Professional Documents
Culture Documents
THE ADAPTIVE CABLES TESTING
SYSTEMS
FOR YOUR CABLE INSTALLATIONS
1
Reliable data on the condition of power generation and distribution equipment is now more critical than ever. As a grid
operator, you need dependable information in order to make practical decisions on maintenance and repairs. For
example, you need answers to questions such as: “Is the insulation on our generators, cables, substations, and
transformers operationally reliable? Do we need special inspection or handling procedures?” This information is
essential for developing maintenance strategies and for planning optimal technical and commercial investments. It also
significantly reduces the risk of unplanned power supply interruptions.
Obtaining this information calls for comprehensive diagnostic measurements that allow the nondestructive assessment
of grid conditions. Such measurements are technically demanding, however, and call for appropriate instrumentation,
operational experience, and extensive know-how to evaluate the results. That is why you need the expertise and
practical experience offered by the engineers at ohv diagnostic!
ohv diagnostic - years of experience in a young company
We founded ohv diagnostic GmbH in 2013 as a group of engineers with many years of experience in the industry. We
develop and build modern measurement and testing systems, repair and upgrade existing equipment, and provide
diagnostic measurements and other services.
In our company, we manufacture testing and measurement equipment for diagnosing conditions of electrical operating
equipment in medium and high voltage cables. Our top goals in development are maximum precision and easy
operation. Our product range is constantly growing and includes DAC testing devices for medium and high voltage
cables, probes, couplers, and accessories for partial discharge measurements, as well as customer-specific devices
and systems. We also develop systems based upon your special requirements, build or repair OEM devices, and
modify existing testing equipment.
We also support your operations with a variety of services. We perform diagnostic measurements for many types of
operating equipment and create a complete test report with recommendations for action. In commissioning projects,
training courses, and seminars, your employees receive the tools they need to perform measurements on their own.
Our range of services also includes calibration of instruments used for partial discharge measurement.
manufacturing
power utilities and distribution
research institutions
assembly
2
OUR PRODUCTS
ohv diagnostic - our products for informative, reliable measurements and tests
OHV DIAGNOSTIC manufactures testing and measurement devices for condition assessment of high voltage
operating equipment. Based upon our experience, we have developed testing and measurement devices that offer the
highest level of confidence when determining the actual condition of high voltage systems. Our product development
also incorporates the latest findings from research, such as optimization of handling (primarily on-site) and precision.
During the energizing phase the cable is charged via a HV reactor up to the
pre-selected peak test voltage by a high voltage source within a couple of
seconds. After having reached the test voltage the DC source will be
disconnected and the HV switch will be closed instantly providing LC
resonance circuit with the cable capacitance and the system inductance.
This provides a damped sinusoidal AC (DAC) voltage.
3
The use of partial discharge and dissipation factor measurement during testing allows users to detect defects
caused by:
faulty assembly
incorrect handling during transportation or installation
faulty joints or terminations
aging of cables or the insulation of cables and cable accessories.
This provides a great deal more information than a simple voltage test. As a voltage source, ohv diagnostic uses
damped AC (DAC), also known as “Oscillating Wave Test System” (OWTS). The test voltage requires very little power
on site and can supply sufficiently high-test levels to cable sections of typical length. The frequency is within the
standard-compliant range of 20 Hz to 300 Hz. In this process, AC voltage is generated based upon the simple principle
of serial resonance: the cable is continuously charged and when the test voltage level is reached, it is discharged using
a high-voltage semiconductor switch on an inductor. This creates an oscillating discharge voltage, during which partial
discharges and the dissipation factor can be measured. The number of oscillating discharges (impulses) is usually 50,
since scientific studies have proven that defects hazardous to operations safely change into measurable partial
discharges within these 50 discharges.
Damped ac testing and diagnostics benefits
The main benefits using DAC voltage test and diagnostic measurements are:
Applicable for all types of MV, HV and EHV power cables for rated voltages up to 380 kV: XLPE, EPR, PILC,
LPOF, HPPT
Applicable for after-laying commissioning tests for long lengths of power cables (0.1 km – 30 km), providing a
condition assessment baseline for future comparison
PD localization in cable insulation and accessories provides accurate information about location and
magnitude of any defects
Reproduces AC stresses from the electrical network
Approved method, accepted by relevant international standards (IEEE, IEC)
Non-destructive and sensitive testing method
Portable test system, compact design and low weight with reduced energy consumption during testing
Combined with standardized partial discharge diagnostics
Combined with dissipation factor measurements at HV conditions
State of the art power electronics and signal processing technologies
Straightforward technology and operation
Using this method, allows much more than a simple go or no-go decision. DAC testing is an advanced maintenance
tool which supports asset management and grid operation as well.
4
DAC M30/M60
Professional testing and diagnosis of medium voltage cables
DAC voltage test and diagnostic measurements (PD and Tan-Delta) provide a reliable detection of:
Poor installation
Failures due to inappropriate laying
Weak spots in cable accessories or
Deterioration of cable insulation due to aging
It allows much more than a simple go or no-go decision. DAC testing is an advanced maintenance tool which supports
asset management and grid operation as well.
In addition to voltage testing, our proven M30 and M60 medium voltage cable
testing systems measure and precisely localize partial discharges. They also
determine the dissipation factor in the same operation, in order to assess age
condition in aging cables. This translates into maximum informative value and
confidence for a rapid assessment of your cable system’s condition.
The system was developed for on-site testing of 10 kV and 15 kV cable systems.
The M30 can generate on-site oscillating discharge voltages with a maximum
peak voltage of 30 kV, or 21.2 kVeff. The system is small and light and can fit into
a large van. Depending upon the cable type, the system can be used to test cable
sections up to several kilometers in length, even though its power requirement is
only 500 W.
5
Despite this system’s very low power requirement, it can test 145
kV / 220kV cable sections of up to several kilometers in length. For
technical data, please refer to the data sheet on our website:
www.ohv-diagnostic.com.
6
CASE STUDIES
1. Shanghai, China 35kV XLPE Cable
In this case study we would like to share with you our experience of the routine on-site tests of Partial Discharges
performed in the city of Shanghai, China.
Partial discharges indicate inhomogeneities within high voltage insulation systems. For this reason, sensitive detecting
as well as exact locating of PD signals are important requirements for condition assessment of high voltage equipment.
On-site DAC voltage test in combination with non-destructive PD and loss factor measurement is unique and
fundamental for reliable service of newly installed, repaired or service-aged cable systems.
Cable details
As this XLPE cable voltage is 35kV, we are used our product M60 with DAC Output voltage 60kV (peak) / 42,2kV
(RMS). Phase Resolved PD Pattern: Typical phase stable PD pattern found on all three phases. The noise level was
100 pC.
PD – Mapping
The joint with high Partial Discharges was cut. The customer found serious
trace of Partial Discharges activities. The customer replaced defective joint
by a new one and we made together the second test with DAC system. This
time, there is no PD concentration anymore in replaced joint.
Conclusion
The defective joint was send by customer to HV laboratory for investigation. This joint was cut
to slice for analysis. Result: the laboratory found the air bladder very clearly in the XLPE
layer.This defect might be caused by the warm shrinking process with bad temperature
controlling.
7
In this case study we would like to share with you another on-site test of Partial Discharges performed in the city of
Nordenham in Germany. This time our customer would like to optimize their maintenance cost of this electrical cable
XPLE 20 kV and find the exact position of cable joints with abnormal level of partial discharges. The main aim was to
reduce risks of costly production stops.
Cable details
Cable voltage 20 kV, type – XLPE.
The length of cable: 435m
The position of cable joint: 221m, 870m, 560m,
1750m.
Test results:
The defective joints and their exact positions were indentified by M60 and customer replaced them by a new joints.
8
Partners
Today we have developed a network of highly qualified and dedicated partners able to deliver solutions in your region
and provide you the service with quality you are expecting.
Our company is very carefully in selecting the partners can provide technical support and are always being prepared
to provide the engineering solution with meeting of the highest industry standards together with repair and service of
OHV Diagnostic products. This approach enables us to maintain close contact with our customers and deliver prompt
after sales support all over the world.
Our analysing solution are designed to customer requirements and are suitable for all type of cables applications. OHV
Diagnostic solutions are tailor designed for your requirements and meet all major international standards.
We continuously look at better serving our customers worldwide, so if you would like to discuss your support
requirements or to find out more about our total capability in cables applications, please contact us.
How we can reduce risk of possible failure?
The periodic monitoring of Partial Discharges can give us an early warning of potential problems. This will enable the
customer to effectively identify any possible issues and resolve them rather than having an expensive interruption to
normal production which at times can also be potentially safety critical.
The main benefit of monitoring systems – using it as the preventive tools that can help to reduce the risk of catastrophic
major failures of the electrical equipment. At the same time, this approach helps the customers to optimize maintenance
cost of these electrical installations and to reduce risks of costly production stops.
For more information about these case studies or about PD monitoring systems that were used, please contact:
info@ohv-diagnostic.com
OHV diagnostic has its headquarters in Dresden. We are part of an international network of companies, which allows
us to rapidly send specialists almost anywhere.
9
‐‐‐‐
10