Surge arresters and Surge Suppressor both are used to protect equipment from
surges. But, there is confusion between the application of surge arrestors /
Lighting arrestor and surge suppressors.
The main differences between a lightning arrester and a surge arrester are its
fault clearing time and its position
Both are doing the same job, but still both are not same
The kA rating of an SPD (surge rating) is one of the most misleading terms.
We normally use 50KA SPD to protect 50KA panel.
The kA rating of the surge arresters has nothing to do with the fault current
rating of electrical distribution board. We can fit a 40kA surge arrester in a
domestic board with a fault current rating of less than 5kA
When a surge enters a panel, it does not know the size of the panel. So It is
totally miscalculation for use 50KA SPD for 50KA Panel
There is a normal Practice that larger panels need larger SPD, but surges are
indifferent to panel size.
The largest surge that can enter a buildings wiring is 10kA, as explained in
the IEEE C62.41 standard. So why would we need a SPD rated for 100KA or
200kA.
Type of SPD:
:Type 1 SPD