You are on page 1of 1

To, Report Date : 16-04-2021

Executive Engineer , M.S.E.D.Co.Ltd.


KARJAT (R) DIVISION

Subject : Distribution Transformer Failure (B-06) Report

Notification No. :- 1001672534 Equipment No.:- 1000000008268842


ERP MO No.:- 100000314320 ERP PO No.:- Not Generated
Date of Failure :- 01-04-2021 Date of Commissioning :- 25-03-2021
Eqp Guarantee Start Date :- 01-01-2021 Eqp Guarantee End Date :- 01-02-2022
Functional Location :- M-Z057-C570-D574-SDN196-DTC5196605
DTC Code - Name :- 5196605 - CHIKALTHAN WADI ; Lat-Long : Not Available
Feeder Code-Name : 204 - 11 KV Pedgaon Gaothan SS Code-Name : 014183 - 33/11 KV Pedgaon
Substation
Circle Name :- A' NAGAR CIRCLE Division Name :- KARJAT (R) DIVISION
Subdivision Name :- SHRIGONDA Section Name :- Adhalgaon Section

Sr. No. Parameter Description Results


1 Equipment Material Code 20113006453
2 Capacity 63 KVA
3 Voltage 11 KV
4 Phase 3
5 Make_code - Serial No 0736-4196699
6 Make code descr ACCORD ELECTROPOWER PVT.LTD
7 Peak Hour Load(A) (LT Side) 56.0 AMP
8 Total Connected Load(KW) on Equipment 45.0 KW
9 Whether Equip Previously Sick? YES
10 Apparent Cause of Failure 30 - Voltage Fluctuation
11 Is it due to manufacturing defect? YES
12 Climatic condition CLEAR
13 Oil level OK
14 Oil Capacity in Litres 88.0
15 Silica gel condition at the time of failure OK
16 Whether Lightening Arrester provided YES
17 Lightening Arrester Condition OK
18 Did LT Fuse Blown? NO
19 Did DO Fuse Blown? YES
20 Did SS Feeder Breaker Tripped? NO
21 Insulation test results a)LV-E (MegaOhm) 100.0
b)HV-E (MegaOhm) 100.0
c)LV-HV (MegaOhm) 50.0
22 Is Transformer New or Repaired ? REPAIRED
23 DTC Type NON_AG
24 Name of Scheme NSC
25 Remark Gaothan dtc

Section Officer.
Ganesh Vijay Wadate (Assistant
Engineer(Distribution))

You might also like