M E D I U M VO LTAG E P R O D U C T S
—
Index
004 – 009 1.
Description
038 – 041 3.
Specific product
characteristics
042– 059 4.
Overall dimensions
060– 067 5.
Electric circuit diagram
4 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
1. Description
General information
HD4 medium voltage circuit-
breakers use sulphur hexafluoride
gas (SF6) to extinguish the electric
arc and as the insulating medium.
Breaking in SF6 gas takes place
without any arc chopping and
without generation of
overvoltages. These characteristics
ensure long electrical life of the
circuit-breaker and limited
dynamic, dielectric and thermal
stresses on the installation.
M E D I U M V O LTA G E P R O D U C T S 5
The circuit-breaker poles, which the poles are fixed to the metal
make up the breaking part, are structure which also acts as a
systems with lifelong sealed support for the kinetics for
pressure (IEC 62271-100 operating the moving contacts.
Standards) and are maintenance- Circuit-breakers in the
free. withdrawable version are fitted
The ESH type mechanical with a truck to allow racking in
operating mechanism, with and racking out of the switchgear
stored energy has free release or enclosure.
and allows opening and closing The light and compact structure
operations independently of the of the circuit-breaker ensures
operator’s actions. great sturdiness and excellent
The operating mechanism and mechanical reliability.
Available versions
HD4 circuit-breakers are available in the fixed and
withdrawable version with front operating
mechanism.
The withdrawable version is available for
PowerCube modules and UniGear type ZS1, ZS2,
ZS3.2 switchgears..
Fields of application
HD4 circuit-breakers are used in power
distribution to control and protect lines,
transformer and distribution substations, motors,
transformers, capacitor banks, etc.
Thanks to the SF6 autopuffer breaking technique,
the HD4 circuit-breakers do not generate
operating overvoltages, and are therefore also
highly suitable for retrofitting, upgrading and
enlarging older installations where the motor,
cable, etc. insulating materials may be particularly
sensitive to dielectric stresses.
6 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
1. Description
7 3
6
4
Main contact separation • with high short-circuit currents, the pressure wave
No electric arc strikes as the current flows through the generated by the electric arc closes the valve between
8 arcing contacts. the two chambers so that the circuit-breaker starts to
During its run downwards, the moving part compresses operate as a “pure self-blast”. The pressure increases in
the gas contained in the lower chamber. The compressed the upper volume thanks to heating of the gas and
gas flows out of the lower chamber into the upper molecular disassociation due to the high temperature.
chamber, taking them both to the same pressure. The increase in pressure generated is proportional to
the arc current and ensures quenching on first passage
Arcing contact separation through current zero.
The current flows thanks to the electric arc which has
struck between the arcing contacts. Circuit-breaker open
The gas cannot get out through the nozzle because the The arc has been interrupted, the self-generated
hole is still closed by the fixed arcing contact and cannot pressure in the upper volume is reduced because the gas
get out through the inside of the moving arcing contact is flowing through the contacts. The valve re-opens and
2
either because the electric arc closes this (clogging so a new flow of fresh gas comes into the breaking
effect). chamber. The apparatus is therefore immediately ready
9 • with low currents, when the current passes through to close and trip again up to its maximum breaking
natural zero and the arc is quenched, the gas flows capacity.
through the contacts. The low pressure reached cannot
1 Terminal chop the current and the modest amount of
2 Insulating case
compressed gas is sufficient to restore dielectric
3 Blasting nozzle
resistance between the two contacts, preventing
4 Moving arcing contact
5 Moving contact restriking on the rising front of the return voltage.
6 Fixed arcing contact
7 Fixed contact
8 Insulating tie-rod
9 Anti-explosion valve
M E D I U M V O LTA G E P R O D U C T S 7
• Individual tests: insulation with voltage at Key locks or padlocks enable opening and closing
industrial frequency in the main circuits and and/or racking-in and racking-out operations.
insulation of the auxiliary and control circuits, The closed door racking-out device only allows the
measurement of the main circuit resistance, circuit-breaker to be racked in and out of the
mechanical and electrical operation. switchgear when the door is closed.
The HD4 circuit-breakers are tested according to Anti-racking-in locks prevent circuit-breakers with
the requirements of the IEC 62271-100 Standard. different rated currents from being racked-in and
GOST versions have been approved by “Scientific racked-out when the circuit-breaker is closed.
and Technical Centre Standartelectro-S of
Moscow” (ask ABB for the Declaration of
Conformity).
ESH operating mechanism
• Just one device for the whole series.
Safety • The same set of accessories for all the types of
Safe distribution switchgear can be constructed HD4 circuit-breaker.
with HD4 circuit-breakers thanks to the full range • Fixed strikers to facilitate assembly or
of mechanical and electrical locks (available on replacement of accessories.
request). • Accessory cabling with socket and plug.
The locks have been designed to prevent incorrect This is a stored energy mechanical actuator with
operations and to allow the installations to be manual and/or motor-operated loading of the
inspected while guaranteeing maximum operator closing spring; the opening spring is loaded by the
safety. same actuator during the closing operation. The
opening and closing operations take place at
speeds that are independent from the operator
and the operating mode (manually using local or
remote push-buttons or by means of the opening
and closing shunt releases). When it is not
equipped with a geared motor for loading the
closing springs, the operating mechanism can
enable the following sequences:
• with c.-breaker open and closing spring loaded:
C-O
• with c.-breaker closed and closing spring
loaded: O - C - O.
When equipped with a geared motor for loading
the closing springs, the operating mechanism can
perform repeated re-closing operations thanks to
automatic reloading after each closing operation.
• Highly reliable operating mechanisms thanks to
a low number of components which are
manufactured using production systems for
large quantities
• Accessories common to the entire range
• Electrical accessories that can be easily and
quickly installed or replaced thanks to wiring pre-
engineered with plug-socket connectors
• Mechanical anti-pumping device is supplied as
standard
• Built-in closing spring charging lever
• Key lock with circuit-breaker open
• Protective covering over the opening and closing
pushbuttons to be operated using a special tool
• Padlock device on the operating pushbuttons
8 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
1. Description
A
K
B L
M
C
D N
E
O
F
P
H Q
I
R
A Gas monitoring device with led J Lock that prevents racking-in when door is open
B Opening pushbutton K Mechanical operation counter
C Mechanical undervoltage override L Pressure switch
D Undervoltage release M Mechanical signalling device for circuit-breaker open/closed
E Service releases (opening and closing) N Key lock removed when circuit-breaker is open
F Operating mechanism locking electromagnet O Contacts for signalling spring charged/discharged
G Closing pushbutton P Signalling device for closing springs charged/discharged
H Open/closed auxiliary contacts Q Closing spring loading motor limit switch
I Protection circuit-breaker for closing spring loading motor R Geared motor for closing spring charging
M E D I U M V O LTA G E P R O D U C T S 9
Quality System
Complies with UNI EN ISO 9001 Standards,
certified by an independent organisation.
Test Laboratory
Complies with UNI CEI EN ISO/IEC 17025
Standards, accredited by an independent
organisation.
Environmental Management
System
Complies with UNI EN ISO 14001 Standards,
certified by an independent organisation.
—
2. Selection and ordering
General characteristics
of fixed circuit-breakers (12 kV)
Circuit-breaker HD4/GT 12
IEC 62271-100 •
Standards
GOST R 52565-2006 (5) •
Rated voltage Ur [kV] 10
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 42
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
Rated normal current (40 °C) (1) Ir [A] 630 1250 630 1250 1250 1600 2000 2500 3150
16 16 16 16 — — — — —
— — — — — 20 — — —
Rated breaking capacity 25 25 25 25 — 25 25 25 25
Isc [kA]
31.5 31.5 31.5 31.5 — 31.5 31.5 31.5 31.5
— — — — 40 40 40 40 40
— — — — 50 50 50 50 50
16 16 16 16 — — — — —
— — — — — 20 — — —
Rated short-time 25 25 25 25 — 25 25 25 25
Ik [kA]
withstand current (3 s) 31.5 31.5 31.5 31.5 — 31.5 31.5 31.5 31.5
— — — — 40 40 40 40 40
— — — — 50 50 50 50 50
40 40 40 40 — — — — —
50 50 50 50 — 50 — — —
— — — — — 63 63 63 63
Making capacity Ip [kA]
80 80 80 80 — 80 80 80 80
— — — — 100 100 100 100 100
— — — — 125 125 125 125 125
[O-0.3s-CO-15s-CO] —
Operation sequence [O-0.3s-CO-20s-CO] •
[O-0.3s-CO-180s-CO] •
Opening time [ms] 35-60
Arcing time [ms] 10-15
Total breaking time [ms] 45-75
Closing time [ms] <=85
H [mm] 586 586 623 623 655 655 655 655 655
Overall W [mm] 496 496 618 618 618 618 730 730 730
H
dimensions D [mm] 446 446 446 446 493 493 493 493 493
W D Pole centre distance I [mm] 150 150 210 210 210 210 275 275 275
Weight [Kg] 114 114 114 114 145 145 165 165 165
Dimension standardization table 1VCD000226 1VCD000226 1VCD000231 1VCD000231 TN 7201 TN 7201 TN 7202 TN 7202 TN 7202
Absolute SF6 gas pressure (2) [kPa] 380 (430 at 31,5 kA)
Operating temperature (3) [°C] -5 ... +40
Tropicalization IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC 62271-1 •
(1) Rated interrupted current defined in free air at 40 °C ambient temperature for HD4 17 and 24
(2) Rated service value
(3) The standard range is -5 °C ... +40 °C; on request it’s available also the range -25 °C ... 40 °C with mandatory a special pressure-switch (with temperature compensation). The
minimum storage temperature is -25 °C; the minimum transportation temperature is minus -25 °C .
(4) Including insulating shields (available on request).
(5) Declaration of Conformity to GOST R 52565-2006 issued by Autonomous organization “Scientific research
M E D I U M V O LTA G E P R O D U C T S 11
General characteristics
of fixed circuit-breakers (17.5 kV)
Circuit-breaker HD4 17
Standards IEC 62271-100 •
Rated voltage Ur [kV] 17.5
Rated insulation voltage Us [kV] 17.5
Withstand voltage at 50 Hz Ud (1 min) [kV] 38
Impulse withstand voltage Up [kV] 95
Rated frequency fr [Hz] 50-60
Rated normal current (40 °C) (1) Ir [A] 630 1250 1600 1600 2000 2500 3150 3600
16 16 16 — — — — —
— — — — — — — —
Rated breaking capacity 25 25 25 — 25 25 25 25
Isc [kA]
31.5 31.5 31.5 — 31.5 31.5 31.5 31.5
— — — 40 40 40 40 40
— — — 50 50 50 50 50
16 16 16 — — — — —
— — — — — — — —
Rated short-time 25 25 25 — 25 25 25 25
Ik [kA]
withstand current (3 s) 31.5 31.5 31.5 — 31.5 31.5 31.5 31.5
— — — 40 40 40 40 40
— — — 50 50 50 50 50
40 40 40 — — — — —
— — — — — — — —
63 63 63 — 63 63 63 63
Making capacity Ip [kA]
80 80 80 80 80 80 80
— — — 100 100 100 100 100
— — — 125 125 125 125 125
[O-0.3s-CO-15s-CO] –
Operation sequence [O-0.3s-CO-20s-CO] •
[O-0.3s-CO-180s-CO] •
Opening time [ms] 35-60
Arcing time [ms] 10-15
Total breaking time [ms] 45-75
Closing time [ms] <=85
H [mm] 623 623 649 655 655 655 655 655
Overall W [mm] 618 618 618 618 618 730 730 730
dimensions H
D [mm] 446 446 561 493 493 603 603 603
W D Pole centre distance I [mm] 210 210 210 210 210 275 275 275
Weight [Kg] 114 114 114 145 145 165 165 165
Dimension standardization table 1VCD000231 1VCD000231 TN 7178 TN 7163 TN 7163 TN 7165 TN 7165 TN 7165
Absolute SF6 gas pressure (2) [kPa] 380 (430 at 31,5 kA)
Operating temperature (3) [°C] -5 ... +40
Tropicalization IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC 62271-1 •
(1) Rated interrupted current defined in free air at 40 °C ambient temperature for HD4 17 and 24
(2) Rated service value
(3) The standard range is -5 °C ... +40 °C; on request it’s available also the range -25 °C ... 40 °C with mandatory a special pressure-switch (with temperature compensation). The
minimum storage temperature is minus 25 °C; the minimum transportation temperature is minus 25 °C .
(4) Including insulating shields (available on request).
(5) Declaration of Conformity to GOST R 52565-2006 issued by Autonomous organization “Scientific research
12 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
2. Selection and ordering
General characteristics
of fixed circuit-breakers (24 kV)
Circuit-breaker HD4 24
Standards IEC 62271-100 •
Rated voltage Ur [kV] 24
Rated insulation voltage Us [kV] 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 50
Impulse withstand voltage Up [kV] 125
Rated frequency fr [Hz] 50-60
Rated normal current (40 °C) (1) Ir [A] 630 1250 630 1250 1600 1600 2000 2500 3150 3600
16 16 16 16 16 — — — — —
20 20 20 20 20 — — — — —
Rated breaking capacity 25 25 25 25 25 25 25 25 25 25
Isc [kA]
31.5 31.5 31.5 31.5 — 31.5 31.5 31.5 31.5 31.5
— — — — — 40 40 40 40 40
— — — — — — — — — —
16 16 16 16 16 — — — — —
— — — — 20 — — — — —
Rated short-time 25 25 25 25 25 25 25 25 25 25
Ik [kA]
withstand current (3 s) — — — — — 31.5 31.5 31.5 31.5 31.5
— — — — — 40 40 40 40 40
— — — — — — — — — —
40 40 40 40 40 — — — — —
— — — — 50 — — — — —
63 63 63 63 63 63 63 63 63 63
Making capacity Ip [kA]
— — — — — 80 80 80 80 80
— — — — — 100 100 100 100 100
— — — — — — — — — —
[O-0.3s-CO-15s-CO] —
Operation sequence [O-0.3s-CO-20s-CO] •
[O-0.3s-CO-180s-CO] •
Opening time [ms] 35-60
Arcing time [ms] 10-15
Total breaking time [ms] 45-75
Closing time [ms] <=85
H [mm] 818 818 730 730 818 655 655 818 (4) 818 (4) 818 (4)
Overall W [mm] 618 618 748 748 618 730 730 730 730 730
dimensions D [mm] 600 600 496 496 600 561 561 620 (4) 620 (4) 620 (4)
H
Pole centre distance I [mm] 210 210 275 275 210 275 275 275 275 275
Weight W D [Kg] 119 119 119 119 114 145 145 165 165 165
Dimension standardization table 1VCD000231 1VCD000237 TN 7179 TN 7174 TN 7165
Absolute SF6 gas pressure (2) [kPa] 380 (430 at 31,5 kA)
Operating temperature (3) [°C] -5 ... +40
Tropicalization IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC 62271-1 •
(1) Rated interrupted current defined in free air at 40 °C ambient temperature for HD4 17 and 24
(2) Rated service value
(3) The standard range is -5 °C ... +40 °C; on request it’s available also the range -25 °C ... 40 °C with mandatory a special pressure-switch (with temperature compensation). The
minimum storage temperature is minus 25 °C; the minimum transportation temperature is minus 25 °C .
(4) Including insulating shields (available on request).
(5) Declaration of Conformity to GOST R 52565-2006 issued by Autonomous organization “Scientific research
M E D I U M V O LTA G E P R O D U C T S 13
General characteristics
of fixed circuit-breakers (36 kV)
Circuit-breaker HD4 36
Standards IEC 62271-100 •
Rated voltage Ur [kV] 36
Rated insulation voltage Us [kV] 36
Withstand voltage at 50 Hz Ud (1 min) [kV] 70
Impulse withstand voltage Up [kV] 170
Rated frequency fr [Hz 50-60
Rated normal current (40 °C) (1) Ir [A] 630 1250 1600 1250 (3) 1600 (3) 2000 (3) 2500 (3)
16 16 16 — — — —
20 (5) 20 (5) 20 (5) — — 20 20
Rated breaking capacity Isc [kA]
— — — 25 25 25 25
— — — 31.5 31.5 31.5 31.5
16 16 16 — — — —
Rated short-time 20 20 20 — — 20 20
Ik [kA]
withstand current (3 s) — — — 25 25 25 25
— — — 31.5 31.5 31.5 31.5
40 40 40 — — — —
50 50 50 — — 50 50
Making capacity Ip [kA]
— — — 63 63 63 63
— — — 80 80 80 80
[O-0.3s-CO-15s-CO] —
Operation sequence
[O-0.3s-CO-3min-CO] •
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 730/1060 (6) 730/1060 (6) 730/1060 (6) 790/1123 (6) 790/1123 (6) 790/1123 (6) 790/1123 (6)
Maximum overall
dimensions without W [mm] 880/955 (6) 880/955 (6) 880/955 (6) 748/805 (6) 748/805 (6) 748/805 (6) 748/805 (6)
insulating screens H
D [mm] 695 695 695 833 833 833 833
between phases (4)
W D Pole centre distance I [mm] 350 350 350 275 275 275 275
Weight [kg] 124 128 128 175 175 180 190
Standardised table of dimensions TN 7241 TN 7241 TN 7241 TN 7268 TN 7268 TN 7268 TN 7315
Absolute SF6 gas pressure (2) [kPa] 380 380 380 450 450 450 450
Operating temperature [°C] - 5 ... + 40
Tropicalizzazione IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC 62271-1 •
(1) Rated normal current defined in free air
(2) Rated service value
(3) For these versions, with 275 mm pole centre distance, special insulating partitions are provided (on request)
(4) For the dimensions of the insulating partitions (available on request), see the standardised table in chapter 5
(5) Operation sequence: O - 0.3 min - CO - 3 min - CO
(6) The second distance refers to the circuit-breaker with truck (available on request)
14 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
2. Selection and ordering
Circuit-breaker HD4/GT/P 12
IEC 62271-100 • •
Standards
GOST R 52565-2006 (5) • •
Rated voltage Ur [kV] 10 10
Rated insulation voltage Us [kV] 12 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 42 (6) 38 (6)
Impulse withstand voltage Up [kV] 75 75
Rated frequency fr [Hz] 50-60 50-60
Rated normal current (40 °C) (1) Ir [A] 630 1250 1250 1600 2000 2500 3150 (4)
16 16 — — — — —
— — — 20 — — —
25 25 — 25 25 25 25
Rated breaking capacity Isc [kA]
31.5 31.5 — 31.5 31.5 31.5 31.5
— — 40 40 40 40 40
— — 50 50 50 50
16 16 — — — — —
— — — 20 — — —
Rated short-time 25 25 — 25 25 25 25
Ik [kA]
withstand current (3s) 31.5 31.5 — 31.5 31.5 31.5 31.5
— — 40 40 40 40 40
— — — 50 50 50 50
40 40 — — — — —
— — — 50 — — —
63 63 — 63 63 63 63
Making capacity Ip [kA]
80 80 — 80 80 80 80
— — 100 100 100 100 100
— — — 125 125 125 125
[O-0.3s-CO-15s-CO]
Operation sequence [O-0.3s-CO-20s-CO] •
[O-0.3s-CO-180s-CO] •
Opening time [ms] 35-60
Arcing time [ms] 10-15
Total breaking time [ms] 45-75
Closing time [ms] ≤85
H [mm] 633 633 702 702 702 702 746
Overall W [mm] 531 531 682 682 682 882 882
dimensions H
D [mm] 661 661 640 640 640 643 643
W D Pole centre distance I [mm] 150 150 210 210 210 275 275
Weight [kg] 120 120 177 177 177 220 230
Standardised table of dimensions 1VCD000227 1VCD000227 TN 7350 TN 7350 TN 7351 TN 7352 TN7371
Absolute SF6 gas pressure (2) [kPa] 380 (430 at 31.5 kA)
Operating temperature (3) [°C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC 62271-1 •
(1) Rated uninterrupted current guaranteed with withdrawable circuit-breaker installed in UniGear type ZS1 switchboard at 40°C ambient temperature externally the panel.
(2) Rated service value.
(3) The standard range is -5 °C ... +40 °C; on request it is also available the range -25 °C ... +40 °C with mandatory a special pressure-switch (with temperature compensation)
(4) Up to 4000 A rated uninterrupted current with forced ventilation.
(5) The locking electromagnet (-RL2) in the truck to prevent the circuit breaker being racked-in with the auxiliary circuits disconnected
(6) UniGear type ZS1 switchboard with rated insulation voltage 17,5 kV
(7) Rated uninterrupted current in switchboard with forced ventilation. In a switchboard with natural ventilation, the rated current is 2300 A
(8) Declaration of conformity to GOST R 52565-2006 issued by Autonomous organization “scientific research center” Standardtelectro-S of Moscow
M E D I U M V O LTA G E P R O D U C T S 15
Circuit-breaker HD4/P 17
Standards IEC 62271-100 •
Rated voltage Ur [kV] 17.5
Rated insulation voltage Us [kV] 17.5
Withstand voltage at 50 Hz Ud (1 min) [kV] 38
Impulse withstand voltage Up [kV] 95
Rated frequency fr [Hz] 50-60
Rated normal current (40 °C) (1) Ir [A] 630 1250 1250 1600 2000 2500 3150 (4)
16 16 — — — — —
— — — — — — —
25 25 — 25 25 25 25
Rated normal current Isc [kA]
31.5 31.5 31.5 31.5 31.5 31.5
— — 40 40 40 40 40
— — — 50 50 50 50
16 16 — — — — —
— — — — — — —
Rated short-time 25 25 — 25 25 25 25
Ik [kA]
withstand current (3s) 31.5 31.5 — 31.5 31.5 31.5 31.5
— — 40 40 40 40 40
— — — 50 50 50 50
40 40 — — — — —
— — — — — — —
63 63 — 63 63 63 63
Making capacity Ip [kA]
— 80 — 80 80 80 80
— — 100 100 100 100 100
— — — 125 125 125 125
Operation sequence [O-0.3s-CO-15s-CO] •
Opening time [ms] 35-60
Arcing time [ms] 10-15
Total breaking time [ms] 45-75
Closing time [ms] ≤85
H [mm] 633 633 702 702 702 702 746
Overall W [mm] 531 531 682 682 682 882 882
H
dimensions D [mm] 661 661 640 640 640 643 643
W D Pole centre distance I [mm] 150 150 210 210 210 275 275
Weight [kg] 120 120 177 177 177 220 230
Standardised table of dimensions 1VCD000227 1VCD000227 TN 7350 TN 7350 TN 7351 TN 7352 TN7371
Absolute SF6 gas pressure (2) [kPa] 380 (430 at 31.5 kA)
Operating temperature [°C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC 62271-1 •
(1) Rated uninterrupted current guaranteed with withdrawable circuit-breaker installed in UniGear type ZS1 switchboard at 40°C ambient temperature externally the panel.
(2) Rated service value.
(3) The standard range is -5 °C ... +40 °C; on request it is also available the range -25 °C ... +40 °C with mandatory a special pressure-switch (with temperature compensation)
(4) Up to 4000 A rated uninterrupted current with forced ventilation.
(5) The locking electromagnet (-RL2) in the truck to prevent the circuit breaker being racked-in with the auxiliary circuits disconnected
(6) UniGear type ZS1 switchboard with rated insulation voltage 17,5 kV
(7) Rated uninterrupted current in switchboard with forced ventilation. In a switchboard with natural ventilation, the rated current is 2300 A
(8) Declaration of conformity to GOST R 52565-2006 issued by Autonomous organization “scientific research center” Standardtelectro-S of Moscow
—
2. Selection and ordering
Circuit-breaker HD4/P 24
Standards IEC 62271-100 •
Rated voltage Ur [kV] 24
Rated insulation voltage Us [kV] 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 50
Impulse withstand voltage Up [kV] 125
Rated frequency fr [Hz] 50-60
Rated normal current (40 °C) (1) Ir [A] 630 1250 1250 1600 2000 2500 (7)
16 — — 16 16 —
20 20 — 20 20 20
25 25 — 25 25 25
Rated breaking capacity Isc [kA]
— — 31.5 31.5 31.5 31.5
— — — — — —
— — — — — —
16 — — 16 16 —
20 20 — 20 20 20
Rated short-time 25 25 — 25 25 25
Ik [kA]
withstand current (3s) — — 31.5 31.5 31.5 31.5
— — — — — —
— — — — — —
40 — — 40 40 —
50 50 — 50 50 50
63 63 — 63 63 63
Making capacity Ip [kA]
— — 80 80 80 80
— — — — — —
— — — — — —
Operation sequence [O-0.3s-CO-15s-CO] •
Opening time [ms] 35-60
Arcing time [ms] 10-15
Total breaking time [ms] 45-75
Closing time [ms] ≤85
H [mm] 736 736 792 821 821 821
Overall W [mm] 636 636 653 842 842 842
dimensions H
D [mm] 799 799 799 788 788 788
W D Pole centre distance I [mm] 210 210 210 275 275 275
Weight [kg] 125 125 177 177 220 220
Standardised table of dimensions 1VCD000236 1VCD000236 1VCD000099 TN 7355 TN 7356 TN 7356
Absolute SF6 gas pressure (2) [kPa] 380 (480 at 25 kA and 40 kA)
Operating temperature [°C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC 62271-1 •
(1) Rated uninterrupted current guaranteed with withdrawable circuit-breaker installed in UniGear type ZS1 switchboard at 40°C ambient temperature externally the panel.
(2) Rated service value.
(3) The standard range is -5 °C ... +40 °C; on request it is also available the range -25 °C ... +40 °C with mandatory a special pressure-switch (with temperature compensation)
(4) Up to 4000 A rated uninterrupted current with forced ventilation.
(5) The locking electromagnet (-RL2) in the truck to prevent the circuit breaker being racked-in with the auxiliary circuits disconnected
(6) UniGear type ZS1 switchboard with rated insulation voltage 17,5 kV
(7) Rated uninterrupted current in switchboard with forced ventilation. In a switchboard with natural ventilation, the rated current is 2300 A
(8) Declaration of conformity to GOST R 52565-2006 issued by Autonomous organization “scientific research center” Standardtelectro-S of Moscow
M E D I U M V O LTA G E P R O D U C T S 17
Rated short-time 25 25 25 25
Ik [kA]
withstand current (3s) 31.5 31.5 31.5 31.5
63 63 63 63
Operation sequence Ip [kA]
80 80 80 80
Operation sequence [O-0.3s-CO-15s-CO] •
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 1575
(1) Rated normal current with circuit-breaker in switchgear UniGear ZS3.2 and ambient temperature outside the switchgear 40 °C
(2) Rated service value
(3) Rated current in ZS3.2 switchgear with forced ventilation; in Powerbloc enclosure the 2500 A rated current is guaranteed with natural ventilation.
(4) The operation sequence becomes O-0.3-CO-3min-CO for the Isc = 31.5 kA performance.
18 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
2. Selection and ordering
—
2. Selection and ordering
Circuit-breaker HD4/P 24
PowerCube module PB4 PB4 PB4 PB5 PB5 PB5
Standards IEC 62271-100 •
Rated voltage Ur [kV] 24
Rated insulation voltage Us [kV] 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 50
Impulse withstand voltage Up [kV] 125
Rated frequency fr [Hz] 50-60
Rated normal current (40 °C) (1) Ir [A] 630 1250 1250 1600 2000 2500 (4)
16 16 — 16 16 16
20 20 — 20 20 20
25 25 — 25 25 25
Rated breaking capacity Isc [kA]
— — 31.5 31.5 31.5 31.5
— — 40 40 40 40
— — — — — —
16 16 — 16 16 16
20 20 — 20 20 20
Rated short-time 25 25 — 25 25 25
Ik [kA]
withstand current (3s) — — 31.5 31.5 31.5 31.5
— — 40 40 40 40
— — — — — —
40 40 — 40 40 40
50 50 — 50 50 50
63 63 — 63 63 63
Making capacity Ip [kA]
— — 80 80 80 80
— — 100 100 100 100
— — — — — —
Operation sequence [O-0.3s-CO-15s-CO] •
Opening time [ms] 35-60
Arcing time [ms] 10-15
Total breaking time [ms] 45-75
Closing time [ms] ≤85
H [mm] 792 792 792 821 821 821
Maximum W [mm] 682 682 641 842 842 842
overall H
dimensions D [mm] 799 799 799 788 788 788
W D Pole centre distance I [mm] 210 210 210 275 275 275
Weight [kg] 125 125 177 177 220 220
Standardised table of dimensions 1VCD000236 1VCD000236 1VCD000099 TN 7355 TN 7356 TN 7356
Absolute SF6 gas pressure (2) [kPa] 380 (480 at 25 kA and 40 kA)
Operating temperature [°C] - 5 ... + 40 - 5 ... + 40 - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1 • • •
Electromagnetic compatibility IEC 62271-1 • • •
Circuit-breaker HD4/W 36
Standards IEC 62271-100 •
Rated voltage Ur [kV] 36
Rated insulation voltage Us [kV] 36
Withstand voltage at 50 Hz Ud (1 min) [kV] 70
Impulse withstand voltage Up [kV] 170
Rated frequency fr [Hz 50-60
Rated normal current (40 °C) (1) Ir [A] 1250 1250 1600 1600 2000 2000 2500 (3) 2500 (3)
Isc [kA] 20 — 20 — 20 — 20 —
Rated breaking capacity 25 — 25 — 25 — 25 —
— 31.5 — 31.5 — 31.5 — 31.5
Ik [kA] 20 — 20 — 20 — 20 —
Rated short-time
25 — 25 — 25 — 25 —
withstand current (3s)
— 31.5 — 31.5 — 31.5 — 31.5
Ip [kA] 50 — 50 — 50 — 50 —
Making capacity 63 — 63 — 63 — 63 —
— 80 — 80 — 80 — 80
[O-0.3s-CO-3min-CO] • • — • — • — •
Operation sequence
[O-0.3s-CO-15s-CO] — — • — • — • —
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
H [mm] 973 973 973 973 973 973 973 973
Maximum W [mm] 882 882 882 882 882 882 882 882
overall H
dimensions D [mm] 788 788 789 789 789 789 789 789
D
W Pole centre distance I [mm] 275 275 275 275 275 275 275 275
Weight [kg] 130 225 225 225 225 225 270 270
Standardised table of dimensions TN 7402 TN 7316 TN 7317 TN 7317 TN 7317 TN 7317 TN 7317 TN 7317
Absolute SF6 gas pressure (2) [kPa] 450
Operating temperature [°C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC 62271-1 •
(1) Rated normal current with circuit-breaker in UniGear ZS2 switch-gear and 40 °C ambient temperature outside the switchgear
(2) Rated service value
(3) Switchgear with forced ventilation
22 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
2. Selection and ordering
Standard equipment
The basic versions of the circuit-breakers are
always three-pole and fitted with:
• manual operating mechanism
• mechanical signalling device for closing springs
charged/discharged
• mechanical signalling device for circuit-breaker
open/closed
• closing pushbutton
• opening pushbutton
• operation counter
• 12 to 36 kV series: set of 14 auxiliary contacts for
Terminals for fixed circuit-breaker.
circuit-breaker open/closed; five closing
contacts (circuit-breaker open signalling) and
seven opening contacts (circuit-breaker closed
signalling) are available for use by the customer
if the apparatus is equipped with all the
electrical applications
• 40.5 kV series: set of 10 auxiliary contacts for
circuit-breaker open/closed; three closing
contacts (circuit-breaker open signalling) and
four opening contacts (circuit-breaker closed
signalling) are available for use by the customer
if the apparatus is equipped with all the
electrical applications Circuit-breaker racking-out/racking-in lever.
Moreover:
• for fixed circuit-breaker
-- connection terminals (not available for low-end
circuit-breakers)
-- terminal board for auxiliary circuits;
• for withdrawable circuit-breaker
-- isolating contacts
-- cord with connector (plug only) for auxiliary
circuits
-- lock to prevent racking-in of circuit-breaker
with different rated current
-- racking-in/out lever (the quantity must be
defined according to the number of pieces of
Tulip isolating contacts for withdrawable circuit-breaker.
apparatus ordered)
-- locking electromagnet in the truck (/P
versions).
—
2. Selection and ordering
opening (as an alternative to the standard 10, of which up to 3 for closing and 4
Set of 14 auxiliary contacts: 5 closing contacts for signalling circuit-
closed.
1A 1B 1C 2 3A 3B 4 5 6A 6B 7 8 9 10
Fixed c.-breakers
HD4/GT 12 • • • • • • • • • – • – – •
HD4 17 • • • • • • • • • – • – – •
HD4 24 • • • • • • • • • – • – – •
HD4 36 • • • • • • • • • – • – – •
Withdrawable circuit-
breakers for UniGear
type ZS1 switchgear
HD4/GT/P 12 • • • • • • • • • – • • • •
HD4/P 17 • • • • • • • • • – • • • •
HD4/P 24 • • • • • • • • • – • • • •
Withdrawable circuit-
breakers for UniGear
36 type ZS3.2 switchgear
HD4/Z 40,5 • • • • • • • • • • – (1) •
Withdrawable circuit-
breakers for PowerCube
modules
HD4/W 12 - HD/P 12 • • • • • • • • • – • • • •
HD4/W 17 - HD/P 17 • • • • • • • • • – • • • •
HD4/P • • • • • • • • • – • • • •
HD4/W 36 (5) • • • • • • • • • – • • • •
Withdrawable circuit-
breakers for UniSec
switchgear
HD4/SEC 24 • • • • • • • • • – • • • •
Two-level pressure switch plus SF6 control device with three LEDs (2).
Mechanical isolation interlock with the switchgear door.
-RLE1 operating mechanism locking magnet.
Electric signalling of springs discharged.
Electric signalling of springs charged.
Insulating partitions.
11 12A 12B 13A 13B 14 15 16 17 18 19A 19B-C 20 21
Fixed c.-breakers
HD4/GT 12 • • • • • • • – • – • • –
HD4 17 • • • • • • • – • – • • –
HD4 24 • • • • • • • – • – • • •
HD4 36 • • • • • • • – • – • • •
Withdrawable circuit-
breakers for UniGear
type ZS1 switchgear
HD4/GT/P 12 • • • • • • • (4) • • • • –
HD4/P 17 • • • • • • • (4) • • • • –
HD4/P 24 • • • • • • • (4) • • • • –
Withdrawable circuit-
breakers for UniGear
36 type ZS3.2 switchgear
HD4/Z 40,5 • • • - - • • • – • (3) • – •
Withdrawable circuit-
breakers for PowerCube
modules
HD4/W 12 - HD/P 12 • • • • • • • – – • • • –
HD4/W 17 - HD/P 17 • • • • • • • – – • • • –
HD4/P • • • • • • • – – • • • –
HD4/W 36 (5) • • • • • • • • – – • • –
Withdrawable circuit-
breakers for UniSec
switchgear
HD4/SEC 24 • • • • • • • • – – • • –
—
2. Selection and ordering
Optional accessories
The accessories identified with the same number 1C Demagnetizing shunt opening release -MBO3
are alternative to each other; consult the table at The opening solenoid (-MBO3) is a special
the end of the chapter for the electrical demagnetizing release for use in conjunction with
characteristics. protection relays against overcurrents of the self-
supplied type (e.g. the old ABB PR521 series). It is
an alternative to the additional shunt opening
release (-MBO2).
1 Shunt opening release
shunt opening
release -MBO1
M E D I U M V O LTA G E P R O D U C T S 27
undervoltage
release -MBU
—
2. Selection and ordering
Note: The main shunt Auxiliary contacts –BGB1 and –BGB2 conform to 6B Auxiliary contacts -BB1-BB2-BB3 for the
opening release and/or
the additional shunt the following standards/regulations/directives: 40.5 kV withdrawable series only
opening release use 1 • IEC 62271-100 Electrical signalling of circuit-breaker open/closed
and/or 2 closing contacts
“a”, thereby reducing the • IEEE C37.54 includes, as standard equipment, a set of 10
number of auxiliary • EN 61373 cat.1 class B / impact and vibration test auxiliary contacts for the 40.5 kV withdrawable
contacts available. Always
check the maximum • Germanish Loyd regulation / vibrations version.
number of contacts envisaged by the shipping registers Set of 10 circuit-breaker open/closed auxiliary
available with non-
standard equipment. • UL 508 contacts. Three closing contacts (circuit-breaker
• EN 60947 (DC-21A DC-22A DC-23A AC-21A) open signalling) and four opening contacts
• RoHS Directive (circuit-breaker closed signalling) are available if
the apparatus is equipped with all the electrical
General characteristics
applications.
Insulation voltage to standard 660 V AC A set of 15 auxiliary contacts for signalling circuit-
VDE 0110, Group C 800 V DC breaker open/closed can be supplied on request.
Rated voltage 24 V ... 660 V Four closing contacts (circuit-breaker open
Test voltage 2 kV for 1 min signalling) and four opening contacts (circuit-
Maximum rated current 10 A - 50/60 Hz breaker closed signalling) are available if the
Breaking capacity Class 1 (IEC 62271-1) apparatus is equipped with all the electrical
Number of contacts 5 applications.
Groups of contacts 10 / 16 / 20
Contact travel 90°
Electrical specifications of the auxiliary contacts of the
Actuating force 0.66 Nm 40.5 kV withdrawable circuit-breaker
Resistance <6.5 mΩ Un = 500 V~ 220 V–
Storage temperature –30 °C ... +120 °C Icu = 15 A 1,5 A
–20 °C ... +70 °C Cosϕ = 0,4 –
Operating temperature
(-30° ref. ANSI 37.09)
T = 500 V~ 10 ms
Contact overtemperature 10 K
10,000 mechanical Un Rated voltage
Mechanical life Cosϕ Power factor
operations
Icu Breaking capacity
Protection class IP20 Ps Inrush power input (inrush duration is given between brackets)
Pc Continuous service power consumption
Cable section 1 mm2
T Time constant
—
2. Selection and ordering
—
2. Selection and ordering
12A contact open: electrical signalling of spring 13 B Closing pushbutton lock (with or without
loaded padlock).
Locks the closing pushbutton with a 4 mm
12B contact closed: spring discharged signal diameter padlock (not part of the standard
equipment). The padlock is only supplied on
request.
spring loaded/discharged
mechanical indicator
34 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
2. Selection and ordering
14 “Circuit-breaker open” key lock (different keys 16 Locking magnet -RLE2 on truck
or the same keys) This accessory is mandatory in withdrawable
The locking action is performed by a special versions for UniGear switchgear type ZS1 and for
circular lock. PowerCube modules so as to prevent the circuit-
Can be supplied with different keys or the same breaker from being racked into the switchgear
keys (for several circuit-breakers). To apply the key when the plug of the auxiliary circuits is
lock, press the opening pushbutton, turn the key disconnected from the switchgear socket. The
and remove it. Local manual closing and remote plug also prevents racking-in if the rated current of
electrical closing are inhibited once the key has the circuit-breaker differs from that of the
been removed. compartment (dedicated striker pins prevent the
plug from being plugged into the socket if the
circuit-breaker’s rated current is lower than the
rated current of the panel).
locking magnet
on operating
mechanism
M E D I U M V O LTA G E P R O D U C T S 35
17 Interlock for fixed circuit-breaker (for fixed 18 Mechanical isolation interlock with the door
apparatus converted to plug-in by the of Unigear ZS1, ZS2 switchgear and the
customer) PowerCube enclosure
This device can be useful when fixed circuit- This device prevents the circuit-breaker from being
breakers are converted into withdrawable ones by racked-in when the switchgear door is open. It is
the customer. only intended for circuit-breakers used in UniGear
It allows the customer to create a mechanical lock ZS1 and ZS2 switchgear and in PowerCube
that inhibits racking-out/racking-in when the modules (which must be equipped with a
circuit-breaker is closed and prevents the circuit- dedicated actuator on the door).
breaker from closing during movement.
Note. The device must be requested when the
order is placed since it must be assembled in the
factory.
—
2. Selection and ordering
—
3. Specific product characteristics
Resistance to vibrations
HD4 circuit-breakers are unaffected by
mechanically generated vibrations.
For the versions approved by the naval registers,
please contact us.
Tropicalization
HD4 circuit-breakers are manufactured in
compliance with the strictest regulations for use in
hot-humid-saline climates.
All the most important metal components are
treated against corrosive factors according to
atmospheric corrosivity class C5 of standard BS
EN 12500.
Galvanisation is carried out in accordance with UNI
ISO 2081 Standards, classification code Fe/Zn 12,
with a thickness of 12x10-6 m, protected by a
conversion layer mainly consisting of chromates in
compliance with the UNI ISO 4520 Standards.
M E D I U M V O LTA G E P R O D U C T S 39
kA
1,50
m=1
Ka = e m (H – 1000)/8150
1,40
1,30
1,20
1,10
1,00
H
1000 1500 2000 2500 3000 3500 4000
Altitude Example
• Installation altitude 2000 m
The insulating property of air decreases as the
• Operation at the rated voltage of 12 kV
altitude increases, therefore this must always
• Withstand voltage at industrial frequency
be taken into account for external insulation of
28 kV rms
the apparatus (the internal insulation does not
• Impulse withstand voltage 75 kVp
undergo any variations as it is guaranteed by
• Factor Ka obtained from graph = 1.13.
the SF6 gas).
The phenomenon must always be taken into Considering the above parameters, the
consideration during the design stage of the apparatus will have to withstand the following
insulating components of apparatus to be values (under test and at zero altitude, i.e. at
installed over 1000 m above sea level In this sea level):
case a correction coefficient must be • withstand voltage at industrial frequency
considered, which can be taken from the graph equal to:
to the side, built up on the basis of the 28 x 1.13 = 31.6 kVrms
indications in the IEC 62271-1 Standards. • impulse withstand voltage equal to:
The following example is a clear interpretation 75 x 1.13 = 84.7 kVp.
of the indications given above. From the above, it can be deduced that for
installations at an altitude of 2000 m above sea
level, with 12 kV service voltage, apparatus must
be provided with 17.5 kV rated voltage,
characterised by insulation levels at industrial
frequency of 38 kVrms with 95 kVp impulse
withstand voltage.
H = altitude in metres;
m = value referred to industrial frequency and the atmospheric
impulse withstand voltages and thosebetween phase and
phase.
40 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
3. Specific product characteristics
—
4. Overall dimensions
Fixed circuit-breakers
496
HD4/GT
150 150 446
2XM8 depth 16 M12 depth 25
TN 1VCD000226 67,5 87 336,5 13,5
Ur 12 kV
630 A
Ir
1250 A
27
16 kA
205
Isc 25 kA
31.5 kA
586
541,5
63
27
260,5
248,5
21,5
43
Fixed circuit-breakers
HD4/GT
TN TN 7201
Ur 12 kV
Ir 1250 A
1600 A
Isc up to 50 kA
M E D I U M V O LTA G E P R O D U C T S 43
Fixed circuit-breakers
HD4/GT
TN TN 7202
Ur 12 kV
Ir 2000 A
2500 A
3150 A
Isc up to 50 kA
Fixed circuit-breakers
HD4 600
581 446 2XM8 depth 16 M12 depth 25
TN 1VCD000231 210 210
87 336,5 13,5
12 kV 67,5
Ur
17.5 kV
Ir 630 A 27
1250 A
16 kA
25 kA
205
Isc
31.5 kA
623
27
63
266,5
231,5
21,5
43
472 13
117 2XM8 depth 16
598 10,5 M12 depth 25
111,5
618
270 34
332
44 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
4. Overall dimensions
Fixed circuit-breakers
HD4
TN 7178
Ur 17 kV
Ir 1600 A
16 kA
Isc 25 kA
31.5 kA
Fixed circuit-breakers
600
HD4
578
TN 7163
210 210
Ur 17.5 kV
Ir 1600 A
40 kA
Isc
50 kA
2 x Ø18
310
310
28
HD4
80
TN 7163 15.5 32
655
622
12 kV YU
Ur
17.5 kV
8
YU
Ir 2000 A
306.5
266.5
25 kA Q6
0 8
31.5 kA
Isc Ø 13
40 kA
43
50 kA
472 Ø 10.5 35
2.5
20
598 322
618 385
561
M E D I U M V O LTA G E P R O D U C T S 45
Fixed circuit-breakers
HD4 137.5 137.5 420 min.
730
TN 7165
708
Ur 17.5 kV
275 275 465
Ir 2500 A
349.5
3150 A
3600 A
670 min.
Isc 25 kA
15
31.5 kA
310
28
62
40 kA
50 kA 20 40
655
20
622
YU
468.5
40
YU
HD4
20
20
TN 7165 8
Ur 24 kV
266.5
4 x Ø18
Ø13
Ir 2500 A
43
3150 A
602 Ø10.5 115 2
3600 A
20
322 35
728
Isc 25 kA 385
748 603
31.5 kA
Insulating partitions (only for 24 kV)
40 kA
to be provided by the customer
(a special kit is available on request).
Fixed circuit-breakers
HD4
TN 7179
Ur 24 kV
Ir 1600 A
Isc 16 kA
20 kA
25 kA
46 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
4. Overall dimensions
Fixed circuit-breakers
600 451,5
HD4 2XM8 depth 16
581 420
M12 depth 25
TN 1VCD000235 210 210 87 356,5 13,5
103,5 103,5
Ur 24 kV
67,5
Ir 630 A
1250 A
27
Isc 16 kA
20 kA
670
310
25 kA
695
623
27
63
468
231
43
302,5
Fixed circuit-breakers
730
HD4
705 2XM8 depth 16 M12 depth 25
451,5
TN 1VCD000237 275 275
87 356,5 13,5
67,5
Ur 24 kV
27
Ir 630 A
1250 A
Isc 16 kA
310
20 kA
27
695
25 kA
623
63
468
302,5
231
Fixed circuit-breakers
HD4 730
708
TN 7174
275 275
Ur 24 kV
Ir 1600 A
Isc 31.5 kA
40 kA
2x Ø18
310
310
80
HD4
28
TN 7174 15.5 32
622
655
Ur 24 kV YU
8
Ir 2000 A YU
Isc 25 kA 8
306.5
266.5
31.5 kA Q6
0
40 kA Ø 13
43
20
728 322
35
385
748 561
Fixed circuit-breakers
HD4 400
880
with truck (on 358
350 350 10
request) Ø 22
50
TN 7241
Ur 36 kV
Ir 630 A
362
1250 A
Ø 22
729.5
1600 A 28
712
639. 5
Isc 16 kA
539
10
20 kA
* 106 0
342.5
21
302.5
(if provided).
755
2x Ø 10.5 120
881 363.5 270
43
901 695.4 37
*4.9
* 348
*Ø 13
* 855 * Ø 13 * 200
* 355 *85
*4
* 915 *40
* 955 * 516.4
48 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
4. Overall dimensions
Fixed circuit-breakers
HD4 730
708
with truck (on
request)
TN 7268
Ur 36 kV
1250 A
Ir
1600 A
25 kA
Isc
31.5 kA
HD4
with truck (on
request)
TN 7268
Ir 2000 A
20 kA
Isc 25 kA
31.5 kA
Fixed circuit-breakers
HD4
with truck (on
request)
TN 7315
Ur 36 kV
Ir 2500 A
20 kA
Isc 25 kA
31.5 kA
10
30 203 119 9
12 kV
Ur
17.5 A
630 A
98,5
Ir
1250 A
16 kA
205 ±1
35
586
Isc 25 kA
619 ±2
619
622,5
541
31.5 kA
260 ±1
154 ±1
19,5
340
4
21,5
4
503 25 320
531 370
501 416 53
492
456 ±2 437 0 + 2
150 150 558
661
608
55
50 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
4. Overall dimensions
10
Ir 1250 A
Isc 40 kA
HD4/P
Ø 79
68
Ø 122
TN 7350 67.5
310 ±1
12 kV
Ur
691
17.5 kV
688
686
668.5
Ir 1600 A
63
543
25 kA
53.5
31.5 kA
280 ±1
Isc 40
40 kA (*)
245
164.5 ±1
89
21
50 kA (*)
Ø 19.5
20
(*) Also suitable for
PowerCube PB2. 550 4
21.5
29 359
4
4
626 ±2
416
653
36 551 ±1.5 53
682
68
Ø 122
67.5
50 kA (*)
310 ±1
(*) Also suitable for
PowerCube PB2.
691
688
686
669
63
543
53.5
280 ±1
40
245
164.5 ±1
89
21
Ø 19.5
20
4
550
21.5
359
4
29
4
626 ±2
416
653 36 551 ±1.5 53
682
M E D I U M V O LTA G E P R O D U C T S 51
10
Ir 2500 A
25 kA
31.5 kA
Isc
40 kA
Ø 109
Ø 152
67.5
50 kA
310 ±1
(*) Also suitable for
688
691
686
668.5
PowerCube PB3.
58
63
43.5
280 ±1
30
245
89
21
164.5 ±1
Ø 19.5
750 4
21.5
4
4
4
29 359
806 ±2
416
853
36 554 ±1.5 53
882
10
Ir 3150 A (*)
25 kA
31.5 kA
Isc
40 kA
50 kA
Ø 109
Ø 152
switchgear ventilation
(consult the UniGear
type ZS1 switchgear
730
732
730
technical catalogue).
58
63
43.5
30
280 ±1
245
89
164.5 ±1
21
Ø 19.5
4
21.5
750 29 359
4
806 ±2 416
853 36 554 ±1.5 53
882
52 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
4. Overall dimensions
20
44
630 A
Ir
1250 A
16 kA(*)
Isc 20 kA
25 kA
310 ±1
(*) 630 A only.
35
772,5
766,5
768
717
645
63
325 ±1
254,5
125
198 ±2
461 ±1
4
610 ±2
697 53
653
746 ±1,5
681
Isc 31.5 kA
20
Ø 92.6
310 ±1
28
Ø 35
792
776
718
682
63
8
329 ±1
25.5
293
125
10
202 ±1
550 4
Ø 19.5
21.5
610 ±2 460
653 36 710 ±1.5 53
682
M E D I U M V O LTA G E P R O D U C T S 53
20
144 232 19
Ir 1600 A
16 kA
20 kA
Isc
25 kA
Ø 79
31.5 kA
Ø 122
67.5
310 ±1
(*) Also suitable for
PowerCube PB5. 58
817.5
814
807
733
63
700
43.5
345 ±1
30
310
125
11
198 ±1
806 ±2 4
4
4
457
853
882 36 699 ±1.5 53
20
Ur 24 kV 19
144 232
Ir 2000 A
16 kA
20 kA
Ø 79
Isc
25 kA
31.5 kA
Ø 122
67.5
310 ±1
58
HD4/P
814
817.5
807
TN 7356 (**)
733
Ur 24 kV
63
700
Ir 2500 A (*)
43.5
20 kA
345 ±1
Isc 25 kA 30
310
125
198 ±1
31.5 kA 11
750
21.5
4
4
457
4
with natural
ventilation. 806 ±2
853 36 699 ±1 53
(**) Also suitable for
PowerCube PB5. 882
54 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
4. Overall dimensions
10
12 kV
Ur
35
17.5 kV
630 A
Ir
1250 A
16 kA
310 ±1
Isc 25 kA 28
688
31.5 kA
691
692
640
280 ±1
89
165 ±1
550 +2
19,5
21,5
359 0
4
626
653 416
681 539
587 ±1,50 53
210 ±1 210 ±1
586,5
55
M E D I U M V O LTA G E P R O D U C T S 55
10
Ur
17.5 kV
Ir 1250 A
40 kA
Isc
Ø 35
Ø 79
50 kA
67.5
310 ±1
28
688
688
691
636
63
16
280 ±1
245
89
165 ±1
4
Ø 19.5
626 ±2
21.5
4
4
29 359 40
653
416
682 36 551 ±1.5 53
640
Ir
2000 A
16 kA
Isc 25 kA
67.5
310 ±1
31.5 kA
28
698
691
668.5
635.5
63
8
Ø 122
Ø 79
280 ±1
245
89
165 ±1
4
Ø 20
550
4
21.5
4
29 359 40
626 ±2
653 36 551 ±1.5 53
682 640
56 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
4. Overall dimensions
10
Ir 3150 A
31.5 kA
Isc 40 kA
Ø 109
50 kA
Ø 152
67.5
310 ±1
742
730
730
732
58
63
43.5
280 ±1
30
245
164.5 ±1
89
21
Ø 19.5
750 29 359
21.5
4
806 ±2 416
853
36 554 ±1.5 53
882
M E D I U M V O LTA G E P R O D U C T S 57
Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
HD4/W
842 788
TN 7402 708
275 275 119 23
Ur 36 kV
67.5 144 232 19
20
Ir 1250 A
20 kA
Isc
25 kA
Ø 35
380
78
941.5
949
952
833
63
60
44
480
198
345
10
125
198
805 4
4
457
836
36 699 53
853
882
Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
HD4/W
842
TN 7316 730
Ur 36 kV 706 18
23
275 275
Ir 1250 A
Ø 35
Isc 31.5 kA
380
953
956
973
484
125
202
805 4
456
836
30 701 57
853
882
58 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
4. Overall dimensions
Withdrawable circuit-breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
HD4/W
842 788
TN 7317 708
119 23
275 275
Ur 36 kV 19
20
67.5 144 232
1600 A
Ir 2000 A
2500 A (*)
Ø 122
Ø 79
20 kA
Isc 25 kA
380
31.5 kA 78
ventilation.
952
949
903.5
833
63
60
44
480
345
125
10
198
21.5
750
Ø 20
4
4
805 457
836 36 699 53
853
882
Isc
31.5 kA
ØA
enclosure
type Powerbloc; with
1288.5
forced ventilation in
switchgear type 27
15
Ø 20
ZS3.2.
100
50
900
23 23
30 40
550
43 43
485
22
Ø 16
Ø 18
120
85
80
32.5 45 103
ØA 140 150
100
25 230 200
1250-1600 A 35 mm 718 503
2000-2500 A (*) 79 mm 760 582
M E D I U M V O LTA G E P R O D U C T S 59
25
630 A 229
Ir
1250 A
45°
1
16 KA
Isc 68
20 kA
79
310 ±1
739
35
A
644,5
734,5
435,5 ±2
63
36 8
325 ±1
254
653 25 320
19
4
681 370
382 4
650 414
210 ±1 210 ±1 687 ±1,5 53
19,5
36,3
25
55
DETAIL A
SCALE 1 : 2
60 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
5. Electric circuit diagram
Electromagnetic effect Conductors in shielded Motor (general symbol) Closing position contact
cable (two conductors (limit switch)
shown)
Earth (general symbol) Resistor Change-over break before Lamp (general symbol)
(general symbol) make contact
M E D I U M V O LTA G E P R O D U C T S 61
62 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
5. Electric circuit diagram
M E D I U M V O LTA G E P R O D U C T S 63
64 H D 4 A C C O R D I N G T O I E C A N D G O S T S TA N D A R D S - G A S I N S U L AT E D M V C I R C U I T- B R E A K E R S
—
5. Electric circuit diagram
Caption
= Number of diagram figure -BGB5 = Contacts for electrical signalling of
* = See note indicated by the letter undervoltage release energised/de-
-BCR = Overcurrent release with energised
microprocessor type PR512 outside -BGK = Contact operated by the key lock
the circuit-breaker (see note D) preventing electrical opening with
-BER = Device for continuous control of earthing truck connected
shunt opening release coil continuity (compulsory accessory for earthing
(see note E) trucks with making capacity)
-BGB1, -BGB2 = Circuit-breaker auxiliary contacts -BGS1 = Limit contacts of the spring charging
-BGB4 = Auxiliary passage contact (with motor
momentary closing during circuit- -BGS2 = Contact for signalling closing springs
breaker opening) loaded-discharged
M E D I U M V O LTA G E P R O D U C T S 65
-BGT1 = Contacts electrically signalling circuit- -KFI = Integrated circuit for gas pressure
breaker in the connected position (see control, including:
note G) -PFG = Green lamp indicating normal gas
-BGT2 = Contacts electrically signalling pressure
circuit-breaker in the isolated -PFR = Red lamp indicating insufficient gas
position (see note G) pressure
-BGT3 = Circuit-breaker position contact, -PFY = Yellow lamp indicating low gas pressure
open during the isolating travel -KFA1 = Auxiliary relay to double the -BP
-BGT5 = Position contacts signalling circuit- pressure-switch contacts with
breaker in the racked-out position intervention for low gas pressure
(these are contacts signalling circuit- -KFA2 = Auxiliary relay to double the contacts of
breaker isolated located in the pressure switch -BPS with intervention
enclosure, in the fixed part: see for insufficient gas pressure
contacts -BGT2 in diagram -XDB5 = Connector
1VCP400036 figures 5-6) -KFT = Undervoltage release electronic time-
-BPS = Pressure-switch with two delay device (see note I)
intervention thresholds: -QAB = Main circuit-breaker
– intervention for low gas pressure. -SFC = Pushbutton or contact for circuit-
Contact 11-12-14 changes over, in breaker closing
relation to the position indicated in -SFO = Pushbutton or contact for circuit-
the diagram, when the gas pressure breaker opening
drops from level A to a value below -SFL1 = Contact for circuit-breaker closing
level B. If rated pressure is restored, lock
this contact changes over again -TB1,-TB2 = Rectifiers for -MBO1 and -MBO2
when, starting from a value below releases
level B, the value of level D is reached. -RF = Filter (only provided with 220V d.c.
– intervention for insufficient gas voltage supply)
pressure. -RLE1 = Locking magnet. If de-energized it
Contact 21-22-24 changes over when mechanically prevents circuit-breaker
the gas pressure at level A reaches a closing
value below level C. If rated pressure is -RLE2 = Locking magnet. If de-energized it
restored, this same contact changes mechanically prevents circuit-breaker
over again when, starting from a value racking-in and isolation (it is possible
below level C, the value of level B is to limit its consumption by
reached. connecting a delayed pushbutton in
-FCM1 = Thermomagnetic circuit-breaker for series to enable the operation)
protection of the spring-charging -XDB = Circuit-breaker circuit connector
motor (see note F) -XDB1 = Switchgear terminal board (outside
-MAS = Motor for loading closing springs (see the circuit-breaker)
note C) -XDB2... -XDB62 = Accessory connectors
-MBC = Shunt closing release
-MBO1 = First shunt opening release (see note Rated absolute Pressure Pressure Pressure
E) service value level level level
-MBO2 = Second shunt opening release (see [kPa] (A*) [kPa] (B) [kPa] (C) [kPa] (D)
—
5. Electric circuit diagram
—
Notes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
—
For more information please contact:
—
Your sales contact:
www.abb.com/contacts
More product information:
www.abb.com/productguide
More service information:
www.abb.com/service
1VCP000245 - Rev. E, en - Technical catalogue - 2017.10 (HD4) (gs)