OPERATORS’ MANUAL FOR
TKE-1030
AUTOMATIC EARTH TESTER
@& TAE KWANG ELECTRONICS CO.INTRODU re) |
1. GENERAL
Model TKE-1030 enables Automatic EARTH
RESISTANCE MEASUREMENTS by using Voltage
Drop System. EARTH RESISTANCE MEASUREMENTS
became quite easy measured automatically with
POWER Switch depressed only. No calibration
or zero adjustment procedures are required.
Also, it has been designed to minimize battery
consumption.
2. FEATURES
1. VOLTAGE DROP SYSTEM enabled the TKE-
1030 to present Automatic EARTH
RESISTANCE Measurements with one
depression of POWER Switch only.
2. TKE-1030 has been designed handy and very
compact arranging function switches in an
ideal layout.
3. Simple Measurements are available by
shorting P Terminal and C Terminal with
attached Cord.
4. Taut Band Meter Movement of Drop-proof
and Internal Core Magnet type minimizes
outside magnetic influence and assures
trouble-free performance.
3. UNPACKING AND INSPECTION
Before unpacking, examine the shipping carton
for any sign of damage. Unpack and inspect the
instrument and accessories for any damage
from mechanical shock, water leakage, or other
causes. If any damage or missing item is found,
consult the local dealer for replacement.
Hrellts [ce MT
1. Automatic EARTH TESTER
2. One set of Measuring Cords (5m, 10m, 15m Simple
Measuring Cord)
3. Two Auxiliary Earth Rods
4. Eight 1.5V (SUM-3) Batteries
5. One Carrying Case
6. One Sack for Accessories. SPECIFICATIO
1. RANGE and VOLTAGE
a. Earth Resistance Range : 102/1002/10002
b. Earth Voltage : 30V
2. ACCURACY
a. Earth Resistance : +3% of full scale value
a-1. Effect of Earth Voltage : Less than +5% of
reading value when earth voltage is 10V.
a-2. Effect of Auxiliary Earthing Resistance : +3%
of reading value when Auxiliary Earthing
Resistance is 5KQ.
b. Earth Voltage : +3% of full scale value
3. MEASURING SYSTEM
Mode! TKE-1030 is an Earth Tester which adopts
the deflection method of Voltage Drop.
MEASURING PRINCIPLE
I(Regulated Current Source)
—
Amplifier
Ex
Filter Rx
Meter Tt
Rie BL
! Cc
Having a regulated current(about 2KHz, 3mA in this
instrument) flow between E and C, measure
Voltage Ex generated in Rx at that time and work
out Rx.
4. BATTERY CHECK : by POWER/BATTLED Lamp
. BATTERIES : Eight 1.5V(SUM-3) Batteries
6. BATTERY CONSUMPTION :
660mW, 12 hour continuous operation
7. DIMENSIONS & WEIGHT :
162(H) x 98(W) x 75(D)mm, 525g
a