Professional Documents
Culture Documents
Chapter
he measurement of partial discharge has become less expensive, easier to use and hence more
popular as a means to determine the condition of the electrical insulation system in high voltage
equipment like switchgears and transformers.
discharge magnitude is the pico-coulomb (pC), which is the product of voltage and capacitance. One is
most concerned with the maximum value of pC because it will indicate the maximum amount of damage
being inflicted on the electrical insulation system.
deterioration of the electrical insulation system. The actual pC value at the location of the partial discharge
cannot be directly measured because the location of the partial discharge is always embedded inside the
electrical insulation system, and hence there will be no direct access for measurement of the actual pC value
due to the partial discharge. However IEC 270 has established the calibration method to determine th pC
equivalent at the measurable voltage of the phase conductor of the electrical equipment due to the partial
discharge. This will require the injection of a known quantity of pC into the phase conductor and to
measure the peak magnitude of the resulting voltage at the phase conductor.
injected pC at the phase conductor is divided by the measured value of low voltage at the phase conductor
to obtain the pC/millivolts relationship. This derived value of pC at the phase conductor is called the
apparent pC, and is directly proportional to the actual pC value at the location of the partial discharge.
The main disadvantage of the pC method of partial discharge measurement is that the measured
electrical equipment need to be de-energized. For any partial discharge measurement to be widely used, it is
crucial for the measurement to be done without any need to de-energize the electrical equipment.
The
transient earth voltage (TEV) technique will provide this feature. This article will share my experience with
the measurement of partial discharge activity using the continuous mode TEV technique with equipment
from EA Technology of UK. The electrical equipment measured are high voltage air-insulated switchgears
and transformers.
very wide frequency spectrum that will radiate in all directions away from the location of the partial
discharge.
The higher frequency components of the radiated electromagnetic waves will be more
electromagnetic waves will hit the inner surface of the earthed metal cladding of switchgears.
At any
available openings, such as joints or air vents, the electromagnetic waves will escape from the switchgear.
This will cause a transient rise in the voltage of the earthed metal cladding of the switchgear. This TEV has
rise time in the range of nano seconds with an amplitude in the millivolts range. The magnitude of the
TEV is a function of the amplitude of the partial discharge and the attentuation in the propagation path
along the air medium and earthed metal cladding of the switchgear. The TEV is measured using a capacitive
probe placed at the earthed metal cladding of the switchgear. The measued value of TEV will be displayed
in dB as explained in the given Equation (1).
Where dB = 20 log10
Measured TEV
1 millivolts
dB
10
52
398
The detection circuit of the continuous mode TEV measurement set has a wide bandwidth of 70
MHz. The measured TEV is from a peak detection circuit, and so only the maximum value of TEV in any
measurement period will be recorded.
Partial discharge activity is often intermittent in nature. This means that the partial discharge may
be dormant for long periods and become active when initiated by changes in switching, loading, temperature
and humidity. In order to detect intermittent partial discharge, it is important to monitor over a period of
time. A minimum of 24 hours is recommended to study the effects due to changes in switching, loading,
temperature and humidity.
The continuous mode TEV measurement set has 12 channels, of which 8 channels are connected to
8 capacitive probes placed at the earthed metal cladding of the switchgears.
required for the measurement of the TEV magnitude at different locations. The remaining 4 channels are
connected to 4 aerial probes, whose purpose is to detect the presence of interference from external
electromagnetic source. Figure 7.1 shows a typical setup. External electromagnetic waves will first trigger
the aerial probe before the capacitive probe. This time delay is used to screen out the external interference.
The resolution time of the TEV measurement set is about 7 nanoseconds and so the minimum separation
distance between the aerial probe and the capacitive probe will be the product of the speed of the
electromagnetic wave (about 3 x 108 m/s) and the 7 nanoseconds resolution time.
2100mm, which is good enough to locate the source of the partial discharge to individual switchgear.
The continuous mode TEV measurement set will provide the following information:
x
number of pulses
number of pulses in any one channel expressed as a percentage of the total number of pulses in
the measurement period.
percentage of the time in which the pulses were active during the measurement period.
It is defined
amplitude x average number of pulses per cycle x duration of when pulses were detected). This number is
more sensitive to detect partial discharge that is continuous or nearly continuous in nature.
Number of Pulses
All pulses detected by the continuous mode TEV measurement set are counted in the total number
of pulses of the summary table, and at the same time allocated to the channel that first detected the pulse.
If the pulse is detected by two channels within the 7 nanoseconds resolution time, then the pulse is deemed
to arrive at both channels at the same time, and the associated counter for both channels will count up by
one. In a 5 minutes measurement period, the number of cycles for 50 hertz supply will be (5 x 60 x
50) or 15,000 cycles.
Number
of Passes
Duration in Seconds
Remarks
12
13
Each channel is
measured for 2
seconds
13 passes over the 12 channels is not possible because the 312 seconds will exceed the 5 minutes or 300
seconds measurement period. Hence the maximum number of passes will be 12.
The maximum number of cycles will be
288
300
x 15,000 )
5 minute measurement period. The total number of pulses detected in the 5 minutes period will be divided
by 14,400 cycles to obtain the number of pulses per cycle. Hence if the partial discharge is continuous over
5 minutes, the total number of pulses will be 14,400 if we assume one partial discharge in each cycle. For a
partial discharge of intermittent nature, the number of pulses over the 5 minutes may be less than 14,400.
For example, the number of pulse per cycle for an intermittent partial discharge of 5,000 pulses will be
(5,000 pulse/14,400 cycle) = 0.35 pulse per cycle.
Therefore for an intermittent partial discharge within a 5 minute measurement period, the number
of pulse per cycle will be smaller than 1, and in EA Technology practice, values of activity greater than 0.05
pulse per cycles [1] or 1 pulse per 20 cycle will require further investigation.
LEVEL
NUMBER OF PULSES
Ch
Max
Level
dB
No. of
Pulses per
cycle
Av
Level
dB
Short
Term
Severity
No. of
Pulses
%
Pulses
Max
Pulses
per
cycle
Assoc
Level
dB
%
Time
Long
Term
Severity
Maximum
Short
Term
Severity
28
0.021
1398
58
0.021
28
44
28
0.026
844
35
0.026
28
44
19
0.000
282
12
0.000
38
0.000
0.000
22
0.000
177
0.001
32
0.000
34
0.000
0.000
0.000
0.000
0.000
16
0.000
11
0.000
16
10
0.000
0.000
11
0.000
0.000
12
0.000
0.000
2423
282
Capacitive Probes
10/03/2003 14:10:09
Finish Time
11/03/2003 13:35:00
Aerial Probes
Channel 2
Channel 12
Channel
3
Channel
4
Channel
5
Channel
6
Channel
7
Channel
8
Channel
9
Channel
10
24kV
VCB
24kV
VCB
24kV
VCB
24kV
VCB
24kV
VCB
24kV
VCB
24kV
VCB
24kV
VCB
Channel 1
Channel 11
The capacitive
because of the relatively large 25dB TEV magnitude. During one of the 5 minutes measurement interval,
of which there are 288 such intervals, the total number of pulses detected were (0.02 pulse per cycle x
14,400 cycles)
or 288 pulses. Figure 7.2 shows the dB magnitude of the pulses measured over the
measurement period for Channel 3. Figure 7.3 shows the number of pulses over the same measurement
period for Channel 3. With all these information, we have the following conclusion for the maximum and
intermittent partial discharge activity at channels 3, 6, 8 and 10.
x
Intermittent partial discharge was detected in one of the 5 minutes measurement interval
because the number of pulses per cycle was not zero and equal to 0.02 pulse per cycle.
However, only a value greater than 0.05 pulse per cycle [1] will require further investigation.
x
The short term severity of zero indicated that the largest magnitude partial discharge was not
large enough nor this same partial discharge occurred very long enough to cause problem.
In addition, a near continuous partial discharge was measured at channel 6 because of the 90% value
in the % time column. Figures 7.4 and 7.5 show the detailed information. A long term severity value of
zero indicated that this near continuous partial discharge was not large enough to cause problems to the
electrical insulation system.
LEVEL
NUMBER OF PULSES
Ch
Max
Level
dB
No. of
Pulses per
cycle
Av
Level
dB
Short
Term
Severity
No. of
Pulses
%
Pulses
Max
Pulses
per
cycle
Assoc
Level
dB
%
Time
Long
Term
Severity
Maximum
Short Term
Severity
31
0.002
804
11
0.033
13
43
0.000
0.000
25
0.020
324
0.020
25
0.000
73
0.001
20
0.000
43
0.001
13
0.000
780
11
0.004
10
90
10
0.000
71
0.002
16
0.020
1943
26
0.020
16
25
0.000
45
0.002
10
13
0.006
303
0.006
13
28
11
40
0.006
3330
45
0.016
13
33
12
0.000
0.000
7351
288
18/03/2003 15:06:00
Finish Time
19/03/2003 14:26:00
Channel 2
Transformer
Inside
Enclosure 1
Aerial Probes
Channel 12
Channel 4
Channel 5
Capacitive Probes
Channel 8
Channel 6
Channel 9
Channel 3
Transformer
Inside
Enclosure 2
Channel 10
Channel 7
Channel 11
Channel 1
In general, the partial discharge magnitude in the electrical equipment must be above 100pC [2]
before reliable TEV can be measured.
TEV measurements are not suitable for gas insulated switchgears (GIS) because the totally
enclosed construction will not allow the escape of any TEV within the GIS to appear at the
outside of the GIS. Again ultrasonic sensors of the contact type will be more suitable for GIS.
19/03/2003 14:21:00
19/03/2003 13:36:00
19/03/2003 12:51:00
19/03/2003 12:06:00
19/03/2003 11:21:00
19/03/2003 10:36:00
19/03/2003 09:51:00
19/03/2003 09:06:00
19/03/2003 08:21:00
19/03/2003 07:36:00
19/03/2003 06:51:00
19/03/2003 06:06:00
19/03/2003 05:21:00
19/03/2003 04:36:00
19/03/2003 03:51:00
19/03/2003 03:06:00
19/03/2003 02:21:00
19/03/2003 01:36:00
19/03/2003 00:51:00
19/03/2003 00:06:00
18/03/2003 23:21:00
18/03/2003 22:36:00
18/03/2003 21:51:00
18/03/2003 21:06:00
18/03/2003 20:21:00
18/03/2003 19:36:00
18/03/2003 18:51:00
18/03/2003 18:06:00
18/03/2003 17:21:00
18/03/2003 16:36:00
18/03/2003 15:51:00
18/03/2003 15:06:00
Number of Pulses
150
100
50
Date/Time
19/03/2003 13:46:00
19/03/2003 13:06:00
19/03/2003 12:26:00
19/03/2003 11:46:00
19/03/2003 11:06:00
19/03/2003 10:26:00
19/03/2003 09:46:00
19/03/2003 09:06:00
19/03/2003 08:26:00
19/03/2003 07:46:00
19/03/2003 07:06:00
19/03/2003 06:26:00
19/03/2003 05:46:00
19/03/2003 05:06:00
19/03/2003 04:26:00
19/03/2003 03:46:00
19/03/2003 03:06:00
19/03/2003 02:26:00
19/03/2003 01:46:00
19/03/2003 01:06:00
19/03/2003 00:26:00
18/03/2003 23:46:00
18/03/2003 23:06:00
18/03/2003 22:26:00
18/03/2003 21:46:00
18/03/2003 21:06:00
18/03/2003 20:26:00
18/03/2003 19:46:00
18/03/2003 19:06:00
18/03/2003 18:26:00
18/03/2003 17:46:00
18/03/2003 17:06:00
18/03/2003 16:26:00
18/03/2003 15:46:00
18/03/2003 15:06:00
Amplitude dB
measurement will provide a higher confidence level to detect intermittent partial discharge.
30
25
20
15
CH3 Amplitude
10
Date/Time
350
300
250
200
Conclusion
Compared to any form of snapshot partial discharge measurement, the continuous mode TEV
In addition,
the TEV technique does not need the de-energization of the electrical equipment, or the removal of any
protective cover panel. The on-line and non-intrusive nature of the TEV technique makes this as a very
19/03/2003 13:36:00
19/03/2003 12:51:00
19/03/2003 12:06:00
19/03/2003 11:21:00
19/03/2003 10:36:00
19/03/2003 09:51:00
19/03/2003 09:06:00
19/03/2003 08:21:00
19/03/2003 07:36:00
19/03/2003 06:51:00
19/03/2003 06:06:00
19/03/2003 05:21:00
19/03/2003 04:36:00
19/03/2003 03:51:00
19/03/2003 03:06:00
19/03/2003 02:21:00
19/03/2003 01:36:00
19/03/2003 00:51:00
19/03/2003 00:06:00
18/03/2003 23:21:00
18/03/2003 22:36:00
18/03/2003 21:51:00
18/03/2003 21:06:00
18/03/2003 20:21:00
18/03/2003 19:36:00
18/03/2003 18:51:00
18/03/2003 18:06:00
18/03/2003 17:21:00
18/03/2003 16:36:00
18/03/2003 15:51:00
18/03/2003 15:06:00
Number of Pulses
30
20
10
Date/Tim e
19/03/2003 13:46:00
19/03/2003 13:06:00
19/03/2003 12:26:00
19/03/2003 11:46:00
19/03/2003 11:06:00
19/03/2003 10:26:00
19/03/2003 09:46:00
19/03/2003 09:06:00
19/03/2003 08:26:00
19/03/2003 07:46:00
19/03/2003 07:06:00
19/03/2003 06:26:00
19/03/2003 05:46:00
19/03/2003 05:06:00
19/03/2003 04:26:00
19/03/2003 03:46:00
19/03/2003 03:06:00
19/03/2003 02:26:00
19/03/2003 01:46:00
19/03/2003 01:06:00
19/03/2003 00:26:00
18/03/2003 23:46:00
18/03/2003 23:06:00
18/03/2003 22:26:00
18/03/2003 21:46:00
18/03/2003 21:06:00
18/03/2003 20:26:00
18/03/2003 19:46:00
18/03/2003 19:06:00
18/03/2003 18:26:00
18/03/2003 17:46:00
18/03/2003 17:06:00
18/03/2003 16:26:00
18/03/2003 15:46:00
18/03/2003 15:06:00
Amplitude dB
14
12
10
CH6 Amplitude
Date/Tim e
60
50
40