After the combustion inspection is complete and the unit is returned to service,
the removed combustion liners and transition pieces can be bench inspected and
repaired, if necessary, by either competent on-site personnel, or off-site at a
qualified GE Combustion Service Center. The removed fuel nozzles can be
cleaned onsite and flow tested on-site, if suitable test facilities are available.
this means that recoating will be required at the hot-gas path inspection. If
recoating is not performed at the hot-gas-path inspection, the run out life of the
buckets would generally extend to the major inspection, at which point the
buckets would be replaced. For F class gas turbines recoating of the first stage
buckets is recommended at each hot gas path inspection.
Visual and borescope examination of the hot gas path parts during the
combustion inspections as well as nozzle-deflection measurements will allow the
operator to monitor distress patterns and progression. This makes part-life
predictions more accurate and allows adequate time to plan for replacement or
refurbishment at the time of the hot-gas-path inspection. It is important to
recognize that to avoid extending the hot-gas-path inspection, the necessary
spare parts should be on site prior to taking the unit out of service.