DEMULSIFIER CHEMICAL INJECTION SKID

ELECTRICAL DATASHEET FOR


DEMULSIFIER INJECTION PUMP MOTOR

Doc. No. LEK-42-4500697254-ZV-E07-00002-0000


02 10.08.16 DE Re-Issued for Approval DM DM -

01 22.03.16 DE Issued for Approval DM DM -

REV DATE BY DESCRIPTION CHK'D APPR CLIENT


Data / requisition sheet for Design book No. : page: 2
Demulsifier Injection Pump Motor Contr. job No. : ELCO-16-008
MESC No. :
1 REQUIREMENTS AND CONDITIONS
2 Specific requirements : DEP 33.66.05.31-GEN, SP-1119
3 Driven Equipment : P-42101A/B/C/D/E ; Type :Refer to Mech. Datasheet
4 Requisition number driven equipment : TBA (If yes refer to VSDS requisitio
5 Motor part of Variable Speed Drive System : no / yes
6 Power Rating : 0.75 kW (Refer to Mechanical data sheet)
7 Speed : 1440 min-1 (synchr) (for VSDS refer to VSDS requisitio
8 Direction of rotation (facing driving end) : Clock wise (or) Counter clock wise Refer to Mech. Datasheet
9 Electrical Supply system : Voltage : 415V, 3 Phase 3 PH + N + PE Frequency :
10 Deviations from nominal voltage / frequency : +/- 5% / +/-2% (details separately sp
11 Service conditions : Continous ambient temperature of 55deg C and 98% Humidity (details separately sp
12 Location : Land / Offshore
13 Number of starts per year : 1000 Starts / Yr as per DEP 33.66.05.31-Gen clause 9.12.3
14 Area Classification of motor : Non hazardous / Zone 2 / Zone 1 ; II A / B / C ; T3 (as per IEC 60
15 Protection type : Ex 'nA' / Ex 'd' / Ex 'e' / Ex 'p'
16 Combustible dust present : no / yes (As per IEC 61241)
17 Test points for shock pulse monitoring (SPM) : no / yes *) (for roller bearin
18 Anti condensation heaters : no / yes (Motors ≥75 kW) Tropical treatment required : no / yes
19 Winding temperature detectors required : no / yes *) Mounting : Horizontal / vertical ; foot / flange
20 Earthquake proof : no / yes *) :
21 Witnessed factory acceptance tests : no / yes *) Motor cable after order placement : Type : Cu/XLPE/SWA/PVC
22 Special tests required (if yes, specify) : no / yes *) : Size : 3C x 2.5 sq.mm (Appr. 15 mm Overall Dia.)
23 Language on equipment : English / Type of Glands : M20
24 Language on documentation : English / Selection based on annual cost : no / yes (details separately sp
25 For motor < 75kW, provided with facility to measure the vibration on the motor (offline monitoring)", And Motor > 75kW & all non accessible LV motors, provided with vibration probes for online monitoring.
26 INFORMATION TO BE SUBMITTED BY MANUFACTURER WITH THE QUOTATION
27 Make and type of motor : ABB & M3GP 80 MD 4
28 Motor designed/tested for VSDS duty : no / yes
29 Country of manufacture : ABB
30 Rated power : 0.75 kW at power factor: 0.71
31 Speed : 1440 rmin-1
32 Full load current (FLC) : 1.8 A
33 Locked rotor current : VTA % of FLC at Un ; VTA % of FLC at 0.8 Un
34 Locked rotor torque : 2.9 % of FLT at Un ; VTA % of FLT at 0.8 Un
35 Efficiency : 81.1 % at full load ; 80.9 % at 75% load
36 Frame size / type of mounting : 80 MD 4 / IM-3001, B5 (Flange)
37 Direction of rotation (facing driving end) : Clock wise (or) Counter clock wise
38 Bearing type : Driving End: 6204-2Z/C3 Non DE : 6203-2Z/C3
39 Type of Explosion protection : Ex nA IIC T3 Gc
40 Te time : NA s (for Ex'e' only)
41 Ex Certification available : yes; Certificate of conformity / Declaration of compliance
42
43 Details as per *) provided : Yes / no / not applicable
44 Deviations from the DEP and the requirements of this requisition (if yes give details) :
45 no / yes
46 SPECIAL REQUIREMENTS AND REMARKS REMARKS ON REVISIONS
47 *) If specified the Manufacturer shall provide details with the quotation 7. Heating and cooling time constant
48 Motor shall comply to the requirements of DEP 33.66.05.31-GEN, SP-1119 8. Starting time (80% & 100% Voltage)
49 1. Starting current shall be limited to 7 times for motors > 55kW. 9. Stalling time (hot and cold) @ 100% & 80 % terminal voltages
50 2. Shall be designed for steady state Voltage variations +/- 5% at motor terminal. 10. IP degree protection:IP54 for the machine and auxiliaries & IP55 for the terminal
51 3.Certificate of area classification (Exn) to be furnished(Temp. Class as mentioned in Line14) box and bearing hous
52 4. Allowed number of successive starts from both hot and cold condition to be furnished 11. Paint Shade : During detail engineering and to comply with painting specifications.
53 by Vendor. 12. Motor routine test shall be witnessed and test result shall be furnished.
54 5.Confirmaton on allowed no.of successive starts during Hot / cold to be furnished by vendor 13. Type test certificate of the identical machine shall be furnished
55 6. Following Additional Curves shall be provided : 14. Separate Auxiliary terminal boxes shall be provided
56 a) Thermal Damage Curve (thermal limiting curve) *** 15. Motor GA drawing to be furnished
57 b) Negative phase sequence current withstand characteristic *** 16. The stator winding shall be of copper.
58 c) Current& torque Vs speed curves at 100% & 80% terminal voltages 17. Bearing selection shall be done as per clause 11.10 .1 of DEP 33.66.05.31-Gen.
59 d) Eff./PF vs load curve *** Where oil is used as the lubricant, oil level sight glass shall be provided on
*** - Not applicable for motors ≤ 1.5 kW bearing housing of motors to aid maintenance activities.”
Made by: DE Date EQUIPMENT : Demulsifier Injection Pump Motor Rev. letter 02
10/8/2016 Tag NO : PM-42101A/B/C/D/E Date 10/08/2016
Chked by: DM Date Description : Data / Requisition sheet Sign.
10/8/2016 Plant : Lekhwair-RMS DAFIQ
Appr. by: DM Date CONSIGNEE : PDO Sheet No. 2
10/8/2016

Eng. by : Equipm. No. PM-42101A/B/C/D/E


Principal : Petroleum Development Oman LLC. Req. No. LEK-42-4500697254-ZV-E07-00002-0
REMENTS AND CONDITIONS

(If yes refer to VSDS requisition sheet)

(for VSDS refer to VSDS requisition sheet)

50 / 60 Hz
(details separately specified)
(details separately specified)

(as per IEC 60079-10)

(for roller bearings only)


*)

Cu/XLPE/SWA/PVC
3C x 2.5 sq.mm (Appr. 15 mm Overall Dia.)

(details separately specified)


g)", And Motor > 75kW & all non accessible LV motors, provided with vibration probes for online monitoring.
TTED BY MANUFACTURER WITH THE QUOTATION

REMARKS ON REVISIONS

10. IP degree protection:IP54 for the machine and auxiliaries & IP55 for the terminal

11. Paint Shade : During detail engineering and to comply with painting specifications.

17. Bearing selection shall be done as per clause 11.10 .1 of DEP 33.66.05.31-Gen.