Professional Documents
Culture Documents
YELLOW
Maintenance
Confidence Testing
ADDRESS
TIME IN:
NAME OF FACILITY
TIME OUT:
TYPE OF TEST:
OPERATIONAL
RED
DATE INSPECTED:
PERFORMANCE
QUARTERLY
SEMI ANNUAL
ANNUAL
PERIODIC TESTING OF SMOKE CONTROL SYSTEMS IN ACCORDANCE WITH BFDDS SECTION 11.09, INCLUDING OPERATIONAL TESTING,
SHALL BE PERFORMED BY QUALIFIED SERVICE TECHNICIANS WHO ARE FAMILIAR WITH THE PROPER OPERATION OF THE SMOKE CONTROL
SYSTEM AND EQUIPMENT. PERFORMANCE TESTING SHALL BE WITNESSED BY A SPECIAL INSPECTOR AND CONDUCTED BASED ON THE
ACCEPTANCE TEST PROCEDURE . THE INTENT OF THIS TESTING IS TO ENSURE THAT THE SYSTEM WILL FUNCTION AS DESIGNED DURING
AN EMERGENCY. CARE MUST BE EXERCISED TO AVOID CREATING CONDITIONS HARMFUL TO LIFE OR PROPERTY.
DOCUMENTATION
NO
NO
N/A
NO
N/A
N/A
to
to
SHAFT PRESSURIZATION
LOWEST TEST
FLOOR/ZONE:
MIDDLE TEST
FLOOR/ZONE:
HIGHEST TEST
FLOOR/ZONE:
MINIMUM OBSERVED P
OF PRESSURIZED STAIR
MINIMUM OBSERVED P
OF PRESSURIZED STAIR
MINIMUM OBSERVED P
OF PRESSURIZED STAIR
MAXIMUM OBSERVED P
OF PRESSURIZED STAIR
MAXIMUM OBSERVED P
OF PRESSURIZED STAIR
MAXIMUM OBSERVED P
OF PRESSURIZED STAIR
DOOR OPENING
FORCES <30 LBS
YES /
NO
YES /
NO
MINIMUM OBSERVED P
OF PRESSURIZED ELEV
PRESSURIZED STAIR
ENCLOSURES TESTED
PRESSURIZED ELEVATOR
HOISTWAYS TESTED
MAXIMUM OBSERVED P
OF PRESSURIZED ELEV
AUTOMATIC DOOR
OPERATION
AUTOMATIC DOOR
OPERATION
YES /
NO
AUTOMATIC DOOR
OPERATION
YES /
NO
AUTOMATIC DOOR
OPERATION
YES /
NO
YES /
NO
COMMENTS
FD - 404
Rev 10/2/07
PAGE 1
ZONE PRESSURIZATION
P TO FLOOR/ZONE ABOVE
LOWEST TEST FLOOR/ZONE
HIGHEST TESTED
EVENT ZONE/FLOOR:
P TO FLOOR/ZONE BELOW
HIGHEST TEST FLOOR/ZONE
P TO FLOOR/ZONE BELOW
LOWEST TEST FLOOR/ZONE
MIDDLE TESTED
EVENT ZONE/FLOOR:
P TO FLOOR/ZONE ABOVE
MIDDLE TEST FLOOR/ZONE
LOWEST TESTED
EVENT ZONE/FLOOR:
P TO FLOOR/ZONE BELOW
MIDDLE TEST FLOOR/ZONE
PRESSURE TESTS
YES
CONDUCTED?
NO
N/A
EXHAUST / AIRFLOW
VELOCITY TESTS
YES
CONDUCTED?
NO
NO
N/A
FAN MAINTENANCE
YES
CURRENT?
NO
N/A
PROBLEMS FOUND :
N/A
NO
NO
N/A
NO
N/A
NO
N/A
TOTAL NUMBER OF
DAMPERS INSPECTED
NO
N/A
YES
NO
COMMENTS:
FLOORS INSPECTED
YES
COMMENTS
NO
N/A
COMMENTS:
NO
YES
SATISFACTORY SYSTEM
PERFORMANCE
I HEREBY CERTIFY THAT THE FIRE PROTECTION SYSTEM LISTED ABOVE HAS BEEN PROPERLY TESTED AND INSPECTED FOR
RELIABILITY. ALL MAINTENENANCE, TESTING, INSPECTIONS, AND REPAIRS ARE CONSISTENT WITH THE INTERNATIONAL FIRE CODE AND NFPA STANDARDS.
DISCREPENCIES AND DEFICIENCIES HAVE BEEN REPORTED TO THE OWNER OR OWNERS REPRESENTATIVE FOR CORRECTIVE ACTION AND REPORTS FORWARDED TO THE BELLEVUE FIRE DEPARTMENT.
*********************THE SYSTEM ABOVE HAS BEEN RESTORED TO SERVICE AND IS FULLY OPERATIONAL
TECHNICIAN NAME :
PRINT NAME:
SIGN :
PAGE 2