SCF Parameters
SCF Parameters
System Data
System voltage
Three phase initial symmetrical short circuit current (rms)
factor for peak short circuit current
Duration of the first current flow
Center-line distance between conductors 400kV
Center-line distance between conductors 220kV
System frequency
Auto reclosing feature
2. Conductor data
Busbar selected
Outer diameter
Inner diameter
Area of cross section
Moment of Inertia
Weigth
Youngs modulus
3. Refference
IEC 865-part I "short circuit current calculation of effects
4. Legend
Initial symmetrical short circuit current (r.m.s.)
Peak short circuit current
Effective distance between main conductors
span between supports
Outer diameter of conductor
Absolute Permeability of vacum
Ratio of dynamic and static force on support
Ratio of stress for a main conductor with or without
three phase autoreclosing
Factor for force on support
Factor for relevant natural frequency estimation
Natural frequency of the tube
Electromagnetic force
Total static weight of bus
5. Formulae used
5.1 Peak value of short circuit current
Ip3
Fm
Fd
fc
5.5 Calculation of VF
As per IEC 865 I (page-107)
fc/f
< 0.04
0.04.0.8
0.8 1.2
1.6 .2.4
2.4 ..2.74
2.74 .3.0
3.0 ..6.0
>6
VF
0.232+3.52*exp(-1.45*k)+0.166 log10(fc/f)
max[{0.839+3.52*exp(-1.45)+0.6*log10(fc/f)}, {2.38+
1.8
1.23+7.2*log10
2.7
8.59-15.5*log10(fc/f)
8.59-15.5*log10(fc/f)
1.5-0.646*log(fc/f)
1
5.6 Calculation of VR
VR
fc/f
<=0.05
0.05.1.0
>1.0
1.8
1-0.615log(fc/f)
1
400/220 kV
Ik3
40000 A
1.81
Tk1
1s
am
6m
am
4m
50
Hz
YES
D0
114.2 mm
Di
97.18 mm
2824.18 sq. mm
4.0E-06 m4
m'
7.678 Kg/m
6.57E+10
N/sq.m
Symbol
Unit
I"K3
Amps
Ip3
Amps
am
D0
0
VF
VR
fc
Hz
Fm
Kgf
Kgf
Fd
Kgf
N/m2
m4
I"K3 x x 2
VF x VR x ax FM
l2
ExJ
m'
log10(fc/f)}, {2.38+6*log10(fc/f)}]