Surge Protection Device connected in the mains power supply, needed to protect the electrical and
electronic equipment, should be able to withstand 100 KA (10/350sec). As per IEC 62305-1, LPL 1
(Lightning Protection Level) maximum expected lightning current is 200 KA. As explained in IEC
62305,100 KA will be dissipated in earth and the balance 100 KA will reach the electrical supply lines.
Power Line SPD’s are to be connected at the mains incoming panel and in addition Distribution Boards
which are more than 15 meters away from the incoming panel. DB’s which are feeding power to critical
and sophisticated electronic equipment, SPD’s must be installed ignoring the cable distance. Suitable
SPD’s also to be used in all Telecommunication, Signalling, automation and instrumentation equipment
according to the Zone concept explained in IEC 62305 for a perfect protection of complete electronic
installations. All SPDs should be tested and ensure performance requirements according to IEC 61643
Protection at the main incomer of the power supply system has to be connected at the Main Distribution
Board after the incoming breaker.
SPD should be connected between Phase and Neutral and between Neutral and Earth with the following
ratings:
Specifications
Sl. No Parameters
Line to Neutral Neutral to Earth
1. Type Encapsulated/Non-exhausting Spark Gap
2. Rated Voltage Un 230V,
3. Maximum Continuous Operating 320 Volt 255 Volt
Voltage, Uc
4. Lightning Impulse Current L-N 40 KA 120 KA
(10/350 sec)
5. Maximum Discharge Current I max 120KA
(8/20) per phase
6. Voltage Protection Level, Up < 1.3 KV < 1.3 KV
7. Residual Voltage Uress at 1kA (8/20) < 700 V < 300 V
9. Response Time < 100 nano seconds
10. Operating temperature range -40C to +85C
11. Degree of Protection IP 20
12. Mounting Type Including HRC Fuse with Metal Enclosure. transparent
cover to visible SPD condition
13. Indication Led Indicator Lights
14. Standards IEC 61643-1 : 2005-03, DIN EN 61643-11: 2002-12,
VDE 0675, Teil 6-11
Sub distribution Panel Protections or main panel as per lightning zone- 3 Phase
Second Stage Protection at the Sub Panel of the power supply system,
Pluggable type SPD with potential free contact, thermal disconnector & provision for inbuilt common
remote indication for defective arresters has to be connected between Line and Neutral and SPD of Spark
Gap type between Neutral and Earth of following ratings should include base element & pluggable
arresters.
Specifications
Sl.No Parameters
Line to Neutral Neutral to Earth
MOV Spark Gap
1. Type with built in Encapsulated / Non-
thermal fuse exhausting
2. Nominal Voltage, Un 230V, 50/60 Hz
3. Test class according IEC 61643-1- Ed.2 Type 1+2
4. Maximum Continuous Operating Voltage, Uc 320 Volt 255 Volt
5. Nominal Discharge Current In , L- N (8/20 sec) 30 KA 30 KA
6. Nominal Discharge Current In 8/20 L1+L2+L3- 90 KA 30kA
N
7. Voltage Protection level Up <1.3kV <1.2kV
8. Maximum Discharge Current Imax L1 (8/20 sec) 50 KA
9. Maximum Discharge Current Imax (8/20) 150 kA 50 kA
L1+L2+L3-N
10. Lightning Impulse Current I imp (10/350 sec) 7 KA 25 KA
11. Response Time < 25 nano seconds < 100 nano seconds
13. Mounting Type Including HRC Fuse and Metal Enclosure
transparent cover to visible SPD condition
14. Indication Mechanical green and red ( optional alarm)
15. Standards IEC 61643-1 : 2005-03, DIN EN 61643-11:
2002-12, VDE 0675, Teil 6-11
Sub Distribution panel Protection
Protection for Sensitive Equipments at the input of the end equipments like UPS, CNC machine, VFD’s or
at Important MCB DB’s feeding power to Computer / Server etc
3 numbers of pluggable type surge arrester with potential free contact, thermal disconnector & provision
for inbuilt common remote indication for defective arresters to connect between Line and Neutral and one
number arrester Spark Gap type to connect between Neutral and Earth of following ratings including base
element & pluggable arresters.
Specifications
Sl.No Parameters
Line to Neutral Neutral to Earth
MOV Spark Gap
1. Type with built in thermal Encapsulated / Non-
fuse exhausting
2. Nominal Voltage, Un 230V, 50/60 Hz
4. Maximum Continuous Operating Voltage, > 320 Volt >255 Volt
Uc
5. Nominal Discharge Current In L-N (8/20 20 KA
sec)
6. Voltage Protection level Up <1.4kV 1.2kV
7. Maximum Discharge Current Imax L1(8/20 ) 40Ka 50Ka
8. Total Discharge Current I total (8/20) 110 kA
L1+L2+L3-N
9. Lightning Impulse Current I imp (10/350) 25 KA
10. Response Time < 25 nano seconds < 100 nano seconds
11. Operating temperature range -40C to +80C
12. Mounting Type Including HRC Fuse and Metal Enclosure with
transparent cover to visible SPD condition
13. Indication Mechanical red and green (optional alarm )
14. Standards IEC 61643-1 : 2005-03, DIN EN 61643-11:
2002-12, VDE 0675, Teil 6-11
N
R
PE
F2
F3
F1
F4
SPD 1
F5
SPD 4 SPD 2
F6
SPD 3
Surge Filters for 230 V AC/DC Single Phase Power Supply at Equipment Level.
(PABX, DVR, Roller Door, Network Switches and other all Electronic Equipment)
Description Specification
Excitation Voltage (DC) 32V
Loop resistance 0Ω
Protection Stage Transient Protection diodes
Clamp Voltage 36V line to screen typical
18V single +ve to –ve typical
150A for 8/20µs pulse line to screen
Earth Clamp 10kA screen to ground 90V
Enclosure rating IP 65
Standards BS 6651
Technical Specifications of Direct Lightning Protection
General
Lightning Protection System (LPS) is to protect structures including their installations, contents,
persons & services connected to the structure against direct and indirect effects of Lightning. The
LPS shall be in accordance with IEC 62305, IS:2309 & IS 3043. The protection in detail shall
include the following;
1.) Air terminal (as per rolling sphere or mesh or protective angle method or any
combination thereof.)
2.) Down conductor
3.) Earthing
No drilling or welding is allowed in the terrace for fixing the air terminal.
Values of Rolling sphere radius, Mesh size and protection angle as per Class of
LPL/LPS.
Conductors shall be securely fixed on the terrace by means of air terminal holder
which is fixed on the roof by adhesive of good quality taking care of varying weather
conditions. Air conductor holder is an insulator & should be of minimum 50 mm
height so that even small amount of water logging on terrace is below the level of
conductor holder. Air terminal holder shall not be more than 0.5 m apart for a flat
conductor & 1m for round conductor of at least 8mm diameter & 1.0 meter apart for
vertical run
In order to take care the expansion of the metal in summer and contraction of the
metal in winter, expansion piece with suitable connectors have to be used at every
20m distance of horizontal air terminal.
Dissimilar metals (For eg: copper with Aluminum) must be connected only by using
bimetal connectors.
Material configuration and Min cross sectional area of air terminal and down
conductors
3. )Earth Terminations:
Earth mat is most preferable. Where earth mat is not possible, ring earthing is the
next best method. Ring earthing must be 1 meter away from the building and 0.5m
below the ground level. The resistance of earthing system shall not exceed 10 ohm as
per IEC 62305. Lower earth resistance is still better.
For earth termination system, 2 basic types of earth electrode arrangements are
applicable.
Type A & Type B arrangement.
The function of a lightning protection system is to discharge lightning current and to distribute
them in the ground. To minimise hazardous potential differences between all electrical equipment
in the inner lightning protection zone, a low-impedance equipotential bonding network must be
established. In addition, the integration of the earth-termination system in the equipotential
bonding system does not only ensure low impedance, but also an increased current carrying
capability of the equipotential bonding network to be established.
These goals can be achieved by an intermeshed equipotential bonding network. To this end, all
conductive parts of the structure and the internal system are integrated in this network and all
metal parts or conductive lines at the boundaries of each LPZ (lightning protection zone) are
connected directly or via adequate surge protective devices.