Professional Documents
Culture Documents
1
features for LTE and WiMAX
RF System Design Procedure
Revision 1.1
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Revision 1.0
iProtect: Internal
Page 2
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Table of Contents
1. INTRODUCTION....................................................................................................8
1.1.
SUPPLEMENT PURPOSE.......................................................................................8
1.2.
EXPLORER WINDOW..........................................................................................10
2.2.
TOOL BAR.........................................................................................................11
4.1.1.
Automatic Allocation...................................................................................17
4.1.2.
Manual Allocation.......................................................................................22
4.2.
4.3.
4.3.1.
Search Tool.................................................................................................25
4.3.2.
4.3.3.
5.1.1.
5.1.2.
6.1.1.
6.1.2.
7. REFERENCES.....................................................................................................42
8. GLOSSARY..........................................................................................................43
Revision 1.0
iProtect: Internal
Page 3
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
List of Tables
Error! No table of figures entries found.
Revision 1.0
iProtect: Internal
Page 4
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
List of Figures
Figure 1: Accessing Station Templates through the Explorer Window............................10
Figure 2: Updating the Channels within Station Templates.............................................11
Figure 3: Accessing Station Templates through the Tool Bar..........................................12
Figure 4: Determining the Maximum Power CPE Parameters........................................14
Figure 5: Coverage Image Properties Window...............................................................15
Figure 6: Transmission Power (UL) Image......................................................................16
Figure 7: Neighbours.......................................................................................................18
Figure 8: Automatic Neighbour Allocation.......................................................................19
Figure 9: Physical Cell IDs..............................................................................................20
Figure 10: Automatic Physical Cell Identification Number Assignment...........................21
Figure 11: Cell Properties................................................................................................22
Figure 12: Cell Properties................................................................................................23
Figure 13: Physical Cell IDs............................................................................................24
Figure 14: Physical Cell ID Audit.....................................................................................24
Figure 15: Physical Cell ID Audit Report.........................................................................25
Figure 16: Search Tool.....................................................................................................26
Figure 17: Search Tool Window.......................................................................................26
Figure 18: Search Results...............................................................................................27
Figure 19: Transmitter Properties....................................................................................27
Figure 20: Display Tab.....................................................................................................28
Figure 21: Field Selection................................................................................................28
Figure 22: Tip Text...........................................................................................................29
Figure 23: Physical Cell IDs............................................................................................30
Figure 24: Physical Cell Identification Number Assignment............................................31
Figure 25: Transmitter Properties....................................................................................33
Figure 26: Cells Tab.........................................................................................................33
Figure 27: Open Cells Table............................................................................................36
Figure 28: Cell Table........................................................................................................36
Figure 29: Transmitter Properties....................................................................................38
Figure 30: Cells Tab.........................................................................................................38
Figure 31: Open Cells Table............................................................................................40
Revision 1.0
iProtect: Internal
Page 5
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Revision 1.0
iProtect: Internal
Page 6
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Revision History
Atoll
Release
Revision
2.8.1
Date
Author
Description
0.1
Dec 18-2009
SSE
Internal review
2.8.1
1.0
Jan 22 2010
SSE
First Release
2.8.1
1.1
Jan 28 2010
SSE
Revision 1.0
iProtect: Internal
Page 7
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
1. Introduction
1.1. Supplement Purpose
This document contains new features introduced in Atoll version 2.8.1 that may be
useful to the processes and procedures of producing LTE and WiMAX RF system
designs. The intent of this document is to describe these new features. This document
is intended to be used along with the existing LTE and WiMAX design procedures (i.e.
the LTE RF System Design Procedure for use with Atoll v1.0 and the WiMAX RF
System Design Procedure for use with Atoll v2.8.0).
The Graphical User Interface (GUI) for Atoll v2.8.1 has minor changes compared to
v2.8.0. Only the GUI changes pertaining to the features presented in this document will
be addressed.
These feature descriptions will be incorporated into the primary RF System Design
Procedure documents when these documents are updated for the next major Atoll
Release, v2.9.0. The GUI changes for Atoll 2.9.0 will be updated in the documentation
at that point.
This document describes five new Atoll features that are introduced with the Atoll point
release v2.8.1. These features are relevant to LTE and WiMAX. Their inclusion into the
RF system design process is not mandatory. They are presented here for use in market
designs which need to show the impacts of these particular features.
ATTENTION: An error message Missing table :MUGTables may appear when opening
a project that was originally created using Atoll v2.8.0 using Atoll v2.8.1 build 3095. The
error relates to an unpopulated MUG table multi-user diversity gain which is only used
when the Proportional Fair scheduler is selected for Monte Carlo simulations. This error
will have no impact no the static modeling conducted in this supplement and can be
ignored.
All five features apply to LTE, while only two applies to WiMAX, as described below.
Revision 1.0
iProtect: Internal
Page 8
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Revision 1.0
iProtect: Internal
Page 9
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Clicking on Station Templates opens the Station Template window (See the following
figure).
Revision 1.0
iProtect: Internal
Page 10
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Channel numbers for each sector of a station template definition can be assigned in the
Channels column. The channel numbers must be separated by semi-colons (;) without
any spaces. (See the figure above). The channels need to be entered into the
Channels column in the order that they will be assigned to the sectors. For example,
based on the figure above, the first sector of a 2x2 RRH site would be assigned channel
0, the second sector would be assigned channel 1 and the third sector would be
assigned channel 2. The previous figure is for an LTE project. A similar window would
exist for WiMAX though the headings will not be the same for all of the columns, but the
Channels column would be modified the same way. Close this window when the
assignments have been completed.
Revision 1.0
iProtect: Internal
Page 11
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
This opens the properties window for the selected station configuration. Click on the
technology tab (WiMAX or LTE) at the top of this window. Click on the Cell Definition
per Sector button. This opens the Cell Definition per Sector window. Pull down the
sector selection bar and select a sector. Place the cursor in the Channels box and
enter the desired channel number to assign to the selected sector. Repeat this for all the
sectors in the site. Click OK when the assignments are completed. Then click OK on
the previous windows to complete the updates to the template. The previous figure
Revision 1.0
iProtect: Internal
Page 12
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
portrays GUI windows for an LTE project. Similar windows would exist for WiMAX,
though some of the field names will differ, but the same approach is used to get to the
Cell Definition per Sector window in order to specify the WiMAX channel numbers.
Revision 1.0
iProtect: Internal
Page 13
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
(for WiMAX) WiMAX 802.16e Parameters > Terminals > (CPE name)
Right click on the desired CPE name to open the CPE Parameters window and
determine the maximum and minimum power levels associated with this CPE (See the
following figure).
Figure 4: Determining the Maximum Power CPE Parameters
Revision 1.0
iProtect: Internal
Page 14
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Select the Display tab and pull down the items in the Field box and select
Transmission Power (UL) (dBm). Pull down the items under the Actions button and
click on shading. In the Shading window, set the value intervals to cover a range from
the maximum CPE power (for the given CPE terminal specified in the Conditions tab)
down to the minimum CPE power. It is also recommend going to the General tab and
renaming the prediction to a more meaningful description, i.e. TxPwrUL.
Revision 1.0
iProtect: Internal
Page 15
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Calculate the prediction once these settings have been made to produce an image
similar to the figure shown below:
Figure 6: Transmission Power (UL) Image
Area with
insufficient
power
The white areas (as seen in the upper left region of the previous figure) represent
locations where the CPE had insufficient transmit power to meet its lowest target MCS
(i.e. the power level required to meet the lowest MCS exceeded the power capabilities
of the CPE).
Revision 1.0
iProtect: Internal
Page 16
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
One condition which significantly impacts the validity of the physical cell identification
number assignment results is the use of a cell neighbor list as a condition within the
automatic cell identification number assignment routine. To automatically generate a cell
neighbor list for this purpose requires the following steps:
Revision 1.0
iProtect: Internal
Page 17
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
In the Explorer window, select the Data tab and right click on Transmitters. This
opens the transmitters menu. Move the cursor down to Cells, then over to Neighbors
and click on Automatic Allocation (See the following figure).
Figure 7: Neighbours
This opens up the Automatic Neighbor Allocation window (See the following figure).
Revision 1.0
iProtect: Internal
Page 18
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Select a value for the Max Inter-site Distance that is far enough to span the distance
from any randomly chosen site to two sites away. The following boxes should be
checked,
The default settings of Max No. of Neighbors as 16 and % Min Covered Area as 10%
are sufficient for purpose of generating a neighbor list to be used by the automated
physical cell identification number assignments routine.
Revision 1.0
iProtect: Internal
Page 19
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Click Calculate to generate the neighbor list. Click Commit to make it accessible by
the automated physical cell identification number assignments routine and click the
Close button to close the window.
4.1.1.2. Automatic Physical Cell Identification Number Assignment
Use the following steps to automatically generate the physical cell identification number
assignments:
In the Explorer window, select the Data tab and right click on Transmitters. This
opens the transmitters menu. Move the cursor down to Cells, then over to Physical
Cell IDs and click on Automatic Allocation (See the following figure).
Figure 9: Physical Cell IDs
This opens up the Physical Cell ID Allocation window (See the following figure).
Revision 1.0
iProtect: Internal
Page 20
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Within the Relations area, check the Neighbors and Min Reuse Distance boxes.
Enter the distance value used in Section 4.1.1.1. Within the SSS ID Allocation Strategy
area, select free (this allows every cell within a site to have a unique ID number).
Click the Calculate button to generate the physical cell identification number
assignments. Click Commit to make the ID number assignments accessible by other
Atoll features (such as ICIC) and click the Close button to close the window.
Revision 1.0
iProtect: Internal
Page 21
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
This opens the Properties window. Select the Cells tab and enter the desired
physical cell identification number in the table indicated with the red in the following
figure.
Revision 1.0
iProtect: Internal
Page 22
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Use the following steps to audit the physical cell identification number assignments:
In the Explorer window, select the Data tab and right click on Transmitters. This
opens the transmitters menu. Move the cursor down to Cells, then over to Physical
Cell IDs and click on Audit (See the following figure).
Revision 1.0
iProtect: Internal
Page 23
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
This opens up the Physical Cell ID Audit window (See the following figure).
Figure 14: Physical Cell ID Audit
Within the conditions area, check the Distance and Neighbors boxes. Enter the
distance value used in Section 4.1.1.1.
Revision 1.0
iProtect: Internal
Page 24
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Click OK button to generate the physical cell identification number assignment audit
report (See the following figure).
Figure 15: Physical Cell ID Audit Report
Review the results presented in the report. The user my take advantage of the cell ID
display features described below in Section 4.3 to determine the need to manually alter
any cell ID assignments (see Section 4.1.2).
Revision 1.0
iProtect: Internal
Page 25
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
This opens the Search Tool window (See the following figure).
Figure 17: Search Tool Window
Click on the Physical Cell ID tab at the bottom of the window. Select the Physical Cell
ID: option and enter a physical cell ID number in the box to the right of the selection
button. Click the Search button. The main map will show only the cells that match the
selected physical cell ID number selected. The up down arrows next to the physical
cell ID number in the Search Tool window can be used to quickly index through all the
assigned physical cell IDs in the system for display (See the following figure which
shows Site 3 sector 1 and Site 5 sector 2 having the same Physical Cell ID).
Revision 1.0
iProtect: Internal
Page 26
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Click on the Reset Display button in the Search Tool window to return to the normal
view of the sites.
Revision 1.0
iProtect: Internal
Page 27
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Select the Display tab at the top of the Transmitters Properties window (See the
following figure).
Figure 20: Display Tab
Pull down the Display Type: options and select Discrete values. Pull down the
Fields: options and select Cells-Physical Cell ID. Click the button next the Tip
Text box to open the Field Selection window (See the following figure).
Figure 21: Field Selection
Revision 1.0
iProtect: Internal
Page 28
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Scroll down within the Available Fields window to the Cell portion and select CellsPhysical Cell ID. Click the >> button to add it to the Selected Fields window. Click
OK to close the Fields Selection window. Click OK at the bottom of the Transmitters
Properties window. The cell markers will now display colours associated with the
physical cell ID numbers and the tip text will now include the physical cell ID number
when the cursor is placed on a cell (See the following figure).
Figure 22: Tip Text
Revision 1.0
iProtect: Internal
Page 29
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
This opens up the Distribution Histogram window (See the following figure).
Revision 1.0
iProtect: Internal
Page 30
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
The user can scroll the Detailed Results data window to see the number of times each
physical cell ID was assigned within the system.
Revision 1.0
iProtect: Internal
Page 31
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Revision 1.0
iProtect: Internal
Page 32
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
This opens the Properties window. Select the Cells tab to access the ICIC parameters
(See the following figure).
Figure 26: Cells Tab
Revision 1.0
iProtect: Internal
Page 33
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
1
2
3
NOTES:
1. Interference Coordination Support - Atoll currently supports static
ICIC modeling of the down link. To select this option, click on the right
end of the parameter box to open the following pull down menu:
Check
the
Static
DL
box
to
activate
ICIC
for
the
cell.
2. ICIC Ratio (DL) (%) The user enters the percentage of the cells
down link traffic that will be utilizing ICIC. Cells with Traffic Load (DL)
(%) = 33 would have an ICIC Ratio (DL) (%) = 100. Cells with Traffic
Load (DL) (%) = 100 would have an ICIC Ratio (DL) (%) = 0.
Revision 1.0
iProtect: Internal
Page 34
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Revision 1.0
iProtect: Internal
Page 35
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
This opens the Cells table from which the ICIC parameters described in Section 5.1.1
can be entered for all cells in the system (See the following figure).
Figure 28: Cell Table
Revision 1.0
iProtect: Internal
Page 36
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Revision 1.0
iProtect: Internal
Page 37
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
This opens the Properties window. Select the Cells tab to access the FPC parameters
(See the following figure).
Figure 30: Cells Tab
Revision 1.0
iProtect: Internal
Page 38
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
NOTES:
1. Fractional Power Control Factor Is a user selected pathloss
reduction factor that is applied when determining the required uplink
PUSCH power. This factor is represented by (alpha) in 3GPP
specifications. This pathloss reduction effectively enables Atoll to
select a lower PUSCH power than would otherwise be used to
achieve the target CINR. The factor values available run from 0 to 1.
A value of 0 represents no power control with all CPE units
transmitting at their maximum power level. This setting maximizes the
total sector throughput at the expense of CPE cell edge throughput. A
value of 1 represents full power control with all CPE units transmitting
Revision 1.0
iProtect: Internal
Page 39
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
Revision 1.0
iProtect: Internal
Page 40
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
This opens the Cells table from which the FPC parameters described in Section 6.1.1
can be entered for all cells in the system (See the following figure).
Figure 32: Cell Table
Revision 1.0
iProtect: Internal
Page 41
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
7. References
1.
Title
Atoll User Manual
2.
6.
LTE ML-CAT
7.
8.
Revision 1.0
Location/Version
http://compass.mot.com/go/31061
2680
http://compass.mot.com/go/31061
2680
http://compass.mot.com/go/18475
6262
http://compass.mot.com/go/31044
2223
http://compass.mot.com/go/31044
8858
iProtect: Internal
Date
Feb-2009
Author(s)
Forsk
Feb-2009
Forsk
Oct-2009
RFPD
Oct-2009
RFPD
Oct-2009
RFPD
Page 42
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
8. Glossary
Acronym
Meaning
AAS
AMS
AP
ENodeB
BE
Best Effort
BS
Base Site
BSID
Base Station ID
CATP
CDF
CINR
CPE
DAP
Diversity ENodeB
DL
Downlink
dB
Decibel
dBi
EFS
ERP
GAP
IAP
Intelligent ENodeB
Kbps
LOS
Line-of-sight
MAC
MAP
Mbps
MCS
MIMO
MMSE
MPR
Mbits
Megabits
NLOS
Non-line-of-sight
nrtPS
Revision 1.0
iProtect: Internal
Page 43
Supplement Atoll v2.8.1 features for LTE and WiMAX RF System Design Procedure
PDU
RTG
TXAA
SDMA
SDU
SM
Spatial Multiplexing
SNR
SISO
TDD
TMA
TTG
Tx
Transmit
TxAA
UL
Uplink
VOIP
Revision 1.0
iProtect: Internal
Page 44