Professional Documents
Culture Documents
Key Words: partial discharges (PD), power cables, discharge magnitude, discharge inception
depend on several practical aspects like PD detection method, PD calibration, level of test voltage applied.
General
It is known that partial discharges (PD) are a good indication of
discharging
medium voltage (MV) power cables. Due are symptoms of dielectric degradation, the electric stresses is essential to
to the fact that the discharging defects analysing PD magnitudes in function of estimate properly the degradation
Figure 1: Application of PD measurement in function of
the AC over-voltage test. Any particular discharge larger than q0 (cable specific acceptance value)
progress [1, 2, 20, 40, 41]. PDs occur in the dielectric and do not completely bridge the insulation and the
forming of the defect can take months or years but than in a matter of minutes, or even throughout the dielectric, bridging the insulation. When the insulation is less the defect can extend
initial
rejection of the object under test, see shaded area. PD referred to U0 are important indicators of PD presence during network operation.
1
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
As a result the detection of partial discharges is a well accepted tool for condition
assessment of new and service aged power cables. Many years of good experiences in factory PD testing of new manufactured components, have resulted in the implementation of PD detection also for on-site testing. In the last 15 years depending on the type of PD testing and diagnosis [8-16].
component, the network levels different solutions have been developed and implemented for
In this contribution with regard to the on-site PD detection on power cables practical aspects will be discussed. In particular, based on practical experiences the fundamental issues of PD occurrence in power cables as well as the interpretation aspects will be mentioned. The goal applying PD diagnosis.
Introduction
Although some in the electric power realize, partial industry all extruded may cable not
(a)
External voltage source Level: e.g. up to 3.0Uo IEC 60060-3 IEEE 400
test
the
Radio frequency (RF) PD detection Radio frequency (RF) PD detection Radio frequency (RF) PD detection Radio frequency (RF) PD detection
experts would agree that the production PD testing of cable components and
(b)
have Figure 2: Principles of off-line PD detection methods for power cables; become so well developed over the last 40 years that the vast majority of defects on newly installed systems are not likely process but rather to to be due to the manufacturing workmanship. Many cable
a) Standardized and calibrated PD detection (conventional) insulation and cable accessories, b) applicable for both factory testing and on-site testing of cable Not-standardized and not-calibrated PD detection
(unconventional) for on-site testing of cable accessories. (IEC 62478 under preparation, Cigre D1.33 brochure under preparation).
production PD test and are using PD diagnostics in the field to compare the results with
known baseline factory tests. In fact, [29] states that if the cable system can be tested in the
field to show that its partial discharge level is comparable with that obtained in the factory
tests on the cable and accessories, it is the most convincing evidence that the cable system is in excellent condition. Although the reason to use PD diagnostics in the field is a natural
2
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
choice for many applications, it is the general experience that the metrics used to assure the overlooked. To sum up the typical misunderstanding, one might say that not all PD tests are on-site (conventional) PD diagnostic test results and (unconventional) PD measurements.
field results can be compared with the factory results are widely misunderstood and often created equal. This is especially true when comparing the factory PD test results with typical
Much research has been performed over the last 15 years to determine the frequency dependence of PD tests [3]. Research indicates that changing the frequency by more than an order of magnitude can significantly change the apparent inception voltage of a PD site. This is a concern, as some off-line PD tests use frequencies outside the range of 20Hz up to a literature search by the author, decreasing the test frequency by an order of magnitude can with the factory PD test [3, 6, 7].
300Hz as recommended in [26, 27] which is used in factory and on-site tests. According to change the apparent inception voltage in a typical range from 5 to 30% when compared
to
RF PD detection
RF PD detection
RF PD detection
RF PD detection
by internal fault in the Figure 3: Principles of on-line PD detection methods for power cables; on-line: insulation systems of the cable network. Visual
non-standardized and not calibrated PD measurement in cable accessories of cable section in service.
inspection of the disturbed components may give insight in the different types of breakdown components of cable network can be made, as reflected in [3, 23].
related insulation defects. Based on these visual inspections, a list of defects in different For many years, withstand testing (AC and DC) was the only testing method applied in the shown in [3, 20, 23, 41], partial discharges (PD) are sensitive and until now they are the best
power cables network, but nowadays also PD testing has become an accepted method. As symptoms of discharging weak spots (insulation defects, degradation processes) in the HV insulation.
It follows hat there is a large diversity on insulation defects which may occur not only in the
accessories of a cable but also in the insulation. Moreover, it is know that PD inception in all
these defects depends on the local electric field enhancement. As a result with regard to accessories).
insulation defects different situations may occur in a cable system (insulation and/or
3
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
1. Cable system is PD-free; starting at higher than 1.7Uo electric stresses e.g. > 3Uo PD any PD inception in defects. discharging with voltage than PD defects higher lower
may start to ignite in accessories; in that case temporary over-stresses will not produce
than 1.7Uo; in that case due to temporary AC or the PD switching over-voltages can be ignited and in the extinction during case of voltage PD development
1Uo
(PDIV)
(a)
but
(b)
3. Cable system contains discharging defect with case in the PDIV< 1.0Uo; in that insulation and/or cable accessories processes during are active PD
(c)
cable
operation.
on the type of defect and the local electric besides field concentration
Depending
network
a) just after PD ignition, both pulses travel in the opposite direction [3] b) after reflection at the remote end, both pulses travel in the same direction
knowledge
c) example of localisation of PD source by analysing the PD wave time (A), after which the reflected wave (B) occurs. The incident wave is
differences; he first detected pulse is the incident wave of the PD event reflected at the detection side of the cable and if not attenuated to noise level, it will appear as A. From the time difference between the incident
the information about the decrease of PDIV, increase to magnitude are essential degradation process. evaluate of PD
and the reflected wave, together with the calibrated propagation velocity
the
It was already shown many years ago [1] that the best way of PD detection as well as the recognition of different discharging defects is related to changes of the applied electric field,
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
see figure 1. This interaction between PD inception voltages (PDIV), PD extinction voltage
(PDEV), and PD magnitude at different voltage stresses provides more detailed picture about the PD processes in different types of cable insulation defects. Obtaining this information in its turn is important in interpretation of discharging defects:
1. The level of PDIV as compared to the nominal service stress is of absolute relevance in mostly more severe that a defect with PDIV =0.9Uo [2, 3, 6].
determining the degradation ration; e.g. discharging defect with if PDIV = 0.3Uo is
2. To declare a power cable PD-free the PDEV has to be at least 1.3Uo [ANSI ICEA]. between PDIV and 1.7Uo is a good indicator of defect severity [2, 3, 6]. it can be of
3. Analyzing the increase of PD level and PD intensity in function of the applied voltage e.g.
Summarizing -
discharging complexity
for sensitive PD diagnosis of power cables the voltage dependence processes is important. of PD
cable systems
of
where the test object is energized from external voltage sources [28] and with regard to
detection
PD detection a distinction can be made between standardized so called conventional detection method [30, 31] and the not-standardized so called unconventional the radio 2. on-line detection where the test object is energized from the network and with regard to PD detection the unconventional RF detection is applicable only. frequency (RF) method,
In the following paragraphs relevant aspects of sensitive PD detection and the practical implications by using these methods for PD detection and localization are discussed.
5
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
The so-called off-line method has been introduced many years ago for factory testing. Since power cables.
a few years this method has also been in use for on-site testing of new and service aged This method can only be applied on cables systems which are disconnected from the network. The off-line PD detection consists of an external voltage source [28], preferably voltage classes: a) c) sinusoidal AC voltage as recommended in the standards for testing power cables of different
To detect PD in the power cable standardized circuit different standards can be applied [30, 31, 33].
Performing off-line PD detection using conventional method covers an important step in value in pC of the smallest the test conditions. Following the
assessing the sensitivity of the particular circuit. The purpose of this step is to determine the PD signal detectable under
80.00 60.00 25 uV/pc 40.00 7 uV/pc 20.00 0.00 0 100 200 300 400 5 Frequency [MHz]
calibrated: [pC] / V ratio depends on the characteristics of the whole has to be estimated.
procedure
detection will be performed in [pC] which is important step and between for on-site Due comparisons testing test full
the
calibration final PD
standards.
the
factory
to
Moreover, applying the conventional PD detection provides PD detection and localisation of discharging defects in the whole cable system: cable insulation and cable accessories.
processing
procedures,
circuit and the selected RF frequency band. Sensitivity in [pC] of the circuit
Amplitude [uV]
6
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
With regard to PD site localisation similar to factory testing procedure can be applied, see
accessories or in the cable insulation, one PD pulse will travel towards the near cable end, end. Finally, this pulse will also arrive at the near end of the cable. When the velocity of the
figure 4. In particular after a discharge process occurred in a cable on location X, e.g. cable
the other pulse travels in the opposite direction, and will reflect on the remote open cable PD pulses is known from standardized calibration, the location of the PD can be determined by measuring the time lag between the first pulse and its reflection. To determine the cable end. The time difference between the original pulse and its reflection, together with velocity a calibration measurement is used where a calibration pulse is injected at the near the known length L of the cable determines the velocity v. This technique is known as Time Domain Reflectometry (TDR). With a devoted software tool for TDR, one can analyse PD measurements to identify partial discharges, their reflections and thus their locations along the whole power cables. To improve this process, the software tool uses a heuristic algorithm, correlation and digital band-pass filtering [3, 34-36]. After this identification specifying a list of joint locations, a convenient graphical overview over a cable is obtained. length and the characteristic HF impedance of the particular cable section [18].
process, it is possible to create location mappings of partial discharges, see figure 5. By Applying TDR for PD site localisation the PD detection sensitivity depends on the cable
Since a few years, in addition to after laying tests of new installed cable accessories the
(a)
frequency (RF) signal processing (using e.g. narrow or wide band amplifiers, spectrum analyzers) 2b. This method is called non moment the no guidelines and have been introduced, see Figure conventional because at this
(b) (c)
or
the
devices are able to couple out by inductive or capacitive sensors the PD signals from the cable
7
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
PD amplitude in [mV] or [V]. Due to the fact that RF systems can use different frequency ranges (up to hundreds of MHz) the PD amplitudes can not be measured in [pC], Figure 6. To determine the meaning of these amplitudes Cigre WG D1.33 and IEC 62478 are preparing the guidelines to estimate the sensitivity level of RF devices. With regard to power cables such procedure may consist of two parts [19, 37]: Laboratory procedure
1. Installation of an artificial PD defect (e.g. PD level below 100pC) on a full size 2. Installation of given type of HF/VHF sensors on the cable accessories and connection of a 3. HV energizing of the full size setup and PD detection using both system: IEC60270 and 4. Analysis of RF response of different types of sensors. different VHF/UHF frequencies. the PD defect from (1) and (3). RF PD detection system. PD detection circuit (IEC60270). combination of power cable part and cable accessories;
5. For PD defect from (1) and (3) ratio estimation of the lowest [pC] reading and [V] for 6. Search for an artificial voltage pulse with similar frequency/amplitude characteristics as 7. Estimation of the whole circuit sensitivity in [pC] and the suitable frequency ranges. On-site procedure
1. Performance check (sensitivity check) of the whole system: cable system, RF PD detection pulses;
system including installed sensors by injection of the by (5) selected artificial voltage
2. Tuning of the unconventional PD system to HF/VHF frequency range with best 3. Optional using [31] standard calibrator injection on the cable termination of PD pulses and estimation of the RF detector responses at frequencies (e.g. below 20MHz) which are typical for TDR analysis of PD pulses in power cables. signal/noise ratio;
accessories only. Depending on the frequency range of the RF detection system the PD activity can be fitted to the particular joint only (frequency range of few hundreds of MHz) or to the PD activity in the whole cable system (frequency range of several MHz only).
accessories, the non- conventional PD detection is applicable for after laying tests of cable
Due to the fact that the above mentioned procedure can only be done for newly installed
8
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
the most overlooked aspects of PD field tests. In the factory, manufacturers go to great lengths, including the erection of electromagnetically shielded test rooms, to assure that the test sensitivity meets the standard requirement. sequences to assure minimal pC magnitude measurement error with their limited bandwidth systems [38]. The most up-to-date guide for PD testing in the field with such systems is They also perform special calibration
PD equipment. PD testing in the field requires the use of ultra-high bandwidth detection According to [30] calibration and sensitivity assessment are critical since poor test
[30].
sensitivity and incorrect pC magnitude assessment commonly lead to faulty test results. The following text describes a sensitivity assessment and calibration procedure which will assure that field tests are in compliance with [30] and comparable with factory test standards.
The practical implications of a proper pC sensitivity assessment and calibration for each cable test are significant. For example, an inaccurate apparent charge calibration and/or outdated measurement equipment can lead to errors in the range of one order of magnitude.
9
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
test results with factory PD tests. The unconventional PD test has an obviously apparent electromagnetic disturbances and noises from the external voltage sources (off-line) or form the network (on-line) can be suppressed by choosing for PD detection VHF or UHF frequency ranges. However, a sensitivity assessment in [pC] according to [30, 38] can not be performed due to differences in detection principles. advantage in the field in that it can be applied to the accessories directly and the
Therefore, since the calibration of unconventional detection can not be performed, the
transformer (CT) is placed in proximity to an energized joint or termination location, it is not attenuation (or gain) factor to correlate the voltage measurements to pC values. Although sensitivity assessment be performed prior to any PD diagnostic test in the field. Otherwise, requirements are not followed and the cable owner should be aware of the risk that the test may not detect all PD activity. practical to inject a pulse on the conductor of the cable system and determine an accurate
possibility of a false negative is significant. If, for example, a radio frequency (RF) current
this example discusses the challenges of unconventional tests, [39] recommends that a without a proper sensitivity assessment of unconventional PD detection the standards
Practical Experiences
Referring to systematic research as performed in the field using on-line PD detection [3, 17, 23-25] in this chapter the practical aspects of conventional and unconventional PD detection differences and specific aspects of using both PD detection methods. will be discussed. In particular the major goal of this discussion is to point out the technical
Applying conventional PD detection provides sensitive PD localisation in length of power cables up to several kilometres [18].
content increases heavily with the cable length, the sensitivity of RF detection systems operating at higher frequencies is limited to a few hundred metres. In figure 7 an example is
Based on the fact that starting from 1520 MHz the attenuation of PD energy frequency
shown of a very short cable (320m), where based on conventional off-line diagnosis PD
activity has been observed in a cable joint at 65m location. Based on unconventional detection as performed on both cable ends the signal reduction of 25% per 100m was observed. As a result the applied on-line detection on cable terminations will experience problems in detecting PDs on cables longer than 0.5km.
10
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
This observation is also confirmed by comparing conventional and unconventional detection as applied to a cable with a typical length of 1950m (PILC insulation), figures 8 and 9. Using conventional PD detection PD activity has been analysed up to 1.7Uo. At PDIV below 1Uo two areas of PD activity have been localised. a) The 1st one PD up to 3.5nC in the cable
1
insulation: 0m up to 600m where no PD b) The 2nd one up to 7.5nC (phase blue) has been observed at the position of 1100m (joint location). concentrations have been observed.
(a)
Analysing the phase resolved patterns as observed presence has been also confirmed. at both terminations the PD
(b)
(c)
performed up to 1.7Uo on terminations 1 and 2 of a PD site mapping: it follows from this graph that at the location 1100m PD activity up to 7.5nC has been observed in the joint; b) and c) PD phase resolved pattern
As shown in figure 8 PD signal attenuation has sensitivity. It follows from the example in less influence on PD
detection
figure 8 that applying conventional detection both cable ends in a similar way.
The same cable has also been tested using the network voltage Uo at both terminations the EM disturbances have been estimated and at the frequency with the highest signal/noise ration the PD signals have been detected and processed to phase resolved patterns. Taking into account the actual length of this cable 1950m and the in figure no sensitive PD detection in cable insulation and in cable joint can be explained.
(b)
power cable:
(AM) of power cable networks. In particular, based on actual condition status AM can
11
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
major goal of PD diagnosis of power cables is to detect and to localize discharging insulation of view of insulation degradation.
optimize the maintenance and the replacement of non-reliable cable sections. Therefore the
defects, to estimate the actual PD magnitude and to interpret the PD presence from the point
The on-line PD test has the obvious advantage that it does not require disconnecting the cable. In some cases, PD in severely degraded terminations and joints can be detected if method, it is vitally important to understand its limitations. These limitations include: a) the low percentage of defects which are detectable at the operating voltage level, they are readily accessible. Although on-line PD testing is a useful tool, as with any test
c) the likelihood of a relatively high percentage of false positive readings. A very low percentage of defects can be detected at the operating voltage level. This is most likely because extruded cable insulation cannot tolerate continuous PD activity for an extended period of time. detected with the on-line method during the relatively short time between the PD activitys For this reason, it is very unlikely that serious defects will be
initiation at operating voltage and failure. In some studies, such as [11], it has been shown that less than 3% of defect sites in cable systems with PD have been reported to be active at system to be defect free only to have a transient voltage turn on a defect a short time later or below operating voltage level. This is a great concern as an on-line test can deem a cable
A sensitivity assessment can not be performed according to [30] while a circuit is live. Therefore, since the sensitivity of the on-line test cannot be determined, the test results are not dependable and cannot be compared to factory test standards.
On-line test results inherently yield a relatively high percentage of false positive readings. switchgear, electrical buses, motors, transformers, and transmission lines. PD activity from
During the test, the cable is left connected to the rest of the power system including external sources interferes with the on-line test and appears to be originating from the cable under test. This challenge of false readings is only complicated if the access points to the cable system are more than a few hundred feet apart.
12
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
Conclusions
In this contribution different aspects of on-site PD detection have been evaluated. Based on this discussion the following can be concluded:
1) For on-site PD detection three methods are in use: a) Off-line (cable section is disconnected and energised by an external voltage source): for many years established conventional detection where PD activity in cable insulation and cable accessories is measured in accordance to standards [30, 31, 33] and the PD magnitude can be evaluated in [pC] and the PD sites in the cable insulation and cable accessories can be localized.
b) Off-line (cable section is disconnected and energised by an external voltage source): unconventional where PD activity in cable accessories only is measured in V or mV and where sensitivity checks are necessary to demonstrate the effectiveness of the method.
c)
On-line (cable section is connected to the network and energised by the line voltage): the sensors to the cable accessories [21, 22].
2) Applying the above mentioned PD detection methods, several practical sensitivity aspects parameters unconventional method is more complex and does not provide measurements in conventional PD detection requests sensitivity checks are necessary.
[pC] but in [V]. As a result to demonstrate the sensitivity of the system, applying non-
References
[1] F.H. Kreuger, Partial discharge detection in high voltage equipment, book 1969 [2] B. Quak, Information strategy for decision support in maintaining high voltage [3] F.J. Wester, Condition Assessment of Power Cables Using PD Diagnosis at Damped AC [4] CIGRE TF 15/33.03.05: PD Detection System for GIS: Sensitivity Verification for the UHF [5] S. Meijer, P.D. Agoris, E. Gulski, P.P. Seitz, T. Hermans, L. Lamballais, Simultaneous Condition Assessment of Accessories of Power Cables using a Wireless VHF/UHF PD Detection System, Conference Proceedings CMD2006, Changwon, Korea, 2006. Method and the Acoustic Method, Electra No. 183, April 1999 Voltages, ISBN 90-8559-019-1, PhD theses TU Delft, 2004. infrastructures, ISBN 978-90-8559-334-8, PhD thesis TU Delft, 2007 Heywood, London, 1989, Butterworths, London
13
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
[6] R. Bodega, A. Cavanelli, P.H.F. Morshuis and F.J. Wester, The effect of voltage frequency on partial discharge activity, 2002 Conference on Electrical Insulation and Dielectric Phenomena, pp.685-689
[7] W. Hauschild, W. Schufft, R. Plath and K. Polster, "The Technique of AC On-Site Testing of 304 HV Cables by Frequency-Tuned Resonant Test Systems", CIGRE 2002, Paris, paper 33-
partial discharge detection of distribution power cable systems. Cigre Electra, 2003, p
[9] E. Gulski, F.J. Wester, J.J. Smit, P.N. Seitz, M. Turner, Advanced PD Diagnosis of MV Power Cables using Oscillating Wave Test System, IEEE EI Magazine March/April 2000, Vol. 16 No.2 P.P. Seitz, B. Quak, E. Gulski, J.J. Smit, P. Cichecki, F. de Vries, F. Petzold, Novel
[10]
Method for On-site Testing and Diagnosis of Transmission Cables up to 250kV, Versailles, June 2007, paper 16
Proceedings Jicable '07. 7th International Conference on Insulated Power Cables, France, [11] [12] [13] M.S. Mashikian, G. Valdes and C. Katz, PD location as a cable operating tool, Jicable
1995, 4th International Conference on Insulated Power Cables, Versailles, France, 1995. Magazine, Vol.6 No.5, Sep/Oct 1990, pp.35-42 S. Boggs, Partial Discharge Part II: Detection Sensitivity, IEEE Electrical Insulation
for a New After Laying Test Method for High Voltage Extruded Cable Systems, CIGRE, 1990, paper 21-105
[14]
Martin D. Judd, Owen Farish: A Pulsed GTEM System for UHF Sensor Calibration, IEEE
[15]
Transactions on Dielectrics and Electrical Insulation, Vol5, Issue2, April 1998, pp.181188 B.R. Hamerling, F.J. Wester, E. Gulski, J.J. Smit and E.R.S. Groot, Fundamental aspects
[16]
of on-line PD measurements on distribution power cables IEEE 7th International Conference on Solid Dielectrics, 2001, pp.408-411 E. Gulski, J.J. Smit, B. Quak, R. Jongen, P.P. Seitz, PD site location by time-domain
[17]
reflectometry in mv power cable, Proceedings CMD 2006 International Conference on Condition Monitoring and Diagnosis 2-5 April, 2006, Changwon, Korea E Lemke et al. Practical aspects of the detection and localisation of partial dischagrs C.G.A. Koreman et. al. Development of a new 380 kV double circuit XLPE insulated Gulski, E, Allan, D, Blackburn, TR, Contin, A, Gockenbach, E, Lemke, E, Lundgaard, L,
Mizutani, T, Montanari, GC, Muhr, M, Okamoto, T, Phung, BT, Sedding, H, Breen, HJ van,
14
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
Wester, FJ . Knowledge rules for partial discharge diagnosis in service (Cigr Brochures, [21] 226). Paris: Cigr C Walton, PD monitoring a critical tool for condition-based assessment, T&D 2003 C Smith, P. Fleming, M. Michel, Advances in contnous PD monitoring, Cired 2007,
[22]
[23]
paper 276
Grotenhuis, Knowledge Rules Support for CBM of Power Cable Circuits, CIGRE 2002 Session, paper 104
E. Gulski, F.J. Wester, W. Boone, N. van Schaik, E.F. Steennis, E.R.S. Groot, J. Pellis, B.J.
[24] Wester, FJ, Gulski, E, Groot, ERS, Vliet, MC van . Sensitivity on on-line PD detection for distribution power cables. In JJ Smit (Ed.), High voltage engineering; Proceedings of the XIIIth international symposium on high voltage engineering (pp. 1-4). Rotterdam: [25] Millpress (ISBN 90-77017-79-8).
Diagnosis of MV Power Cables, Cired 2003, 17th International Conference on Electricity Distribution, Barcelona, Spain, 2003.
F.J. Wester, E. Gulski, J.J. Smit and E.R.S. Groot, Sensitivity Aspects of On-line PD
[26]
voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) Test methods and requirements IEC 62067, Standard Power cables with extruded insulation and their accessories for
IEC 60840 Power cables with extruded insulation and their accessories for rated
[27]
rated voltages above 150 kV (Um = 170 kV) up to 500 kV (Um = 550 kV) - Test methods and requirements. IEC 60060-3 High Voltage test techniques Part 3: Definitions and requirements for IEEE 400 Guide for Field Testing and Evaluation of the Insulation of Shielded Power
[28]
on-site testing
IEEE 400.3 Guide for PD Testing of Shielded Power Cable Systems in a Field IEC 60270 Measurement of partial discharges, 2000 EPRI Accessory Project 0420002 IEC885-3 High-voltage test techniques - Test methods for partial discharge
[32]
[33]
[34] Quak B., F. Wester, E. Gulski, J.J. Smit, P.N. Seitz; Advanced partial discharge site
location in power cable using numeric data processing. In: ICSD'01: Proceedings. 2001 IEEE 7th International Conference on Solid Dielectrics (Eindhoven, June 25-29, 2001), IEEE, Piscataway, 2001, p. 416-419. ISBN: 0-7803-6352-3,
cables. In Marsden, H (Ed.), Conference record of the 2002 IEEE international symposium on electrical insulation: Proceedings. (pp. 83-86). Piscataway: IEEE.
[36] Quak, B, Gulski, E, Wester, FJ, Seitz, PN . Wavelet analysis of PD in power cables. In JJ Smit (Ed.), High voltage engineering; Proceedings of the XIIIth international symposium on high voltage engineering (pp. 1-4). Rotterdam: Millpress (ISBN 90-77017-79-8).
15
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components
[37]
check for on-line VHF/UHF PD detection on Transmission cables, Conference Proceedings ICPADM 2006, Denpasar, Indonesia, 2006.
[38] [39]
Sensors and sensing used for non-conventional PD detection Proceedings 41 CIGRE 2006 Session International Council on Large Electric Systems, 27th August 1st September, 2006 Paris, France
[40]
Power Cables, in Proceedings of 2008 IEEE International Symposium on Electrical Insulation, Vancouver, Canada
E. Gulski, P.P. Seitz, R. Bodega, Th. Hermans, On-site Testing and PD Diagnosis of HV
[41]
[42]
J. Densley, Ageing Mechanisms and Diagnostics for Power Cables An Overview, IEC60502 Power cables with extruded insulation and their accessories for rated
voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
16
onsite hv solutions is an international organization with a team of highly qualified specialists, providing modern onsite solutions for an optimal use & maintenance of medium and high-voltage components