You are on page 1of 1

To, Report Date : 02-06-2021

Executive Engineer , M.S.E.D.Co.Ltd.


KARJAT (R) DIVISION

Subject : Distribution Transformer Failure (B-06) Report

Notification No. :- 1001782432 Equipment No.:- 1000000007935847


ERP MO No.:- 100000328062 ERP PO No.:- Not Generated
Date of Failure :- 01-06-2015 Date of Commissioning :- 01-06-2012
Eqp Guarantee Start Date :- 01-06-2012 Eqp Guarantee End Date :- 01-06-2017
Functional Location :- M-Z057-C570-D574-SDN196-DTC4196703
DTC Code - Name :- 4196703 - GAOTHAN ; Lat-Long : Not Available
Feeder Code-Name : 207 - 11KV VELU SS Code-Name : 017010 - 132KV SHRIGONDA
Circle Name :- A' NAGAR CIRCLE Division Name :- KARJAT (R) DIVISION
Subdivision Name :- SHRIGONDA Section Name :- Adhalgaon Section

Sr. No. Parameter Description Results


1 Equipment Material Code 20101242583
2 Capacity 25 KVA
3 Voltage 11 KV
4 Phase 3
5 Make_code - Serial No 0999-458644212
6 Make code descr NNP
7 Peak Hour Load(A) (LT Side) 22.0 AMP
8 Total Connected Load(KW) on Equipment 15.0 KW
9 Whether Equip Previously Sick? YES
10 Apparent Cause of Failure 06 - External short
11 Is it due to manufacturing defect? YES
12 Climatic condition RAINY
13 Oil level OK
14 Oil Capacity in Litres 44.0
15 Silica gel condition at the time of failure OK
16 Whether Lightening Arrester provided YES
17 Lightening Arrester Condition OK
18 Did LT Fuse Blown? YES
19 Did DO Fuse Blown? NO
20 Did SS Feeder Breaker Tripped? NO
21 Insulation test results a)LV-E (MegaOhm) 100.0
b)HV-E (MegaOhm) 100.0
c)LV-HV (MegaOhm) 50.0
22 Is Transformer New or Repaired ? NEW
23 DTC Type NON_AG
24 Name of Scheme NSC
25 Remark GAOTHAN DTC. CHIKHALTHANWADI
VILLAGE

Section Officer.
Ganesh Vijay Wadate (Assistant
Engineer(Distribution))

You might also like