Professional Documents
Culture Documents
Electrical Testing Procedures
Electrical Testing Procedures
Electrical Safety:
Policy and Procedures
Contents
1 Scope .......................................................................................................................... 5
2 Use of Equipment....................................................................................................... 5
2.1 Policy................................................................................................................... 5
2.1.1 Offices .......................................................................................................... 5
2.1.2 Laboratory .................................................................................................... 5
2.1.3 Laptops ......................................................................................................... 5
2.1.4 Home office.................................................................................................. 6
2.2 Testing................................................................................................................. 6
2.3 Auditing............................................................................................................... 7
2.4 Rig Risk Assessment ........................................................................................... 7
2.5 Elemental Risk Assessment ................................................................................ 8
2.6 Operating Procedures .......................................................................................... 8
2.7 Standard Procedures............................................................................................ 9
2.7.1 Positioning of Equipment............................................................................. 9
2.7.2 RCD Protection ............................................................................................ 9
2.7.3 Switching...................................................................................................... 9
2.7.4 Extension leads and plug boards ................................................................ 10
2.7.5 Earth bonding ............................................................................................. 10
2.7.6 Submersible equipment .............................................................................. 10
2.8 Faults ................................................................................................................. 11
2.9 Disposal............................................................................................................. 11
2.10 People .............................................................................................................. 11
2.10.1 User .......................................................................................................... 11
2.10.2 Electrical Safety Assessor ........................................................................ 11
3 Tests ......................................................................................................................... 11
3.1 Brand New Equipment ...................................................................................... 11
3.2 Equipment from Other Sources......................................................................... 12
3.3 Standard Tests ................................................................................................... 12
3.3.1 Cable damage ............................................................................................. 12
3.3.2 Casing damage and condition .................................................................... 12
3.3.3 Fuse rating .................................................................................................. 12
3.3.4 Earth bond .................................................................................................. 12
3.3.5 Insulation.................................................................................................... 13
3.3.6 Operational ................................................................................................. 13
3.3.7 Earth leakage .............................................................................................. 13
3.4 Flash Tests......................................................................................................... 13
3.5 Supplementary Tests ......................................................................................... 13
4 Documentation ......................................................................................................... 14
1
DAMTP
25 March 2004
DAMTP
25 March 2004
DAMTP
25 March 2004
DAMTP
1 Scope
This document outlines the various procedures, responsibilities, and risks
associated with the use of mains-operated electrical equipment in the Fluid
Dynamics Laboratory. The document provides guidance for the development of
Risk Assessments, and describes the various test procedures and hazards
associated with the main classes of equipment used in the Laboratory and
Workshop.
NOTE: A replacement for this document is under preparation. A draft of the
new CMS Site Policy may be found at
http://www.damtp.cam.ac.uk/lab/safety/ElectricalDraftPolicy.pdf
2 Use of Equipment
2.1 POLICY
2.1.1 Offices
No mains-operated electrical or electronic equipment may be used unless it has a
valid test sticker issued by the Department. Test stickers from other sources are
not acceptable alternatives. This requirement applies to all office equipment and
domestic appliances, including computers and even if they are brand new. Any
equipment that has been modified or is not standard equipment must be subject to
the procedures and standards outlined for laboratory equipment.
The user must be familiar with the manufacturers instructions for the equipment
and use it in accordance with these.
Failure to observe these procedures may result in sanctions or disciplinary action
against the offender.
2.1.2 Laboratory
No mains-operated electrical or electronic equipment may be used unless it has a
valid test sticker issued by the Department and a Risk Assessment has been
carried out. Test stickers from other sources are not acceptable alternatives, and
stickers are required even for brand new equipment. The user must have read and
be familiar with the Operational Procedures for the equipment. The user must also
be familiar with and adhere to the general guidance and procedures given in the
Laboratory Safety Guidelines and the specific procedures outlined below.
Failure to observe these procedures may result in sanctions or disciplinary action
against the offender.
2.1.3 Laptops
All laptops purchased or owned by the Department must be tested in accordance
with this policy, even if the laptop is never used within the Department itself.
Testing should include inspection of any multi-standard mains adapter that may
be used with the laptop.
When outside the Department, users should only connect to the mains if they are
confident that the electrical outlet is safe and that their laptop is not damaged.
25 March 2004
DAMTP
Visitors from outside the Department are requested not to connect their laptops
unless they have been tested to a level comparable to that outlined in this
document. The Department is happy to test laptops for long-term visitors. It is
recommended that short-term visitors run their laptops from batteries. The
Department does not condone the use of laptops that have not been tested and
cannot be held liable for any injury, damage or other consequence of failing to
observe this guideline.
2.2 TESTING
Prior to 2000, the test stickers on items of equipment indicated only the date the
equipment was last tested. From July 2000 onwards, the stickers indicate both the
date tested, and the date the next test is due. With the older type of stickers, the
user should seek verification that the equipment is still safe to use for any
equipment where the date is more than two years before the present. For the
newer style of sticker, equipment must not be used beyond the next test due
date.
For equipment where the mains power cable is not integral, both the cable and the
equipment itself should have a valid test sticker.
Brand new items, and equipment sourced from elsewhere must also be issued with
test stickers. The equipment must not be used until this has been completed. The
level of testing required for this is detailed elsewhere in this document.
In the Risk Assessment for a laboratory experiment, the user must list all electrical
equipment and record the next test due date for each item. It is the responsibility
of the user to react accordingly when this due date is approaching. It is
recommended that a re-test is requested four weeks before the due date. Note that
failure to request testing at least three weeks in advance of the due date may lead
to delays in the experimental programme while awaiting for a test to be
undertaken.
The user should also complete a visual inspection of all equipment on a regular
basis. Any defective, damaged or otherwise unsafe equipment should be
disconnected immediately and the reason for the disconnection indicated on the
25 March 2004
DAMTP
equipment. Notices for indicating faults are available from the Electronics
Technician. The defect should also be reported to the Electronics Technician.
Not all equipment will be subject automatically to regular testing. The testing of
items that have not been used for a long time, or are only used infrequently, may
be allowed to lapse to avoid unnecessary testing. It is the responsibility of the
user to check that the testing is up to date before connecting the equipment.
2.3 AUDITING
All equipment in active use will be audited on a regular basis. For equipment in
the Laboratory and Workshop, this auditing will occur every six months. For
equipment in the offices, this auditing will occur annually.
Typically, an audit will involve inspecting a subset of equipment to ensure the
relevant procedures have been adhered to.
During an audit (or at any other time), any equipment found not to have a valid
test sticker, found not to meet standard practices, or found to have an obvious
defect, must be disconnected immediately. Such equipment must not be
reconnected until it has been tested and any problems have been rectified. The
Safety Officer must be informed of all such equipment. In most cases, failure
during an audit will trigger a more detailed examination of any associated
equipment.
25 March 2004
DAMTP
Such separate Elemental Risk Assessments are required for all discrete electrical
components that are custom-built, modified in any way, or used in a manner or for
a purpose differing from that envisaged by the manufacturer.
All queries concerning electrical safety should be directed to the Director of the
Laboratory or the Electronics Technician. The Electronics Technician will
normally undertake any electrical tests required.
DAMTP
with the Laboratory Safety Officer. Electronic copy in Acrobat format may be
created from hardcopy by the use of a suitable scanner.
2.7.3 Switching
Never turn off, connect or disconnect equipment when your hands are wet, or
when standing on a wet floor.
25 March 2004
DAMTP
Similarly, do not operate equipment with wet hands or when you are in contact
with water unless the equipment has been designed to allow safe operation when
wet. In such cases, the need for such operation and the risks involved must be
assess in the Risk Assessment.
Ensure the power to the equipment may be safely shut off in the event of an
accident. This should be marked clearly as it may be necessary for someone
unfamiliar with the equipment or rig to do so.
Any cut-out switch should be of a type that may be operated safely with wet
hands. Operation of the cut-out switch should be tested at six-month intervals.
25 March 2004
10
DAMTP
2.8 DISPOSAL
If an item of equipment is sold, given away or otherwise disposed of, the
equipment must be marked with a sticker stating that it has not been electrically
tested and that it is the recipients responsibility to ensure the electrical safety
before use. In the case of any equipment disposed of through the rubbish, the plug
must be cut off.
2.9 PEOPLE
2.9.1 User
For the purposes of this document, the User is the person or group of people who
will make direct use of the equipment. In the case of a group, every member must
understand any limits or procedures imposed by the Risk Assessment or
Operational Procedures.
3 Tests
This section outlines the various standard tests that may be performed on
electrical and electronic equipment. Additional tests for certain categories of
equipment are detailed under the documentation for that equipment.
11
DAMTP
laid out in this document. If the equipment is deemed safe based on the
manufacturers testing then the test sticker should be completed with New in
place of the date tested, and with an appropriate date entered for the date the next
test is due. All equipment processed in this manner must be logged and the record
sheet must indicate that no tests were undertaken.
25 March 2004
12
DAMTP
The electrical resistance between all exposed metal parts and the earth terminal on
the connector should not exceed 0.1. Circumstances where the resistance
exceeds this value should be investigated and, when there is an acceptable reason
for higher values, this should be noted on the test sheet. A resistance exceeding
0.1 must either lead to the equipment being repaired or decommissioned, or lead
to a full Risk Assessment being undertaken.
If an earlier test or Risk Assessment has recorded a resistance more than 20%
lower than the new figure, the reasons for this must be explained and assessed.
3.3.5 Insulation
This test applies 500V DC between the power conductors and a nominal earth.
This test should not be performed on electronic equipment.
This test is different if earthed or double-insulated equipment. For earthed
equipment, the test is between the combined live/neutral pins and the earth pin.
For double-insulated equipment, the test is between the combined live/neutral pins
and a probe applied to the outside of the case. For submersible double-insulated
equipment, the second probe may be applied to the liquid surrounding the
submersed item; this will provide a check for any cracks in the insulation through
which the liquid may penetrate.
If the insulation is found to be less than 2M, then the equipment must be
repaired or decommissioned.
3.3.6 Operational
Check that current within specified limits.
The equipment should be run in accordance with the standard operational
procedures and the current drain measured. This current should be within 20% of
the value specified by the manufacturer (or in any Risk Assessment).
The source of any unexpected noise should be investigated.
Any evidence of sparking (except if as an intended part of the equipment design)
must be investigated.
Failure of this test must either lead to the equipment being repaired or
decommissioned, or lead to a full Risk Assessment being undertaken.
25 March 2004
13
DAMTP
actually submersed, and confirmation of earth terminals and routes to earth for
probes. Recommended supplementary tests for each category of equipment are
listed in 7.
4 Documentation
4.1 RECORD SHEET
The test record sheet for every item should be completed. If an item fails, this
should be recorded, along with details of the cause of failure. Details of the
remedy should also be recorded.
Any item that deviates from the expected performance (e.g. the operational
current), must be noted along with the conditions under which the deviation was
found. Future tests should always include assessing whether this level of deviation
has changed.
When a record sheet is changed, it must be moved to the Updated folder. At
regular intervals, the details in this folder will be added to the database and the
corresponding sheets returned to the main folder.
If an item is disposed of, the record sheet should be removed from the main series
and transferred into the Decommissioned folder. The reason for
decommissioning should be recorded.
4.3 DATABASE
The database should reflect the contents of the Record Sheets and tie this
information in with the main equipment inventory, operation manuals and risk
assessments.
The database should be updated at regular intervals (at least quarterly) from the
Record Sheets contained in the Updated folder. Once the details contained by an
updated Record Sheet has been transferred to the database, the sheet should be
marked and returned to the main folder.
Once a quarter, the database should be used to generate a list of equipment for
which a test is over due, and a list of tests due in the coming quarter.
25 March 2004
14
DAMTP
5 Office Equipment
5.1 OFFICE APPLIANCES
5.1.1 Desk lamps
Elements of risk assessment
Location.
Proximity to combustible material.
Routing of cable.
Test interval
Three years.
Tests required
Standard tests.
Switch.
5.1.2 Fans
Elements of risk assessment
Location.
Routing of cable.
Stability.
Test interval
Three years.
Tests required
Standard tests.
Finger guards.
5.1.3 Heaters
Elements of risk assessment
Location.
Routing of cable.
Stability.
Proximity to flammable materials.
Test interval
Three years.
Tests required
Standard tests.
Finger guards.
Tilt switch.
25 March 2004
15
DAMTP
Test interval
Three years.
Tests required
Standard tests.
Automatic turn off.
5.2.2 Microwaves
Manual kettles are not permissible.
Test interval
Three years.
Tests required
Standard tests.
Timer.
Test interval
One year.
Tests required
Standard tests.
25 March 2004
16
DAMTP
5.3 IT EQUIPMENT
5.3.1 Computers
Elements of risk assessment
Location.
Ergonomics.
Routing of cables.
Power and data.
Interchangeable power cables.
These must be designated explicitly to the associated IT item and not
interchanged with any other cable. The 13A mains plug must be clearly
marked as to which item it belongs to. It is recommended that the IEC
connector is also marked. The cable must carry a test sticker and be re-tested
at the same time as the computer. If either the cable or the computer has a test
sticker that is out of date, then both must be re-tested.
Test interval
Three years.
Tests required
Standard tests.
Cable.
Dust.
Fan operational.
Obstruction of ventilation.
Internal operational temperatures (where motherboard/BIOS provide these).
25 March 2004
17
DAMTP
Test interval
Three years.
Tests required
Standard tests.
Obstruction of ventilation.
5.3.3 Laptops
Elements of risk assessment
Damage due to transportation.
Especially of power cables and power supplies.
Connection to other standards.
Any adapters should be tested.
Test interval
One year.
Tests required
Standard tests.
Cable.
Adapter.
5.3.4 Printers
Elements of risk assessment
Adequacy of ventilation.
Toner spillage.
Interchangeable power cables.
These must be designated explicitly to the associated IT item and not
interchanged with any other cable. The 13A mains plug must be clearly
marked as to which item it belongs to. It is recommended that the IEC
connector is also marked. The cable must carry a test sticker and be re-tested
at the same time as the printer. If either the cable or the printer has a test
sticker that is out of date, then both must be re-tested.
Test interval
Three years.
Tests required
Standard tests.
Cable.
Obstruction of ventilation.
Filters.
Internal dust and toner.
25 March 2004
18
DAMTP
Test interval
Three years.
Tests required
Standard tests.
Test interval
Three years.
Tests required
Standard tests.
Test interval
Three years.
Tests required
Standard tests.
Test interval
As recommended in Service Contract.
Tests required
As recommended in Service Contract.
5.5.2 Binders
25 March 2004
19
DAMTP
Test interval
Three years.
Tests required
Standard tests.
Finger guards.
Test interval
Three years.
Tests required
Standard tests.
Fan & ventilation slots.
Procedure for replacing bulb.
Test interval
One year.
Tests required
Standard tests.
Fan & ventilation slots.
Procedure for replacing bulb.
Test interval
Three years.
25 March 2004
20
DAMTP
Tests required
Standard tests.
Fan & ventilation slots.
Procedure for replacing bulb.
Test interval
Three years.
Tests required
Standard tests.
Obstruction of ventilation.
6 General Equipment
6.1 CATERING EQUIPMENT
All catering equipment in the Pavilion A kitchen is the responsibility of the
University Catering Service. Members of the Department do not have access to
this equipment. All testing and servicing of this equipment will be arranged by
the University Catering Service.
6.2 PLANT
All plant, including machinery located in the Plant Room, wall-mounted or
under-bench water heaters, hand driers, extract equipment and other fixed
equipment is the Responsibility of Estate Management and Building Services.
Members of the Department have a responsibility to report any faults, but
EMBS will arrange for any tests necessary.
7 Laboratory Equipment
7.1 OFFICE APPLIANCES
7.1.1 Desk lamps
Elements of risk assessment
Location.
Proximity to combustible material.
Protection for luminary.
25 March 2004
21
DAMTP
Test interval
Three years if in Office.
Two years if in Laboratory.
Tests required
Standard tests.
Switch.
7.1.2 Fans
Elements of risk assessment
Location.
Stability.
Test interval
Three years if in Office.
Two years if in Laboratory.
Tests required
Standard tests.
Finger guards.
Test interval
One year.
Tests required
Standard tests.
RCD plug (wet and dry).
Test interval
Three years.
Tests required
Standard tests.
25 March 2004
22
DAMTP
7.2.2 Refrigerator
Elements of risk assessment
Nature of contents.
Location of electrics in event of leakage.
Test interval
Three years.
Tests required
Standard tests.
Dust on condenser & compressor.
Corrosion damage.
Warning notices.
7.2.3 Freezer
Elements of risk assessment
Nature of contents.
Use: storage or experiment.
Risk of damage from experiments.
Location of electrics in event of leakage.
Test interval
Two years.
Tests required
Standard tests.
Dust on condenser & compressor.
Corrosion damage.
Warning notices.
Temperature within acceptable range.
7.3 IT EQUIPMENT
7.3.1 Computers
Elements of risk assessment
Office or Laboratory location.
Location relative to experiments.
Risk of splashing.
Connection to control or measurement circuits.
Connection to data ports and other computer peripherals.
25 March 2004
23
DAMTP
Test interval
Three years.
Tests required
Standard tests.
Dust.
Fan operational.
Obstruction of ventilation.
Internal operational temperatures (where motherboard/BIOS provide these).
Test interval
Three years.
Tests required
Standard tests.
Obstruction of ventilation.
7.3.3 Printers
Elements of risk assessment
Office or Laboratory location.
Risk of splashing.
Adequacy of ventilation.
Test interval
Three years.
Tests required
Standard tests.
Obstruction of ventilation.
Filters.
Internal dust and toner.
25 March 2004
24
DAMTP
Test interval
Three years.
Tests required
Standard tests.
Test interval
One year.
Tests required
Standard tests.
Test interval
Three years.
Tests required
Standard tests.
Obstruction of ventilation.
25 March 2004
25
DAMTP
Risk of splashing.
Adequacy of ventilation.
Stability and crispness of picture.
Equipment stacks.
Video monitors are often positioned directly on top of VTRs. While this
practice is acceptable, it is not acceptable to subsequently position any further
equipment or items on top of the video monitor.
Test interval
Three years.
Tests required
Standard tests.
Obstruction of ventilation.
Test interval
Three years.
Tests required
Standard tests.
Obstruction of ventilation.
Test interval
Three years.
Tests required
Standard tests.
26
DAMTP
Test interval
Two years.
Tests required
Standard tests.
Test interval
Two years.
Tests required
Standard tests.
Obstruction of ventilation.
Damage to low voltage cable.
Test interval
Two years.
Tests required
Standard tests.
Obstruction of ventilation.
25 March 2004
27
DAMTP
Operation of fan.
Integrity of tripod plate or other mounting system.
Test interval
Two years.
Tests required
Standard tests.
Obstruction of ventilation.
Case temperature.
28
DAMTP
Test interval
Two years.
Tests required
Standard tests.
Test interval
Two years.
Tests required
Standard tests.
Diffusers and end caps.
The diffuser and end caps provide part of the protection to the tube and
electrics within the lamp. The diffuser and end caps, or a suitable alternative
arrangement, must be secure and intact.
Temperature.
25 March 2004
29
DAMTP
The operational temperature, when the lamp has been left on for a number of
hours, should be checked if air flow around the lamp is hindered in any way.
Test interval
Two years.
Tests required
Standard tests
25 March 2004
30
DAMTP
ensure no light causes a risk or inconvenience to other Laboratory users. Noncombustible materials must be used for any shielding closer to the lamp than
500mm. All shielding must be secured firmly and designed to prevent any
hindrance to the air flow through the lamp.
Can low voltage lamps or light sources in other locations be used instead?
The typical location of these turntable lamps exposes the user to greater risk
than would be the case if the lighting was provided by low voltage lamps or
provided from a remotely mounted lamp.
Test interval
One year.
This short test interval is required due to the presence of the high voltages
associated with striking the arc.
Tests required
Standard tests.
Obstruction of ventilation of power supply.
Obstruction of ventilation of lamp.
Check cable to lamp.
Check and clean cable terminals/connectors.
Test interval
Two years.
Tests required
Standard tests.
7.6 LASERS
Not currently in use. Secured under lock and key.
25 March 2004
31
DAMTP
It is often possible and desirable to locate the power supplies well clear of the
experiment, bringing only low-voltage connections through to the experiment.
Adequacy of ventilation.
Adequacy of physical attachment.
When the supply is integrated into an experimental rig such as a rotating table,
it is essential that it is firmly attached.
Low-voltage route to earth.
Under most circumstances the low voltage side of the power supply should be
earth-referenced. This will ensure that, in the event of power supply failure,
the equipment will remain safe. This earth referencing is most conveniently
achieved at the power supply itself; often power supplies have an earth
terminal and a removable strap between this and either the positive or
negative side. If connection to earth is not possible or not desirable (e.g. to
avoid earth loops), then an earth point should still be provided somewhere in
the equipment.
Test interval
Two years.
Tests required
Standard tests.
Obstruction of ventilation.
Earth terminal.
Test interval
Two years.
Tests required
Standard tests.
Low voltage cable insulation.
25 March 2004
32
DAMTP
Test interval
One year.
Tests required
Standard tests.
Check HV insulation.
Test interval
Two years.
25 March 2004
33
DAMTP
Tests required
Standard tests.
Input/output isolation.
Test interval
Two years.
Tests required
Standard tests.
Probe isolation.
7.8.3 Multimeters
Battery-powered multimeters should also be tested.
Test interval
Two years.
Tests required
Standard tests.
Probe isolation.
7.8.4 Oscilloscopes
Elements of risk assessment
Location relative to experiments.
By use of probe cables of a suitable length, the location of the oscilloscope
need not be close to the experiment.
25 March 2004
34
DAMTP
Test interval
Two years.
Tests required
Standard tests.
Probe isolation.
Test interval
One year.
Tests required
Standard tests.
25 March 2004
35
DAMTP
Check HV insulation.
Test interval
Two years.
Tests required
Standard tests.
Output isolation.
Test interval
Two years.
Tests required
Standard tests.
Output isolation.
7.9.3 AC motors
Elements of risk assessment
Location relative to experiments.
Risk of splashing or leaks.
Adequacy of physical attachment.
Risk of entanglement or injury.
25 March 2004
36
DAMTP
Test interval
Two years.
Tests required
Standard tests.
7.10 PUMPS
7.10.1 Integrated pumps
Elements of risk assessment
Location within experimental rig.
Risk of splashing or leaks.
What additional risks will occur if the pump leaks risks both due to the pump,
and due to anything that may be contaminated as the result of the pump
leaking?
Adequacy of physical attachment.
Cable routing.
Does this take the best route available? Is it protected from mechanical
damage? Is it possible to inspect the cable for damage?
Switching and control.
How is the pump to be controlled? Can it be shut off safely in the result of a
leak or a detached hose?
Guards.
Some integrated pumps are not self-contained units. In such cases, the
question of whether guards are necessary should be addressed.
Test interval
Two years.
Tests required
Standard tests.
Check for leaks.
Test interval
Two years.
25 March 2004
37
DAMTP
Tests required
Standard tests.
Check for leaks.
Test interval
One year.
Tests required
Standard tests.
Optional: check insulation and/or leakage current when submerged.
RCD required.
Test interval
Two years.
Tests required
Standard tests.
25 March 2004
38
DAMTP
Test interval
One year.
Tests required
Standard tests.
Speed control.
RCD required.
Check for leaks.
Check shielding from water.
Test interval
One year.
Tests required
Standard tests.
Speed control.
RCD required.
7.11 TURNTABLES
7.11.1 Turntables
Elements of risk assessment
Location of controller.
Can this be operated safely while the table is rotating?
Risk of splashing or leaks.
Is the controller located well clear of any splashes or leaks? Are the turntable
motor and mains outlets adequately protected?
Adequacy of physical attachment.
Are all items on the turntable adequately secured?
Risk of entanglement or injury.
Are there sharp corners on the turntable or equipment mounted on it?
Trip hazard.
The routine of the cables between controller and turntable. Also any other
potential hazards around the turntable base.
25 March 2004
39
DAMTP
Emergency shut-off.
Are the provisions for stopping the turntable in an emergency adequate? Will
this also cut the power to the mains sockets?
Maximum speed.
Is there a limit on the maximum speed of the turntable? Is this limit safe? Who
has the ability to change or over-ride this limit? What will happen if this limit
is exceeded?
Test interval
Two years.
Tests required
Standard tests.
RCD required.
Shut-off switch.
Speed limiter.
Verify that turntable cannot be rotated faster than the maximum allowable
speed.
Test interval
Two years.
Tests required
Standard tests.
Check for leaks.
Check earth leakage current when full.
7.12.2 Stirrers
Elements of risk assessment
Location relative to experimental rig.
Risk of splashing or leaks.
What additional risks will occur if the bath or associated tubing leaks risks
both due to the bath, and due to anything that may be contaminated as the
result of the bath leaking?
25 March 2004
40
DAMTP
Test interval
Two years.
Tests required
Standard tests.
7.12.3 Scales
Elements of risk assessment
Location.
Contamination by chemicals.
Test interval
Two years.
Tests required
Standard tests.
Test interval
Two years.
Tests required
Standard tests.
Check for leaks.
Check leakage current when immersed.
RCD required.
25 March 2004
41
DAMTP
The metalwork of tanks may become live due to the failure of equipment, the
incorrect connection of equipment, or as a result of stray electromagnetic
fields. To prevent this happening, all metalwork must be connected to earth as
described by the wiring regulations BS7671.
A conductor with cross-section not less than 6mm2 must connect all fixed
frames to a suitable earth. Water supply pipe work may be used as the earth
only once its continuity to earth has been adequately verified to have a
resistance of less than 0.1.
Moveable frameworks and tanks must be provided with a suitable earth
terminal and lead. This earth lead must be connected to a suitable earth
whenever the framework or tank is used in conjunction with any electrical
equipment. It is recommended that the connection be made through the same
RCD-protected circuit as the electrical equipment used with the framework or
tank. This connection may be through a dedicated earth terminal on the
electrical equipment, or using an adapted earth-only mains plug inserted into
a socket.
Each electrically separate but mechanically integrated part of the metalwork
must be connected with an earth strap of at least 2.5mm2 cross-section (4mm2
if not sheathed or mechanically protected). This earth strap may be omitted
only when a reliable earth with a resistance of less than 0.1 is formed as an
inherent part of the design of the framework or tank.
Test interval
Three years.
Tests required
Test earth bonding of all exposed metal work on frames and tanks.
Test interval
Three years.
Tests required
Visual inspection.
Earth continuity.
Fuse.
25 March 2004
42
DAMTP
Test interval
Two years.
Tests required
Visual inspection.
Earth continuity.
Fuse.
Test interval
One year.
Tests required
Visual inspection.
Earth continuity.
Fuse.
RCD.
25 March 2004
43
DAMTP
Excess cable should be avoided, within reason. Cable may only be coiled if the
total load on the plug board is less than 50% of the rated load of the cable,
and even then only coiled loosely (diameter of coil greater than 250mm).
Similarly, cables should not be stretched taut.
Trip hazard.
Standing.
The plug board must not be located where it may be accidentally kicked or
stood on.
Total electrical load.
Cascading
No plug board should have more than one further plug board connected to it
either directly or indirectly,
Test interval
One year.
Tests required
Standard tests.
Test interval
Two years.
One year if not integrated into apparatus.
Tests required
Standard tests.
25 March 2004
44
DAMTP
Test interval
One year.
One year if not integrated into apparatus.
Tests required
Standard tests.
7.16 RCDS
7.16.1 RCD adapters
Elements of risk assessment
Test interval
Six months.
Tests required
Visual inspection
Check trip current
25 March 2004
45
DAMTP
Test interval
Three years.
Tests required
Standard tests.
7.17.2 Heaters
Elements of risk assessment
Cable routing.
Proximity of combustible material.
Test interval
Three years.
Tests required
Standard tests.
Tests required
Standard tests.
Isolator.
Cut-out switch.
Operating procedures.
7.18.2 Flumes
Elements of risk assessment
Test interval
Two years.
Tests required
Standard tests.
Isolator.
Cut-out switch.
Operating procedures.
25 March 2004
46
DAMTP
Tests required
Standard tests.
Isolator.
Cut-out switch.
Operating procedures.
Tests required
Standard tests.
Isolator.
Cut-out switch.
8 Workshop
8.1 HAND TOOLS
8.1.1 Drills
Elements of risk assessment
Damage to cable.
Indirect mechanical damage due to regular use and exposure to potentially
abrasive or sharp obstacles.
Contact with live circuits when drilling.
Always check that nearby circuits are isolated before drilling.
RCD protection.
The drill should normally be connected to the mains through a RCD plug
permanently wired to its cable.
Eye protection.
Ear protection.
Test interval
Two years.
Tests required
Standard tests.
8.1.2 Grinders
25 March 2004
47
DAMTP
Test interval
One year.
Tests required
Standard tests.
RCD required.
8.1.3 Saws
Elements of risk assessment
Damage to cable.
There are two principal sources of cable damage: indirect mechanical damage
to the cable (from sharp or abrasive obstacles), and direct damage to the cable
through it contacting with the saw blade.
Contact with live circuits when grinding.
Always check that nearby circuits are isolated before cutting.
RCD protection.
The saw should normally be connected to the mains through a RCD plug
permanently wired to its cable.
Eye protection.
Ear protection.
Test interval
One year.
Tests required
Standard tests.
RCD required.
8.1.4 Routers
Elements of risk assessment
Damage to cable.
There are two principal sources of cable damage: indirect mechanical damage
to the cable (from sharp or abrasive obstacles), and direct damage to the cable
through it contacting with the router cutter.
25 March 2004
48
DAMTP
RCD protection.
The router should normally be connected to the mains through a RCD plug
permanently wired to its cable.
Eye protection.
Ear protection.
Test interval
One year.
Tests required
Standard tests.
RCD required.
Test interval
Two years.
Tests required
Standard tests.
Test interval
Two years.
Tests required
Standard tests.
Test interval
Three years.
Tests required
Standard tests
25 March 2004
49
DAMTP
Tests required
Standard tests
Isolator
Cut-out switch
8.3.2 Lathes
Elements of risk assessment
Test interval
Three years.
Tests required
Standard tests
Isolator
Cut-out switch
Tests required
Standard tests
Isolator
Cut-out switch
8.3.4 Compressor
Elements of risk assessment
Test interval
Three years.
Tests required
Standard tests
Isolator
Cut-out switch
25 March 2004
50
DAMTP
Tests required
Standard tests
Isolator
Cut-out switch
25 March 2004
51