BEHAVIOUR OF REINFORCED CONCRETE BEAMS STRENGTHENED

IN SHEAR
1
S.F.A.RAFEEQI , S.H.LODI2, Z.R.WADALAWALA3

ABSTRACT
Non-engineered construction in rural areas of developing third world in recent years has
gained attention of many agencies mainly due to the alarming damage to property and life
caused by earthquakes. Ferrocement having excellent ductility may become one of the main
structural materials for retrofitting and strengthening of modest span reinforced concrete beams
in such construction, specially, in earthquake prone areas.
Shear mode of failure in beams is undesired mainly being a brittle failure. An attempt,
therefore, has been made to explore the potentials of Ferrocement in transforming brittle mode
to ductile mode, through an experimental study presented in this paper.
Test results of 4 beams in which shear spans were strengthened by providing a complete
Ferrocement warp and equally spaced strips, with one and two layers of woven square mesh are
presented and compared with reinforced beam having identical material and sectional
properties. The beams were loaded up to service load, de-loaded and strengthened prior to test
up to failure. The sections were designed for brittle shear-compression failure by keeping shear
stirrups, which provided 3.5 to 4 times the shear capacity of concrete alone. The flexural
reinforcement was kept as the minimum that is normally provided in expected non-engineered
construction.
The strengthened beams showed a marked improvement in performances at service load,
greatly improved ductility at ultimate with either a ductile shear failure or seemingly a transition
from shear to flexure mode of failure.
Key words: ferrocement wrap; ferrocement strips; shear; strengthening; non-engineered
construction.
INTRODUCTION
Reinforced concrete in one of the most abundantly used construction material not only in the
developed world, but also in the remotest parts of the developing world. In the rural areas of the
developing world, however, due to transference of expertise and technology know how,
reinforced concrete poses threat due to its abuse rather than use, and majority of the houses are
constructed in traditional manner using indigenously developed techniques preferably following
simpler and economical procedures. Unfortunately such non-engineered construction is mostly
prevalent in earthquake prone areas of the developing world e.g. Turkey, Pakistan, India and
Iran. The rural population in the developing world have mostly to rely on local skill, material and
technology. The transformation of non-engineered construction into an engineered one, therefore
needs to be such that it could be sustained. The methodology should be simple in execution, offer
better performance even when handled by less experienced workers, must involve materials,
which are readily available, and yet durable, strong and economical. Ferrocement is one such

1 Professor and Co-Chairman, Dept. of Civil Engrg. , NED Univ. of Engrg. & Tech., Karachi, Pakistan.
2 Professor, Dept. of Civil Engrg. , NED Univ. of Engrg. & Tech., Karachi, Pakistan.
3 Assistant Professor, Dept. of Civil Engrg. , NED Univ. of Engrg. & Tech., Karachi, Pakistan.

material which could afford to offer answer to such a situation and hence the present study is part
of a programme under taken at NED University where the potentials of Ferrocement are
explored for its utilization in non-engineered construction, for improved performance in the
event of an earthquake.
LITERATURE REVIEW
A 30 years record of major Turkish earthquake shows almost 0.2 million dwellings destroyed
by earthquake [1], which is about 65% of the destruction caused by all other natural disasters.
Dinar earthquake of 1995 and Kocoeli earthquake of 1999 have substantially increased the
percentage.
Almost all post earthquake studies and damage assessment have led to the conclusion that a
building should be designed and constructed such that in the event of the probable maximum
earthquake intensity: the building should not suffer total or partial collapse; it should not suffer
such irreparable damage which would require demolishing and rebuilding and in case it sustain
such damage it could be repaired quickly and easily to bring it to its usual functioning [2].
Ferrocement over the years have gained respect in terms of its superior performance and
versatility, and now is being used not only in housing industry but its potentials are being
continuously explored for its use in retro-fitting and strengthening of damaged structural
members [3,4]. Ductility requirements are the main feature of an efficient earthquake restraint
design process, and Ferrocement being highly ductile material have led to its application in
rehabilitation of houses damaged by earthquake and the effectiveness of its use has been reported
by many researchers [5,6,7,8]. Taking the lead from its potential use in enhancing earthquake
resisting abilities, 5 houses were built in Northern area of Pakistan, using indigenous materials
and local skills utilizing Ferrocement bands to improve the earthquake resisting of such houses in
1990 [9]. The houses since then have performed remarkably well and have sustained low to
moderate shocks effectively. The detail were simple to follow and execute by the local skilled
workers, and materials were readily available from near by cities.
Reinforced concrete elements are designed to fail in a ductile manner by emphasizing on the
detailing requirements due to the brittle nature of concrete. Shear failure are also classified as
brittle and shear zones are therefore reinforced by provision of stirrups for transformation to
ductile failure, however, a limit is imposed on the provision to avoid brittle shear-compression
failure. In the event of an earthquake, however, the shear loads can exceed shear capacities, and
damage in shear zones may lead to catastrophic failure of such members.
Many experimental studies has been conducted in recent years to strengthen flexure members
by using various materials [10,11,12,13,14,15].
Andrew and Sharma [10 ] in an experimental study compared the flexural performance of
reinforced concrete beams repaired with conventional method and Ferrocement. They [10]
concluded that beams repaired with Ferrocement showed superior performance both at service
and ultimate load. The flexural strength and ductility of beams repaired by Ferrocement was
reported to be greater than the corresponding original beams and the beams repaired by
conventional method.
Al-Farabi et al [11] while investigating the effectiveness of Fiberglass bonded plates for
capacity enhancement, reported increased strength and reduced ductility. Premature failure by
plate separation was also identified as a potential problem at the plate curtailment place.
Steel plates bonded by epoxy were used to repair shear cracked beams utilizing various forms
of plate bonding by Basunbul et al [12]. The experimental investigation clearly demonstrated that
the effectiveness of the repair primarily depends on how effectively the diagonal tension cracks
in the shear-damaged beams were trapped. Flexural mode of failure was observed surpassing
shear capacity for only those specimens where full encasement of the shear zone was carried,

while for all other forms of bonding the failure either occurred due to separation or ripping of
steel plates. Enhanced ductility was, however, reported for all methods.
In a similar study where fiberglass plates were bonded instead of steel plates, Al-Sulaimani et
al [13] reported almost similar results. The shear capacities for beams where full encasement of
shear zone was carries, was enhanced to such an extend that the failure occurred by flexure, with
enhanced ductility.
An experimental study in strengthening of reinforced concrete beams using Ferrocement
laminates was conducted by Ong et al [14], where eight beams were strengthened with a 20 mm
thick laminate attached on the tension face. Three different series with different methods of
attachments including Ramset nails, Hilti bolts and epoxy resin adhesive were used. The
performance of the strengthened beams were compared to the control beams with respect to
cracking, deflection and ultimate strength. All the strengthened beams exhibited higher ultimate
flexural capacity and greater stiffness. Use of epoxy resin adhesive and Ramset nails at closer
spacing of shear connectors were able to ensure composite action. A decrease in the volume
fraction of reinforcement of Ferrocement laminates from 3.25% to 2.36% resulted in a reduction
of strength. The presence of the Ferrocement laminates had an inhibiting effect on the tensile
crack, and the crack spacing and crack width were reduced after strengthening.
Paramasivam et al [15] reported tests on six damaged RC beam repaired by Ferrocement
laminates. Repair of cracks was done by epoxy resin injection and the beams were then
strengthened by Ferrocement laminates attached to the soffit by means of L-shaped bar
connectors, to ensure composite action between the Ferrocement laminates and the in-situ
concrete. The results showed that substantial improvement in the ultimate capacity and stiffness
may be obtained, provided the shear connectors are adequately spaced and the cracks are well
grouted.
Paramasivam [16] reported that a total of six T-beams were tested inverted and simply
supported under static and cyclic loads applied at mid span by Aurellado [17]. Except for control
beam all beams were strengthened with Ferrocement laminates as encasements onto the beam
web and soffit. Three methods of attachment were examined with bar shear connectors installed
through web or through flanges of beams. This was compared with conventional methods of
strengthening where additional U shaped stirrups were inserted through predrilled holes in the
flange before bending the ends in to form closed links. The results showed that the beams were
substantially strengthened and stiffened due to the provision of the Ferrocement laminates.
OBJECTIVES AND SCOPE
The objective of the study is to provide the rural population especially in earthquake prone
areas, with a simple and easily applied technology to upgrade and strengthen non-engineered
structural members. It has been observed that most of the time the rural learned in an effort to
provide sufficient shear strength and a flexure mode of failure, fails to recognize the danger of
over-reinforcing shear zones and thereby paving way to catastrophic failure.
The scope of the study was thus confined to study the effect of confining shear spans of such
beams with Ferrocement, where shear stirrups provides 3.5 to 4 times the shear capacity of
concrete alone. The main parameters of the study were confined to one and two layers of woven
square mesh and application of Ferrocement by way of providing wraps in full shear span and
equally spaced strips in shear span.
EXPERIMENTAL PROGRAM
In all, five beams were cast where beam A was the control specimen while B1, B2 and C1, C2
were the beams to be strengthened by way of providing Ferrocement strips and wraps with one
or two layers of wire mesh respectively.

All beams having 100 mm width, 200 mm over all depth and 170 mm effective depth, were
cast with same mix having proportion of 1:2:4 with a w/c ratio of 0.55. The overall length of all
beams were kept as 915 mm whereas the simply supported span was 762 mm. The beams were
reinforced with 2-12.7 mm dia. bars having yield strength of 445 N/mm2 as main flexural
reinforcement, and 2-6 mm dia. bars were used as hanger bars, shear stirrups consisted of 6 mm
dia. bars spaced at 50 mm c/c. The yield strength of 6 mm dia. bars was 240 N/mm2. Material
strengths were obtained by testing control specimens in Material Testing Laboratory, NED
University of Engineering and Technology , Karachi.
18 gauge woven square mesh with wire diameter of 0.9 mm and mesh opening of 4.6 mm was
used for Ferrocement, where 1:2 cement-fine sand mortar with a w/c ratio of 0.45 was used for
all strengthened beams. The yield strength of the single wire was found to be 229 N/mm2. The
average cylindrical crushing strength of concrete was found to be 22 N/mm2. The average cube
crushing strength of mortar using 50 mm x 50 mm x 50 mm cubes was found to be 25 N/mm2,
while the tensile strength was evaluated through briquette test and was found to be 3.5 N/mm2.
Testing of Specimen
All specimens were loaded under third point loading using Forney Universal Loading
Machine having a resolution of 0.025kN and capacity of 300 kN, at Material Testing Laboratory,
NED University of Engineering and Technology, Karachi. One end of specimen rested on a
roller arrangement allowing horizontal movement and the other on a simple support. All the
beam specimen were tested under load control with monotonically prescribed incremental loads.
At each incremental load of 10kN, deflections, crack pattern, crack width and surface strains
were recorded.
Each specimen was loaded up to 70kN and de-loaded to represent a beam in service and than
the prescribed strengthening method was applied, and reloaded to failure. The description of load
sequence and method of strengthening is presented in Table 1. Plate 1 and Plate 2 shows the
specimens of B and C series before application of 1:2 cement-sand mortar.
Table 1 - Testing sequence and method of strengthening
Specimen
Load Applied
Method of Strengthening
Control specimen loaded from unN.A
A-i
cracked state to P70 and de-loaded.
Loaded from cracked state up to
A-ii
failure
N.A
Loaded from un-cracked, unstrengthened beam to P70 and deN.A
B1-i
loaded

Table-1 Contd
Specimen

B1-ii

B2-i

B2-ii

C1-i

C1-ii

C2-i

Load Applied

Method of Strengthening
After de-loading from P70
i.e. as B1-i, 3-50 mm
equally spaced strips in the
shear span were chiseled
from all around the beam
Loaded from strengthened
up to outside of stirrups
state up to failure
One layer of mesh strips
cut to size, wrapped and
impregnated with mortar
Left for 14 days curing
before testing to failure
Loaded from un-cracked unstrengthened beam to P70 and
N.A
de-loaded
After de-loading from P70
i.e. as B2-i, 3-50 mm
equally spaced strips in the
Loaded from strengthened
shear span were chiseled
state up to failure
from all around the beam
up to outside of stirrups.
Two layers of mesh strips
cut to size, wrapped and
impregnated with mortar.
Left for 14 days curing
before testing to failure.
Loaded from un-cracked, unN.A
strengthened beam to P70 and
de-loaded
After de-loading from P70
i.e. as C1-i beam, full
Loaded from strengthened
shear span on both sides
state up to failure
were chiseled from all
around the beam up to
outside of stirrups.
One layer of mesh strip cut
to size and wrapped all
around and impregnated
with mortar
Left for 14 days causing
be for testing to failure
Loaded from un-cracked unN.A
strengthened beam to P70 and
de-loaded.

Table-1 Contd
Specimen

C2-ii

Load Applied

Method of Strengthening
After de-loading from P70 i.e. as C2-i,
3-50 mm equally spaced strips in the
shear span were chiseled from all
Loaded
from
un-cracked
unaround the beam up to outside of
strengthened beam to P70 and destirrups.
loaded.
Two layers of mesh strips cut to size,
wrapped and impregnated with mortar.
Left for 14 days curing before testing to
failure.
P70 = Estimated service load of 70 kN

Plate 1- Detail of beam strengthened by


ferrocement strips in shear span.

Plate 2- Detail of beam strengthened by


ferrocement wraps in shear span.

TEST RESULTS
The load-deflection curves of second cycle of loading for control specimen and strengthened
beams are presented in - Fig. 1.
140
130
120

Measured load (kN)

110
100
90
80
70
60
50
40

A - ii
B 1- ii
B 2 - ii
C 1 - ii
C 2 - ii

30
20
10
0
0

0.5

1.5

2.5

3.5

4.5

5.5

6.5

7.5

8.5

Measured mid span deflection (mm)

Fig. 1- Measured load-deflection curves for control and strengthened specimen.


The state of strengthened specimens is presented in Plate 3 through Plate 6. Plate 3 shows the
control specimens loaded to failure in a cracked state where failure occurred due to shearcompression failure. Specimen B2-ii representing beam strengthened with Ferrocement having
two layers of wire mesh applied in equally spaced strips in the shear span is presented in Plate 4.
Specimen C1-ii represent beam strengthened with complete wrap of one layer of wire mesh
along full shear span, Plate 5, while C2-ii represents beam strengthened with complete wrap of
two layers of wire mesh along full shear span as shown in Plate 6 receptively.

Plate 3 - Typical brittle shear-compression


failure of controlled specimen A-ii.

Plate 4 - Specimen B2-ii at failure.

Plate 5 - Specimen C1-ii at failure.

Plate 6 - Specimen C2-ii at failure.


The failure loads of the test specimen and their deflections at cracking load, service load and
ultimate load along with the failure mode are presented in Table 2.

Specimen
test
Reference

A-i
A-ii
B1-i
B1-ii
B2-i
B2-ii
C1-i
C1-ii
C2-i
C2-ii

Table 2 - Measured results at cracking, P70 and ultimate.


Mode of
Cracking Mid-span Mid-span Mid-span Ultimate
load
Failure
load
Deflection deflection deflection
at ultimate
at Crackat P70
load
ing Load
(mm)
(mm)
(kN)
(kN)
(mm)
28
1.18
2.31
2.71
5.55
120
Brittle, shearcompression
29
1.15
2.23
2.50
6.49
122
Brittle, shearcompression
28
0.98
2.18
2.41
7.22
124
Shear-compression,
more cracks and
delayed failure
30
1.21
2.34
2.45
7.90
125
Seemingly transition
to ductile
26
1.32
2.26
2.35
8.20
127
Ductile, shear

DISCUSSION OF RESULTS
At service stage the strengthened beams showed improved performance, as is evident from Fig. 1 and column (3), column (4) of Table 2, where increased stiffness due to Ferrocement strips
and wraps and relatively decreased deflection in comparison with control specimen is evident.
Increased number of cracks with decrease in crack width was observed for strengthened
specimen, however, no significant difference in pattern was noticed between the two methods of
Ferrocement application.
The mode of failure as described in Table 2 is also evident from Plate 3 to Plate 6.
The load that the test specimen could sustain theoretically in shear was calculated to be 119.5
kN, using ACI Code model without using capacity reduction and load factors.
The increase in shear capacity varied between 1.5% to 5.8% , the maximum being for C2-ii,
where the specimen was wrapped with 2 layer of wire mesh. The increase in shear capacity,
therefore, is not substantial, however, an evidence of transformation of brittle, shear-compression
failure to ductile shear failure is evident from - Fig. 1 and Plate 6. Almost all the failures were
shear failures, however, the presence of Ferrocement strips and wraps delayed the failure giving
ample warning before failure, which is considered as the desired mode of failure by almost all
codes. Greater number of cracks and sufficient ductility is apparent from - Fig. 1 and Plate 3
through Plate 6 of the strengthened beams. This is a significant result, which may allow beams
that are over-reinforced in shear to fail in a ductile mode. In earthquake zones where larger
moments had to be resisted by beam on small openings, the use of Ferrocement wrap may allow
use of shear stirrups of capacity more than 4 times the capacity of the beam.
CONCLUSIONS
The following conclusions may be drawn from the present experimental study.
1. Confining concrete in the shear zone by Ferrocement have the potential of transforming
brittle shear-compression failure to ductile shear failure.

2. Ferrocement wraps are more effective than Ferrocement strips.


3. The enhancement in load carrying capacity is not substantial, however, is present. In
service range increased stiffness of strengthened beams reduces the crack width and
deflections in comparison with the un-strengthened beam.
4. The method is simple to understand and apply, and, therefore, may be utilized in nonengineered rural construction and could achieve maximum results.
ACKNOWLEDGEMENT
The authors wish to acknowledge the financial support provided by the Department of
Civil Engineering, NED University of Engineering and Technology, Karachi, and wish to thank
all those students and staff of the laboratory who helped in carrying out work in the laboratory.
REFERENCES
1. Gulkan, P.; Wasti, S.T.; and Karaesmen, E., Some Aspects of Earthquake Engineering
Research in Turkey, Research Report, Middle East Technical University, Ankara, Turkey
1980.
2. A Manual of Earthquake Resistant Non-Engineered Construction, Book Published by
Indian Society of Earthquake Technology, University of Roorkee, 1981. 155 pp.
3. Singh, K.K., Kaushik, S.K.; and Parakash, A., Strengthening of Brick Masonary Columns
by Ferrocement, Proceedings of the Third International Symposium on Ferrocement. Roorkee,
University of Roorkee, 1998, pp. 306-315.
4. Waliuddin, A.A.; and Rafeeqi, S.F.A., Study of the Behaviour of Plain Concrete Confined
with Ferrocement, Journal of Ferrocement, V. 24, No.2, April 1994, pp. 139-151.
5. Shake Table Tests Conducted in India, News letter, Earthquake Hazard Center, V. 2, No.
2, Oct. 1998, pp. 2-3.
6. Giesecke, L.Z..; Bartolome A.S.; and Quiun, D., Reconditioning of Existing Adobe
Housing to Mitigate the Effects of Earthquakes, Proceedings of the 11th World Conference in
Earthquake Engineering, Mexico, 1996.
7. Desia, R .; Field Shake Test Programme at Latur, Western India, News letter, Earthquake
Hazard Centre, New Zealand, V. 3, No.2, Oct. 1999, pp. 4-5.
8. Wasti, S.T.; Erberik, M.A.; Sucuoglu, H.; and Kaur, C., Studies on Strengthening of Rural
Structures Damaged in the 1995 Dinar Earthquakes, Proceedings of the Eleventh European
Conference on Earthquake Engineering, CD-ROM, Paris, France, 1998.
9. Non-Engineered Construction in Earthquake Prone Areas and Earthquake Mitigation with
Special Reference to Pakistan, Project Report, Department of Civil Engineering, NED
University of Engineering and Technology, Karachi, Pakistan, 1998, 103 pp.
10. Andrews, G.; and Sharma, A.K., Repaired Reinforced Concrete Beams ACI, Concrete
International, Detriot, April 1998, pp. 47-50.
11. Al-Farabi, M.S.; Baluch, M.H.; Al-Sulaimani, G.J.; and Basunbul, I.A., Repair of
Damaged R/C Beams using Externally Bonded Fiber Glass Plates, Fourth International
Conference Structural Failure, Durability and Retroffiting, Singapore, July 14-16, pp. 621-628.
12. Basunbul, I.A.; Husain, M.; Sharif, A.M.; Al-Sulaimani, G.J.; and Baluch, M.H.,
Repair of Shear Cracked R/C Beams with Bonded External Steel Plates, Fourth International
Conference on Structural, Failure, Durability and Retro-fitting, Singapore, July 14-15, 1993,
pp. 629-634.
13. Al-Sulaimani, G.J.; Al-Farabi, S.; Basunbul, I.A.; Baluch, M.H.; and Ghaleb, B.M.,
Shear Repair for Reinforced Concrete by Fiber Glass Plate Bonding, ACI Structural Journal,
V. 91, No. 3, July-August 1994, pp. 458-464.

14. Ong, K.C.G.; Paramasivam, P.; and Lim, C.T.E., Flexural Strengthening of Reinforced
Concrete Beams using Ferrocement Laminates, Journal of Ferrocement, V. 22, No. 4, October
1992, pp. 331-342.
15. Paramasivam, P.; Ong, K.C.G.; Lim, C,T.T., Repair of Damaged RC Beams using
Ferrocement Laminates, Fourth International Conference on Structural, Failure, Durability
and Retrofitting,, Singapore, July 14-15, pp. 613-620.
16. Paramasivam, P., Recent Research and Application of Ferrocement in Singapore,
Proceedings of the sixth International Symposium on Ferrocement, University of Michigan Ann
Arbor, June 7-10 , 1993, pp. 53-64.
17. Aurellado. P. G. Jr., Performance of Repaired Reinforced Concrete T-beams, M.Sc.
Dissertation, National University of Singapore, Sig., 1994, 103 pp.

You might also like