SprinklerSpacing
andLocation
RolandAsp
Manager of Technical Services
ManagerofTechnicalServices
March 5, 2013
asp@nfsa.org
RolandAsp
ManagerofTechnicalServices
1
CopyrightMaterials
AIACESProgram#:NFSATV1113
Provider#:G131
1.5LU/HSW
ThispresentationisprotectedbyUSand
InternationalCopyrightlaws.
Reproduction,distribution,displayanduseof
the presentation without written permission of
thepresentationwithoutwrittenpermissionof
TheNationalFireSprinklerAssociationis
prohibited.
NationalFireSprinklerAssociationisaRegisteredProviderwithTheAmerican
InstituteofArchitectsContinuingEducationSystems(AIA/CES).Credit(s)
earned on completion of this program will be reported to AIA/CES forAIA
earnedoncompletionofthisprogramwillbereportedtoAIA/CES
for AIA
members.CertificatesofCompletionforbothAIAmembersandnonAIA
membersareavailableuponrequest.
ThisprogramisregisteredwithAIA/CES forcontinuingprofessionaleducation.
Assuch,itdoesnotincludecontentthatmaybedeemedorconstruedto
beanapprovalorendorsementbytheAIAofanymaterialofconstruction
oranymethodormannerofhandling,using,distributing,ordealinginany
materialorproduct.
NationalFireSprinklerAssociation2013
Questionsrelatedtospecificmaterials,methods,andserviceswillbe
addressedattheconclusionofthispresentation
National Fire Sprinkler Association 2013
ProgramDescription
ReferenceMaterials
Therulesfordeterminingacceptable
spacingforspraysprinklerswillbe
reviewed.Thisincludespendent,
upright and sidewall styles Maximum
uprightandsidewallstyles.Maximum
andminimumdistancesbetween
sprinklersandthosefromsprinklersto
wallswillbecoveredalongwiththe
calculationofallowablecoverageareas
persprinkler.
National Fire Sprinkler Association 2013
2ndEdition,Layout,Detail,and
CalculationofFireSprinklerSystems,
KennethE.Isman,P.E
2013EditionofNFPA13
Whatspacesinabuildinggetsprinklers?
LearningObjectives
Everyspaceinabuildingunless
thereisaspecificexceptionthat
allowssprinklerstobeomitted.
Sprinklerscanbeomittedfrom:
Furniture&Equipment
Concealedspacesconstructedof
noncombustibleandlimited
combustiblematerial
16differentconcealedspacesmade
ofcombustiblematerial
OtherspacesasdiscussedNFPA13
7
GeneralConsiderations
Considerations
Heatrises sprinklershouldbe
locatedclosetoceiling.
Gravity waterfromthesprinkler
needstoreachfire.
Damage
D
sprinklersshouldbe
i kl
h ld b
locatedtoprotectfromphysical
damage
Ceilingconstruction
Typeofsprinklerselected
Minimumallowabledistancebetween
sprinklers
Placementofwallsandroomdividers
Maximumallowabledistancesbetween
sprinklers
Hazardclassificationoftheoccupancy
Obstructionstoheatflowand
discharge
Heatzonesnearheatsources
CeilingConstruction
10
ObstructedConstruction
Panelconstructionandother
constructionwherebeams,
trusses,orothermembers
impedeheatfloworwater
distribution in a manner that
distributioninamannerthat
materiallyaffectstheabilityof
sprinklerstocontrolorsuppress
afire.
ObstructedorUnobstructed
11
12
UnobstructedConstruction
Constructionwherebeams,trusses,or
othermembersdonotimpedeheatflow
orwaterdistributioninamannerthat
materiallyaffectstheabilityofsprinklers
tocontrolorsuppressafire.
Horizontalstructuralmembersarenot
solidandopeningsareatleast70% ofthe
crosssectionareaandthedepthofthe
memberdoesnotexceedtheleast
dimensionoftheopening.
Allconstructionwherethespacingof
structuralmembersexceeds7.5ft on
center.
Sprinklers
Conventional Residential
Standard
Response
Several Orifice Sizes
Spray
Sprinklers
Quick
Response
Several Orifice Sizes
Large
Drop
Extended
Coverage
(See Listing)
Extended Coverage
Light Hazard
ESFR
Quick Response
Extended Coverage
(See Listing)
Extended Coverage
Ordinary Hazard
13
SprinklerSpacing BasicRules
RulesforUprightandPendentSpraySprinklers
Upright,PendentandSidewall
BasicRules
ProtectionAreaofSprinkler
Maximumdistancebetweensprinklers
Maximumdistancetoawall
15
DeterminationofAreaofCoverageforEach
Sprinkler(8.5.2.1)
16
SandLDimensionsaremeasuredtothe
sprinklers,notthebranchlines
Alongbranchlines
Chooselargerof
Distancebetweensprinklers
Twicedistancetowallor
obstruction
Thisdimensionis
This dimension is S
S
Betweenbranchlines
Distancebetweenbranchlines
Twicedistancetowallor
obstruction
ThisdimensionisL
AreaofCoverage=AS =SxL
National Fire Sprinkler Association 2013
17
18
Minimumallowabledistancesbetweenstandard
spraysprinklers(8.6.3.4.2)
DetermineAreaofCoverageforEachSprinkler
Spr.
1
2
3
4
5
6
S
10
12
12
10
12
12
L
10
10
10
12
12
12
Minimumdistancebetween
sprinklers:6ft
Onlyappliestoceilingsprinklers
(notinrack)
Exceptionallowssprinklerstobe
closerthan6ftifbafflesare
installed.
AS
100
120
120
120
144
144
19
Maximumallowabledistancesbetweenstandard
spraysprinklers(8.6.2.2.1)
20
DistanceFromWalls
Maximumdistancebetween
sprinklers:
LightandOrdinaryHazard15ft
ExtraHazardandHighPiledStorage
12ft
EHandHPOccupancieswith25ft
bays,spacingof12ft6inchesis
permitted
EHandHPOccupancieswith
densitieslessthan0.25gpm/sqft,
spacingof15ftispermitted
National Fire Sprinkler Association 2013
Minimum:4inchesfromwalls
Maximum:
Maximum:oftheallowable
of the allowable
distancebetweensprinklers
Alsoseethesmallroomrule
21
MeasuringDistancestoWalls
22
MeasuringDistancestoWalls
Measureperpendiculardistance
betweensprinklerandwall
(8.5.3.2.2).Thisisthedimension
thatisnotallowedtoexceedthe
allowable distancebetween
sprinklers
i kl
Forroomswithangleslessthen90,
additionalrulethatthedistancefrom
sprinklertocornermustnotexceed0.75
allowable distancebetweensprinklers
(8.6.3.2.3)
S
S
23
24
MaximumAreaLimitationsStandardSpray
SprinklersTable8.6.2.2.1(a)
MeasuringDistancestoWalls
Light Hazard(HydraulicallyCalculated)
MaximumArea of
CeilingConstruction
CoverageperSprinkler
Thedistancefromthewalltothe
sprinklershallbemeasuredtothe
wallbehindfurniture,suchas
wardrobes,cabinets,andtrophy
cases
Noncombustible Unobstructed
225sqft
NoncombustibleObstructed
225sqft
NoncombustibleUnobstructed
Noncombustible
Unobstructed withno
with no
exposedmembers
225sqft
CombustibleUnobstructedwithexposed
members3ftor moreoncenter
225sqft
CombustibleObstructedwithexposed
members3ftormoreoncenter
168sqft
Combustible(ObstructedorUnobstructed)
withmembers lessthan3ftoncenter
130sqft
Woodjoistortruss,specialatticrules
8ftx15ftor 10ftx12ft
25
26
MaximumAreaLimitationsStandardSpray
SprinklersTable8.6.2.2.1(a)
MaximumAreaLimitationsStandardSpray
SprinklersTable8.6.2.2.1(b)
Forlighthazardoccupancypipe
schedulesystems,themaximum
areashallnotexceed200sqftper
sprinkler
OrdinaryHazard
MaximumAreaof
CalculationMethod
Coverageper
Sprinkler
All
130 ft
130sqft
27
MaximumAreaLimitationsStandardSpray
SprinklersTable8.6.2.2.1(c)
28
MaximumAreaLimitationsStandardSpray
SprinklersTable8.6.2.2.1(d)
HighPiledStorage
ExtraHazard
MaximumArea
CalculationMethod ofCoverageper
Sprinkler
Pi S h d l
PipeSchedule
90 ft
90sqft
Hydraulically
calculatedusing0.25
100sqft
gpm/sq.ft.ormore
Hydraulically
calculatedusingless
130sq ft
than0.25 gpm/sq.ft.
CalculationMethod
Hydraulicallycalculated
using0.25gpm/sq.ft.or
more
Hydraulicallycalculated
usinglessthan0.25
gpm/sq.ft.
29
Maximum
Areaof
Coverageper
Sprinkler
100sqft
130sq ft
30
SmallRoomDefinition(3.3.21)
IsThisSpacingacceptableforOrdinaryHazard?
Spr.
1
2
3
4
5
6
S
10
12
12
10
12
12
L
12
10
10
12
12
12
Roomwithinlighthazard
occupancies
Unobstructedconstruction
Floorareasnotexceeding800sqft
Eachwallcanhaveopeningswitha8
inchminimumlinteldepthandtotal
widthnotexceeding8feet
Singleopeningof3feetorless
withoutalintelispermitted
AS
120
120
120
120
144
144
31
32
SmallRoomRule
SmallRoomRule
Withinroomsoflighthazardoccupancies
havingunobstructedconstructionand
floorareasnotexceeding800sqft,
sprinklersshallbepermittedtobelocated
notmorethan9ftfromanysinglewall
Distancesbetweensprinklersand
Distances between sprinklers and
maximumarealimitationsstillapply
Theareapersprinklerisdefinedasthe
totalareaoftheroomdividedbythetotal
numberofsprinklersintheroom
AS = 30 x 15 2 = 225 sq ft
33
34
UnobstructedConstruction
withTrussesandBarJoists
DeflectorDistancesBelowCeilings
UnobstructedConstruction(8.6.4.1.1.1)
112inchesbelowceiling
1-12
End View
Side View
National Fire Sprinkler Association 2013
35
36
StandardSpraySprinklers
ObstructedConstruction
DeflectorDistancesBelowCeilings
StandardSpraySprinklers
ObstructedConstruction(8.6.4.1.2)
16inchesbelowstructuralmembers
Notmorethan22inchesbelowceiling
Seenextfewslidesforsomeexceptions
37
38
ExceptiontoObstructedConstructionRule
[8.6.4.1.2(3)]
ExceptiontoObstructedConstructionRule
[8.6.4.1.2(2)]
Sprinklerscanbeinstalledineach
bayofobstructedconstruction
withdeflectors112inchesbelow
theceiling
ExceptiontoObstructedConstructionRule
[8.6.4.1.2(4)]
Sprinklersshallonlybepermitted1to6
belowcompositewoodjoiststoamax.22
belowceiling/roofwhere joistchannelsare
firestoppedtothefulldepthofthejoists
withmaterialequivalenttotheweb
constructionsothattheindividualchannel
areasdonotexceed300sqft.
39
40
ExceptiontoUnobstructedConstructionRule
[8.6.4.1.2(5)]
Deflectorsofsprinklersunder
concreteteeconstructionwithstems
spacedlessthan7.5ftbutmorethan
3ftoncentershall(regardlessofthe
depth of the tee) be permitted to be
depthofthetee)bepermittedtobe
locatedatorabovetheplane1inch
belowthebottomofthestemsof
theteesandshallcomplywiththe
beamrule
42
ConcreteTeesBetween3ftand7.5ftOnCenter
Skylights(8.5.7)
Sprinklersarenotrequiredinskylightsup
to32sqftinarearegardlessofthedepth
andregardlessofthehazardclassification
oftheoccupancy
Appliesregardlessofthetypeofsprinkler
Applies regardless of the type of sprinkler
Ifthereismorethanoneskylightina
compartment,theyneedtobeseparated
bymorethan10ftinordertoutilizethis
provision
43
44
UnsprinkleredCeilingPockets
Ceilingpockets(8.6.7)
Sprinklerscanonlybeomittedfromceiling
pocketswhenthefollowingaremet
Volumedoesnotexceed1000ft3
Depthofthepocketdoesnotexceed36in
Floorspaceunderthepocketiscoveredby
sprinklersatthelowerceilingelevation
i kl
t th l
ili
l ti
Totalsizeofallunprotectedpocketswithin10
ftofeachotherdoesnotexceed1000cubic
feet
Constructionisnoncombustibleorlimited
combustiblefinish
Quickresponsesprinklersareusedthroughout
thecompartment
Noncombustible or
limited combustible
construction
Not to exceed 3 ft
Volume not to
Exceed 1000 ft3
Quick response sprinklers
completely protect floor area using
spacing rules of NFPA 13
45
46
CeilingPocketExample
CeilingPocketExample
Q Aresprinklersrequiredintheupperceilingarea
iftheoccupancyislighthazardandthesprinklers
areon15x15spacing?Assumeroomis20ft
wideinthedimensionnotshown.
No,sprinklersarenotrequired:
3x4x20=240ft3
4 ft
7 ft
15 ft
2 ft
4 ft
7 ft
11 ft
8 ft
15 ft
11 ft
8 ft
47
2 ft
48
Nonuniformceilings
Nonuniformceilings
Whereaceilingchangeselevationand
thedifferencebetweenthesprinkler
deflectoratthelowelevationandthe
ceilingatthehighelevationislessthan
or equal to 3 ft
orequalto3ft
Uprightandpendentstandard
sprayandextendedcoverage
sprinklers
Thedistancefromthesprinklerto
theceilingisrequiredtobe
measuredovertheentireareaof
coverageforthatsprinkler
Treatthehigherelevationasapocket;or
Sprinklerignoringthechangeinelevation
Sprinklersinupperelevationmustmeet
obstructionrulesifprotectingspaceunder
lowerceilingelevation
49
50
Nonuniformceilings
Nonuniformceilings<36ft
Ifthechangeinelevationisgreater
than3ft
Thehigherceilingelevationneeds
tohaveitsownsprinklers;and
Theplacewheretheelevation
h l
h
h l
i
changesistreatedasawallforthe
purposeofdeterminingsprinkler
spacingandlocation
51
52
Slopedceilings
Nonuniformceilings>36ft
Measuredistancebetween
sprinklersalongslope
Highestsprinklermustbe
within3ftverticallyatthe
peak
Specialrulesforvery
steeplypitchedroof
Specialrulesforconcealed
spaces(attics)
National Fire Sprinkler Association 2013
53
54
Slopedceilings
Steeplypitchedroofs
SprinklersUnderPitchedSurfaces
Distancesbetween
sprinklersaremeasured
alongtheslope
Fordeterminingthe
For determining the
amountofwaternecessary
tomeetthedensity/area
requirements(hydraulic
calculations),theprojected
areaonthefloorshallbe
used.
56
SpecialConcealedSpace(Attic)Rules
Ifconstructioniswoodjoistorwoodtruss;and
Ifmembersarespacedlessthan3ftoncenter;
and
Ifroofslopeexceeds4in12.Then:
Maximumcoverageareapersprinkleris120sqft
8x15with8ftdimensionmeasuredperpendicular
8 x 15 with 8 ft dimension measured perpendicular
toslope;or
10x12(with10ftdimensionmeasured
perpendiculartoslope)ifpressureisatleast20psi
Sprinklernearbottom,minimum 5fttothe
bottomofthespace
Sprinklerwithin12inchesofpeak
58
Sloped/ConcealedSpaceSprinklerSpacing
UnoccupiedAtticRules(8.6.2.2.1(a))
Choice 2
Choice 1
8 ft
10 ft
Plan View
Plan View
Elevation View
Elevation View
National Fire Sprinkler Association 2013
60
SidewallSprinklers
SidewallSprinklers
Section8.4.2coverswherethe
sprinklerscanbeused
LightHazardoccupancieswithflat,
smooth,horizontalceilings
LightHazardoccupancieswithflat,
smooth,slopedceilings
h l
d ili
OrdinaryHazardoccupancieswithflat
smoothceilingswherespecificallylisted
forsuchuse
Protectbeneathoverheaddoorsinany
occupancy
Section8.7coversinstallationrules
National Fire Sprinkler Association 2013
61
DeterminationofAreaofCoveragefor
EachSprinkler(8.7.2.1)
62
StandardSidewallSprinklersTable8.7.2.2.1
LightHazard
Alongthewall
Chooselargerof
Distancebetweensprinklers
Twicedistancetowallorobstruction
ThisdimensionisS
Acrosstheroom
Between
Sprinklers
Room Width
(singlerow)
Maximum
Area
Distancetowalloppositesprinkler
Midpointifsprinklersareon
oppositewalls
ThisdimensionisL
AreaofCoverage=AS =SxL
National Fire Sprinkler Association 2013
Combustible
Finish
Noncombustible
or Limited
Combustible
Finish
14ft
14ft
12ft
14ft
120ft2
196ft2
63
SidewallSprinklerExample
StandardSidewallSprinklersTable8.7.2.2.1
OrdinaryHazard
65
Combustible
Finish
Noncombustible
or Limited
Combustible
Finish
B t
Between
Sprinklers
10ft
10ft
Room Width
(singlerow)
10ft
10ft
MaximumArea
80ft2
100ft2
Standard SidewallSprinkler
StandardSidewallSprinklerLocations
SpacingConsiderations
Deflectors46fromceiling
unlessotherwiselisted.
HorizontalS/W612or12
18
Installedathighpointofslope,
Installed at high point of slope
pointingdownwithdeflector
paralleltoslope
Wheresoffitsaremorethan8
wide,anadditionalsprinkleris
requiredbelowthesoffit
Sidewallsprinklersarenotallowedtobe
installedbacktobackunlessprotected
byacontinuouslintelorsoffit(8.7.3.1.4)
Roomwidthcanbeincreasedto24ftin
lighthazardand20ftinordinaryhazard
withsidewallsprinklersontwoopposite
walls(8.7.3.1.5)
Sidewallsprinklersshallbepermittedto
beinstalledonopposingoradjacent
wallsaslongasnosprinkleriswithinthe
maximumprotectionareaofanother
(8.7.3.1.6)
National Fire Sprinkler Association 2013
67
TemperatureConsiderationsfor
LocationofSprinklers
68
ObstructionstoSprinklers
Sprinklersneedtobe
locatedfarenoughaway
fromobstructionstomake
surethatanyfireinthe
compartmentiscontrolled
p
orsuppressed
Ingeneral,useOrdinaryTemperature
sprinklersaslongasceiling
temperaturedoesnotexceed100F
Usehighertemperaturesprinklersin
thefollowing
Forambienttemperaturesover100F
seeTable6.2.5.1
Forlocalheatsources,see8.3.2.5and
Tables8.3.2.5(a) (c)
SeeFigure8.3.2.5forHighTemperature
ZoneandIntermediateTemperature
Zonearoundunitheaters
National Fire Sprinkler Association 2013
Familiarizeyourselfwiththe
obstructionruleslocatedin
Chapter8ofNFPA13
69
Summary
70
ThankYou
Questions?
DontforgettodothequizforCEUcredit.
NextTechTuesday:
1.Employtherulesfordetermining
acceptablespacingforspraysprinklers.
2.Applythemaximumandminimum
di t
distancesbetweensprinklers.
b t
i kl
3.Calculatetheallowablecoverageareas
persprinkler.
4.Applythesmallroomrulecorrectly.
March19,2013
SelectingSprinklers
Selecting
Sprinklers
Basic JefferyM.Hugo,CBO
RolandAsp
ManagerofTechnicalServices
NationalFireSprinklerAssociation
asp@nfsa.org
71