You are on page 1of 4

Cable duct from Raw material storage substation to reclaimer

side drg No W14-06-03-201

Cable duct section from Raw material storage substation to


reclaimer side drg No W14-06-03-221

Observations

The length of the duct is approx. 60 meter as per DTS > distance pit should not
be more than 50 meter.
200 dia PVC pipes are shown for the LV power cables ?? As per DTS >= 250
mm.
The density of the cable should be restricted to 60%. To confirm this validation
from the electrical designer may be needed.

Lafarge DTS -14 for the installation