.1.1, using the
mandrel diameters of table U.1. The test sample
is then examined in accordance with IEC 608513:1996, 5.1.1.4, followed by the test of 5.2.2 of
this standard except applying the test voltage
between the wire and the mandrel. A test voltage
shall be the appropriate voltage in table 5B (see
5.2.2) of this standard.
However, the minimum values shall be as follows:
- for BASIC INSULATION or SUPPLEMENTARY
INSULATION, 1500 V, or;
- for REINFORCED INSULATION, 3000 V.
Replacement:
Mandrel diameter
Attachment 3 to
SYBH(A)074112010
Verdict
N/A
N/A
N/A
N/A
Page 9 of 10
U.3.2
Requirement Test
Replacement:
Replace with the following. The test voltage for
ROUTINE TESTING shall be the appropriate
voltage in table 5B (see 5.2.2) of this standard.
However,
the minimum values shall be as follows:
- for BASIC INSULATION or SUPPLEMENTARY
INSULATION, 1500 V r.m.s. or 2100 V peak, or;
- for REINFORCED INSULATION, 3000 V r.m.s.
or 4200 V peak.
Replacement:
Replace with the following.
Twisted pair samples shall be tested in
accordance with IEC 60851-5:1996, 4.4.1. The
minimum breakdown voltage shall not be less
than twice the appropriate voltage in table 5B
(see 5.2.2) of this standard. However, the
minimum values shall
be as follows:
- for BASIC INSULATION or SUPPLEMENTARY
INSULATION, 3000 V r.m.s. or 4200 V peak, or;
- for REINFORCED INSULATION, 6000 V r.m.s.
or 8400 V peak.
Attachment 3 to
SYBH(A)074112010
Result Remark
Verdict
N/A
N/A
Page 10 of 10
Attachment No. 4
Safety Test Report of
IEC60950-22
Attachment contains
Cover page:
1 page
System diagram:
19 pages
Total:
Attachment 4 to
SYBH(A)074112010
18 pages
Page 1 of 19
Attachment 4 to
SYBH(A)074112010
Page 2 of 19
IEC 60 950-22
Information technology equipment
Safety Part 22: Equipment to be installed outdoors
Report Reference No...................... :
SYBH(A)074112010
Compiled by
(printed name and signature) .......... :
Maggie Zhang
Reviewed by
(printed name and signature) .......... :
Kelvin Shi
Approved by
(printed name and signature) .......... :
Zhang Guoqing
2010-12-26
Address ............................................ :
Applicants ...................................... :
..........................
.....................
................
Address ............................................ :
Test specification:
Standard ........................................... :
st
N/A
IEC60950_22A
Huawei
Dated 2009-01
Copyright 2007 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from
the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB
Scheme procedure shall be removed.
Test item description .....................:
ITS1000M Cabinet
HUAWEI
Manufacturer .................................... :
Attachment 4 to
SYBH(A)074112010
Page 3 of 19
Ratings ............................................. :
Summary of testing:
Tests performed (name of test and test clause):
The submitted samples were found to comply with
the requirements of:
EN 60950-22/A11: 2008
IEC60950-22
Testing location:
Reliability Laboratory of Huawei Technologies Co.,
Ltd.
Huawei Base, Bantian, Longgang District,
Shenzhen
518129, P.R. China
Attachment 4 to
SYBH(A)074112010
Page 4 of 19
OVC I
OVC II
OVC III
OVC IV
Attachment 4 to
SYBH(A)074112010
Page 5 of 19
Requirement + Test
Pass
4.1
Pass
Pass
AC mains supply
Pass
4.2
4.3
Result - Remark
Pass
N/A
N/A
Pass
Pass
Verdict
Pass
Pass
See instructions.
Pass
Pass
according to
Pass
6.1
Pass
Pass
Pass
6.2
Attachment 4 to
SYBH(A)074112010
N/A
No such circuit in the
equipment.
N/A
Page 6 of 19
Requirement + Test
Result - Remark
Pass
Pass
N/A
Pass
8.1
General
Pass
Pass
No such parts.
Parts serving as a functional part of an OUTDOOR
ENCLOSURE (e.g., dials, connectors, etc.) comply with
the same environmental protection requirements as
for the OUTDOOR ENCLOSURE
N/A
N/A
Verdict
N/A
N/A
The equipment is metal
enclosure.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
All parts:
N/A
N/A
8.3
Resistance to corrosion
Pass
8.3.1
General
Pass
Attachment 4 to
SYBH(A)074112010
Page 7 of 19
Requirement + Test
Result - Remark
Verdict
Pass
N/A
Test apparatus
Pass
Pass
Pass
8.3.3
Test procedure
Pass
8.3.4
Compliance criteria
8.4
Pass
Pass
N/A
Gaskets
Pass
Pass
8.5.1
General
Pass
8.5.2
Oil resistance
8.5.3
Securing means
Pass
Pass
9.1
Pass
9.2
Pass
9.3
Pass
8.3.2
8.5
Attachment 4 to
SYBH(A)074112010
IP 55
Pass
N/A
Page 8 of 19
Requirement + Test
10
Pass
10.1
General
Pass
10.2
Impact test
(4.2.5 of IEC 60950-1)
Pass
Compliance criteria:
Pass
Pass
Pass
N/A
11
Result - Remark
Verdict
N/A
N/A
N/A
N/A
Pass
Pass
N/A
C.1
N/A
C.2
N/A
C.3
N/A
C.4
N/A
Attachment 4 to
SYBH(A)074112010
Page 9 of 19
Requirement + Test
D.1
Gasket tests
D.2
Pass
Pass
Pass
Pass
Compression test
(for gaskets with closed cell construction)
Pass
Pass
Pass
Pass
Pass
Pass
N/A
Swelling (%)................................................................ :
N/A
N/A
D.3
D.4
Result - Remark
Verdict
Pass
Pass
ANNEX E, RATIONALE
E.1
General
E.2
Electric shock
E.3
E.4
Fire
E.5
Mechanical hazards
E.6
E.7
Radiation
E.8
Chemical hazards
E.9
Biological hazards
E.10
Explosion hazards
Attachment 4 to
SYBH(A)074112010
Page 10 of 19
Pass
General
Delete all the country notes in the reference document according to the following
list:
4.1
Note 3
4.3
Note
8.5
Note
10.2
Note
D.3
Note
D.4
Note
Pass
ZA
ZB
N/A
4.1
N/A
10.2
N/A
D.3
N/A
Attachment 4 to
SYBH(A)074112010
Page 11 of 19
8.2a)
N/A
Material identification
(manufacturer, type designation) ...................... :
Set 1
(without Annex C conditioning)
Test sample #
Set 2
(after Annex C conditioning)
Test sample #
Attachment 4 to
SYBH(A)074112010
Page 12 of 19
8.2b)
N/A
Material identification
(manufacturer, type designation) ...................... :
Set 1
(without Annex C conditioning)
Test sample #
Set 2
(after Annex C conditioning)
Test sample #
Attachment 4 to
SYBH(A)074112010
Page 13 of 19
8.2c)
N/A
Material identification
(manufacturer, type designation) ...................... :
Test method
(according to Tables 2 and 3 of ISO 179) ......... :
Set 1
(without Annex C conditioning)
Test sample #
Set 2
(after Annex C conditioning)
2
Test sample #
Attachment 4 to
SYBH(A)074112010
Page 14 of 19
8.2d)
N/A
Material identification
(manufacturer, type designation) ...................... :
Test method
(according to Tables 2 and 3 of ISO 179) ......... :
Set 1
(without Annex C conditioning)
Test sample #
Set 2
(after Annex C conditioning)
2
Test sample #
Attachment 4 to
SYBH(A)074112010
Page 15 of 19
8.2e)
N/A
Material identification
(manufacturer, type designation) ...................... :
Test method
(according to Table 1 of ISO 180) ..................... :
Set 1
(without Annex C conditioning)
Test sample #
Set 2
(after Annex C conditioning)
2
Test sample #
Attachment 4 to
SYBH(A)074112010
Page 16 of 19
8.2f)
N/A
Material identification
(manufacturer, type designation) ...................... :
Test method
(according to Table 1 of ISO 180) ..................... :
Set 1
(without Annex C conditioning)
Test sample #
Set 2
(after Annex C conditioning)
2
Test sample #
Attachment 4 to
SYBH(A)074112010
Page 17 of 19
8.2g)
N/A
Material identification
(manufacturer, type designation) ...................... :
Set 1
(without Annex C conditioning)
Test sample #
Set 2
(after Annex C conditioning)
2
Test sample #
Attachment 4 to
SYBH(A)074112010
Page 18 of 19
8.2h)
N/A
Material identification
(manufacturer, type designation) ...................... :
Set 1
(without Annex C conditioning)
Test sample #
Set 2
(after Annex C conditioning)
2
Test sample #
Attachment 4 to
SYBH(A)074112010
Page 19 of 19
Attachment No. 5
System Diagram
Attachment contains
Cover page:
1 page
System diagram:
Total:
Attachment 5 to
SYBH(A)074112010
1 pages
2 pages
Page 1 of 2
FAN
FAN
RELAY
48VDC
TEC
48VDC
For single TEC configuration
Attachment 5 to
SYBH(A)074112010
Page 2 of 2
Attachment No. 6
Photographs
Attachment contains
(Total 9 Pages including this Cover Page, two photos mean one page)
Supplement file name
Description
photo-01
photo-02
photo-03
photo-04
photo-05
photo-06
photo-07
photo-08
photo-09
photo-10
photo-11
photo-12
photo-13
photo-14
photo-15
photo-16
photo-17
photo-18
Marking+
photo-19
Marking-
Warning label-1
photo-20
photo-21
photo-22
Warning label-2
Warning label-3
photo-23
Warning label-4
photo-24
Warning label-5
photo-25
Warning label-6
Attachment 6 to
SYBH(A)074112010
Page 1 of 22
Attachment 6 to
SYBH(A)074112010
Page 2 of 22
Attachment 6 to
SYBH(A)074112010
Page 3 of 22
Attachment 6 to
SYBH(A)074112010
Page 4 of 22
Attachment 6 to
SYBH(A)074112010
Page 5 of 22
Attachment 6 to
SYBH(A)074112010
Page 6 of 22
Attachment 6 to
SYBH(A)074112010
Page 7 of 22
Attachment 6 to
SYBH(A)074112010
Page 8 of 22
Attachment 6 to
SYBH(A)074112010
Page 9 of 22
Attachment 6 to
SYBH(A)074112010
Page 10 of 22
Attachment 6 to
SYBH(A)074112010
Page 11 of 22
Attachment 6 to
SYBH(A)074112010
Page 12 of 22
Attachment 6 to
SYBH(A)074112010
Page 13 of 22
Attachment 6 to
SYBH(A)074112010
Page 14 of 22
Attachment 6 to
SYBH(A)074112010
Page 15 of 22
Attachment 6 to
SYBH(A)074112010
Page 16 of 22
Attachment 6 to
SYBH(A)074112010
Page 17 of 22
Photo- 18 Marking+
Photo- 19 Marking-
Attachment 6 to
SYBH(A)074112010
Page 18 of 22
Attachment 6 to
SYBH(A)074112010
Page 19 of 22
Attachment 6 to
SYBH(A)074112010
Page 20 of 22
Attachment 6 to
SYBH(A)074112010
Page 21 of 22
Attachment 6 to
SYBH(A)074112010
Page 22 of 22
Attachment No. 7
Production-Line Testing Requirements
(Total 1 Pages)
Test probe
location 1
DC input
Test probe
location 2
Earthing terminal
Test Potential
Test probe
location 1
Earthing terminal
Test current, A
ITS1000M
1002Vdc
Test Time, s
2
Note:
Earthing Continuity Test
Model
ITS1000M DC
configuration
Note:
Attachment 7 to
SYBH(A)074112010
25
Test Time, s
2
Page 1 of 1