Professional Documents
Culture Documents
By George J. Berbari, Member ASHRAE Sleiman Shakkour, Member ASHRAE & Fadi Hashem, Associate Member ASHRAE
By George J. Berbari, Member ASHRAE Sleiman Shakkour, Member ASHRAE & Fadi Hashem, Associate Member ASHRAE
By George J. Berbari, Member ASHRAE; Sleiman Shakkour, Member ASHRAE; & Fadi Hashem, Associate Member ASHRAE
he United Arab Emirates (UAE) has one of the highest wetbulb design temperatures in the world (87F [30.56C]),
ASHRAE Journal
overall efficiency but also proved effective for controlling the indoor conditioned
space relative humidity.
The increased supply of outdoor air
needed for ventilation to achieve those
acceptable indoor air quality levels recommended in ANSI/ASHRAE Standard
62-1989, Ventilation for Acceptable Indoor Air Quality, significantly increases
the cooling and heating loads that the
HVAC equipment needs to handle, resulting in higher initial and operating system
costs. To compensate, system designers
look for innovative ways to reduce the
energy consumption associated with the
treatment of the supply of fresh air.
An analysis based on a 20-year life
About the Authors
George J. Berbari is CEO at DC PRO Engineering
in the UAE. Sleiman I. Shakkour is district energy
specialist at FVB Energy in Woodbridge, ON, Canada.
Fadi Hashem is assistant mechanical engineering
manager at DC PRO Engineering in the UAE.
January 2007
The six units use different air-to-air energy transfer technologies and are used to precondition outdoor air before it is mixed
with return air from the conditioned space (Figure 1).
A. Conventional fresh air-handling unit with cooling coil
and supply fan. The cooling coil dehumidifies the air to
a constant 56F (13.3C) dew point, which is equivalent
to the desired indoor condition of 76F (24.4C) dry bulb
and 50% RH, without reheating it to a neutral dry-bulb
temperature.
B. Double wheel energy recovery unit with a total recovery
wheel and a sensible heat recovery wheel. This unit has
two energy transfer stages between adjacent fresh air supply duct and exhaust air duct, with air flowing at opposite
directions, creating a counterflow heat exchange arrangement. In the first recovery phase, total energy exchange
combining both latent and sensible energy transfer is
achieved by virtue of a revolving enthalpy wheel (total
effectiveness = 80%) having an aluminum backbone
structure with a desiccant coating and large internal
January 2007
35
1
Fresh
Air
B
2
Fresh
Air
Treated
Fresh Air
3
Chilled Water
45F/55F
Bag
2 in.
Prefilter Filter
Supply
Air
4
Purge
Air
Purge
Air
1Prefilter
3Cooling Coil
Exhaust
Air
2Bag Filter
4Supply Fan
Total Energy
Recovery
Wheel
Cooling Coil
2 in.
Filter
Sensible
Energy
Recovery
Wheel
Optional
Variable Speed
Control
Return
Air
C
Fresh
Air
Chilled Water
45F/55F
2 in.
Bag
Prefilter Filter
Fresh
Air Duct
Exhaust
Air
Fresh
Air
Chilled Water
45F/55F
2 in.
Bag
Prefilter Filter
Exhaust
Air
Exhaust
Duct
Air
Purge
Air
2 in.
Filter
Runaround
Coil
Total Energy
Recovery
Wheel
Optional
Variable Speed
Control
Optional
Three-Way
Valve
Exhaust
Air
Supply
Air
Total Energy
Recovery Wheel
Return
Air
Cooling Coil
Optional Variable
Speed Control
2 in.
Filter
Heat Pipe
Optional
Variable Speed
Control
2 in.
Bag
Prefilter Filter
Purge
Air
Purge
Air
Exhaust
Air
Duct
Chilled Water
45F/55F
Fresh
Air
Fresh
Air Duct
Chilled Water
45F/55F
2 in.
Bag
Prefilter Filter
Supply
Air
Fresh
Air
Cooling Coil With Horseshoe Heat Pipe
Exhaust
Air
Purge
Air
Total Energy
Recovery Wheel
2 in.
Filter
Return
Air
2 in.
Filter
Optional Variable
Speed Control
ASHRAE Journal
ashrae.org
January 2007
Outdoor Conditions
Tdb
Twb BIN
F
F Hours
95
87 Abu-Dhabi
94
86
56.3
56.1
11.6
Sensible Wheel
Supply Exhaust
Air Outlet Air Inlet
Tdb Twb Tdb Twb
F
F
F F
25.6
70
61.3
76 63.4
Exhaust
Air Outlet
Tdb Twb
F
F
62.3
58.5
Dubai
56.3
56.1
11.4
24.7
70
61.3
76 63.4
62.3
58.5
33
56.3
56.1
14.4
16.4
70
61.3
76 63.4
62.3
58.5
106.6 76.7
91
56.3
56.1
13.7
16.7
70
61.3
76 63.4
62.3
58.5
102.1 77.7
333
56.3
56.1
12.9
17.5
70
61.3
76 63.4
62.3
58.5
97.2 78.8
687
56.3
56.1
12.0
18.4
70
61.3
76 63.4
62.3
58.5
92.3 79.1
992
56.3
56.1
11.1
18.7
70
61.3
76 63.4
62.3
58.5
56.3
56.1
10.2
17.5
70
61.3
76 63.4
62.3
58.5
56.3
56.1
9.4
14.7
70
61.3
76 63.4
62.3
58.5
56.3
56.1
8.0
10.6
70
61.3
76 63.4
62.3
58.5
56.3
56.1
6.3
6.8
70
61.3
76 63.4
62.3
58.5
110.4 76.3
57.6 54.3
279
49.1 44.2
Total
8,767
67,026 114,193
Table 1a: Double wheel heat recovery with total energy wheel and sensible energy wheel (10,000 cfm supply/exhaust model).
Outdoor Conditions
Tdb
F
95
Twb BIN
F Hours
87
110.4 76.3
33
82.6
66.2
76.0 63.4
68.5
61.3
56.3
56.1
131,760 151,300
70.4
60.8
106.6 76.7
91
81.9
66.2
76.0 63.4
68.1
61.3
56.3
56.1
127,440 151,300
70.1
60.8
102.1 77.7
333
81.0
66.5
76.0 63.4
67.6
61.8
56.3
56.1
122,040 169,100
69.7
60.4
97.2 78.8
687
80.1
66.8
76.0 63.4
67.2
62.4
56.3
56.1
117,720 186,900
69.2
60.2
92.3 79.1
992
79.1
66.9
76.0 63.4
66.7
62.7
56.3
56.1
112,320 195,800
68.7
60
78.2
66.5
76.0 63.4
66.3
62.6
56.3
56.1
108,000 195,800
68.2
59.9
77.3
65.5
76.0 63.4
65.6
61.5
56.3
56.1
100,440 160,200
68
60
75.8
63.9
76.0 63.4
64.5
60.2
56.3
56.1
88,560 120,150
66.8
59.5
74.0
62.8
76.0 63.4
64.6
59.5
56.3
56.1
89,424
65.8
59.2
57.6 54.3
49.1 44.2
Total
97,900
279
1
8,767
Table 1b: Total energy wheel with horseshoe arrangement (10,000 cfm supply/exhaust model).
To compare these units and decide which is the most advantageous to use, it is necessary to consider the cost of the
equipment and its impact on the associated chiller plant cost,
and the annual energy consumption cost. For this purpose, a
10,000 cfm (4720 L/s) model was chosen for comparison, and
it was assumed that the fan brings this amount of outdoor air
for 24 hours/day, every day of the year. Different selections and
quotations were obtained from various major manufacturers.
38
ASHRAE Journal
ashrae.org
January 2007
Equipment
Supply
Fan
kW
Supply
Fan
kWh
Exhaust
Fan
kW
Exhaust
Fan
kWh
Energy
Wheel
kWh
Sensible Runaround
Wheel Coil Pump
kWh
kWh
Total
Power
kWh
6.38
54,163
4.23
35,916
90,079
7.93
69,534
5.79
50,786
5,092
125,413
10.29
90,181
5.79
50,786
5,092
146,060
8.91
78,078
7.64
66,981
5,092
5,092
155,244
8.88
77,888
7.44
65,184
5,092
2,033
150,197
Energy Recovery
With Runaround Coil
(2.6 m/s Face Velocity)
10.67
93,504
9.34
81,893
5,092
2,033
182,521
Energy Recovery
With Heat Pipe Coil
(1.6 m/s Face Velocity)
9.12
80,000
7.69
67,444
5,092
152,537
Energy Recovery
With Heat Pipe Coil
(2.6 m/s Face Velocity)
11.14
97,657
9.85
86,337
5,092
189,086
8.31
72,857
6.63
58,096
5,092
5,092
141,137
10.29
90,181
5.25
46,040
5,092
141,314
Notes: Purge air is included. Fan static pressure includes pressure drop in wheels, cooling coil, runaround coils, heat pipe coils, filters and external pressure drop.
total energy wheel with horseshoe arrangement. Design conditions are shown in the first row according to ASHRAE climatic
design conditions. Air conditions are obtained at each section of
the unit, and the total annual cooling energy consumption was
determined in that manner. It is assumed that the unit is cycled
off when the ambient temperature drops below that required for
indoor comfort conditions in accordance with ANSI/ASHRAE
Standard 55-1992, Thermal Environmental Conditions for Human Occupancy, at 76F (24.4C) and 50% RH.
Electrical energy was calculated taking into account the power
consumption of the supply fan, the exhaust fan, the runaround
pump, and the total energy and sensible wheels energy. Total
energy was calculated based on the operating hours for each
unit.
Table 2 shows a summary for the electrical energy consumption calculation. Two cases were considered for the dual energy
recovery units with runaround coils and heat pipe options:
1. Face velocity through the coils 315 fpm (1.6 m/s); and
2. Face velocity through the coils 510 fpm (2.6 m/s).
Because of the large size of the energy wheel, enough crosssectional area is available for the coils, which helps reduce the
face velocity and consequently the energy consumption of the
fan, but for the cost of a bigger coil. Thus, these two options
were considered to study the feasibility of increasing the coils
size for reducing energy consumed.
Table 3 shows a summary of results for the cooling coil
design load, annual cooling energy and electrical energy
required for each unit.
January 2007
39
Design
FAHU Coil
Total Coil
Additional
Additional
AHU Electric
Condition Cooling Capacity Cooling Energy Cooling Effect Cooling Effect Power & Exhaust
Equipment
Fan Power
db/wb, F
Tons
Ton-Hours/Year
Tons
Ton-Hours/Year
kWh/Year
Fresh Air Handling Unit
95/87
101.0
362,139
18
150,480
90,079
34.6
195,220
18
150,480
125,413
95/87
23.7
106,243
64,357
146,060
95/87
25.6
114,193
45,831
155,244
95/87
25.3
116,385
54,234
150,197
95/87
26.2
124,014
63,858
182,521
95/87
24.7
111,299
44,609
152,537
95/87
25.9
121,471
55,609
189,086
30.5
130,349
45,831
141,137
26.3
124,785
63,224
141,314
Notes: All above AHUs have a chilled water coil for cooling and dehumidification. Additional cooling effect is measured as: 1.08cfm(76FTs,o)/12,000
where Ts,o is the supply temperature entering the space.
ASHRAE Journal
The following are summarized design parameters recommended based on the preceding analysis and our experience
installing and maintaining these systems.
Total energy or sensible wheel to have a maximum air face
velocity of 600 fpm (3 m/s). This limits the pressure drop,
blower power and cross leakage to modest levels.
Heat pipe and runaround coil to have a maximum air face
velocity of 400 fpm (2 m/s):
ashrae.org
January 2007
Equipment
FAHU
Cooling
Capacity
Ton
Chilled
Water Plant
Capital Cost
Outdoor Air
AHU & Exhaust
Fan Capital Cost
Total
Capital
Cost
Total Annual
Consumption
Cost
20 Years
Life Cycle
Cost NPV
Outdoor AHU
101.0
$121,200
$15,076
$136,276
$38,354
$382,379
34.6
$41,460
$20,000
$61,460
$24,853
$223,752
23.7
$28,440
$27,717
$56,157
$17,754
$170,806
25.6
$30,720
$26,902
$57,622
$18,988
$180,493
25.3
$30,312
$27,717
$58,029
$18,916
$180,370
26.2
$31,392
$26,087
$57,479
$21,377
$196,593
24.7
$29,592
$33,424
$63,016
$18,573
$182,505
25.9
$31,032
$29,620
$60,652
$21,499
$200,259
30.5
$36,600
$26,902
$63,502
$19,714
$190,685
26.3
$31,560
$27,717
$59,277
$19,209
$183,478
Notes: Total consumption assumed is 1.7 kW/ton. Electricity cost considered is U.S. 5.43 cents/kWh. Air cooled chiller plant is based on $1,200/ton including
mechanical, electrical, civil and utility connections works. Discount rate for net present value calculation = 11.75%.
As the area defined by the wheel allows larger rectangular coil area;
Heat pipe and runaround coils typically have lower effectiveness than sensible wheel at same face velocity,
for runaround coil or heat pipe (typically eight rows or
less); and
Life-cycle analysis justifies use of lower face velocity.
Wheels and heat pipes should be tested and rated according
to the following:
ANSI/ARI Standard 1060-2001, Performance Rating
of Air-to-Air Heat Exchangers for Energy Recovery
Ventilation Equipment; and
ANSI/ASHRAE 84-1991, Method of Testing Air-to-Air
Heat Exchangers.
Recommended maximum air duct velocity to be 1,200 fpm
(6 m/s) and total external air static pressure drop should not
exceed 1.5 in. w.g. (380 Pa) for each of the fresh air and
exhaust air ductwork. It is recommended to use the static
regain method for duct sizing.
Recommended maintenance spacing between wheel, coils,
heat pipe and fans is 1.7 ft to 2 ft (500 to 600 mm).
The energy wheel edges should be protected with an epoxy
coating (or equivalent) to eliminate edge corrosion.
Proper filtration should be provided at the fresh air intake
January 2007
41
Bibliography
2001 ASHRAE HandbookFundamentals.
Selection and Pricing Software from SEMCO Inc. Heat Pipe and
SPC Inc. and Bry-Air.
42
ASHRAE Journal
ashrae.org
January 2007