You are on page 1of 5

Full Hydraulic Calculations Computer Printout Page No 1

Submitted by Engr Anwar Ul Karim, MBA, PMP


MIEB No M/34416

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Source:

DeFire Bangladesh

Standpipe & Hose System of ATHL (3 Std Bldg 1)


Chandra. Gazipur
DB-ATHL-2H1-V1.0
Most Unfavourable
ordinary
National Fire Protection Association
2910.9 l/min @ 6.463 bar

Tel: Fax:

Project Data and Design Parameters


Project name
Area reference
Address / location
Project number
Installation number(s)
Drawing number(s)
Issue no / date
Designers reference
Project Data File
Hazard classification
Design authority
Insurance company
Specified density of discharge
Assumed maximum area of operation
Number of operating sprinkler heads
Maximum area covered per head
Highest head / nozzle above source
Number of pipes in system
Pressure loss equation used
Fluid
Pipe Data Table
Maximum fluid velocity
Volume of pipework and fittings
Elbows are welded for
Comment
Checked by & Date

:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:

Standpipe & Hose System of ATHL (3 Std Bldg 1)


Most Unfavourable
Chandra. Gazipur
DB-ATHL-2H1-V1.0
0
DB-ATHL-2H1-V1.0
17.06.15
2th floor
C:\DOC
ordinary
National Fire Protection Association
--0.00 mm/min (l/min/m2)
0.00 m2
3
0.00 m2
0.00 m
86
from 65 to 200 mm
Hazen-Williams
Water
STD_PIPE.PDT
4.47 m/s in pipe 169 170
7.13 m3
65
mm and above
---

Source duty = 2910.9 l/min @ 6.463 bar at node no 100

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com

Program FHC

Full Hydraulic Calculations Computer Printout Page No 2


Submitted by Engr Anwar Ul Karim, MBA, PMP
MIEB No M/34416
DeFire Bangladesh

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Source:

Standpipe & Hose System of ATHL (3 Std Bldg 1)


Chandra. Gazipur
DB-ATHL-2H1-V1.0
Most Unfavourable
ordinary
National Fire Protection Association
2910.9 l/min @ 6.463 bar

Tel: Fax:

Operating Sprinkler Heads, Nozzles and Hydrants


Head|Node| Size | 'K' |F l o w|A
no | no | mm | factor| l/min |
22 164
445.95
971.7
23 166
445.95
946.0
25 170
445.95
993.2

r e a|Density mm/min|Pressure bar|Heights|Pipe


m2 |Req.d
Actual| Min
Actual|
m
| no
0.000
0.00
0.00
4.50
4.748
6.940
64
0.000
0.00
0.00
4.50
4.500 10.450
66
0.000
0.00
0.00
4.50
4.961
6.940
70

0 heads are under the required density / minimum pressures

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com

Program FHC

Full Hydraulic Calculations Computer Printout Page No 3


Submitted by Engr Anwar Ul Karim, MBA, PMP
MIEB No M/34416
DeFire Bangladesh

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Source:

Standpipe & Hose System of ATHL (3 Std Bldg 1)


Chandra. Gazipur
DB-ATHL-2H1-V1.0
Most Unfavourable
ordinary
National Fire Protection Association
2910.9 l/min @ 6.463 bar

Tel: Fax:

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size
Type| L/min | Length VJ|Dir. | Eq.len | Start | Start
Frict
no | End |Bore
'C'| Vel m/s |EL T
VT|Slope| mbar/m |
End | End
Static
1 100 200mm
MW
2910.9
1.000
Up
15.96
0.000
6.463 -0.019
101 206.40 120
1.5
0 0
MV 90.0
1.2
1.000
6.346 -0.098
3 101 200mm
MW
2910.9
1.600
180
13.24
1.000
6.346 -0.016
103 206.40 120
1.5
0 1
0.0
1.2
1.000
6.330 +0.000
6 103 200mm
MW
2910.9
29.180
90
40.82
1.000
6.330 -0.048
106 206.40 120
1.5
0 1
0.0
1.2
1.000
6.282 +0.000
7 106 150mm
MW
2910.9
6.970
0
16.48
1.000
6.282 -0.078
107 155.32 120
2.6
0 1
0.0
4.7
1.000
6.205 +0.000
9 107 150mm
MW
2910.9
25.570
0
25.57
1.000
6.205 -0.120
109 155.32 120
2.6
0 0
0.0
4.7
1.000
6.084 +0.000
11 109 150mm
MW
2910.9
34.370
0
34.37
1.000
6.084 -0.162
111 155.32 120
2.6
0 0
0.0
4.7
1.000
5.923 +0.000
12 111 150mm
MW
2910.9
4.380
270
7.23
1.000
5.923 -0.034
112 155.32 120
2.6
1 0
0.0
4.7
1.000
5.889 +0.000
13 112 150mm
MW
2910.9
14.070
0
16.92
1.000
5.889 -0.080
113 155.32 120
2.6
1 0
0.0
4.7
1.000
5.809 +0.000
14 113 100mm
MW
993.2
22.120
270
29.10
1.000
5.809 -0.125
114 105.14 120
1.9
0 1
0.0
4.3
1.000
5.684 +0.000
15 113 150mm
MW
1917.7
5.940
0
5.94
1.000
5.809 -0.013
115 155.32 120
1.7
0 0
0.0
2.2
1.000
5.796 +0.000
17 115 150mm
MW
1917.7
60.720
0
60.72
1.000
5.796 -0.132
117 155.32 120
1.7
0 0
0.0
2.2
1.000
5.664 +0.000
18 117 150mm
MW
1917.7
2.100
270
4.95
1.000
5.664 -0.011
118 155.32 120
1.7
1 0
0.0
2.2
1.000
5.654 +0.000
61 118 100mm
MW
1917.7
1.520
Up
3.61
1.000
5.654 -0.053
161 105.14 120
3.7
1 0
90.0
14.5
2.520
5.452 -0.149
63 161 100mm
MW
1917.7
4.420
Up
4.42
2.520
5.452 -0.064
163 105.14 120
3.7
0 0
90.0
14.5
6.940
4.955 -0.433
64 163
65mm
MW
971.7
1.520
180
6.27
6.940
4.955 -0.206
164
68.67 120
4.4
0 1
0.0
32.9
6.940
4.748 +0.000
65 163 100mm
MW
946.0
3.510
Up
3.51
6.940
4.955 -0.014
165 105.14 120
1.8
0 0
90.0
3.9
10.450
4.597 -0.344
66 165
65mm
MW
946.0
1.520
180
3.10
10.450
4.597 -0.097
166
68.67 120
4.3
1 0
0.0
31.3
10.450
4.500 +0.000
67 114 100mm
MW
993.2
1.520
Up
3.61
1.000
5.684 -0.016
167 105.14 120
1.9
1 0
90.0
4.3
2.520
5.519 -0.149
69 167 100mm
MW
993.2
4.420
Up
4.42
2.520
5.519 -0.019
169 105.14 120
1.9
0 0
90.0
4.3
6.940
5.067 -0.433
Continued on the next page

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com

Program FHC

Full Hydraulic Calculations Computer Printout Page No 4


Submitted by Engr Anwar Ul Karim, MBA, PMP
MIEB No M/34416
DeFire Bangladesh

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Source:

Standpipe & Hose System of ATHL (3 Std Bldg 1)


Chandra. Gazipur
DB-ATHL-2H1-V1.0
Most Unfavourable
ordinary
National Fire Protection Association
2910.9 l/min @ 6.463 bar

Tel: Fax:

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size
Type| L/min | Length VJ|Dir. | Eq.len | Start | Start
Frict
no | End |Bore
'C'| Vel m/s |EL T
VT|Slope| mbar/m |
End | End
Static
70 169
65mm
MW
993.2
1.520
180
3.10
6.940
5.067 -0.106
170
68.67 120
4.5
1 0
0.0
34.2
6.940
4.961 +0.000

FHC - Hydraulic Analysis Software - Ver: 1.8.0