Typically 500mmx500mm
trench is shown in the drawing.
Typically 500mmx500mm
trench is shown in the drawing.
Pro-erection Recommendations :
Insert plates/ suitable fixing arrangement for fixing a M12x 200 mm continuous steel plate to be foreseen
for transformer entry and retrieval.
A equi-potential bonding point to be foreseen in each of the transformer room Presently missing in the
Earthing implantation diagram .
If possible suitable cable trays ( 300 mm wide for the primary , 400 mm 1No + 1 duct tray for the PGT for
control.
The secondery cables in the existing line -1 are single core . If we are going in line 2 also single core there
are approx 24 No of 240 sqmm. Accommodating them for the proper job to be foreseen.
Typical distribution transformer having 200 xM12 Plate welded on the insert
plate