Professional Documents
Culture Documents
The tower manufacturer shall also have provided some or all of the following information:
(1) design exit air density, lbm/ft3
(2) design exit air temperature, F
(3) design liquid-gas ratio, L/G
(4) design air rate, acfm
If design exit air temperature is provided, the air is assumed to be saturated.
Corresponding values of specific volume and specific humidity may be obtained from
psychrometric tables or curves; either the design acfm or design L/G may be calculated
depending on which is provided. If the design air density is provided along with the design
exit air temperature, the design L/G or acfm may be calculated by using the tables. If the
design L/G is provided, the exit air conditions may be calculated by using the tables.
Enthalpy of entering air
qt
he = fn( spec:volume)
iteration method----->
Assume an exit air temp between hot and cold water temperature, obtain corresponding
sp:volume from table and calculate exit air enthalpy. Compare corresponding temperature
from table with the assumed temp and repeat till the assumed temp and calculated temp
are equal.