EK NOTLAR =

RWT [OC] = Dn Su Scakl = Tin


LWT [OC] = k Su Scakl = Tout
SP [barg]= Gaz Emme Basnc = SP
DP [barg]=fleme-k Gaz Basnc = DP
ST [OC] = Gaz Emme Scakl =ST

OLASI ALARM
LSTES
BREAKER FAULT
SSPS FAULT
SP TR. OUT OF RANGE
DP TR. OUT OF RANGE
ST TR. OUT OF RANGE
EEV BOARD COM
ALARM
SUCTION PRESS.LOW
DISCHARGE PRESS
HIGH
FAN PROTECTION
SERIAL
COMMUNICATION
AUX ALARM
EEV IN OCILLATION
DISCHARGE TEMP. HIGH
HIGH SUPERHEAT
LOW SUPERHEAT

EVRLER
ALTER-SGORTA HATASI
KOMPRESR KORUMA MODL HATASI
EMME BASINCI TRANSDSER UYGUN DEER ARALIINDA
DEL
BASMA BASINCI TRANSDSER UYGUN DEER ARALIINDA
DEL
GAZ EMME SICAKLII TRANSDSER UYGUN DEER ARALIINDA
DEL
GENLEME VALF KARTI-PANEL ALARMI
EMME BASINCI DK
BASMA BASINCI DK
FAN KORUMASI

SER LETM
YARDIMCI-YEDEK DEVRE ALARMI
GENLEME VALF SALINIMDA
GAZ BASMA SICAKLII YKSEK
YKSEK SPERISITMA-KIZDIRMA
DK SPERISITMA-KIZDIRMA
GAZ BASMA SICAKLIK TRANSDSER UYGUN DEER
DT TR. OUT OF RANGE
ARALIINDA DEL
WATER OVERTEMP.
YKSEK SU SICAKLII
IKI SU SICAKLII TRANSDSER UYGUN DEER ARALIINDA
LWT TR. OUT OF RANGE DEL
DN SU SICAKLII TRANSDSER UYGUN DEER ARALIINDA
RWT TR OUT OF RANGE DEL
FREEZE PROTECTION
AL
DONMA KORUMASI
NO WATER
CIRCULATION
SU SRKLASYONU YOK
SERIAL
COMMUNICATION
SER LETM

MEMORY FATAL ERROR


POWER OFF
PUMP1 BREAKER FAULT
PUMP2 BREAKER FAULT
POWER SUPPLY
NO ALARM

HAFIZA HATASI
G KAPALI
POMPA 1 ALTER HATASI
POMPA 2 ALTER HATASI
G BESLEME
HATA YOK

RNEK ALARM MESAJLARI =


ALARM MASTER WATER OVERTEMP.

ALARMIN OLUTUU
BLGE HAKKINDA BLG
VERR. MASTER
ALARMIN GENEL SSTEMDE
OLDUUNA ARET EDER.

ALARMIN TRN ANLATIR.


BU RNEKTE WATER
OVERTEMP . YKSEK SU
SICAKLIINA ARETTR.

ALARM COMPRESSOR N.X SUCTION PRES. LOW

ALARMIN OLUTUU BLGE


HAKKINDA BLG VERR.
COMPRESSOR N.X
KOMPRESR DEVRESNDE OLAN
ARIZALARI ANLATIR.

ALARMIN TRN ANLATIR.


BU RNEKTE SUCTION
PRES. LOW DK EMME
BASINCI OLDUU ANLAMINA
GELR.

ALARM MASTER LWT TR. OUT OF RANGE

ARIZA TANIM KODU

LOKASYON KODU

8.1 GENEL SSTEM ALARMLARI


8.1.1 Antifriz Alarm
Eer k su scakl ve dn su scakl arasndaki fark 1 saniyeden fazla 5 OC nin altnda
kalrsa;

Genel alarm gsterge rlesinin devreye alnmas


Tm kompresrlerin devreden karlmas
Mesaj: ALARM MASTER FREEZE PROTECTON AL ;
ESC butonuyla manual reset atlmas

Tahmini oluma nedenleri;

Ayar noktas dk, termal-ssal yk ok dk


Su nitesinde bulunan glikol yzdesi ok dk
Evaporatr kirli
Evaporatrden geen su ak dk, sirklasyon pompasnda sorun var

8.1.2 Scaklk Uyars


Eer dn su scakl 10 dakika boyunca (gaz emi basnc + 10 OC ) den fazla olursa;

Mesaj ALARM MASTER WATER OVERTEMP


Dn su scakl emi basncndan dk olduunda otomatik reset yada ESC ye
manual olarak basmak

Bu alarm makinann altrld ilk 6 saatte aktif deildir.


Tahmini oluma nedenleri;

Prosesin termal yk
Buharlatrcnn kir veya dk ak nedeniyle veriminin dmesi
Gaz dolumu
Yksek evre scakl, kondenser kirli ya da dk hava ak nedeniyle veriminin
dmesi

8.1.3 Ak alteri Alarm ( Flow Switch Alarm)


Eer ak alter-switch konta 10 saniyeden fazla ak kalrsa;

Mesaj:ALARM MASTER NO WATER CIRCULATION


Sistemin durmas
Alarm oluturan koullarn ortadan kalmasndan 30 saniye sonra otomatik reset

Tahmini oluma nedenleri;

Evaporatrden geen su aknn dmesi, evaporatrn kir nedeniyle tkanmas


Su nitesinde dk glikol yzdesi; evaporatrn donmas
Sirklasyon pompasnn dzgn almamas
Boru hattnda hava balonlar
Boru tesisatnda bulunan filtrenin tkanmas
Giri veya k valflerinin kapal olmas
Pompa yklemesi iin yeterli suyun olmamas
Diferansiyel su ak switch inin hasar grmesi

8.1.4 Seri-Sral letiim Alarm


Eer ana sistemle kontrol edilen yan sistemin sral iletiimi kopmusa, kontrol eden ana
sistem yan sistemden ayrlr.

Mesaj: ALARM COMPRESSOR N.X SERIAL COMMUNICATION


Ana sistem hata veren yan sistemden ayr olarak alr
Otomatik reset.

Eer yan sistem 1 dakika boyunca ana sistemden hibir sinyal-mesaj alamazsa;

LED lamba frekansnn arttrr


Kompresrler devreden kar
Otomatik reset

Tahmini oluma nedenleri;

Ana sistem yan sistem kablolama sisteminin hasar almas


Balayclarn durumu
Elektrik paneli fonksiyonlar
Elektrik paneli voltaj beslemesi
Dardan elektromanyetik etkilerin mdahalesi

8.1.5 Set-up Alarm


Kontrol aygtnn-kumandasnn altrlmas srasnda kurulum parametreleri kontrol edilir.
Parametre numaras XX in deeri programlanan deerlerin dndaysa ;

Mesaj:ALARM MAKE SET UP:YXXX PRESS<ON> TO START


Makine durur.
Kurulum gzden geirilerek manual reset atlr ve kontrol aygt resetlenir.

Bu alarmn olumas durumunda FRGELle iletiime geiniz.

8.1.6 Alglayclarn-Problarn Alarm (Sistem)


Eer k su scakl probu ksa devre yaparsa(dk akm durumu) veya ak devre
olursa(yksek ak durumu);

Mesaj:ALARM MASTER LWT TR.OUT OF RANGE


Kompresrler durur.
Alarm oluturan koulun ortadan kaldrlmasnn ardndan otomatik reset.

Eer dn su scakl probu ksa devre yaparsa(dk akm durumu) veya ak devre
olursa(yksek ak durumu) ve kontrol dn su scakl probundaysa ;

Mesaj:ALARM MASTER RWT TR.OUT OF RANGE


Kompresrler durur.
Alarm oluturan koulun ortadan kaldrlmasnn ardndan otomatik reset.

Tahmini oluma nedenleri;

Probun elektriksel balants


Sensrn hasar almas
Anakart analog kanalnn hasar almas

8.1.7 Pompalarn Manyeto-termik Alarm


Eer pompalarn ynetimi aktifse ve alter-sigorta yardmc konta aksa;

Mesaj; ALARM MASTER PUMPN BREAKER FAULT


Eer alarmn oluma srasnda tm pompalar aktifse sistem durur.
Alarm oluturan koulun ortadan kalmasndan 20 saniye sonra otomatik reset.

Tahmini oluma nedenleri;

Pompa fazla akm ektiyse, motorun fazla snmas


Tek faz eksiklii
Voltaj besleme deerleri standardn dnda
alma basnc dk
Su devresinde havann varl
Kavitasyon koullar

8.1.8 G Besleme Alarm


Eer faz detektr modl yardmc konta 1 saniyeden fazla ak kalrsa ;

Mesaj:ALARM MASTER POWER SUPPLY


Genel alarm gsterge rlesini devreye aln
Makine durur
Kompresrler durur
Pompalar devre d kalr
ESC butonuyla manual reset atn.

Tahmini oluma nedenleri;

Tek faz eksiklii


Voltaj besleme deerleri standardn dnda
G besleme kontrol modl hasar alm
Elektrik kablo balantlar

8.2 KOMPRESR DEVRES ALARMLARI


8.2.1 Kompresr Manyeto-termik alteri-Sigortas
Eer kompresr devre alteri yardmc konta 1 saniyeden fazla ak kalrsa;

Kompresr durur.
Mesaj: ALARM COMPRESSOR N.# BREAKER FAULT
ESC anahtaryla manual olarak reset.

Tahmini oluma nedenleri;

Kompresr besleme voltaj dk


Motor fazla snm
Tek faz eksiklii
Kompresr amplifikasyonu fazla yksek
Kontaktr skm
Otomatik devre alteri mekanik olarak hasar alm

8.2.2 Kompresr Sistem Korumas SSPS

Eer KRIWAN (kompresr koruma modl-CPM) alarm konta 1 saniyeden fazla ak


kalrsa;

Kompresrler durur
Mesaj: ALARM COMPRESSOR N.# SSPS FAULT
ESC butonuyla manual olarak reset atlr.

DKKAT: Alarmn ardndan kompresr reseti kurulum parametrelerine bal olarak kilitlenir.
Reset atabilmek iin nce kompresrn kilidi almaldr.
Tahmini oluma nedenleri;

Kompresr voltaj beslemesi


Motorun fazla snmas
Ya scaklnn ok yksek olmas
Kompresr koruma modlnn(CPM) hasar almas
Kompresr koruma modlnn(CPM) elektrik alamamas
Kompresr koruma modl(CPM) in Ana kart balantsnn hasar almas

8.2.3 Problarn Devre Alarm


Eer devre kontrolndeki problarn bir veya birka ksa devre yaparsa veya ak devre
olursa;

Kompresr durur
Mesaj: ALARM COMPRESSOR N.# X TR.OUT OF RANGE
Alarm oluturan koul giderildikten sonra otomatik olarak reset atlr.

DKKAT: Gaz emii basn transformatrleri iin bu durum kompresrn minimum on time
(MOT)durumu sonuna kadar atlanr.
Tahmini oluma nedenleri;

Probun elektriksel balants


Sensrn hasar almas
Anakartn analog kanalnn hasar almas

8.2.4 Emi Basn Alarm


Eer kompresr emme basnc 2 barn altnda 30 saniyeden fazla kalrsa( bu koul
kompresrn MOT(minimum on time) modunun sonuna kadar aranmaz) ;

Mesaj:ALARM COMPRESSOR N.X SUCTION PRES.LOW


Kompresr durur
Alarm koulunun ortadan kalkmasnn ardndan ESC butonuyla manual olarak
reset atlr.

Tahmini oluma nedenleri;

Gaz kaaklar
Antifriz yzdesinin dk olmas
Su aknn dk olmas
Dk termal yk
Dk evre scakl
Elektronik reglatr-genleme valfinin dzgn almamas
Gaz emme transformatrnn yanl okumas

8.2.5 k-fleme Basnc Alarm


Eer k basnc 23.5 Bardan fazla olursa;

Kompresrler durur.
Mesaj:ALARM COMPRESSOR N.X DISCHARGE PRES.HIGH
Alarm koulunun giderilmesinin ardndan ESC butonuyla manual reset atlr.

Tahmini oluma nedenleri;

evre scakl fazla yksek


Fann devresinin durmas ( fan alarm durumu)
Kondenserden geen hava akmnn dmesi
k basnc transformatrnn yanl okumas
Sv soutucu filtresinin kirlenmesi
Kondenser ak takmnn kirlilii

8.2.6 Yksek Basn Alarm


Eer yksek basn switch i aksa ( k basnc 24.5 Bardan fazla);

Mesaj: ALARM COMPRESSOR N.X HIGH PRES. SWT FAULT


Sistem durur.
ESC tuuyla manual olarak reset atlr.

DKKAT: Yksek basn koruma switchi HP switch kutusunun iinde bulunan reset
butonuna elle baslarak resetlenmelidir.
Tahmini oluma nedenleri;

Yksek basn switchinin hatal olmas

8.2.7 Reglatr-Genleme Valfi Seri letiim Alarm


Eer EEV( reglatr-genleme valfi) kart seri balysa ve iletiim kopmusa;

Mesaj:ALARM COMPRESSOR N.X EEV BOARD ERROR;


Kompresr durur.
Otomatik reset .

Tahmini oluma nedenleri;

Anakart ve valf kart-paneli aras balant kablolarnda sorun


Konektrlerin ve pinlerin durumu
Anakart ve valf paneli-kartnda ilev bozukluklar

8.2.8 Fan Koruma Alarm


Eer fan koruma modl alarm konta aksa;

Mesaj:ALARM COMPRESSOR N.X FAN PROTECTION


Kompresr durmaz.(Uyardr.)
Otomatik reset.

DKKAT: Frasz fan iten elektronik kontrol sistemiyle korunmaktadr. Fann tekrar
otomatik olarak almamas durumunda ,fann g kablosunu 10-20 saniyeliine karmak i
koruma sistemini resetlemek iin yeterlidir.
Tahmini oluma nedenleri;

Motor kutusu iinde bulunan elektronik paralarn fazla snmas


Motorun fazla snmas
Doru olmayan rotor pozisyonu
Dk voltaj
Kilitlenmi rotor korumas
Faz hatas

8.2.9 Aux Alarm (Eer Yardmc-yedek Devre Alarm Sistemde Mevcutsa)


Eer aux alarm devredeyse ve AUX AL girdisi belirli bir zaman gecikmesi deeri iin
fazlaysa;

Mesaj:ALARM COMPRESSOR N.# AUX ALARM


Kompresr durur.

ESC butonuyla manual reset atlr.

8.2.10 Yksek Gaz k Scakl Alarm (Eer Sistemde Gaz k


Scakl Probu Varsa)
Eer k scakl 20 saniye boyunca 110 OC den fazlaysa;

Mesaj:ALARM COMPRESSOR N.X HIGH DISCHARGE TEMP


Kompresr durur.
Alarm koulunun ortadan kaldrlmasnn ardndan ESC butonuyla manual reset
atlr.

Tahmini oluma nedenleri;

evre scaklnn yksek olmas


Soutucu eksiklii
Kompresr iinde ya eksiklii
Akkan enjekte selenoid valfi almyor

8.2.11 Reglatr-Genleme Valfi Salnm-Titreim Alarm


Eer sper stma-kzdrma deeri Tsup belirlenen kriterlerin dnda 5 dakikadr periyodik
olarak salnmdaysa;

Mesaj:ALARM COMPRESSOR N.X EEV IN OSCILLATION


Kompresr durmaz.(Sadece uyardr.)
Alarm durumunu oluturan koul kaldrldktan 30 saniye sonra otomatik reset

Tahmini oluma nedenleri;

Termal yk dk
evre scakl dk
Soutucu eksiklii

Bu sadece uyardr. Kompresr durmaz.

8.2.12 Yksek Sper Istma-Kzdrma Alarm


Eer sper stma-kzdrma scakl Tsup 2 dakika boyunca 12 OC den fazla olursa;

Mesaj:ALARM COMPRESSOR N.X HIGH SUPERHEAT


Kompresr durur.
ESC butonuyla manual olarak reset atlr.

Kompresr minimum on durumundayken bu alarm devre ddr.

Tahmini oluma nedenleri;

Termostatik genleme valfi kilitlenmi


Soutucu eksiklii
Emme basn veya scaklk probu hatal

8.2.13 Dk Sper Istma-Kzdrma Alarm


Eer sper stma deeri Tsup 2 dakika boyunca 0 OC den kkse;

Mesaj:ALARM COMPRESSOR N.X LOW SUPERHEAT


Kompresr durur.
ESC butonuyla manual olarak reset atlr.

Kompresr minimum on durumundayken bu alarm devre ddr.


Tahmini oluma nedenleri;

Termostatik genleme valfi kilitlenmi


Emme basn veya scaklk probu hatal
Krank muhafazas-motor karteri stcs kompresr kapalyken almyor.