Elektropaks P.P.H.U. performs onsite HV cables
after-laying tests with Megger HV
Customer
Elektropaks –
Polish energy construction sector
www.elektropaks.pl
Facts
■ 35 million € annual turnover
■ 270 employees
■ 1.000 km line length
Requirement
Onsite acceptance tests
Goal
■ Detect assembling errors
■ Secure use of the HV 110 kV cables
Implementation
16/11/2018
The polish construction company Elektropaks uses Sheath fault test
Megger services to perform on-site acceptance
tests on newly installed HV 110 kV power ca- The sheath of the 450 meter long cable is tes-
bles. The HV DAC 300 system has been employ- ted with the MFM 10-1. This instrument detects
ed for monitored voltage withstand testing and sheath faults through a voltage up to 10 kV dc
sensitive PD diagnosis. Thanks to TDR analysis of and 750 mA. With this measurement, a techni-
recorded PDs, systems can localise cable weak cian can not only check whether the insulation
spots, which can be repaired before network is faultless, but they can also locate damages to
energising. HV tests involve DAC volta- the cable.
ge increasing up to 128 kVrms and 50x
DAC excitations per single cable phase.
Fast and easy system setup allows for time
efficient tests. Small footprint and compact test
setup gives the user the opportunity to perform
tests on power cables directly under the towers
or in small substations.